Bently nevada 3300 xl руководство

  1. Manuals
  2. Brands
  3. GE Manuals
  4. Measuring Instruments
  5. 3300
  6. Installation manual
  • Contents

  • Table of Contents

  • Bookmarks

Quick Links

Installation Manual

Bently Nevada™ Asset Condition Monitoring

3300 System Installation

Part Number 80172-01

Rev. N (08/07)

loading

Related Manuals for GE Bently Nevada 3300

Summary of Contents for GE Bently Nevada 3300

  • Page 1
    Installation Manual Bently Nevada™ Asset Condition Monitoring 3300 System Installation Part Number 80172-01 Rev. N (08/07)
  • Page 2
    Bently Nevada Keyphasor, Proximitor Contact Information The following ways of contacting Bently Nevada are provided for those times when you cannot contact your local representative: Mailing Address 1631 Bently Parkway South Minden, Nevada USA 89423 Telephone 1.775.782.3611 1.800.227.5514 1.775.215.2873 Internet www.ge-energy.com/bently…
  • Page 3
    Additional Information Notice: This manual does not contain all the information required to operate and maintain the product. Refer to the following manuals for other required information. 3300 System Overview (Part Number 80171-01) 3300 System Troubleshooting (Part Number 80173-01) The above two documents and 80172 are available as Part Number 80170-01 or -02. 3300/12 AC Power Supply (Part Number 89602-01) 3300/14 DC Power Supply (Part Number 101256-01) 3300/03 System Monitor (Part Number 89604-01)
  • Page 4: Table Of Contents

    3300 System Installation Manual Contents RECEIVING INSPECTION ……………………..1 HANDLING & STORING CONSIDERATIONS………………2 RACK ASSEMBLY OPTIONS……………………3 RACK INSTALLATION [PANEL MOUNT]………………..4 RACK INSTALLATION [19-INCH EIA] ………………… 5 PANEL CUTOUT DIMENSIONS……………………. 6 WEATHERPROOF HOUSING INSTALLATION ………………7 POWER SUPPLY INSTALLATION ………………….13 SYSTEM MONITOR INSTALLATION ………………….15 MONITOR INSTALLATION [TYPICAL] ………………..16 POWER INPUT MODULE……………………17…

  • Page 5: Receiving Inspection

    Section 1 — RECEIVING INSPECTION 1. RECEIVING INSPECTION 1. Visually inspect the exterior of rack assembly and components for obvious shipping damage. 2. Inspect interior of monitors and power supply. Loosen screws to pull each monitor and power supply out from rack. DAMAGE CLAIMS If shipping damage is apparent, file a claim with the carrier and…

  • Page 6: Handling & Storing Considerations

    3300 System Installation Manual 2. HANDLING & STORING CONSIDERATIONS Handling and storing of printed circuit boards is extremely critical. Circuit boards contain devices that are susceptible to damage when exposed to electrostatic charges. Damage caused by obvious mishandling of the board will void the warranty. To avoid damage, observe the following precautions in the order given.

  • Page 7: Rack Assembly Options

    Section 3 — RACK ASSEMBLY OPTIONS 3. RACK ASSEMBLY OPTIONS EXTERNAL DIMENSIONS 01,11,21,31 = 4 POSITIONS 11.00 IN. (279.4 mm) 8.00 IN. (203.2 mm) 02,12,22,32 = 6 POSITIONS 15.00 IN. (381.0 mm) 12.00 IN. (304.8 mm) 03,13,23,33 = 8 POSITIONS 19.00 IN.

  • Page 8: Rack Installation [Panel Mount]

    3300 System Installation Manual 4. RACK INSTALLATION [PANEL MOUNT] Slide rack through panel cutout.

  • Page 9: Rack Installation [19-Inch Eia]

    Section 5 — RACK INSTALLATION [19-INCH EIA] 5. RACK INSTALLATION [19-INCH EIA]…

  • Page 10: Panel Cutout Dimensions

    3300 System Installation Manual 6. PANEL CUTOUT DIMENSIONS OPTIONS RACK SIZE 01,11,21,31 4 POSITIONS 8.56 IN. (217.5 mm) 01.12.22.32 6 POSITIONS 12.57 IN (319.3mm) 03,13,23,33 8 POSITIONS 16.57 IN. (420.8mm) 04,14,24,34 10 POSITIONS 20.58 IN (522.7 mm) 05,15,25,35 12 POSITIONS 24.58 IN (624.3 mm) 06,16,26,36 14 POSITIONS…

  • Page 11: Weatherproof Housing Installation

    Section 7 — WEATHERPROOF HOUSING INSTALLATION 7. WEATHERPROOF HOUSING INSTALLATION The next 5 pages contain the weatherproof housing installation drawing, 330006.

  • Page 12
    3300 System Installation Manual…
  • Page 13
    Section 7 — WEATHERPROOF HOUSING INSTALLATION…
  • Page 14
    3300 System Installation Manual…
  • Page 15
    Section 7 — WEATHERPROOF HOUSING INSTALLATION…
  • Page 16
    3300 System Installation Manual…
  • Page 17: Power Supply Installation

    Section 8 — POWER SUPPLY INSTALLATION 8. POWER SUPPLY INSTALLATION For systems with the AC Power Supply, perform the following steps. For systems with the DC Power Supply, perform the steps on the following page. WARNING High voltage present could cause shock, burns, or death.

  • Page 18
    3300 System Installation Manual For systems with the DC Power Supply, perform the following steps. WARNING High voltage present could cause shock, burns, or death. Do not touch exposed wires or terminals. 1. Slide Power Supply into rack and fasten two screws.
  • Page 19: System Monitor Installation

    Section 9 — SYSTEM MONITOR INSTALLATION 9. SYSTEM MONITOR INSTALLATION 1. Slide System Monitor panel to the right before inserting monitor. Slide System Monitor board into rack to engage connector on backplane. 2. Slide front panel to the left and fasten two screws.

  • Page 20: Monitor Installation [Typical]

    3300 System Installation Manual 10. MONITOR INSTALLATION [TYPICAL] 1. Slide monitor front panel to the right before inserting monitor. Slide monitor circuit board into rack to engage connector on backplane. If the monitor is a dual width monitor with two separate circuit boards, line the lower edges of both boards up with the slots in the rack and slide the boards in simultaneously.

  • Page 21: Power Input Module

    Section 11 — POWER INPUT MODULE 11. POWER INPUT MODULE For grounding technique see Section 15.

  • Page 22: Signal Input Relay Modules

    3300 System Installation Manual 12. SIGNAL INPUT RELAY MODULES WARNING CAUTION High voltage present The following information is not could cause shock, applicable to the Velomitor. Refer to burns, or death. the 3300/55 Maintenance Manual for jumper configuration of the Do not touch exposed Velomitor Relay Module.

  • Page 23
    Section 12 — SIGNAL INPUT RELAY MODULES WARNING CAUTION High voltage present The following information is not applicable to the Velomitor. could cause shock, Refer to the 3300/55 burns, or death. Maintenance Manual for jumper Do not touch exposed configuration of the Velomitor wires or terminals.
  • Page 24
    3300 System Installation Manual SIGNAL INPUT/QUAD RELAY CARD OPTION * RELAY OPTIONS INSTALL REMOVE ALERT RELAYS W2,3C W3A,4C NORMALLY W3D,4D DE-ENERGIZED ALERT RELAYS W3A,4C W2,3C NORMALLY W3D,4D ENERGIZED DANGER RELAYS W1,3B W4B,4F NORMALLY W4A,4E DE-ENERGIZED DANGER RELAYS W4B,4F W1,3B NORMALLY W4A,4E ENERGIZED * For more information on relay configuration refer to…
  • Page 25
    Section 12 — SIGNAL INPUT RELAY MODULES WARNING CAUTION High voltage present The following information is not applicable to the could cause shock Velomitor. Refer to the burns or death 3300/55 Maintenance Manual for jumper Do not touch exposed configuration of the wires or terminals Velomitor Relay Module.
  • Page 26
    3300 System Installation Manual JUMPER RELAY OPTIONS INSTALL REMOVE ALERT RELAYS W4,W9 NORMALLY DE-ENERGIZED ALERT RELAYS W4,W9 NORMALLY ENERGIZED DANGER RELAYS W1,W10 NORMALLY DE-ENERGIZED DANGER RELAYS W1,10 NORMALLY ENERGIZED…
  • Page 27: Alert Relay Actuation Circuits

    Section 13 — ALERT RELAY ACTUATION CIRCUITS 13. ALERT RELAY ACTUATION CIRCUITS The following diagram shows the functional concept of jumper configurations for Alert relay bus actuation for the Dual Relay Module. For more detail refer to schematics in the applicable monitor manuals.

  • Page 28
    3300 System Installation Manual FUNCTION JUMPER INSTALL REMOVE Set Alert relay for normally energized operation* W4,W11 Set Alert relay for normally de-energized operation* W4,W11 Select Alert bus 1 Select Alert bus 2 * REFER TO SECTION 12 FOR JUMPER CONFIGURATION OF RELAYS IN A SYSTEM WITH INTERNAL BARRIERS.
  • Page 29
    Section 13 — ALERT RELAY ACTUATION CIRCUITS The following diagram shows the functional concept of jumper configurations for Alert relay actuation for the Quad Relay Module. Note: The jumper configuration shown is not applicable to the Velomitor Signal Input Relay Module. Refer to the Dual Velocity Monitor Maintenance Manual.
  • Page 30: Danger Relay Actuation Circuits

    3300 System Installation Manual 14. DANGER RELAY ACTUATION CIRCUITS The following diagram shows the functional concept of jumper configurations for Danger relay bus actuation for the Dual Relay Module. Note: The jumper configuration shown is not applicable to the Velomitor Signal Input Relay Module.

  • Page 31
    Section 14 — DANGER RELAY ACTUATION CIRCUITS The following diagram shows the functional concept of jumper configurations for Danger Relay actuation for the Quad Relay Module. Note: The jumper configuration shown is not applicable to the Velomitor Signal Input Relay Module. For more details refer to schematics in the applicable monitor manuals.
  • Page 32: Field Grounding Technique

    3300 System Installation Manual 15. FIELD GROUNDING TECHNIQUE 1. Refer to the applicable monitor manual for monitor connections. 2. For single point ground on typical system installations, install a jumper wire between the terminals labeled «Single Point Ground» on the Power Input Module. For systems with external safety barriers, refer to the field wiring diagrams in the appropriate monitor maintenance manuals for grounding requirements.

  • Page 33
    Section 15 — FIELD GROUNDING TECHNIQUE…

3300 XL NSv Proximity Transducer System

Datasheet

BentlyNevadaMachineryCondition Monitoring

147385Rev. K

Description

The3300XL NSvProximity Transducer system is intended for usewith centrifugalair compressors, refrigeration compressors, process gas compressors and other machines with tight installation requirements. The3300XL NSvProximity Transducer System consists of:

a 3300NSvprobe

a 3300NSvextension cable

a 3300XL NSvProximitor Sensor(1)

Theprimary uses for the3300XL NSvTransducer System are for areas wherecounter bore, sideview or rearview restrictions limit theuseofstandard Bently Nevada 3300and 3300XL 5 and 8mm Transducer Systems. It is also idealfor smalltarget applications, such as measuring radialvibration on shafts smaller than 51mm (2 in) or axialposition on flat targets smaller than 15mm (0.6in). It is primarily used in the following applications on fluid-filmed bearing machines wherea smallshaft or reduced side-view is present:

Radialvibration and radialposition measurements

Axial(thrust) position measurements

Tachometer and zero speed measurements

Phasereference(Keyphasor signals)

The3300XL NSvTransducer System design allows it to replace both the3300RAMTransducer Systems and the3000-series or 7000-series 190Transducer System. Upgrades from the 3300RAMsystem to the3300XL NSvsystem may usethe existing probe, extension cable, and monitoring system with 3300XL NSvProximitor Sensor. Upgrades from the3000-series or 7000-series Transducer System must replacetheprobe, extension cableand Proximitor Sensor with NSvcomponents.

3300XL NSv Proximity TransducerSystem

Datasheet

147385Rev. K

The3300XL NSvTransducer System has an AverageScaleFactor of7.87V/mm (200 mV/mil), which is themost common output for eddy current transducers. Its enhanced sideview and smalltarget characteristics giveit a shorter linear rangethan theBently Nevada 3300XL-series 5and 8mm Transducer System. With The1.5mm (60mils) oflinear range exceeds thelinear rangeofthe3000-series 190 Transducer System.

Although theterminals and connector on theProximitor Sensor have protection against electrostatic discharge, takereasonableprecautions to avoid electrostatic dischargeduring handling.

Proximitor Sensor

The3300XL NSvProximitor Sensor has similar features to thosefound in the3300XL 8mm Proximitor Sensor. Its thin design allows the user to mount it in either a high-density DIN-rail installation or a moretraditionalpanelmount configuration. Improved RFI/EMIimmunity allows the3300XL NSvProximitor Sensor to achieveEuropean CE mark approvals without any specialmounting considerations. This RFI immunity also prevents nearby high frequency radio signals from adversely affecting the transducer system. SpringLoc terminalstrips on theProximitor Sensor requireno special installation tools and facilitatefaster, highly robust field wiring connections.

Proximity Probe and Extension Cable

The3300NSvprobeand extension cableare mechanically and electrically compatibleand interchangeablewith Bently Nevada’s previous 3300RAMproximity probeand extension cable. TheNSvprobehas increased chemical resistancecompared to the3300RAMprobe, which allows its usein many process compressor applications. Theside-view characteristics ofthe3300NSvprobearealso superior to thoseofthe3000-series 190probe when gapping the3300NSvprobeat thesame distancefrom theprobetarget.

The3300NSvprobecomes in varying probe caseconfigurations, including armored and unarmored ¼ -28, 3⁄8-24, M8X1and M10X1 probethreads. Thereversemount 3300NSv probecomes standard with either 3⁄8-24or M10X1threads. Allcomponents ofthe transducer system havegold-plated brass ClickLocconnectors. ClickLoc connectors lock into placeand prevent theconnection from loosening. Thepatented TipLocmolding method provides a robust bond between the probetip and theprobebody. Bently Nevada’s patented CableLocdesign provides 220N(50 lb) ofpullstrength and securely attaches the probecableto theprobetip. Connector protectors arerecommended for useon the probe-to-extension cableconnection, as well as on thecable-to-Proximitor Sensor connection. Connector protectors prevent most liquids from entering into theClickLoc connectors and adversely affecting the electricalsignal(2).

Notes:

(1)ProximitorSensors aresupplied by default from thefactory calibrated to AISI4140steel. Calibration to other target materials is available upon request.

(2)Siliconetapeis also provided with each 3300NSvextension cableand can beused instead ofconnector protectors. Siliconetape is not recommended in applications wherethe probe-to-extension cableconnection willbe exposed to turbineoil.

2/30

3300XL NSv Proximity TransducerSystem

Datasheet

147385Rev. K

(1,000 feet)between the3300 XL

NSv ProximitorSensorand the

monitor. Seethefrequency

Unless otherwisenoted, thefollowing

responsegraphs Figure16 and

Figure17 forsignal rolloff at high

specifications arefor a 3300XL NSvProximitor

frequencies when using longerfield

Sensor, extension cableand probebetween 0°C

wiring lengths.

and +45°C(+32°F to +113°F), with a -24Vdc

1.5 mm (60 mils). Linearrange

power supply, a 10kΩload, a Bently Nevada

begins at approximately 0.25 mm

supplied AISI4140steeltarget that is 31mm (1.2

LinearRange

(10 mils)from target and is from

in) diameter or larger, and a probegap of1.0

0.25 to 1.75 mm (10 to 70 mils)

mm (40mils). Thesystem accuracy and

(approximately -1 to -13 Vdc).

interchangeability specifications do not apply

Recommended

1.0 mm (40 mils)

when using a transducer system calibrated to

Gap Setting

any target other than a Bently Nevada AISI4140

System performance over ambient temperature

steeltarget.

range (0°C to 45°C)

Electrical

Proximitor

Accepts onenon-contacting 3300

RAM or3300 NSv Proximity Probe

SensorInput

and Extension Cable.

Requires -17.5 Vdc to -26 Vdc

without barriers at 12 mA maximum

Power

consumption, -23 Vdc to -26 Vdc

with barriers. Operation at a more

positivevoltagethan -23.5 Vdc can

result in reduced linearrange.

Supply

Less than 2 mV changein output

voltagepervolt changein input

Sensitivity

voltage.

Output

50 Ω

resistance

Probe dc Resistance

ProbeLength

Resistancefrom theCenter

Conductorto theOuterConductor

(m)

(RPROBE)(ohms)

0.54.0 ± 0.5

1.04.2 ± 0.5

5.05.3 ± 0.7

7.05.9 ± 0.9

Extension

Centerconductor: 0.220 Ω/m

(0.067 Ω/ft)

cabledc

resistance

Shield:0.066 Ω/m (0.020 Ω/ft)

Extension

69.9 pF/m (21.3 pF/ft)typical

cable

capacitance

2

0.2 to 1.5 mm (16 to 24 AWG) [0.25

2

to 0.75 mm (18 to 23 AWG)with

Field Wiring

ferrules]. Recommend using three-

conductorshielded triad cable.

Maximum length of 305 metres

Incremental

7.87 V/mm (200 mV/mil)+12.5%/-

20% including interchangeability

ScaleFactor

errorwhen measured in increments

(ISF)

of 0.25 mm (10 mils)overthe1.5

mm (60 mil)linearrange.

Deviation from

Less than ±0.06 mm (±2.3 mils).

best fit straight

line(DSL)

Frequency

0 to 10 kHz: +0, -3 dB typical, with up

to 305 metres (1000 feet)of field

Response

wiring.

Minimum: 8.9 mm (0.35 in)

diameter

Recommended minimum: 13 mm

(0.5 in)diameter

Target Size(flat

Axial position measurements on

target)

shaft diameters smallerthan 13mm

(0.5 in)will generally result in a

changein scalefactor. Reducing

thegap between theprobeand

target will help limit thechangein

scalefactor. SeeFigure12 for

additional information.

Minimum (standard X-Y probe

configuration): 30 mm (1.2 in)

Minimum (X-Y proximity probes

offset axially by 23 mm (0.9 in)): 20

mm (0.8 in)

Shaft Diameter

Measurements on shaft diameters

smallerthan 30 mm (1.2 in)usually

requireclosespacing of radial

vibration oraxial position

transducers. This creates the

potential fortheirelectromagnetic

emitted fields to interact with one

3/30

3300XL NSv Proximity TransducerSystem

Datasheet

147385Rev. K

another(cross-talk), resulting in

Extension

75 Ωcoaxial, fluoroethylene

erroneous readings. To prevent

Cable

propylene(FEP)insulated.

cross-talk, maintain minimum

Material

separation of m transducertips of

Proximitor

at least 25 mm (1.0 in)foraxial

Sensor

A380 aluminum

position measurements or23 mm

Material

(0.9 in)forradial vibration

System

5 or7 metres including extension

measurements. ProbeCross-talk

with Probes Mounted in Parallel and

Length

cable

ProbeCross-talk with Probes

Extension

FlexibleAISI 302 SSTwith/without FEP

Mounted in X-Y Configuration

CableArmor

Radial vibration orradial position

(optional)

outerjacket.

measurements on shaft diameters

220 N(50 lb)probecaseto probe

smallerthan 20 mm (0.8 in)will

Tensile

lead. 220 N(50 lb)at probelead to

generally result in greaterthan a

Strength

extension cableconnectors. 220 N

10% changein AverageScaleFactor

(maximum

(50 lb)probecaseto stainless steel

(ASF). SeeFigure13 foradditional

rated)

armor.

information.

Connector

Minimum: 9.5 mm (0.375 in)

Gold-plated brass

material

Recommended minimum: 13 mm

Recommended

case hole and tap size for 1/4-28

(0.5 in)

case

Counterbores smallerthan 13 mm

Drill Size

0.213 in

Counterbore

(0.5 in)generally result in a change

HoleSize

0.218 to 0.222 in

in scalefactorat fargaps.

HoleDepth

0.376 to 0.750 in

Reducing thegap between the

Tap Drill Size

#3

probeand thetarget will allow the

transducersystem to maintain its

Recommended

case hole and tap size for M8x1

AverageScaleFactor(ASF)overa

case

reduced linearrange. SeeFigure9

Drill Size

7.4mm

foradditional information.

HoleSize

7.511 to 7.622 mm

Effects of 60 Hz Magnetic Fields Up to 300 Gauss

HoleDepth

12 to 24 mm

(5 metre system)

Tap Drill Size

L

Output voltagein mil pp/gauss

Recommended case hole and tap size for 3/8-24

Gap

Proximitor

Probe

Ext. Cable

case

Sensor

Drill Size

0.332 in

0.25 mm

0.006

0.001

0.001

HoleSize

0.338 to 0.343 in

(10 mils)

HoleDepth

0.562 to 0.xxx1.125 in

1.0 mm (40

0.007

0.002

0.001

Tap Drill Size

Q

mils)

1.75 mm (70

0.008

0.002

0.003

Recommended

case hole and tap size for M10x1

mils)

case

Mechanical

Drill Size

9.4mm

HoleSize

9.541 to 9.662 mm

ProbeTip

Polyphenylenesulfide(PPS).

HoleDepth

15 to 30 mm

Material

Tap Drill Size

U

ProbeCase

AISI 304 stainless steel (SST).

Material

Connector-to-connector Torque

75 Ωcoaxial, fluoroethylene

ProbeCase

Maximum Rated

Recommended

ProbeCable

propylene(FEP)insulated probe

Torque

Specifications

cablein thefollowing total probe

¼ -28 orM8x1

lengths: 0.5, 1, 5, or7 metres.

7.3 N•m

5.1 N•m

probecases

4/30

3300XL NSv Proximity TransducerSystem

Datasheet

147385Rev. K

Connector-to-connector Torque

Storage

-52°C to +105°C (-62°F to +221°F)

Temperature

(65 in•lb)

(45 in•lb)

100% condensing, non-submersible

3/8-24 orM10x1

33.9 N•m

11.3 N•m

Relative

when connectors areprotected.

probecases

(300 in•lb)

(100 in•lb)

Humidity

Tested to IEC 68-2-3 damp heat.

3300 NSv probes aredesigned to seal

3/8-24 orM10x1

22.6 N•m

7.5 N•m

probecases –

differential pressurebetween the

first three

(200 in•lb)

(66 in•lb)

probetip and case. Theprobe

threads

Probe

sealing material consists of a Viton

O-ring. Probes arenot pressure

Reversemount

22.6 N•m

7.5 N•m

Pressure

tested priorto shipment. Contact our

probes

(200 in•lb)

(66 in•lb)

custom design department if you

requirea test of thepressureseal for

yourapplication

Recommended

Fingertight

It is theresponsibility of thecustomeroruser

torque

Maximum

0.56 N• m (5 in• lb)

to ensurethat all liquids and gases are

torque

contained and safely controlled should

leakageoccurfrom a proximity probe. In

Minimum Bend

addition, solutions with high orlow pH

Radius (with or

25.4 mm (1.0 in)

values may erodethetip assembly of the

without sst

probecausing media leakageinto

armor)

surrounding areas. Bently Nevada will not

System Weight (typical)

beheld responsibleforany damages

Probe

Approximately 14 to 150 g (0.5 to

resulting from leaking 3300 NSv Proximity

5.3 oz)

Probes. In addition, 3300 NSv Proximity

Probes will not bereplaced undertheservice

Extension

45 g/m (0.5 oz/ft)

plan dueto probeleakage.

Cable

Armored

Field Wiring Limitations

Extension

64 g/m (0.7 oz/ft)

Cable

Type

Gas

Capicitance

Inductance

L/R Ratio

Approval

Group

(μF)

(mH)

(μH/Ω)

Proximitor

255 g (9 oz)

IIC

0.078

0.99

29.2

Sensor

ATEX and

IEC Zone

IIB

0.645

7.41

117.0

Environmental Limits

0/1

IIA

2.144

15.6

234.0

A & B

0.070

1.0

29.2

ProbeTemperatureRange

CSA Div 1

C

0.600

5.0

117.0

Operating

-52°C to +177°C (-62°F to +351°F)

D

2.09

11.0

234.0

Temperature

CSA Div 2

All

0.460

100.0

N/A

-52°C to +177°C (-62°F to +351°F)

Storage

Exposing theprobeto

temperatures below -34°C (-

Temperature

30°F)fora sustained period

of timemay causepremature

failureof thepressureseal.

Extension Cable Temperature Range

Operating

and Storage -52°C to +177°C (-62°F to +351°F) Temperature

Proximitor Sensor Temperature Range

Operating

-52°C to +100°C (-62°F to +212°F)

Temperature

5/30

orwhen installed with galvanic isolators.

3300XL NSv Proximity TransducerSystem

Datasheet

147385Rev. K

Compliance and

Certifications

FCC

This devicecomplies with part 15ofthe FCCRules. Operation is subject to the following two conditions:

This devicemay not causeharmful interference.

This devicemust accept any interferencereceived, including interferencethat may cause undesired operation.

EMC

EN61000-6-2

EN61000-6-4

EMCDirective2014/30/EU

RoHS

RoHS Directive2011/65/EU

Maritime

ABS 2009SteelVessels Rules 1-1-4/7.7,4-8-3/1.11.1,4-9-7/13

Hazardous Area Approvals

Forthedetailed listing of country and product specific approvals, referto theApprovals Quick ReferenceGuide(108M1756)availablefrom Bently.com.

CSA/NRTL/C

3300 XL Proximitor Sensor

ia

Class I, Zone0: AEx/Ex ia IIC T4/T5

When installed

Ga;

Class I, Groups A, B, C, and D,

with

Class II, Groups E, F and G,

intrinsically

Class III;

safezener

T5

@ Ta= -55°˚C to + 40°˚C.

barriers per

drawing 141092

T4

@ Ta= -55°˚C to + 80°C.

Class I, Zone2: AEx/Ex nA IIC T4/T5

Gc;

nA, ec

Class I, Division 2, Groups A, B, C,

and D;

When installed

Class I, Zone2: AEx/Ex ec llC T4/T5

without

Gc;

barriers per

Class I, Division 2, Groups A, B, C,

and D;

drawing

140979.

T5 @ Ta= -55°C to + 40°C

T4 @ Ta= -55°C to + 80°C

3300 XL Probe

ia

When installed

Class I, Zone0: AEx/Ex ia IIC T5…T1

with

Ga;

intrinsically

Class 1, Groups A, B. C, and D,

safezener

Class II, Groups E, F, and G,

barriers per

Class III;

drawing 141092

(seeTemperatureScheduletableto

orwhen

installed with

follow)

galvanic

isolators.

nA, ec

Class I, Zone2: AEx/Ex nA IIC T5…T1

Gc;

When installed

Class 1, Division 2, Groups A, B, C, D;

Class 1, Zone2: AEx/Ex ec llC T5…T1

without

Gc; Class I, Division 2, Groups A, B, C,

barriers per

and D;

drawing

(seeTemperatureScheduletableto

140979.

follow)

6/30

3300XL NSv Proximity TransducerSystem

Datasheet

147385Rev. K

ATEX/IECEx

3300 XL Proximitor Sensor

II 1 G

Ex ia IIC T4/T5 Ga

Ex ia IIIC T90C/T105C Dc

ForEPL Dc:

T105C @ Ta = -55°C to 100°C

ia

T90C @ Ta = -55°C to +85°C

Ui= -28V

Uo= -28V

Ii= 140mA

Io= 140mA

Pi= 0.91W

Po= 0.742W

Ci47nF

Co= 1.5nF

Li= 1460µH

Lo= 610µH

II 3 G

Ex nA IIC T4/T5 Gc

nA,ec

Ex ec llC T4/T5 Gc

Ui= -28V

li= 140 mA

T5 @ Ta= -55˚ C to + 40˚C

T4 @ Ta= -55 ˚C to + 80˚C

3300 XL Probe

Probeentity parameters aremet when used with BNextension cables and connected to BNProx.

II 1 G

Ex ia IIC T5…T1 Ga,

(seeTemperatureSchedule

tableto follow)

ia

Ex ia IIIC T90°C … T280°C Dc

ForEPL Dc:

Ui= -28V

Ci = 1.5 nF

Ii = 140 mA

Li =610 μH

Pi = 0.91 W

nA,ec

II 3 G

Ex nA IIC T5…T1 Gc,

Ex ec llC T5…T1 Gc,

(seeTemperatureSchedule

tableto follow)

Ui= -28V

li= 140 mA

Temperature Schedule

Temperature

Ambient Temperature

Classification

(Probe Only)

For EPL Ga and Gc

T1

-55°C to +232°C

T2

-55°C to +177°C

T3

-55°C to +120°C

T4

-55°C to +80°C

T5

-55°C to +40°C

For EPL Dc

T280°C @ Ta

-55°C to +232°C

T225°C @ Ta

-55°C to +177°C

T170°C @ Ta

-55C to +120°C

T130°C @ Ta

-55°C to +80°C

T105°C @ Ta

-55°C to +100°C

T90°C @ Ta

-55°C to +40°C

7/30

3300XL NSv Proximity TransducerSystem

Datasheet

147385Rev. K

Hazardous Area Conditions of Safe Use

CSA/NRTL/C:

ia

Installper Bently Nevada drawing 141092. nA, ec

Installper Bently Nevada drawing 140979.

ATEX/IECEx:

ia

Installper Bently Nevada drawing 141092. nA, ec

TheProxmust beinstalled so as to providethe terminals with a degreeofprotection ofat least IP54.

Field Wiring Limitations

Type

Gas

Capicitance

Inductance

L/R

Ratio

Approval

Group

(μF)

(mH)

(μH/Ω)

ATEXand

IIC

0.078

0.99

29.2

IEC Zone

IIB

0.645

7.41

117.0

0/1

IIA

2.144

15.6

234.0

A & B

0.070

1.0

29.2

CSA Div 1

C

0.600

5.0

117.0

D

2.09

11.0

234.0

CSA Div 2

All

0.460

100.0

N/A

8/30

Bently Nevada 3300 XL NSv Specifications

3300XL NSv Proximity TransducerSystem

Datasheet

147385Rev. K

1 2

Miniaturecoaxial ClickLoc connector,

Ordering Information

FluidLoc cable

E: Agency Approval Option

Forthedetailed listing of country and product

0 0

Not required

specific approvals, referto theApprovals Quick

0 5

MultipleApprovals

ReferenceGuide(108M1756)availablefrom

Bently.com.

3300 NSv Proximity Probes

330901 3300 NSv Probe, 1/4-28 UNF thread, without armor

330902 3300 NSv Probe, 1/4-28 UNF thread, with armor

330908 3300 NSv Probe, 3/8-24 UNF thread, without armor

330909 3300 NSv Probe, 3/8-24 UNF thread, with armor

Part Number-AA-BB-CC-DD-EE

A: Unthreaded Length Option

Unthreaded length must beat least 0.7 inch less than thecaselength.

Orderin increments of 0.1 in

Length configurations:

Maximum unthreaded length: 9.2 in

Minimum unthreaded length: 0.0 in

Example: 0 4 = 0.4 in

B: Overall Case Length Option

Orderin increments of 0.1 in

Threaded length configurations:

Maximum caselength: 9.9 in

Minimum caselength: 0.8 in

Example: 2 4 = 2.4 in

C:Total Length Option 0 5 0.5 metre(20 in) 1 0 1.0 metre(39 in)

5 0 5.0 metres (16.4 feet)

7 0 7.0 metres (23.0 feet)

D:Connector and Cable-Type Option

0 1

Miniaturecoaxial ClickLoc connectorwith

connectorprotector, standard cable

0 2

Miniaturecoaxial ClickLoc connector,

standard cable

1 1

Miniaturecoaxial ClickLoc connectorwith

connectorprotector, FluidLoc cable

3300 NSv Proximity Probes, Metric

330903 3300 NSv Probe, M8 x 1 thread, without armor

330904 3300 NSv Probe, M8 x 1 thread, with armor

330905 3300 NSv Probe, M10 x 1 thread, without armor

330910 3300 NSv Probe, M10 x 1 thread, with armor

Part Number-AA-BB-CC-DD-EE

A: Unthreaded Length Option

Unthreaded length must beat least 20 mm less than thecaselength.

Orderin increments of 10 mm. Length configuration: Maximum unthreaded length: 230 mm

Minimum unthreaded length: 0 mm

Example:

0 6 = 60 mm

B: Overall Case Length Option

Orderin increments of 10 mm.

Metric thread configurations:

Maximum length: 250 mm

Minimum length: 20 mm

Example: 0 6 = 60 mm

C:Total Length Option 0 5 0.5 metre(20 in) 1 0 1.0 metre(39 in)

5 0 5.0 metres (16.4 feet)

7 0 7.0 metres (23.0 feet)

D:Connector and Cable-Type Option

0 1

Miniaturecoaxial ClickLoc connectorwith

connectorprotector, standard cable

9/30

Заказать Bently Nevada 3300 XL

  • Применение
  • Компоненты и заказные номера
  • Взаимозаменяемость компонентов

Токовихревой преобразователь перемещения Bently Nevada 3300 XL

Системы бесконтактного измерения перемещений Bently Nevada (BN) Proximitor®, основанные на технологии вихревых токов, выполняют преобразование осевого перемещения и виброперемещения в электросигнал.

Применение

Данные устройства предназначены для контроля параметров вибрации и осевых перемещений промышленного оборудования. Результаты измерений применяются в системах мониторинга, управления и защиты для предотвращения повреждений или выхода из строя оборудования и его компонентов, а также защиты персонала.

Система Тип измерения Тип оборудования
Bently Nevada 3300 XL 5, 8 и 11 мм Вибрация и смещение Оборудование с гидродинамическими подшипника
25 мм Дифференциальное расширение Турбогенераторы средних и больших размеров
50 мм Дифференциальное расширение или расширение ротора Большие паровые турбины
Bently Nevada 3300 NSv Радиальная вибрация и радиальное положение, осевое положение, скорость вращения, опорная фаза Центробежные воздушные компрессоры, холодильные компрессоры, компрессоры технологического газа и другое оборудование со строгими требованиями к установке
7200 5 и 8 мм Положение вала, вибрация Компрессорное и вращающееся оборудование
3300 16 мм HTPS (для температур до +350 °C) Вибрация, осевое перемещение Внутри горячих зон газовых, паровых турбин и другого вращающегося оборудования

Компоненты и заказные номера

Преобразователи состоят из датчика, генератора колебаний Proximitor® и соединительного кабеля.

Токовихревой преобразователь перемещения Bently Nevada 3300 XL 16 мм HTPS

При изменении перемещения контролируемого объекта пропорционально меняется напряжение или ток генератора.

Система Датчик Блок генератора (проксиметр Bently Nevada) Кабель
Американская унифицированная тонкая резьба Метрическая резьба
Bently Nevada 3300 XL 5 мм 330171 и 330172 330173 и 330174 Bently Nevada 330180 330130
8 мм Bently Nevada 330101 и 330102 330103 и 330104
11 мм (обновление старой системы 7200 11 мм и 14 мм) 330701, 330702, 330707, 330708 330703, 330704, 330709, 330710 330780 330730
25 мм 330851 330850 330854
50 мм 330876 330878 330877
Bently Nevada 3300 NSv 330901, 330902, 330908, 330909 330903, 330904, 330905, 330910 330980 330930
7200 5 мм 21500, 21501

22812, 22813

18745 21747
8 мм 21504, 21505 22810, 22811
3300 16 мм HTPS 330301 и 330303 330302 330380 330330

Взаимозаменяемость компонентов

В настоящее время проксиметры Bently Nevada очень распространены на промышленных предприятиях. Они широко используются для контроля состояния и / или автоматического отключения оборудования средней или высокой критичности.

С момента, когда Дон Бентли изобрел и впервые применил вихретоковый датчик Proximitor® в конце 1960-х годов, качество, надежность и простота применения являются одними из главных приоритетов этих систем. Приверженность этим ценностям подтверждается полной взаимозаменяемостью компонентов. Под взаимозаменяемость подразумевается возможность простой замены датчиков, кабелей и генераторов Proximitor® без необходимости калибровки или специальных инструментов.

Bently Nevada Proximitor 3300 XL 5/8 мм

Производитель сумел обеспечивать взаимозаменяемость между основными семействами Proximitor®. Каждое  семейство имеет собственную цветовую кодировку для простой идентификации.

Система Цвет
3300 XL 5 и 8 мм голубой
11 мм фиолетовый
25 мм зеленый лаймовый
50 мм коричневый
NSv серый
7200 5 и 8 мм светло–желтый
3300 16 мм HTPS оранжевый

Ассортимент продукции Bently Nevada

  • Contents

  • Table of Contents

  • Bookmarks

Quick Links

Operation Manual

Bently Nevada™ Asset Condition Monitoring

3300/25 Dual Accelerometer Input

Monitor

Part Number 80181-01

Rev. AA (08/07)

loading

Related Manuals for GE Bently Nevada 3300/25

Summary of Contents for GE Bently Nevada 3300/25

  • Page 1
    Operation Manual Bently Nevada™ Asset Condition Monitoring 3300/25 Dual Accelerometer Input Monitor Part Number 80181-01 Rev. AA (08/07)
  • Page 2
    Transient Data Manager, Trendmaster, TrimLoc, Velomitor Contact Information The following ways of contacting Bently Nevada are provided for those times when you cannot contact your local representative: Mailing Address 1631 Bently Parkway South Minden, Nevada USA 89423 Telephone 1.775.782.3611 1.800.227.5514 1.775.215.2873 Internet www.ge-energy.com/bently…
  • Page 3
    Additional Information Notice: This manual does not contain all the information required to operate and maintain the product. Refer to the following manuals for other required information. 3300 System Overview (Part Number 80171-01) 3300 System Installation Instructions (Part Number 80172-01) 3300 System Troubleshooting (Part Number 80173-01) 3300/12 Power Supply (AC supply) (Part Number 89602-01) 3300/14 Power Supply (DC supply) (Part Number 101256-01)
  • Page 4
    3300/25 Dual Accelerometer Input Monitor Operation Manual In this document procedures are given only for channel A. Procedures for channel B are similar except for the obvious substitutions of corresponding switches, terminals, and indicators. NOTE: The information in this manual pertains to monitor main boards with part number 105513-xx and 79552-xx (all revisions) and filter boards with part numbers 148921-01 (all revisions), 105521-01 (all revisions and 79562-01 revision J and later.
  • Page 5: Table Of Contents

    Contents Dual Accelerometer Monitor System …………..1 Monitor Functions ………………..2 LED Functionality………………..6 OK LEDs ………………….6 Bypass LEDs ………………..7 Alert LEDs…………………. 8 Danger LEDs ………………..9 Read Channel Values ………………10 Read Setpoint Levels………………11 Monitor Removal and Disassembly …………..12 Monitor Disassembly ………………

  • Page 6
    3300/25 Dual Accelerometer Input Monitor Operation Manual 19. Appendix B–Filter Board Options PWA 79562-01 and PWA 105521-01 …54 19.1 Identify Filter Board ………………54 19.2 Filter Board Jumper Locations …………..55 19.3 Integrator/Gain Stage Flow Path…………..56 19.4 General Procedure………………57 19.5 Filter Board Options ……………….58 19.6 Integrator/Gain Stage Options …………..59 19.7…
  • Page 7: Dual Accelerometer Monitor System

    Section 1 — Dual Accelerometer Monitor System 1. Dual Accelerometer Monitor System Do not use this figure as a wiring diagram. Refer to 3300/25 Field Wiring Packet.

  • Page 8: Monitor Functions

    3300/25 Dual Accelerometer Input Monitor Operation Manual 2. Monitor Functions DUAL ACCELEROMETER INPUT — The 3300/25 Dual Accelerometer Input Monitor provides two independent channels of on-line machine monitoring using accelerometers for the transducer inputs. Accelerometers are generally used for high frequency measurements on machines such as turbines, gear boxes, compressors, and pumps.

  • Page 9
    Section 2 — Monitor Functions OK RELAY — The System OK Relay is mounted on the Power Input Module. Every channel in the rack must be OK or bypassed to energize the OK Relay. ALARM — Pressing the ALERT or DANGER switches on the monitor front panel causes the corresponding Alert (first level alarm) or Danger (second level alarm) setpoints to be displayed on the front panel meter.
  • Page 10
    3300/25 Dual Accelerometer Input Monitor Operation Manual transducer not OK condition. With this option, the recorder output will clamp to either +2mA or +4mA (user selectable) when a transducer is not OK. TRIP MULTIPLY — The Trip Multiply function multiplies setpoints by 2X or 3X in response to an external contact closure through terminals on the Power Input Module.
  • Page 11
    Section 2 — Monitor Functions…
  • Page 12: Led Functionality

    3300/25 Dual Accelerometer Input Monitor Operation Manual 3. LED Functionality 3.1 OK LEDs BLINK LED DISPLAY OK RELAY CONDITION DRIVE* Channel A and B are in operating range. If a channel’s OK LED goes off, that channel is not OK, has been latched not OFF** OK, or is bypassed.

  • Page 13: Bypass Leds

    Section 3 — LED Functionality 3.2 Bypass LEDs BLINK LED DISPLAY CONDITION The monitor is in the Danger Bypass mode. The system is in the Power-Up mode. User invoked Self Test is in progress. BYPASS Timed OK/Channel Defeat is active. Both channels are bypassed.

  • Page 14: Alert Leds

    3300/25 Dual Accelerometer Input Monitor Operation Manual 3.3 Alert LEDs BLINK ALERT LED DISPLAY CONDITION RELAY DRIVE ALERT If a channel ALERT LED comes on, that channel has exceeded its Alert setpoint ALERT level. Read Setpoint Levels, Section describes how to read alarm setpoint levels.

  • Page 15: Danger Leds

    Section 3 — LED Functionality 3.4 Danger LEDs BLINK DANGER RELAY LED DISPLAY DRIVE CONDITION Voting Voting * DANGER If a channel’s DANGER LED comes on, that channel has exceeded its DANGER Danger setpoint level. Section 5 describes how to read setpoint levels.

  • Page 16: Read Channel Values

    3300/25 Dual Accelerometer Input Monitor Operation Manual 4. Read Channel Values The monitor continuously indicates measured acceleration or velocity. The front panel below is indicating an acceleration of 0.9 g for channel A and 1.55 g for channel B. Note: The meter scale units must be compatible with the full scale option configured in Section…

  • Page 17: Read Setpoint Levels

    Section 5 — Read Setpoint Levels 5. Read Setpoint Levels Press the ALERT switch to read Press the DANGER switch and the Alert setpoints for both read the Danger setpoints for channel A and channel B on the both channel A and channel B on meter scale.

  • Page 18: Monitor Removal And Disassembly

    3300/25 Dual Accelerometer Input Monitor Operation Manual 6. Monitor Removal and Disassembly Caution Improper rack operation may occur. Power down rack or inhibit rack alarms when installing or removing a monitor. • Loosen two monitor retaining screws on the front of the monitor. •…

  • Page 19: Monitor Disassembly

    Section 7 — Monitor Disassembly 7. Monitor Disassembly 7.1 Filter and Expander Board Removal Caution Component damage may result from removing the filter or expander board while power is on. Not all Dual Accelerometer Monitors contain the Expander Board. If this board does not exist, its functionality has been incorporated into the main board and connector J3 must be jumpered as shown…

  • Page 20: Filter Board Removal

    3300/25 Dual Accelerometer Input Monitor Operation Manual Caution Component damage may result from removing the filter or expander board while power is on. When performing the following instructions, refer to the drawing on the previous pages. 7.1.1 Filter Board Removal 1.

  • Page 21: Front Panel Removal

    Section 7 — Monitor Disassembly 7.2 Front Panel Removal 1. Disconnect J2 by pressing the connector latches outward. Caution 2. Unscrew two sliding standoffs. Component damage may result from removing the filter or expander board while power is on.

  • Page 22: Signal Input Relay Module Removal

    3300/25 Dual Accelerometer Input Monitor Operation Manual 7.3 Signal Input Relay Module Removal Caution WARNING Machine protection provided by High voltage present. Contact this monitor will be lost while the could cause shock, burns, or death. Signal Input Relay Module is Do not touch exposed wires or removed from the rack.

  • Page 23: Signal Input Relay Modules (Sirm)

    Section 7 — Monitor Disassembly 7.4 Signal Input Relay Modules (SIRM) A monitor can be configured with the Signal Input Relay Modules shown below. Refer to options EE & FF in Monitor Ordering Options, Section 8.2 of this manual. DUAL QUAD INTERNAL INTERNAL…

  • Page 24: No Relay And Dual Relay Sirm

    3300/25 Dual Accelerometer Input Monitor Operation Manual 7.5 No Relay and Dual Relay SIRM WARNING NOTE: For relay configuration of monitors with Internal Safety Barriers, refer to High voltage present. Contact could 3300 Internal Barriers, Installation cause shock, burns, or death. Do not touch exposed wires or terminals.

  • Page 25: Quad Relay Signal Input Module Options

    Section 7 — Monitor Disassembly 7.6 Quad Relay Signal Input Module Options WARNING High voltage present. Contact could cause shock, burns, or death. Do not touch exposed wires or terminals. Remove the Signal Input Relay Module from the rack before changing option jumpers. Note: AND voting logic must be done externally by wiring the contacts in series.

  • Page 26: Internal Barrier Options Sirm

    3300/25 Dual Accelerometer Input Monitor Operation Manual 7.7 Internal Barrier Options SIRM For relay configuration of monitors with internal safety barriers, refer to the 3300 Internal Barriers, Installation Manual (88837) or the 3300 System Installation Instructions (80172). The Alert Relays and Danger Relays sections of the table below do not apply to the No Relay SIRM.

  • Page 27: Monitor Options

    Section 8 — Monitor Options 8. Monitor Options 8.1 Field Programmable Options First Out Alert Mode Timed OK/Channel Defeat ** Enabled * Latching * Enabled * Disabled Nonlatching Disabled Alarm Delays Danger Mode Danger Relay Voting ++ 0.1 Second Latching * OR voting for relay drive * 1 Second Nonlatching…

  • Page 28: Monitor Ordering Options

    3300/25 Dual Accelerometer Input Monitor Operation Manual 8.2 Monitor Ordering Options *TRANSDUCER INPUT, CHANNEL A CHANNEL B CHANNEL UNITS FULL SCALE RANGE FULL SCALE RANGE Dual accelerometer inputs; 0 to 2 g pk 0 to 2 g pk both channels indicate in acceleration units.

  • Page 29
    Section 8 — Monitor Options Monitor Ordering Options (Continued) AGENCY BARRIERS ALARM TRIP APPROVAL USED RELAY MULTIPLY 00 None 00 None None None 01 CSA/NRTL/C 01 External Dual Relays, 2X trip multiply Epoxy Sealed 02 BASEEFA 02* Internal Dual Relays, 3X trip Hermetically Sealed multiply…
  • Page 30: Meter Scale Replacement

    3300/25 Dual Accelerometer Input Monitor Operation Manual 9. Meter Scale Replacement The monitor meter scales can be replaced for operation with different full scale ranges. The replacement meter scales are located in the back of this manual. Set the monitor full scale range. (See the Appendix A, Main Board Options.) Cut the meter scale from the back of this manual.

  • Page 31: Alarm Setpoint Adjustment

    Section 10 — Alarm Setpoint Adjustment 10. Alarm Setpoint Adjustment Setpoints cannot be adjusted if trip multiply is installed and active. Trip multiply is active when the trip multiply contacts are closed. Open the front panel by loosening the two monitor retaining screws and sliding the front panel to the right.

  • Page 32: Channel Bypass

    3300/25 Dual Accelerometer Input Monitor Operation Manual 11. Channel Bypass Caution Machine protection provided by this monitor will be lost while Channel Bypass is on. You can use Channel Bypass to take a Not OK or unconnected channel off line. This will restore the OK Relay to the OK state.

  • Page 33: Danger Bypass

    Section 12 — Danger Bypass 12. Danger Bypass Caution Machine protection provided by this monitor will be lost while Danger Bypass is on. Open the front panel by loosening the two monitor retaining screws and sliding the front panel to the right. Set DB (Danger Bypass) switch to the left (ON).

  • Page 34: Test Alarms

    3300/25 Dual Accelerometer Input Monitor Operation Manual 13. Test Alarms Use this procedure to test the alarm setpoints that you set in the Alarm Setpoint Procedure Section. The test uses a function generator to exceed the setpoint levels so that you can verify that the appropriate LEDs come on. Use this procedure to test the alarms for both channels.

  • Page 35: Connect And Adjust The Test Instruments

    Section 13 — Test Alarms 13.1 Connect and Adjust the Test Instruments Caution WARNING Tests will exceed alarm setpoint High voltage present. Contact could levels causing alarms to activate. cause shock, burns, or death. This could result in relay contacts Do not touch exposed wires or changing state.

  • Page 36
    3300/25 Dual Accelerometer Input Monitor Operation Manual Adjust the input frequency of the function generator according to this equation: frequency f × where: = high-pass corner frequency. = low-pass corner frequency. then use these values to calculate the input If you use.. frequency low-pass filter only = 240 CPM (4 Hz) *…
  • Page 37: Test The Alert Setpoint Level

    Section 13 — Test Alarms 13.2 Test the Alert Setpoint Level 1. Adjust the function generator DC offset to -7.5 Vdc. 2. Wait 30 seconds for the completion of the Timed OK/Channel Defeat delay, then press the RESET switch on the System Monitor.

  • Page 38: Test The Danger Setpoint Level

    3300/25 Dual Accelerometer Input Monitor Operation Manual 13.3 Test the Danger Setpoint Level 1. Adjust the function generator amplitude past the Danger setpoint level and verify that the DANGER LED comes on (flashing if the First Out option is selected). 2.

  • Page 39: Prepare To Bring The Monitor On Line

    Section 13 — Test Alarms 13.4 Prepare to Bring the Monitor On Line 1. Reduce the function generator amplitude to below the alarm setpoints and observe that the ALERT and DANGER LEDs go off (if nonlatching alarm jumpers are installed). 2.

  • Page 40: Test Ok Limits

    3300/25 Dual Accelerometer Input Monitor Operation Manual 14. Test OK Limits Caution WARNING Tests will exceed alarm setpoint High voltage present. Contact could levels causing alarms to activate. cause shock, burns, or death. This could result in relay contacts Do not touch exposed wires or changing state.

  • Page 41
    Section 14 — Test OK Limits 3. Adjust the power supply voltage for -7.5 Vdc with respect to common. 4. Wait 30 seconds for the completion of the Timed OK/Channel Defeat delay, then press the RESET switch on the System Monitor. Verify that the channel A OK LED is 5.
  • Page 42
    3300/25 Dual Accelerometer Input Monitor Operation Manual Gradually increase the power supply voltage (more negative) until the OK LED goes off (upper limit). Verify that the upper OK Limit is between -11.5 Vdc and -12.0 Vdc and that the OK Relay de-energizes. Return the power supply voltage to -7.5 Vdc and verify that the OK LED comes back on and the OK Relay energizes.
  • Page 43: Calibrate Channels

    Section 15 — Calibrate Channels 15. Calibrate Channels Before you begin Channel Calibration, you must choose the full scale range and set the appropriate jumpers (See Section 18.6). Calibrate both channels of your monitor. To calibrate channels you will need these instruments and tools •…

  • Page 44: Set The Filter Option To No Filters

    3300/25 Dual Accelerometer Input Monitor Operation Manual 15.1 Set the Filter Option to No Filters NOTE: This procedure may alter your filter configuration. Caution WARNING Tests will exceed alarm setpoint High voltage present. Contact could levels causing alarms to activate. cause shock, burns, or death.

  • Page 45: Connect And Adjust The Test Instruments

    Section 15 — Calibrate Channels 15.2 Connect and Adjust the Test Instruments (Repeat for channels A and B.) Connect the function generator to the channel A terminals as shown in the figure above. (Note: For a single transducer input system, do not repeat this step for channel B.) Adjust the function generator sine wave to 307.5 ±…

  • Page 46: Calibrate The Channels

    3300/25 Dual Accelerometer Input Monitor Operation Manual 15.3 Calibrate the Channels (Repeat for channels A and B) Measure the proportional signal output at TP39 (BPPLA) for Channel A and TP40 (BPPLB) for Channel B. The testpoint locations are shown in the figure below. The voltages at these testpoints should match the voltages listed in the following table.

  • Page 47: Prepare To Bring The Monitor On Line

    Section 15 — Calibrate Channels 15.4 Prepare to Bring the Monitor On Line (Repeat for channels A and B) Disconnect the test equipment and reconnect the transducer wiring A to the channel A terminals. ( Field wiring is shown the 3300/25 Field Wiring Diagram Packet.) WARNING…

  • Page 48: Self Test

    3300/25 Dual Accelerometer Input Monitor Operation Manual 16. Self Test The monitor has three levels of self tests: SELF TEST PERFORMED Power-up When the monitor is turned on. Continuous during monitoring Cyclic operations. When you initiate the self test by User-invoked temporarily shorting the self-test pins.

  • Page 49
    Section 16 — Self Test Recall stored error codes by using the User-invoked self test. Use the following steps to run the User-invoked self test, read error codes, and clear stored error codes: Caution Machine protection provided by this monitor will be lost for the duration of the self test.
  • Page 50
    3300/25 Dual Accelerometer Input Monitor Operation Manual Read any other stored error codes by pressing and holding the ALERT switch for approximately one second. For example, the display to the far right contains a second stored error code — number 10. When you reach the end of the error code list, the LCD bargraph comes on at full scale range and…
  • Page 51
    Section 16 — Self Test When you press the RESET switch on the System Monitor, the OK LEDs will stop flashing.
  • Page 52: Error Codes

    3300/25 Dual Accelerometer Input Monitor Operation Manual 17. Error Codes Refer to the Monitor Functions, Section 2 and Self Test, Section 16 for more information about displaying error codes. Refer to the Self Test section for information about clearing stored errors. ERROR DESCRIPTION EXPLANATION/RECOVERY…

  • Page 53: Appendix A-Main Board Options

    Section 18 — Appendix A–Main Board Options 18. Appendix A–Main Board Options 18.1 Jumper Locations for PWA 105513-xx NOTE: This drawing applies to main boards with part number 105513-xx.

  • Page 54: Shipped As Options

    3300/25 Dual Accelerometer Input Monitor Operation Manual 18.2 Shipped As Options The monitor is shipped with the following configuration: OPTION SHIPPED SETTING First Out Enabled OK Mode Nonlatching Timed OK/Channel Defeat Enabled Alert Mode Latching Recorder Outputs +4 to +20 mA +4 to +20mA Recorder Disabled Not OK Output (+2 mA clamp) *…

  • Page 55: Main Board Option Settings

    Section 18 — Appendix A–Main Board Options 18.3 Main Board Option Settings Use these and the tables on the following pages to configure main board options: OPTION SETTING INSTALL REMOVE Enabled* W16C None First Out Disabled None W16C Latching W20, W23** None OK Mode Nonlatching*…

  • Page 56: Recorder Options

    3300/25 Dual Accelerometer Input Monitor Operation Manual 18.4 Recorder Options Use the following table to configure Main Board 105513-xx. OPTION SETTING INSTALL REMOVE W8A,B +4 to +20 mA * W11C W11A,B W12A W12B W8A,C RECORDER OUTPUTS +1 to +5 V W11B W11A,C W12B…

  • Page 57: Channel Types

    Section 18 — Appendix A–Main Board Options 18.5 Channel Types TRANSDUCER INPUT, JUMPERS CHANNEL UNITS INSTALL REMOVE Dual Accelerometer, W3B,E Channel A Acceleration W6B,E Channel B Acceleration W22B W22A ** Dual Accelerometer, W3B,F Channel A Acceleration W6B,E Channel B Velocity W22B W22A ** Dual Accelerometer,…

  • Page 58: Full Scale Options

    3300/25 Dual Accelerometer Input Monitor Operation Manual 18.6 Full Scale Options Caution If you change full scale options, recalibrate both channels and replace the meter scale on the front panel. MONITOR CHANNEL A JUMPERS CHANNEL B JUMPERS FULL SCALE OPTIONS INSTALL REMOVE INSTALL…

  • Page 59: Main Board Buffered Out And Filter Options

    Section 18 — Appendix A–Main Board Options 18.7 Main Board Buffered Out and Filter Options BUFFERED TRANSDUCER OUTPUT CHANNEL A CHANNEL B INSTALL REMOVE INSTALL REMOVE * Buffered transducer output not filtered. W18C W18A Buffered transducer output filtered W18A W18C * Standard configuration.

  • Page 60: Appendix B-Filter Board Options Pwa 79562-01 And Pwa 105521-01

    3300/25 Dual Accelerometer Input Monitor Operation Manual 19. Appendix B–Filter Board Options PWA 79562-01 and PWA 105521-01 19.1 Identify Filter Board The configuration of the low pass filter is depends upon which filter board is being used. The filter board can be identified by looking at the PWA (Printed Wiring Assembly) number that is silkscreened on the component side of the board.

  • Page 61: Filter Board Jumper Locations

    Section 19 — Appendix B–Filter Board Options PWA 79562-01 and PWA 105521-01 19.2 Filter Board Jumper Locations…

  • Page 62: Integrator/Gain Stage Flow Path

    3300/25 Dual Accelerometer Input Monitor Operation Manual 19.3 Integrator/Gain Stage Flow Path This diagram is meant to illustrate the signal path through the Integrator/Gain Stage and the filters. It should not be used to determine jumper configurations. Follow the instructions in Section 19.4 determine the necessary jumper configuration.

  • Page 63: General Procedure

    Section 19 — Appendix B–Filter Board Options PWA 79562-01 and PWA 105521-01 19.4 General Procedure Follow these steps, in the order below, to program the monitor to operate with or without filters. After choosing the filter type and the location of the Integrator/Gain Stage you can check the signal flow path using figure 1 in section 19.3.

  • Page 64: Filter Board Options

    3300/25 Dual Accelerometer Input Monitor Operation Manual 19.5 Filter Board Options Choose the filter type by installing and removing the jumpers on the filter board as shown in the table below. See Section 19.2 for the location of the jumpers on the Filter Board.

  • Page 65: Integrator/Gain Stage Options

    Section 19 — Appendix B–Filter Board Options PWA 79562-01 and PWA 105521-01 19.6 Integrator/Gain Stage Options When measuring acceleration, configure the filter after the Integrator/Gain Stage. When measuring velocity, configure: the Low-Pass filter after the Integrator/Gain Stage and the High-Pass filter before the Integrator/Gain Stage Set the location of the Integrator/Gain Stage by installing or removing the jumpers on the main and filter boards as shown in the table below.

  • Page 66
    3300/25 Dual Accelerometer Input Monitor Operation Manual Channel B Integrator/Gain Stage Location CHANNEL B Main Board Filter Board INTEGRATOR/GAIN STAGE LOCATION INSTALL REMOVE INSTALL REMOVE W41,60 *Integrator/Gain Stage with W61,85 W5B,3B W3A,3C NO Filtering W3A,3C W61,85 **Filter after the W41,60 Integrator/Gain Stage W3A,3C W41,60…
  • Page 67: High Pass Filter Options

    Section 19 — Appendix B–Filter Board Options PWA 79562-01 and PWA 105521-01 19.7 High Pass Filter Options Install the jumpers on the filter board as shown in this table. Select frequencies not listed in this table by using the procedure in Section 19.8.

  • Page 68
    3300/25 Dual Accelerometer Input Monitor Operation Manual CHANNEL A — CHANNEL B — 10020 10560 10980 11520 12060 12480 13020 13560 14040 14520 15060 16080 16500 17040 17520 18000 18540 29760 45300 1003 60180 2006 120360 2996 179760 R = REMOVE JUMPER, I = INSTALL JUMPER Use the procedure in the following section to set a high-pass corner frequency not listed in the table.
  • Page 69: Non Standard High Pass Filter Options

    Section 19 — Appendix B–Filter Board Options PWA 79562-01 and PWA 105521-01 19.8 Non Standard High Pass Filter Options Follow this procedure only if the desired high-pass corner frequency is not listed in the table in the previous section. Select a high-pass corner frequency, , in the range 3.7 Hz to 3008 Hz.

  • Page 70: Example High-Pass Filter Configuration

    3300/25 Dual Accelerometer Input Monitor Operation Manual 19.9 Example High-Pass Filter Configuration This example shows how to configure channel A with a high-pass filter that has a corner frequency, , of 24000 CPM (400 Hz). The High Pass Filter is located after the Integrator/Gain Stage.

  • Page 71
    Section 19 — Appendix B–Filter Board Options PWA 79562-01 and PWA 105521-01 Use the formula in step 3 of Section 19.8 to obtain a value for the multiplier, D. In this case: The result is D = 33.9 Step 4 of Section 19.8 requires that you convert D to the closest 8 bit binary integer.
  • Page 72: Low-Pass Freq. Configuration Table

    3300/25 Dual Accelerometer Input Monitor Operation Manual 19.10 Low-Pass Freq. Configuration Table Use the tables on the next four pages to select the low-pass corner frequency . The — 3dB frequency is 1.06 x . For frequencies not listed in this table, follow the procedure in the following section.

  • Page 73
    Section 19 — Appendix B–Filter Board Options PWA 79562-01 and PWA 105521-01 CHANNEL A — CHANNEL B — 1440 1980 2520 2940 3540 3960 4440 5040 5520 5880 6480 6960 7500 7980 8520 9120 9600 10080 11040 12120 12960 14160 15000 15960 17040…
  • Page 74
    3300/25 Dual Accelerometer Input Monitor Operation Manual CHANNEL A — CHANNEL B — 25020 27780 30000 32580 35280 37500 40560 45480 49980 55560 1000 60000 1087 65220 1163 69780 1250 75000 1351 81060 1515 90900 1667 100020 2083 124980 2500 150000 3333 199980…
  • Page 75
    Section 19 — Appendix B–Filter Board Options PWA 79562-01 and PWA 105521-01 CHANNEL A — CHANNEL B — 25020 27780 30000 32580 35280 37500 40560 45480 49980 55560 1000 60000 1087 65220 1163 69780 1250 75000 1351 81060 1515 90900 1667 100020 2083…
  • Page 76: Non Standard Low Pass Filter Options

    3300/25 Dual Accelerometer Input Monitor Operation Manual 19.11 Non Standard Low Pass Filter Options Use this procedure only if the desired low pass corner frequency is not listed in the table in the previous section. The procedure consists of these two parts: •…

  • Page 77
    Section 19 — Appendix B–Filter Board Options PWA 79562-01 and PWA 105521-01 5. Convert M to the closest 8 bit binary integer M0 to M7. 6. Set the anti-aliasing filter corner frequency, Install/Remove jumpers for the multiplier value M and constant K, according to the following table.
  • Page 78: Setting The Low-Pass Corner Frequency

    3300/25 Dual Accelerometer Input Monitor Operation Manual 19.11.2 Setting the Low-Pass Corner Frequency Select a value for clock frequency (fCLK) from this list. We recommend that you start with 3.58 MHZ. Calculate the divider ratio D using this equation. is The clock frequency, f , (in Hz) is selected in step 1 and f is the desired low pass corner frequency (in Hz).

  • Page 79
    Section 19 — Appendix B–Filter Board Options PWA 79562-01 and PWA 105521-01 Set the jumpers for the input clock frequency ( ) according to this table. R = REMOVE JUMPER, I = INSTALL JUMPER SWITCHED CAPACITOR FILTER INPUT CLOCK JUMPER TABLE CHANNEL A — CHANNEL B -…
  • Page 80: Divider Ratio Table

    3300/25 Dual Accelerometer Input Monitor Operation Manual 19.12 Divider Ratio Table CHANNEL CHANNEL DIVIDER DIVIDER RATIO D RATIO D 2048 R = REMOVE JUMPER, I = INSTALL JUMPER…

  • Page 81: Example Low-Pass Filter Configuration

    Section 19 — Appendix B–Filter Board Options PWA 79562-01 and PWA 105521-01 19.13 Example Low-Pass Filter Configuration This example shows how to configure channel B with a low-pass filter that has a corner frequency, , of 7500 CPM (125 Hz). (The resulting -3dB point is at 1.06 x or 7950 CPM (132.5 Hz).

  • Page 82
    3300/25 Dual Accelerometer Input Monitor Operation Manual Calculate the multiplier value M. In this case: Convert M to the closest 8 bit binary integer. The closest integer to 32.57 is 33, and the 8 bit binary representation is 00100001. M7 is the most significant bit (MSB), and M0 is the least significant bit (LSB).
  • Page 83
    Section 19 — Appendix B–Filter Board Options PWA 79562-01 and PWA 105521-01 Calculate D with = 1 MHZ. 1000000 × There is not a match for D = 200 within ±1 in the Divider Ratio Table so select = 500 kHz. Calculate D with = 500 kHz.
  • Page 84: Band-Pass Filters

    3300/25 Dual Accelerometer Input Monitor Operation Manual 19.14 Band-Pass Filters A band-pass filter consists of cascaded high-pass and low-pass filters. To configure the Band-Pass filter, follow the instructions for programming the high-pass and low-pass filters. The center frequency of the bandpass filter is given by: f ×…

  • Page 85: Test Filter Option

    Section 19 — Appendix B–Filter Board Options PWA 79562-01 and PWA 105521-01 19.15 Test Filter Option This procedure verifies filter settings by using a function generator to simulate a signal with an amplitude equal to full scale at the -3dB frequency. Since the filter attenuates a signal with this frequency by 3dB, the monitor output should be 65% to 75% of full scale.

  • Page 86
    3300/25 Dual Accelerometer Input Monitor Operation Manual Adjust the settings on the function generator according to this table: PARAMETER SETTING wave form sine wave DC offset -7.5 Vdc filter corner frequency, frequency to test high pass filters (1.06) x (f to test low pass filters amplitude See step 5…
  • Page 87
    Section 19 — Appendix B–Filter Board Options PWA 79562-01 and PWA 105521-01 Step 5a continued: Step 5b continued: For Full Scale Range options 01, 02, For Full Scale Range options 05, 06, 03, 04, 11, 12, 13, 14 15, 16, 17 For example, if the Full Scale Range For example if the Full Scale Range option is 11, set the amplitude to 204…
  • Page 88
    3300/25 Dual Accelerometer Input Monitor Operation Manual The bargraph reading may be slightly lower if you have a Low Pass Filter with a corner frequency above 13.7 kHz. The reading will be lowest when the corner frequency is at its highest setting, 22.372 kHz.
  • Page 89: Test Filter Option (Alternate Procedure)

    Section 19 — Appendix B–Filter Board Options PWA 79562-01 and PWA 105521-01 19.16 Test Filter Option (Alternate Procedure) This procedure should only be used when your Full Scale Range Option is 05, 06, 15, 16, or 17 (see Section 8.2) and the full scale amplitude calculated in step 5b of the main procedure…

  • Page 90
    3300/25 Dual Accelerometer Input Monitor Operation Manual Configure the main board as follows to change the Gain Stage back to an Integrator Stage: Channel A: Install Remove W6B,C Channel B: Install Remove W3D,E Choose an integrator test frequency according to the following criteria: The test frequency must be within the passband of the filter.
  • Page 91
    Section 19 — Appendix B–Filter Board Options PWA 79562-01 and PWA 105521-01 Verify that the front panel bargraph reads 85% to 95% of full scale range. The figure below shows a monitor bargraph reading 90% of full scale. Return to step 7 of the main procedure (Section 19.15).
  • Page 92: Appendix C-Filter Board Options Pwa 148921-01

    3300/25 Dual Accelerometer Input Monitor Operation Manual 20. Appendix C–Filter Board Options PWA 148921-01 20.1 Identify Filter Board The configuration of the low pass filter is depends upon which filter board is being used. The filter board can be identified by looking at the PWA (Printed Wiring Assembly) number that is silkscreened on the component side of the board.

  • Page 93: Filter Board Jumper Locations

    Section 20 — Appendix C–Filter Board Options PWA 148921-01 20.2 Filter Board Jumper Locations…

  • Page 94: Integrator/Gain Stage Flow Path

    3300/25 Dual Accelerometer Input Monitor Operation Manual 20.3 Integrator/Gain Stage Flow Path This diagram is meant to illustrate the signal path through the Integrator/Gain Stage and the filters. It should not be used to determine jumper configurations. Follow the instructions in Section 20.4 to determine the necessary jumper configuration.

  • Page 95: General Procedure

    Section 20 — Appendix C–Filter Board Options PWA 148921-01 20.4 General Procedure Follow these steps, in the order below, to program the monitor to operate with or without filters. After choosing the filter type and the location of the Integrator/Gain Stage you can check the signal flow path using Figure 1 Section…

  • Page 96: Filter Board Options

    3300/25 Dual Accelerometer Input Monitor Operation Manual 20.5 Filter Board Options Choose the filter type by installing and removing the jumpers on the filter board as shown in the table below. See Section 20.2 for the location of the jumpers on the Filter Board.

  • Page 97: Integrator/Gain Stage Options

    Section 20 — Appendix C–Filter Board Options PWA 148921-01 20.6 Integrator/Gain Stage Options When measuring acceleration, configure the filter after the Integrator/Gain Stage. When measuring velocity, configure: the Low-Pass filter after the Integrator/Gain Stage and the High-Pass filter before the Integrator/Gain Stage Set the location of the Integrator/Gain Stage by installing or removing the jumpers on the main and filter boards as shown in the table below.

  • Page 98
    3300/25 Dual Accelerometer Input Monitor Operation Manual Channel B Integrator/Gain Stage Location CHANNEL B Main Board Filter Board INTEGRATOR/GAIN STAGE LOCATION INSTALL REMOVE INSTALL REMOVE W41,60 *Integrator/Gain Stage with W61,85 W5B,3B W3A,3C NO Filtering W3A,3C W61,85 **Filter after the W41,60 Integrator/Gain Stage W3A,3C W41,60…
  • Page 99: High Pass Filter Options

    Section 20 — Appendix C–Filter Board Options PWA 148921-01 20.7 High Pass Filter Options Install the jumpers on the filter board as shown in this table. Select frequencies not listed in this table by using the procedure in Section 20.7. CHANNEL A- CHANNEL B- 12.5…

  • Page 100
    3300/25 Dual Accelerometer Input Monitor Operation Manual CHANNEL A — CHANNEL B — 10020 10560 10980 11520 12060 12480 13020 13560 14040 14520 15060 16080 16500 17040 17520 18000 18540 29760 45300 1003 60180 2006 120360 2996 179760 R = REMOVE JUMPER, I = INSTALL JUMPER Use the procedure in the following section to set a high-pass corner frequency not listed in the table.
  • Page 101: Non Standard High Pass Filter Options

    Section 20 — Appendix C–Filter Board Options PWA 148921-01 20.8 Non Standard High Pass Filter Options Follow this procedure only if the desired high-pass corner frequency is not listed in the table in the previous section. Select a high-pass corner frequency, , in the range 3.7 Hz to 3008 Hz.

  • Page 102: Example High-Pass Filter Configuration

    3300/25 Dual Accelerometer Input Monitor Operation Manual 20.9 Example High-Pass Filter Configuration This example shows how to configure channel A with a high-pass filter that has a corner frequency, , of 24000 CPM (400 Hz). The High Pass Filter is located after the Integrator/Gain Stage.

  • Page 103
    Section 20 — Appendix C–Filter Board Options PWA 148921-01 Use the formula in step 3 of Section 20.8 to obtain a value for the multiplier, D. In this case: The result is D = 33.9 Step 4 of Section 20.8 requires that you convert D to the closest 8 bit binary integer.
  • Page 104: Low Pass Filter Options

    3300/25 Dual Accelerometer Input Monitor Operation Manual 20.10 Low Pass Filter Options Configure the low pass filters using the following tables. The jumper settings at the tops of the pages apply to all frequencies (rotational speeds) on their respective pages. All possible cutoff frequencies are listed.

  • Page 105
    Section 20 — Appendix C–Filter Board Options PWA 148921-01 Page is blank…
  • Page 106
    3300/25 Dual Accelerometer Input Monitor Operation Manual Low Pass Filter Options W100 W101 W102 W103 Ch. A W200 W201 W202 W203 Ch. B Ch. A Ch. B 1380 1860 2340 2820 3300 3780 4260 4680 5160 5640 6120 6600 7020 7560 7980 8460…
  • Page 107
    Section 20 — Appendix C–Filter Board Options PWA 148921-01 Low Pass Filter Options (Continued) Ch. A W104 W105 W106 W107 W108 W109 W110 W111 Ch. B W204 W205 W206 W207 W208 W209 W210 W211 W112 W113 W114 W115 W116 W117 W118 Ch.
  • Page 108
    3300/25 Dual Accelerometer Input Monitor Operation Manual Low Pass Filter Options (Continued) W100 W101 W102 W103 Ch. A W200 W201 W202 W203 Ch. B Ch. A Ch. B 16440 16920 17340 17820 18300 18780 19260 19740 20220 20640 21600 22080 22560 23040 23520…
  • Page 109
    Section 20 — Appendix C–Filter Board Options PWA 148921-01 Low Pass Filter Options (Continued) Ch. A W104 W105 W106 W107 W108 W109 W110 W111 Ch. B W204 W205 W206 W207 W208 W209 W210 W211 W112 W113 W114 W115 W116 W117 W118 Ch.
  • Page 110
    3300/25 Dual Accelerometer Input Monitor Operation Manual Low Pass Filter Options (Continued) W100 W101 W102 W103 Ch. A W200 W201 W202 W203 Ch. B Ch. A Ch. B 31440 31920 32400 32880 33300 33840 34260 34740 35220 35700 36180 36600 37080 37560 38040…
  • Page 111
    Section 20 — Appendix C–Filter Board Options PWA 148921-01 Low Pass Filter Options (Continued) Ch. A W104 W105 W106 W107 W108 W109 W110 W111 Ch. B W204 W205 W206 W207 W208 W209 W210 W211 W112 W113 W114 W115 W116 W117 W118 Ch.
  • Page 112
    3300/25 Dual Accelerometer Input Monitor Operation Manual Low Pass Filter Options (Continued) W100 W101 W102 W103 Ch. A W200 W201 W202 W203 Ch. B Ch. A Ch. B 45540 46020 46500 46920 47400 47880 48360 48840 49320 49800 50220 50700 51180 51660 52140…
  • Page 113
    Section 20 — Appendix C–Filter Board Options PWA 148921-01 Low Pass Filter Options (Continued) Ch. A W104 W105 W106 W107 W108 W109 W110 W111 Ch. B W204 W205 W206 W207 W208 W209 W210 W211 W112 W113 W114 W115 W116 W117 W118 Ch.
  • Page 114
    3300/25 Dual Accelerometer Input Monitor Operation Manual Low Pass Filter Options (Continued) W100 W101 W102 W103 Ch. A W200 W201 W202 W203 Ch. B Ch. A Ch. B 59160 59640 R = REMOVE JUMPER, I = INSTALL JUMPER. This table is two pages wide.
  • Page 115
    Section 20 — Appendix C–Filter Board Options PWA 148921-01 Low Pass Filter Options (Continued) Ch. A W104 W105 W106 W107 W108 W109 W110 W111 Ch. B W204 W205 W206 W207 W208 W209 W210 W211 W112 W113 W114 W115 W116 W117 W118 Ch.
  • Page 116
    3300/25 Dual Accelerometer Input Monitor Operation Manual Low Pass Filter Options (Continued) W100 W101 W102 W103 Ch. A W200 W201 W202 W203 Ch. B Ch. A Ch. B 1002 60120 1042 62520 1082 64920 1123 67380 1163 69780 1203 72180 1243 74580 1282…
  • Page 117
    Section 20 — Appendix C–Filter Board Options PWA 148921-01 Low Pass Filter Options (Continued) Ch. A W112 W113 W114 W115 W116 W117 W118 Ch. B W212 W213 W214 W215 W216 W217 W218 W104 W105 W106 W107 W108 W109 W110 W111 Ch.
  • Page 118
    3300/25 Dual Accelerometer Input Monitor Operation Manual Low Pass Filter Options (Continued) W100 W101 W102 W103 Ch. A W200 W201 W202 W203 Ch. B Ch. A Ch. B 2405 144300 2445 146700 2485 149100 2525 151500 2564 153840 2604 156240 2644 158640 2684…
  • Page 119
    Section 20 — Appendix C–Filter Board Options PWA 148921-01 Low Pass Filter Options (Continued) Ch. A W112 W113 W114 W115 W116 W117 W118 Ch. B W212 W213 W214 W215 W216 W217 W218 W104 W105 W106 W107 W108 W109 W110 W111 Ch.
  • Page 120
    3300/25 Dual Accelerometer Input Monitor Operation Manual Low Pass Filter Options (Continued) W100 W101 W102 W103 Ch. A W200 W201 W202 W203 Ch. B Ch. A Ch. B 3807 228420 3846 230760 3886 233160 3926 235560 3966 237960 4007 240420 4047 242820 4087…
  • Page 121
    Section 20 — Appendix C–Filter Board Options PWA 148921-01 Low Pass Filter Options (Continued) Ch. A W112 W113 W114 W115 W116 W117 W118 Ch. B W212 W213 W214 W215 W216 W217 W218 W104 W105 W106 W107 W108 W109 W110 W111 Ch.
  • Page 122
    3300/25 Dual Accelerometer Input Monitor Operation Manual Low Pass Filter Options (Continued) W100 W101 W102 W103 Ch. A W200 W201 W202 W203 Ch. B Ch. A Ch. B 5208 312480 5248 314880 5289 317340 5329 319740 5369 322140 5409 324540 5449 326940 5489…
  • Page 123
    Section 20 — Appendix C–Filter Board Options PWA 148921-01 Low Pass Filter Options (Continued) Ch. A W112 W113 W114 W115 W116 W117 W118 Ch. B W212 W213 W214 W215 W216 W217 W218 W104 W105 W106 W107 W108 W109 W110 W111 Ch.
  • Page 124
    3300/25 Dual Accelerometer Input Monitor Operation Manual Low Pass Filter Options (Continued) W100 W101 W102 W103 Ch. A W200 W201 W202 W203 Ch. B Ch. A Ch. B 6611 396660 6651 399060 6691 401460 6732 403920 6772 406320 6812 408720 6852 411120 6892…
  • Page 125
    Section 20 — Appendix C–Filter Board Options PWA 148921-01 Low Pass Filter Options (Continued) Ch. A W112 W113 W114 W115 W116 W117 W118 Ch. B W212 W213 W214 W215 W216 W217 W218 W104 W105 W106 W107 W108 W109 W110 W111 Ch.
  • Page 126
    3300/25 Dual Accelerometer Input Monitor Operation Manual Low Pass Filter Options (Continued) W100 W101 W102 W103 Ch. A W200 W201 W202 W203 Ch. B Ch. A Ch. B 8014 480840 8054 483240 8094 485640 8134 488040 8174 490440 8214 492840 8254 495240 8294…
  • Page 127
    Section 20 — Appendix C–Filter Board Options PWA 148921-01 Low Pass Filter Options (Continued) Ch. A W112 W113 W114 W115 W116 W117 W118 Ch. B W212 W213 W214 W215 W216 W217 W218 W104 W105 W106 W107 W108 W109 W110 W111 Ch.
  • Page 128
    3300/25 Dual Accelerometer Input Monitor Operation Manual Low Pass Filter Options (Continued) W100 W101 W102 W103 Ch. A W200 W201 W202 W203 Ch. B Ch. A Ch. B 9416 564960 9456 567360 9496 569760 9536 572160 9576 574560 9615 576900 9655 579300 9695…
  • Page 129
    Section 20 — Appendix C–Filter Board Options PWA 148921-01 Low Pass Filter Options (Continued) Ch. A W112 W113 W114 W115 W116 W117 W118 Ch. B W212 W213 W214 W215 W216 W217 W218 W104 W105 W106 W107 W108 W109 W110 W111 Ch.
  • Page 130
    3300/25 Dual Accelerometer Input Monitor Operation Manual Low Pass Filter Options (Continued) W100 W101 W102 W103 Ch. A W200 W201 W202 W203 Ch. B Ch. A Ch. B 10256 615360 10416 624960 10576 634560 10736 644160 10899 653940 11059 663540 11219 673140 11379…
  • Page 131
    Section 20 — Appendix C–Filter Board Options PWA 148921-01 Low Pass Filter Options (Continued) Ch. A W112 W113 W114 W115 W116 W117 W118 Ch. B W212 W213 W214 W215 W216 W217 W218 W104 W105 W106 W107 W108 W109 W110 W111 Ch.
  • Page 132
    3300/25 Dual Accelerometer Input Monitor Operation Manual Low Pass Filter Options (Continued) W100 W101 W102 W103 Ch. A W200 W201 W202 W203 Ch. B Ch. A Ch. B 16347 980820 16507 990420 16670 1000200 16830 1009800 16990 1019400 17150 1029000 17312 1038720 17472…
  • Page 133
    Section 20 — Appendix C–Filter Board Options PWA 148921-01 Low Pass Filter Options (Continued) Ch. A W112 W113 W114 W115 W116 W117 W118 Ch. B W212 W213 W214 W215 W216 W217 W218 W104 W105 W106 W107 W108 W109 W110 W111 Ch.
  • Page 134: Band-Pass Filters

    3300/25 Dual Accelerometer Input Monitor Operation Manual 20.11 Band-Pass Filters A band-pass filter consists of cascaded high-pass and low-pass filters. To configure the Band-Pass filter, follow the instructions for programming the high-pass and low-pass filters. The center frequency of the bandpass filter is given by: f ×…

  • Page 135: Test Filter Option

    Section 20 — Appendix C–Filter Board Options PWA 148921-01 20.12 Test Filter Option This procedure verifies filter settings by using a function generator to simulate a signal with an amplitude equal to full scale at the -3dB frequency. Since the filter attenuates a signal with this frequency by 3dB, the monitor output should be 65% to 75% of full scale.

  • Page 136
    3300/25 Dual Accelerometer Input Monitor Operation Manual Adjust the settings on the function generator according to this table: PARAMETER SETTING wave form sine wave DC offset -7.5 Vdc filter corner frequency, frequency to test high pass filters filter corner frequency, f to test low pass filters amplitude See step 5…
  • Page 137
    Section 20 — Appendix C–Filter Board Options PWA 148921-01 Step 5a continued: Step 5b continued: For Full Scale Range options 05, 06, 15, 16, 17 For Full Scale Range options 01, 02, 03, 04, 11, 12, 13, 14 For example if the Full Scale Range option is 06 and the corner frequency is 53 Hz, calculate the amplitude like this: Amplitude (mVpk) =(3.25 mVpk/Hz)X(53 Hz)
  • Page 138
    3300/25 Dual Accelerometer Input Monitor Operation Manual The bargraph reading may be slightly lower if you have a Low Pass Filter with a corner frequency above 13.7 kHz. The reading will be lowest when the corner frequency is at its highest setting, 22.372 kHz.
  • Page 139: Test Filter Option (Alternate Procedure)

    Section 20 — Appendix C–Filter Board Options PWA 148921-01 20.13 Test Filter Option (Alternate Procedure) This procedure should only be used when your Full Scale Range Option is 05, 06, 15, 16, or 17 (see Section 8.2) and the full scale amplitude calculated in step 5b of the main procedure (Section 20.12) is greater than 3.5V or too small to set up accurately on your…

  • Page 140
    3300/25 Dual Accelerometer Input Monitor Operation Manual Configure the main board as follows to change the Gain Stage back to an Integrator Stage: Channel A: Install Remove W6B,C Channel B: Install Remove W3D,E Choose an integrator test frequency according to the following criteria: The test frequency must be within the passband of the filter.
  • Page 141
    Section 20 — Appendix C–Filter Board Options PWA 148921-01 Verify that the front panel bargraph reads 85% to 95% of full scale range. The figure below shows a monitor bargraph reading 90% of full scale. Return to step 7 of the main procedure (Section 20.12).
  • Page 142: Appendix D-Integrated Signals

    3300/25 Dual Accelerometer Input Monitor Operation Manual 21. Appendix D–Integrated Signals 21.1 Integrator Response The integrator circuit converts a 100 mV/g acceleration signal to a 500 mV/in/sec velocity signal. The 0 dB (unity gain) frequency of the integrator occurs at approximately 307 HZ.

  • Page 143: Integrated Buffered Output Calculation

    Section 21 — Appendix D–Integrated Signals 21.2 Integrated Buffered Output Calculation This section shows how to calculate the buffered output voltage for a transducer or function generator signal that is being integrated by the monitor. The formula only applies when the unfiltered signal is at the buffered output. For an unfiltered buffered output, all filters should be located after the Integrator/Gain Stage.

  • Page 144: Sample Calculation, Buffered Output

    3300/25 Dual Accelerometer Input Monitor Operation Manual 21.2.1 Sample Calculation, Buffered Output Monitor is configured as: BB or CC option 16 (50 mm/sec (peak)) Input vibration level is: 1g (peak) Input signal frequency is: 100 Hz = 6000 CPM Transducer scale factor is: 100 mV/g Step 1.

  • Page 145: Integrated Meter Reading Calculations

    Section 21 — Appendix D–Integrated Signals Entering component values and simplifying we get: Vout × × × × × × Taking the magnitude, we have: Vout 009097 × 21.3 Integrated Meter Reading Calculations This section shows how to calculate the front panel meter reading for a transducer or function generator signal that is being integrated by the monitor.

  • Page 146: Conversion Factor Calculation

    3300/25 Dual Accelerometer Input Monitor Operation Manual If the transducer signal is simulated by a function generator, Vsig is the peak or RMS signal level. Calculate the front panel meter reading: Vsig × Front Panel Meter ading Where: ‘Vsig’ is the input voltage to monitor. ‘K’ is the conversion factor is from the tables below.

  • Page 147: Sample Calculation, Meter Output

    Section 21 — Appendix D–Integrated Signals 21.3.2 Sample Calculation, Meter Output Monitor is configured as: BB or CC option 16 (50 mm/sec (peak)) Input vibration level is: 1g (peak) Input signal frequency is: 100 Hz = 6000 CPM Transducer scale factor is: 100 mV/g Step 1.

  • Page 148: Recommended Spare Parts

    3300/25 Dual Accelerometer Input Monitor Operation Manual 22. Recommended Spare Parts To order replacement parts see the Specifications and Ordering Information section at the end this manual. The complete part number must be specified, as indicated on the identification decal. The part number is explained on page If you have a monitor that has been modified, the modification number must be specified on the parts order.

  • Page 149: Index

    Section 23 — Index 23. Index Accelerometer………………….2,22 Alarm……………………3,25 Alert……………………..3 AND Voting ………………….3,9,19 Buffered Output………………..3,21,53 Buffered Output, Integrated ………………137 Bypass, Channel ………………..2,26 Bypass, Danger …………….3,27,32,33,82,132 Calibration……………………. 37 Calibration with Filter / Integrator …………… 79,129 Channel Bypass………………….

  • Page 150
    3300/25 Dual Accelerometer Input Monitor Operation Manual LED, Alarm ……………………3 LED, Alert …………………..3,8,31,41 LED, Bypass ………………..2,3,7,26,27 LED, Danger ………………..3,9,27,41 LED, OK…………………..2,4,6,26,41 Meter Reading ………………..10,11,140 Not OK Channel………………….6 NOT OK Mode ………………..2,34,41 OK ………………………2,6 OK Limits ……………………2 OK Mode……………………2 OK Relay ……………………2 Options, Monitor ………………

На сегодняшний день номенклатура данных устройств охватывает широкий спектр вариантов для различных применений:

  • Система токовихревого датчика (преобразователя) Bently Nevada 3300 XL 8 мм
    Проксиметр Bently Nevada 330180. Характеризуется рядом улучшений по сравнению с предыдущими моделями. Конструкция 330180 позволяет использовать его на DIN-рейке, в условиях высокой плотности монтажа устройств. Также данный датчик можно установить на панели в традиционной конфигурации: Bently Nevada 330180 имеет монтажный участок с 4 отверстиями, идентичный более старым конструкциям Bently Nevada Proximitor.
    Наиболее популярная модель датчика Bently Nevada 330101 8 мм.
  • Система токовихревого датчика (преобразователя) Bently Nevada 3300 NSv. Предназначена для применений, когда расточные отверстия слишком малы для использования стандартных систем с датчиками виброперемещения.
  • Система токовихревого преобразователя 3300 XL 11 мм.
  • Токовихревой преобразователь для применения в условиях высоких температур (+350°C) 3300 XL 16 мм.
  • 3300 XL 25 мм.
  • 3300 XL 50 мм.
  • Компактная независимая система для проведения бесконтактных измерений с датчиком виброперемещения PROXPAC* XL.

Проксиметры Bently Nevada являются отраслевыми стандартами качества, надежности и точности. Они полностью соответствуют требованиям API 670, обладают превосходной производительностью и взаимозаменяемостью в тяжелых условиях эксплуатации.

Понравилась статья? Поделить с друзьями:
  • Сульфат магния лекарственное средство инструкция по применению взрослым
  • Wi vibe chorus инструкция на русском
  • Ксм 509н руководство по эксплуатации
  • Volkswagen polo liftback 2020 руководство по ремонту
  • Альбен для индюков инструкция по применению