SUPPLY NETWORK ANALYZER
AR5-L
( Code M 80111 )
(CHECK-METER Program)
( Cod. M 80225 )
INSTRUCTION MANUAL
( M98110301-03-04A )
CIRCUTOR S.A.
(c)
Related Manuals for Circutor AR5-L
Summary of Contents for Circutor AR5-L
-
Page 1
SUPPLY NETWORK ANALYZER AR5-L ( Code M 80111 ) (CHECK-METER Program) ( Cod. M 80225 ) INSTRUCTION MANUAL ( M98110301-03-04A ) CIRCUTOR S.A. -
Page 2: Table Of Contents
5.4.- FILES Menu ………………18 5.4.1.- DIR: Directory …………….18 5.4.2.- DELETE: Deleting a file …………… 18 5.4.3.- FORMAT: Formatting the AR5-L internal memory ……. 19 5.5.- Menu OFF: Enable / Disable Password……….19 5.6.- Menu LANGUAGE …………….19…
-
Page 3
AR5-L COMMUNICATIONS …………… 28 TECHNICAL SPECIFICATIONS…………29 SAFETY WARNINGS …………….. 31 10.- MAINTENANCE……………… 31 11.- TECHNICAL SERVICE…………… 31 CABLE ARRANGEMENT …………..32 QUICK GUIDE (AR5-L) …………….. 33 C. QUICK GUIDE FOR AR5 — CHECK-METER……… 33 D. EXAMPLE OF TRANSFORMATION RELATIONS …….. 34… -
Page 4: Basic Instructions
1.3.- Connection instructions Before powering and connecting the analyzer check the following points: a) Supply voltage: Through and external power supplier set. Input mains 80 V a.c. – 265 V a.c. / output to AR5-L 12V d.c. b) Frequency : 45…65 Hz.
-
Page 5: Analyzer Startup
(LOAD PROGRAM). Press [ENTER] or wait for a while to confirm this operation. • Select the position to save the program into. • The AR5-L will perform a test to check that the cartridge has been properly connected. • If an inserted cartridge is detected, then the program will be loaded.
-
Page 6: Choice Of The Operation Mode Program
Page nº 2.2.- Choice of the operation mode program The AR5-L can hold in memory different operation mode programs. The choice of the program to be used is done when starting the AR5-L up. • Turn the AR5-L on. •…
-
Page 7: Connection Modes
————— SUPPLY NETWORK ANALYZER AR5-L ———— Page nº 3.- CONNECTION MODES A.- THREE-PHASE MODE CONNECTION DIAGRAM B.- SINGLE-PHASE MODE CONNECTION DIAGRAM…
-
Page 8
————— SUPPLY NETWORK ANALYZER AR5-L ———— Page nº C.- ARON MODE CONNECTION DIAGRAM… -
Page 9: Data Visualization On Display
Energy values are partial values. The value is always reset to zero when accessing this screen. These values are not accumulated. Pressing the key [SET] from this screen m the set-up menu is accessed. When powering the AR5-L on, the display will show: CHECK-METER INST…
-
Page 10: Screen For Energy Meter Check
————— SUPPLY NETWORK ANALYZER AR5-L ———— Page nº Inductive reactive power: The inductive reactive power is calculated from instantaneous voltage and current data. The readout gives the instantaneous values of the inductive reactive power of each phase and also the three phase total instantaneous inductive reactive power, which is the addition of each phase value.
-
Page 11: Warning Messages
5.6.-). 5.1.- Set-up of Instantaneous Values To accessing AR5-L setup options press the key [SET], on the instantaneous values screen The analyzer will then inquiry for a password that consists of a key sequence to be pressed (the user has 15 seconds to press this sequence). If the…
-
Page 12
————— SUPPLY NETWORK ANALYZER AR5-L ———— Page nº All programs have an independent setup, therefore, the setup must be always check to ensure a proper operation, since any modification will only affect the active operation program. Diverse setting MENUS are available:… -
Page 13: Setup Menu
————— SUPPLY NETWORK ANALYZER AR5-L ———— Page nº 5.1.1.- SETUP menu The AR5-L meter can be user-configured to different performances involving its data analysis and recording modes, as it is followed shown: SETUP MEASURE COMM SETUP menu. CLOCK PASSWORD RECALL…
-
Page 14: 1.- Wiring: Circuit Type
AR5-L analyzer (Never directly connect the 5 A signal to the AR5-L.). For this case, the C.T. primary must be set at the primary value of the C.T. used for measuring purposes.
-
Page 15: Clock: Internal Clock
————— SUPPLY NETWORK ANALYZER AR5-L ———— Page nº Though keys [6], [5] the value of the selected position is increased or decreased. [ENTER] to validate the total value or [ESC] to exit with no modification. 5.1.4.- CLOCK: Internal clock Use this section to set the analyzer internal clock in time: date / time and displaying format.
-
Page 16: Recall: Read Configuration
A confirmation is requested: “Recall Setup sure <yes> or <no>“. With keys [4] & [3] select yes or no, and then press [ENTER]. A “Standard” operation program for the AR5-L is available to be user-recalled. Its features are: — C.T. Ratio (SET + A) — V.T.
-
Page 17: Display Menu
… 5.2.1.- CONTRAST: Screen contrast The user can here vary the contrast of the AR5-L display: With the [4] you can intensify the display contrast and with the key [3] this can be lowered: CONTRAST 5.2.2.- POWER FACTOR…
-
Page 18: Files Menu
Page nº 5.3.- FILES Menu Non-volatile AR5-L internal memory is storing data up to its maximum capacity. Once full, no new data will not be saved in, nor stored data will be lost (provided no incorrect operation is done). When memory is full, the display will show: «MEMORY FULL».
-
Page 19: Format: Formatting The Ar5-L Internal Memory
5.4.- Menu OFF: Enable / Disable Password. In order to avoid an accidental manipulation of the analyser, the AR5-L can be set to request for a password when the user wants to turn it off.
-
Page 20: Setup For Energy Meter Check
6. RECORD: To save in memory the record of the performed check. 7. This section will show the real value measured by the AR5-L and also the value that the CHECK-METER should have measured according to the user-programmed values (points: 3, 4 &…
-
Page 21: Operation Mode
————— SUPPLY NETWORK ANALYZER AR5-L ———— Page nº 6.- Operation mode When checking energy meters it is advisable to: • For any type of energy meter: To perform the energy meter check when the installation is at full operation conditions. The higher the consumption is, the higher the check reliability will be.
-
Page 22: Checking Mechanic Energy Meters
————— SUPPLY NETWORK ANALYZER AR5-L ———— Page nº 7.- Checking energy meters 7.1.- Checking mechanic energy meters AR5 CHECK-METER (1) User’s data User Name 1/1V 5/5A (2) P.T. and C.T. ratios (3) Check of energy meters TURNS/IMP (4) Check of number turns or pulses…
-
Page 23
————— SUPPLY NETWORK ANALYZER AR5-L ———— Page nº 7.- During some moments of data recording: 8.- You will see again at the bottom of the screen: STOP 9.- The energy meter checking process will be stopped when pressing again [ENTER]. -
Page 24: Checking Electronic Energy Meters
————— SUPPLY NETWORK ANALYZER AR5-L ———— Page nº 7.2.- Checking electronic energy meters AR5 CHECK-METER (1) User’s data User Name 1/1V 5/5A (2) P.T. and C.T. ratios (3) Check of energy meters TURNS/IMP nTURNS? kWh START (5) Check start and end energy test…
-
Page 25
————— SUPPLY NETWORK ANALYZER AR5-L ———— Page nº 7.- During some moments of data recording 8.- You will see again at the bottom of the screen: STOP 9.- The energy meter checking process will be stopped when pressing again [ENTER]. -
Page 26: Checking Electronic Energy Meters Using The Optical Reader
————— SUPPLY NETWORK ANALYZER AR5-L ———— Page nº 7.3.- Checking electronic energy meters using the optical reader. It is possible to connect an optical reader (ref XXXXXXX) for those meters that have a LED. Connect the optical reader into AUX plugin…
-
Page 27
Page nº 6.- Connect the optical reader, if it is not connected yet , to the Ar5-l and align optical head with the LED of the meter. 7.- Press [ENTER] to start the energy meter checking process. After requesting a… -
Page 28: Ar5-L Communications
Perform the connection using the two wires factory-delivered with the AR5-L. One cable will link the AR5-L to the power supplier set, and another cable is a standard RS232 connector. When starting communication tasks take into account: •…
-
Page 29: Technical Specifications
————— SUPPLY NETWORK ANALYZER AR5-L ———— Page nº 9.- TECHNICAL SPECIFICATIONS Supply voltage: Through an external power supplier set 230 V a.c. (+10% / -15%) Frequency : 50…60 Hz Burden : 8 VA Operation temperature : 0 / 50 ºC…
-
Page 30
— 1000 case (with protection rubber CPR-1000) ….CODE M 89923 — 2000 case (with protection rubber CPR-2000) ….CODE M 89921 − Adapters — connector adapter AR5 clamp to AR5L ..……..CODE. M 89927 — Connector adapter AR5-L C-FLEX clamp to AR5-L ..CODE. M 89928… -
Page 31: Safety Warnings
11.- MAINTENANCE The AR5-L does not require any special maintenance. No adjustment, maintenance or repairing actions should be done over the instrument open and, should those are essential, high-qualified operators must perform them.
-
Page 32: Cable Arrangement
————— SUPPLY NETWORK ANALYZER AR5-L ———— Page nº A. CABLE ARRANGEMENT Different cables used with the AR5-L have following arrangements: • Communication cable RS232: PC — Power supplier set POWER SUPPLIER • Power supply/Communication: Power supplier set — AR5-L. POWER…
-
Page 33: Quick Guide (Ar5-L)
————— SUPPLY NETWORK ANALYZER AR5-L ———— Page nº B. QUICK GUIDE (AR5-L) Menu Description Options Standard Setup Measure Circuit Choice type of measuring circuit. Three-phase Three-phase Single-phase Tr. Rel Rel. V Voltage transformers ratio. Primary=1 Secondary=1 Rel. A Current transformers ratio.
-
Page 34: Example Of Transformation Relations
————— SUPPLY NETWORK ANALYZER AR5-L ———— Page nº D. EXAMPLE OF TRANSFORMATION RELATIONS Clamps connected in the secondary one 27000 V 500 A 110 V 5 A 5A clamps METER CHECK-METER USER 27000/110V 500/5 Clamps connected in the primary one…
(с) CIRCUTOR S.A.
1.1 Введение: проверьте комплектность поставки 4
1.2 Требования техники безопасности 4
1.3 Инструкции по подсоединению 4
1.4 Инструкции по эксплуатации 5
2. ОСНОВНЫЕ ХАРАКТЕРИСТИКИ АНАЛИЗАТОРА 6
2.1 Основные характеристики 6
Функции клавиатуры 11
3 Установка и запуск 11
3.1 Этапы запуска start-up 12
3.2 Схема соединения 13
3.3 Пуск анализатора AR5 18
3.4 Загрузка новой программы 20
3.5Выключение анализатора 21
3.6 Подсветка 21
3.7 Выбор рабочей программы 21
3.8 Зарядка батарей прибора 22
3.9 Экономия электроэнергии 22
4Вывод данных на экран 23
4.1 Основной экран 23
4.1.1 Экран мгновенных значений 23
4.1.2Экран максимальных и минимальных значений 24
4.2 Другие экраны 25
4.2.1 Вывод на экран 3 параметров в режиме большого экрана 25
4.2.2 Гистограмма 26
4.2.3 Осциллоскоп 27
4.2.4 Визуализация установленных параметров 31
4.3 Предупреждающие сообщения 31
5 Программирование анализатора 32
5.1 Меню уставки SETUP menu 33
5.1.1 Измерение 34
5.1.2 RECORD menu 35
5.1.3 COMM: параметры связи 41
5.1.4 CLOCK : встроенные часы 41
5.1.5 PASSWORD (ПАРОЛЬ): Защита уставок 42
5.1.6 RECALL: Считывание конфигурации 43
5.2 Меню DISPLAY 44
5.2.1 BAR.GR. 44
5.2.2 EXPAND 44
5.2.3 CONTRAST: Контрастность экрана 44
5.2.4 ANGLE: коэффициент мощности 44
5.3 RUN: Статус процесса записи данных 45
5.4 Меню FILES 45
5.4.2 DELETE: удаление файла 46
5.4.3 FORMAT : форматирование внутренней памяти прибора 46
5.5 Меню CLEAR: удаление данных 46
5.6 Mеню OFF: включить/отключить пароль 47
5.7 Меню LANGUAGE 47
6 СОЕДИНЕНИЯ AR5 48
7 Технические характеристики 48
Механические характеристики: 49
8 Требования техники безопасности 50
9 Техническое обслуживание 51
10 Замена батарейки 51
11 Сервисное обслуживание 52
1 Основные инструкции
Настоящее руководство предназначено для ознакомления пользователя с работой портативных анализаторов электропотребления моделей AR5 и AR5-L и наиболее полного использования всех свойств прибора.
Анализатор электропотребления был разработан с использованием самых современных технологий в области микроэлектроники и требований рынка в области измерений и регистрации электрических параметров промышленных электрических сетей.
Убедительная просьба прочесть настоящее руководство перед подключением анализатора для избежания неисправностей, вызванных неправильным подключением.
а) Соответствие модели анализатора спецификации вашего заказа.
Specifications:
|
Accompanying Data:
Circutor AR5-L Measuring Instruments PDF Quick Start Manual (Updated: Friday 24th of February 2023 07:28:41 AM)
Rating: 4.1 (rated by 83 users)
Compatible devices: CEM-C31-T1, QNA-303, CVM-C5 Series, CEM-C10, Wibeee Max, MPC-20, VLOG-10, CAVA-252.
Recommended Documentation:
Circutor AR5-L: Text of Quick Start Manual
(Ocr-Read Version Summary of Contents, UPD: 24 February 2023)
-
1, DESCRIPCIÓN1. Los analizadores de la serie AR5 y AR5L son instru- mentos de medida programables que miden, calculan y registran en memoria los principales parámetros eléctricos en redes industriales trifásicas. Este manual es una guía de instalación. Para más información, se puede descargar el manual completo en la página Web de CIRCUTOR: www.circutor.es ¡IMPORTANTE! Antes de ef…
-
2, PONER EN MARCHA EL EQUIPO2. Conexión de la batería2.1 Para conectar la batería, debe abrirse el compartimiento que se encuentra en la parte posterior del equipo (Fig. 1). Antes de abrir la tapa desconectar todas las conexiones de tensión y corriente. El conector solo entra en una posición, no forzar.• Volver a colocar la tapa• ¡IMPORTANTE! Antes de iniciar las mediciones…
-
3, AVVIARE IL DISPOSITIVO2. Collegamento della batteria2.1 Per collegare la batteria si deve aprire lo scomparto che si trova nella parte posteriore del dispositivo (Fig. 1). Prima di aprire il coperchio scollegare tutti i collegamento di tensione e corrente. Il connettore entra in una sola posizione, non bisogna • forzarlo. Rimettere il coperchio• IMPOR…
-
4, CONSIDERACIONES INICIALES DES-3. PUÉS DE LA PUESTA EN MARCHA Pulsar SET , entrar código según FIG.2 y: Seleccionar Idioma 3.1 (Tabla conf. 1) Programación de relación de transformado-3.2 res y pinzas (Tabla conf. 2) Congurar Fecha y Hora 3.3 (Tabla conf. 3) Borrar máximos, mínimos y contadores3.4 (Tabla conf. 4) Formatear la memoria 3.5 (Tabla conf. 5) Asignar nomb…
-
5, CONSIDERAZIONI INIZIALI DOPO 3. L’AVVIAMENTO Premere SET , inserire il codice in conformità alla FIG. 2 e: Selezionare la lingua 3.1 (Table conf. 1) Programmazione di rapporto di trasforma-3.2 tori e pinze (Table conf. 2) Congurare Data e Ora 3.3 (Table conf. 3) Cancellare massimi, minimi e contatori 3.4 (Table conf. 4) Formattare la memoria 3.5 (Table conf. 5) Assegna…
-
6, English Español Table conf. 1 PROGRAM A, B PROGRAMA A, B SP Seleccionar Idioma SETUP DISPLAY RUN FILES CLEAR OFF LANGUAGE English Español Default LANGUAGE CONFIG. PA NTALLA GRABAR FICHEROS BORRAR APAGADO IDIOMA English Español Defecto IDIOMA GB Language F Sélectionner Langue I Selezione lingua D Sprache auswählen Pt Seleccionar Idioma Table conf. 2 PROGR…
-
7, English Español Table conf. 8 PROGRAM A PROGRAMA A SP Selección de parámetros para gra- bar SETUP DISPLAY RUN FILES CLEAR OFF LANGUAJE SETUP SETUP MEASURE RECORD COMM CLOCK PASSWORD RECALL RECORD RECORD PERIOD TRIGGER NAME PA RAM PA RAM Selec. Param. 99max: INST MAX MIN HARM CONFIG. PA NTALLA GRABAR FICHEROS BORRAR APAGADO IDIOMA CONFIG. CONFIG. MEDIDA GRABAR COM. FECHA CODIGO DEFECTO GR…
-
8, Características técnicas Technical features Tensión de alimentación: Supply voltage: A través alimentador externo 100 V c.a. – 240 V c.a. / Through an external power supplier set 100 V a.c. … 240 V a.c. Bateria Battery 5 VHAA 1200 (Ni-MH) Frecuencia Frequency 50….60 Hz Consumo Burden 15 V·A Temperatura de trabajo Operation temperature 0 … 40 ºC Alti…
Circutor AR5-L: Recommended Instructions
23HF5473, 505-2571, DP42851, RVS-218637
-
112 mm Allen key X 19 104 mm Allen key X 1 3 mm Allen key X 12-1Wiring installation instructions2-2Installation instructionACBMotor oil indicator can be set up, install as two stroke motor oil indicator, or other positive(+12V) or negative actions’ indicator.YAMAHAHONDASUZUKIKAWASAKISYMKYMCOPGOMain power switch wire reference:PowerGroundBrownBrownBlackGreenThe color listed above may …
DB-01 6
-
CTME BASICO CONTADOR DE TIEMPO POR MONEDA O FICHA INSTALACIÓN ATENCIÓN: La instalación y el montaje de los aparatos eléctricos debe ser realizada por un instalador autorizado. — Retirar el cajón inferior, abrir la tapa superior e introducir los conductores por el taladro dispuesto para ello. — Conectar los conductores a la regleta siguiendo el esquema. Borne 1 …
CTME BASICO 2
-
OPERATORS MANUAL FOR MODEL 6634A RESISTANCE STANDARD NOTICE The contents and information contained in this manual are proprietary to Guildline Instruments Limited. They are to be used only as a guide to the operation and maintenance of the equipment with which this manual was issued and may not be duplicated or transmitted by any means, either in whole or in pa …
6634A Resistance Standard 22
-
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 cm0 1 2 3 4 5 6 7 8 9 00.05mmObject to be measured is positioned between these surfaces.Measures extremal dimensions. Move Slide to open and close.Measures the height of steps.Measures internal dimensions. Move Slide to open and close.Position surfaces inside object to be measured.①Measuring Surfa …
GHS Series 2
-
Agilent TechnologiesAgilent X-SeriesSignal AnalyzerN9079A TD-SCDMA with HSPA/8PSK Measurement Application Measurement GuideThis manual provides documentation for the following X-Series Analyzers:MXA Signal Analyzer N9020AEXA Signal Analyzer N9010A …
N9020A 107
-
IntroductionYour Gems DM21 Rate Meter with Total is one model in a family of 1/8 DIN unitswhich offers breakthrough display technology as well as easy-to-program single-lineparameters. Designed to provide instant visual feedback regarding an application’skey input value, the DM21 not only has a 0.71” high LED display (27% larger thanother 1/8 DIN units), but also …
DM21 Series 12
-
F-2600 & F-2700 Series Vortex Flow Meter Installation and Operation Guide11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 www.onicon.com • [email protected] / 19204 …
F-2600 Series 130
-
QuickNav MOISTURE METER Owner’s Manual Version 2.01 For Meters starting with Serial # 12545 Delmhorst Instrument Co. Rev 4 May, 2014 www.GlobalTestSupply.comFind Quality Products Online at: [email protected] …
QuickNav 12545 16
-
EyedroGREEN SOLUTIONS INC.®Quick Start GuideElectricity Monitoring System (EBEM1)Limited One Year WarrantyEyedro Green Solutions Inc. warrants this product for a period of one year from date of purchase for all defects in material and workmanship. Defective parts may be repaired or replaced, at the discretion of the manufacturer, during this period.Full warranty policy d …
EBEM1 2
Additional Information:
Popular Right Now:
Operating Impressions, Questions and Answers:
Loading…
SUPPLY NETWORK ANALYZER
AR5 and AR5-L
INSTRUCTION MANUAL
(M98151101-03-10B )
(c)CIRCUTOR S.A.
CONTENTS |
page |
|
1.- |
BASIC INSTRUCTIONS ……………………………………………………………… |
4 |
1.1.- Introduction: check the contents of your package…………………………… |
4 |
|
1.2.- Safety conditions……………………………………………………………………….. |
4 |
|
1.3.- Connection instructions………………………………………………………………. |
4 |
|
1.4.- Operation instructions………………………………………………………………… |
5 |
|
2.- |
ANALYZER MAIN FEATURES…………………………………………………….. |
6 |
2.1.- Basic features …………………………………………………………………………… |
6 |
|
2.2.- Other characteristics………………………………………………………………….. |
6 |
|
3.- |
KEYBOARD FUNCTIONS…………………………………………………………… |
9 |
4.- |
Installation AND START-UP ………………………………………………………… |
9 |
4.1.- Steps necessary for the START-UP …………………………………………….. |
9 |
|
4.2.- Connection diagram…………………………………………………………………. |
11 |
|
4.3.- Starting the analyzer up……………………………………………………………. |
16 |
|
4.4.- Loading a new program ……………………………………………………………. |
18 |
|
4.5.- Turn the analyzer off………………………………………………………………… |
19 |
|
4.6.- Back-light ……………………………………………………………………………….. |
19 |
|
4.7.- Choice of the working program ………………………………………………….. |
19 |
|
4.8.- Recharging the analyzer battery ………………………………………………… |
20 |
|
4.9.- Energy saving …………………………………………………………………………. |
20 |
|
5.- DATA VISUALIZATION ON DISPLAY…………………………………………. |
21 |
|
5.1.- Base screen……………………………………………………………………………. |
21 |
|
5.1.1.- Screen of instantaneous values……………………………………………. |
21 |
|
5.1.2.- Screen of maximum and minimum values …………………………….. |
22 |
|
5.2.- Other visualization screens……………………………………………………….. |
23 |
|
5.2.1.- Visualization of 3 parameters in a big size mode…………………….. |
23 |
|
5.2.2.- Bar graphs ………………………………………………………………………… |
24 |
|
5.2.3.- Oscilloscope………………………………………………………………………. |
25 |
|
5.2.3.1.- Three phases: Voltage — Current……………………………………… |
25 |
|
5.2.3.2.- Zoom…………………………………………………………………………… |
26 |
|
5.2.3.3.- Harmonic factorization. ………………………………………………….. |
27 |
|
5.2.4.- Setup visualization……………………………………………………………… |
29 |
|
5.3.- Warning messages ………………………………………………………………….. |
29 |
|
6.- |
PROGRAMMING THE ANALYZER…………………………………………….. |
30 |
2 |
6.1.- SETUP menu………………………………………………………………………….. |
31 |
|
6.1.1.- MEASURE ………………………………………………………………………… |
32 |
|
6.1.1.1.- WIRING: Circuit type……………………………………………………… |
32 |
|
6.1.1.2.- PT/CT : Transformation ratios…………………………………………. |
32 |
|
6.1.2.- RECORD menu …………………………………………………………………. |
32 |
|
6.1.2.1.- PERIOD: recording period ……………………………………………… |
33 |
|
6.1.2.2.- TRIGGER: Trigger conditions …………………………………………. |
34 |
|
6.1.2.3.- NAME: recording file name …………………………………………….. |
37 |
|
6.1.2.4.- PARAM: Choosing the parameters to be saved…………………. |
38 |
|
6.1.3.- COMM: Communication parameters……………………………………… |
39 |
|
6.1.4.- CLOCK: Internal clock ………………………………………………………… |
39 |
|
6.1.5.- PASSWORD: Safety setting. ……………………………………………….. |
40 |
|
6.1.6.- RECALL: Read configuration……………………………………………….. |
41 |
|
6.2.- DISPLAY menu……………………………………………………………………….. |
42 |
|
6.2.1.- BAR.GR……………………………………………………………………………. |
42 |
|
6.2.2.- EXPAND …………………………………………………………………………… |
42 |
|
6.2.3.- CONTRAST: Screen contrast ………………………………………………. |
42 |
|
6.2.4.- ANGLE……………………………………………………………………………… |
43 |
|
6.3.- RUN: data recording process status …………………………………………… |
43 |
|
6.4.- FILES Menu……………………………………………………………………………. |
43 |
|
6.4.1.- DIR: Directory ……………………………………………………………………. |
43 |
|
6.4.2.- DELETE: Deleting a file ………………………………………………………. |
43 |
|
6.4.3.- FORMAT: Formatting the analyzer internal memory………………… |
44 |
|
6.5.- CLEAR menu: Deleting data……………………………………………………… |
44 |
|
6.6.- Menu OFF: Enable / Disable Password………………………………………. |
45 |
|
6.7.- Menu LANGUAGE…………………………………………………………………… |
45 |
|
7.- |
ANALYZER COMMUNICATIONS ………………………………………………. |
45 |
8.- |
TECHNICAL SPECIFICATIONS…………………………………………………. |
46 |
9.- |
SAFETY WARNINGS……………………………………………………………….. |
48 |
10.- |
MAINTENANCE……………………………………………………………………….. |
49 |
11.- |
CHANGING THE BATTERY………………………………………………………. |
49 |
12.- |
TECHNICAL SERVICE……………………………………………………………… |
50 |
3
1.- BASIC INSTRUCTIONS
This manual is aimed to familiarize de user with the operation of the portable power analyzers model AR5-L and AR5 in order to get the best from its features.
These analyzers have been built with components incorporating the most advanced technology in microelectronics and offer benchtop features over the market in measurement and recording of electrical magnitudes in industrial power supply networks.
You are kindly requested to carefully read this manual before connecting and powering the analyzer in order to avoid irreversible damage, which might be caused by an improper connection.
1.1.- Introduction: check the contents of your package
After receiving the analyzer, please check the following points:
a)The analyzer model corresponds with your order specifications.
b)After unpacking, check that the instrument has not been damaged in transit.
c)The standard set includes the following items:
•Kit AR5-L or AR5
•1 Power supplier set 100 V a.c. – 240 V a.c. / 12 V d.c.
•1 Connection cord between the power supplier set and the main.
•1 Connection cable between the analyzer and the power supplier set.
•1 RS-232 communication cable.
•4 Voltage leads.
•4 Alligator clamps (3 in AR5 model).
•1 Instruction Manual.
•CD with the PC program
1.2.- Safety conditions
The manual you hold in your hands contains information and warnings about the analyzer that the user should respect in order to guarantee a proper operation of all the instrument functions and keep its safety conditions.
1.3.- Connection instructions
Before powering and connecting the analyzer check the following points:
a) Supply voltage: Through and external power supplier set.
Input mains 100 V a.c. – 240 V a.c. / output to AR5/AR5-L 12V d.c.
b) Frequency |
: 45…65 Hz. |
c)Maximum voltage at the voltage measuring circuit:
500 V a.c. Phase-to-neutral (CAT III)
4
d) Current measuring range: according to the Current clamp used
Current clamps |
Measuring range |
|
CP-2000-200 |
10 to 2000 A a.c. (switch at 2000) |
|
1 to 200 A a.c. (switch at 200) |
||
CPR-1000 |
5 to 1000 A a.c. |
|
CPR-500 |
2,5 to 500 A a.c. |
|
CP-100 (M1-U) |
0, 5 to 100 A a.c. |
|
CP-5 |
25 mA to 5 A a.c. |
|
Flexible clamp |
Measuring range |
C-FLEX 200-2000-20000 |
100 to 20000 A a.c (scale 20000 |
A) |
|
10 to 2000 A a.c. (scale 2000 A) |
|
1 to 200 A a.c. (scale 200 A) |
NOTE: It is advisable to measure near of full-scale value to get better accuracy.
1.4.- Operation instructions
The analyzer is a programmable instrument so offering diverse operation modes, which can be selected from the available programming menus (6.- PROGRAMMING THE ANALYZER).
Please read carefully the paragraphs involving (4.- Installation AND STARTUP 6.- PROGRAMMING THE ANALYZER) in order to select the most suitable operation mode for your requirements.
If the instrument is not used according to manufacturer’s specifications, the protection of the instrument can be damaged.
5
2.- ANALYZER MAIN FEATURES 2.1.- Basic features
The AR5 series analyzers are programmable instruments that measure, calculate and store to memory the main parameters of three phase electrical supply networks.
Clamp inputs (.. 2 V a.c.).*
IL3 |
IL2 |
IL1 |
IN |
|
VL3 |
VL2 |
VL1 |
N |
AUX |
* |
a.c. Voltage inputs
Power Supply: 12 V c.c. / Serial input
* IN only in AR5-L models
Setup: Analyzer’s setting is completed through a system of spreadable menus that provide a friendly-use and intuitive configuration process.
Data visualization: By means of a liquid crystal graphical display, 160 x 160 pixels and with backlight ability, the user can view instantaneous, maximum and minimum values of each parameter at each phase.
Internal battery: permits the user to accomplish with analysis works without the need of an external auxiliary power supply. The analyzer is equipped with an intelligent battery charging system, which expands the battery life span. For recharge the battery is necessary to connect the power supplier.
Installation: Analyzer is suitable for analysis works over any type of electric networks (single-phase, bi-phase, 3-wire and 4-wire).
Measuring: Measurement of average values of main electrical parameters, as well as, recording of maximum and minimum values. To execute these measurements, the analyzer is equipped with three a.c. voltage inputs and four a.c. current inputs (through current clamps ../ 2 V a.c.).
Data collection: The analyzer has a 1 Mb on-board memory to save into all the parameters measured or calculated by the analyzer, in order to be further retrieved from a PC.
PC software: together with the analyzer, it is also factory supplied a friendlyuse, powerful software that permits data downloading from the internal memory to a PC and a further complex analysis of recorded data.
2.2.- Other characteristics
6
—Small size, low weight, portable instrument.
—True R.M.S. measuring system.
—Instantaneous, maximum and minimum values of each discrete electric parameter.
—Electrical energy meters incorporated
—Harmonic measurement
—Neutral current measurement (only in AR5-L model)
—RS-232 communication to PC
—Ability of setting a recording threshold, so that data is only recorded in memory when measured values are not within the defined threshold (see Section 6.1.2.2.-TRIGGER: Trigger conditions).
—Automatic data collection in memory at regular user-definable periods.
Depending on the type of circuit under analysis, following enumerated parameters are measured and can be saved in memory:
NOTE: It’s not allow to save cosϕ data in memory. Only can be read on display.
•4-wire three-phase system:
Parameter |
Symbol |
L1 |
L2 |
L3 |
Three-phase value |
Phase-to-Neutral voltage |
V |
x |
x |
x |
|
Current |
A |
x |
x |
x |
x |
Neutral current |
IN |
x |
|||
(only in AR5-L model) |
|||||
Frequency |
Hz |
x |
|||
Active power |
kW |
x |
x |
x |
x |
Reactive power L |
kvarL |
x |
x |
x |
x |
Reactive power C |
kvarC |
x |
x |
x |
x |
Apparent power |
kVA |
x |
|||
Power factor |
PF |
x |
x |
x |
x |
Active energy |
kW h |
x |
x |
x |
x |
Reactive-energy (inductive) |
kvaLh |
x |
x |
x |
x |
Reactive-energy (capacitive) |
kvaCh |
x |
x |
x |
x |
Voltage harmonics |
x |
x |
x |
||
Current harmonics |
x |
x |
x |
||
Current Neutral harmonics |
x |
||||
(only in AR5-L model) |
7
•3-wire three-phase system:
Parameter |
Symbol |
L1-L2 |
L2-L3 |
L3-L1 |
Three-phase value |
Phase-to-Phase voltage |
V |
x |
x |
x |
|
Current |
A |
x |
x |
x |
x |
Frequency |
Hz |
x |
|||
Active power |
kW |
x |
x |
x |
x |
Reactive power L |
kvarL |
x |
x |
x |
x |
Reactive power C |
kvarC |
x |
x |
x |
x |
Apparent power |
x |
||||
Power factor |
PF |
x |
x |
x |
x |
Active energy |
kW h |
x |
x |
x |
x |
Reactive-energy (inductive) |
kvahL |
x |
x |
x |
x |
Reactive-energy (capacitive) |
kvahC |
x |
x |
x |
x |
Voltage harmonics |
x |
x |
x |
||
Current harmonics |
x |
x |
x |
• Single-phase system: |
|||||||||||
Parameter |
Symbol |
L1 |
|||||||||
Voltage |
V |
x |
|||||||||
Current |
A |
x |
|||||||||
Frequency |
Hz |
x |
|||||||||
Active power |
kW |
x |
|||||||||
Reactive power L |
kvarL |
x |
|||||||||
Reactive power C |
kvarL |
/(-C) |
x |
||||||||
Apparent power |
x |
||||||||||
Power factor |
PF |
x |
|||||||||
Active energy |
kW h |
x |
|||||||||
Reactive-energy (inductive) |
kvahL |
x |
|||||||||
Reactive-energy (capacitive) |
kvahC |
x |
|||||||||
Voltage harmonics |
x |
||||||||||
Current harmonics |
x |
||||||||||
• Bi-phase system: |
|||||||||||
Parameter |
Symbol |
L1-N |
L2-N |
Bi-phase |
|||||||
value |
|||||||||||
L1-L2 |
|||||||||||
Voltage |
V |
x |
x |
x |
|||||||
Current |
A |
x |
x |
x |
|||||||
Neutral current* |
IN |
x |
|||||||||
Frequency |
Hz |
x |
|||||||||
Active power |
kW |
x |
x |
x |
|||||||
Reactive power L |
kvarL |
x |
x |
x |
|||||||
Reactive power C |
kvarC |
x |
x |
x |
|||||||
Apparent power |
x |
||||||||||
Power factor |
PF |
x |
x |
x |
|||||||
Active energy |
kW h |
x |
|||||||||
Reactive-energy (inductive) |
kvahL |
x |
x |
x |
|||||||
Reactive-energy (capacitive) |
kvahC |
x |
x |
x |
|||||||
Voltage harmonics |
x |
x |
|||||||||
Current harmonics |
x |
x |
|||||||||
Neutral current harmonics |
x |
||||||||||
*only in AR5-L model |
8
3.- KEYBOARD FUNCTIONS
The analyzer has a 9 buttons keyboard to perform configuration and control actions of all the instrument options.
—[ON] to turn the analyzer on.
—[OFF] (Quick press) to turn on/off the display back-light.
—[OFF] (5 seconds press) to turn analyzer off.
—[6], [5], [4] & [3]. To select among several options.
—[SET] to access setting options.
—[ENTER] to validate a setting option or to program some parameters of the visualization screens.
—[ESC] to select different visualization screens or to exit the setting actions.
However, most of keys are double functional: The own instrument understands the meaning of the order at each case.
4.- Installation AND START-UP
The manual you hold in your hands contains information and warnings that the user should respect in order to guarantee a proper operation of all the instrument functions and keep its safety conditions.
If the instrument is not used according to manufacturer’s specifications, the protection of the instrument can be damaged. Note that with the instrument powered on, cover opening or elements removal actions may allow accessing dangerous parts. Therefore, before any adjustment, replacement, maintenance or repairing operation is carried out, the instrument must be disconnected from any power supply source.
When any protection failure is suspected to exist, the instrument must be immediately put out of service. Contact then with a qualified service representative.
4.1.- Steps necessary for the START-UP
9
For the Star-up of the equipment and to let it ready to begin to register is necessary to make the following steps.
1)Plug the battery, see point 11.-CHANGING THE BATTERY
2)Format the memory, see 6.4.3.-FORMAT: Formatting the analyzer internal memory
3)Set the analyzer in hour, see point 6.1.4.-CLOCK: Internal clock
4)Charge the battery by a period of minimum 14 hours. .
10
4.2.- Connection diagram
A.- CONNECTION DIAGRAM FOR THREE-PHASE — 4-WIRE – SYSTEM
This connection is only available for AR5-L model
( SET —> SETUP —> MEASURE —> WIRING —> 3Φ 4 WIRES) |
||||
L1 |
||||
L2 |
||||
L3 |
||||
N |
||||
IL3 |
IL2 |
IL1 |
IN |
|
VL3 |
VL2 |
VL1 |
N |
AUX |
11 |
B.- CONNECTION DIAGRAM FOR THREE-PHASE — 3-WIRE — SYSTEM.
( SET —> SETUP —> MEASURE —> WIRING —> 3Φ 3 WIRES )
L1
L2
L3
IL3 |
IL2 |
IL1 |
IN |
|
VL3 |
VL2 |
VL1 |
N |
AUX |
12
C.- CONNECTION DIAGRAM FOR THREE-PHASE — 3-WIRE (ARON)
( SET —> SETUP —> MEASURE —> WIRING —> 3 PT – 2 CT
L1
L2
L3
IL3 |
IL2 |
IL1 |
IN |
|
VL3 |
VL2 |
VL1 |
N |
AUX |
13
D.- CONNECTION DIAGRAM FOR SINGLE-PHASE — SYSTEM
( SET —> SETUP —> MEASURE —> WIRING —> 1Φ) |
||||
L1 |
||||
N |
||||
IL3 |
IL2 |
IL1 |
IN |
|
VL3 |
VL2 |
VL1 |
N |
AUX |
14 |
E.- CONNECTION DIAGRAM FOR BI-PHASE — SYSTEM
This connection is only available for AR5-L model
( SET —> SETUP —> MEASURE —> WIRING —> 1Φ Split ) |
||||
L1 |
||||
L2 |
||||
N |
||||
IL3 |
IL2 |
IL1 |
IN |
|
VL3 |
VL2 |
VL1 |
N |
AUX |
15 |
4.3.- Starting the analyzer up
Before connecting the instrument to the mains, please consider following points: 5) Supply voltage: 100 V a.c. – 240 V a.c. , 50… 60 Hz.
The instrument must be energized by a supply circuit with protection earth terminal.
6)Maximum input voltage at the voltage measuring circuit:
500 V a.c. phase-neutral (CAT III)
Use always the voltage leads factory-shipped with the instrument.
7)Burden: 15 VA.
Operation conditions:
—Operation temperature: 0 ºC to 40 ºC.
—Operation humidity: 80% for temperatures up to 31ºC decreasing linearly to 50% relative humidity at 40ºC.
9)Safety : Designed to meet protection category III 600V as per EN 61010.
10)Current measuring range: according to the current clamp used
Current clamps |
Measuring range |
CP-2000-200 clamp |
10 to 2000 A a.c. (scale 2000 A) |
1 to 200 A a.c. (scale 200 A) |
|
CPR-1000 clamp |
5 to 1000 A a.c. |
CPR-500 clamp |
2,5 to 500 A a.c. |
CP-100 (M1-U) clamp |
0´5 to 100 A a.c. |
CP-5 clamp |
25 mA to 5 A a.c. |
Flexible clamp |
Measuring range |
C-FLEX 200-2000-20000 |
100 to 20000 A a.c. (scale 20000 A) |
10 to 2000 A a.c. (scale 2000 A) |
|
1 to 200 A a.c. (scale 200 A) |
NOTE: It is always advisable to take measurements at the high range of the scale to obtain a better accuracy.
To start measurement works with the analyzer:
11)Connect to the main with the factory-shipped cables. Also connect the protection earth terminal to avoid possible disturbances over the analyzer.
12)Connect the voltage leads at each phase of the monitored system, as well as the neutral when it exists.
13)Connect the Current clamps at each phase conductor. Each current phase must coincide with its voltage phase.
14)Respect the connection modes shown at each diagram to correctly achieve powers, PF and energies readouts.
16
6.-
Operation mode ………………………………………………………………………. 21
7.-
AR5-L COMMUNICATIONS ……………………………………………………… 28
8.-
9.-
SAFETY WARNINGS ………………………………………………………………. 31
10.-
MAINTENANCE………………………………………………………………………. 31
11.-
TECHNICAL SERVICE…………………………………………………………….. 31
CABLE ARRANGEMENT ……………………………………………………………. 32
QUICK GUIDE (AR5-L) ………………………………………………………………. 33
Page
3
nº