Digital operator jnep 31 v инструкция

■ Functions of LCD digital operator

JNEP-31 LCD digital operator has 2 modes: DRIVE mode and PRGM mode.

When the inverter is stopped, DRIVE mode or PRGM mode can be selected by

pressing the key

the PRGM mode, the parameter settings for operation can be changed but the

operation is not enabled. The component names and function are shown as below:

DRIVE FWD

REV

REMOTE

SEQ

DIGITAL OPERATOR JNEP-31

PRGM

DSPL

DRIVE

JOG

FWD

REV

RUN

STOP

PRGM

. In DRIVE mode, the operation is enabled. Instead, in

DRIVE

operation mode indicators

DRIVE : lit when in DRIVE mode

FWD : lit when there is a forward run command input

REF

REV

SEQ

REF

LCD Display

EDIT

Chinese Display : 2-line by 8-character

ENTER

English Display: 2-line by 20-character

RESET

Keys (Key functions are defined in Table 7)

Fig. 10 LCD Digital operator

: lit when there is a reverse run command input

: lit when the run command is enabled from the

control circuit terminal or RS-485 port

(REMOTE mode)

: lit when the frequency reference from the control

circuit terminals (VIN or AIN) or RS-485 port is

enabled (REMOTE mode)

28

  • 34

    PART II

    OPERATION MANUAL

  • 35

    1. DESCRIPTION OF USING 7200GS1.1 Using LCD (or LED) digital
    operator

    7200GS are standard with LCD digital operator JNEP-34. Moreover,
    an LED digitaloperator JNEP-33 is also available. Three two digital
    operator have the sameoperation functions except the LCD and
    7-segments LED display difference.

    The LCD and LED digital operator has 2 modes: DRIVE mode and
    PRGM mode.When the inverter is stopped, DRIVE mode or PRGM mode can
    be selected bypressing the key PRGMDRIVE . In DRIVE mode, the
    operation is enabled. Instead, in thePRGM mode, the parameter
    settings for operation can be changed but theoperation is not
    enabled.

    a> The LCD digital operator component names and functions
    shown as below:

    RUN STOP

    PRGMDRIVE DSPL

    EDITENTER

    DIGITAL OPERATOR JNEP-31

    DRIVE FWD REV REMOTESEQ REF

    FWDREV

    JOG

    RESET

    operation mode indicatorsDRIVE : lit when in DRIVE modeFWD : lit
    when there is a forward run command inputREV : lit when there is a
    reverse run command inputSEQ : lit when the run command is enabled
    from the control

    circuit terminal or option card (REMOTE mode)REF : lit when the
    frequency reference from the control

    circuit terminals (VIN or AIN) or option card enabled(REMOTE
    mode)

    LCD DisplayChinese Display: 2 row, each row has 8 characters at
    mostEnglish Display: 2 row, each row has 20 characters at most

    Keys (Key functions are defined in Table 11)

    Fig 9 LCD Digital operator component names and functions

    b> The LED digital operator component names and functions
    shown as below:

    RUN STOP

    PRGMDRIVE DSPL

    EDITENTER

    DIGITAL OPERATOR JNEP-31

    DRIVE FWD REV REMOTESEQ REF

    FWDREV

    JOG

    RESET

    operation mode indicatorsDRIVE : lit when in DRIVE modeFWD : lit
    when there is a forward run command inputREV : lit when there is a
    reverse run command inputSEQ : lit when the run command is enabled
    from the control

    circuit terminal or option card (REMOTE mode)REF : lit when the
    frequency reference from the control

    circuit terminals (VIN or AIN) or option card enabled(REMOTE
    mode)

    LED Display5 digitals 7-degment LED.

    Keys (Key functions are defined in Table 11)

    34

    3233

  • 36

    Fig 10 LED Digital operator component names and functions

    Table 11 Keys functions

    Key Name Function

    PRGMDRIVE PRGM/DRIVE key

    Switches between operation (PRGM) and operation(DRIVE).

    DSPL DSPL key Display operation status

    JOG JOG keyEnable jog operation from digital operator in
    operation(DRIVE).

    FWDREV FWD/REV key Select the rotation direction from digital
    operator.

    RESETRESET key

    Set the number of digital for user constant settings.Also it
    acts as the reset key when a fault hasoccurred.

    INCRENMNT key Select the menu items, groups, functions, and
    userconstant name, and increment set values.

    DECRENENT key Select the menu items, groups, functions, and
    userconstant name, and decrement set values.

    EDITENTER EDIT/ENTER key

    Select the menu items, groups, functions, and userconstants
    name, and set values (EDIT). After finishingthe above action, press
    the key (ENTER).

    RUN RUN keyStart inverter operation in (DRIVE) mode whenoperator
    is used. The led will light.

    STOP STOP key

    Stop 7200GS operation from LCD digital operator. Thekey can be
    enable or disabled by setting a constantSn-05 when operating from
    the control circuit terminal(in this case, the LED will light).

    RUN, STOP indicator lights or blinks to indicate the 3 operating
    status:

    STOPRUN

    STOP

    RUN

    STOP

    Inverter output frequency

    Frequency Setting

    ON Blink OFF

  • 37

    1.2 DRIVE mode and PRGM mode displayed contents

    *1 : When the inverter is put into operation,

    the inverter system immediately enters into

    DRIVE mode. Press the PRGMDRIVE key,

    the system will switch into PRGM mode.

    *2 : If the fault occurred before power

    supply was turned off, the fault contents

    are displayed when power ON.

    Fault occurrence order and display are

    provided by or key.

    Un fault : n =1~4,the fault occurrence

    Order, fault :the fault contents,

    please refer to page 131~138,the fault display.

    Power on

    PRGM mode DRIVE modePRGMDRIVE *1

    DSPL

    An- monitorset

    DSPL

    bn- monitorset

    DSPL

    Sn- monitorset

    DSPL

    Cn- monitorset

    When faultsOccurred beforepower supplywas turned off

    *2DSPL

    Frequency reference

    DSPL

    Un- monitor

    DSPL

    An- monitorset

    DSPL

    bn- monitorset

    DSPL

    Sn- monitor

    DSPL

    Cn- monitor

    *4

    DSPL *5

    RESET

    DSPL

    Output Frequency

    Output Current

    Display of faults which occurred before power supply

    was turned off

    *3

  • 38

    *3 : If no fault occurred before power supply

    was turned off , display the monitored data

    according to the bn-10 setting

    *4 : This block will be by passed if no fault occurred before
    power supply was turned off or a

    fault occurs and was reset by RESET

    *5 : When in the DRIVE mode, press the DSPL key and RESET key,
    the setting values of Sn-and Cn- will only be displayed for
    monitoring but not for changing or setting.

  • 39

    1.3 Parameter Description

    The 7200GS has 4 groups of user parameters:

    Parameters*4 Description

    An- Frequency command

    bn- Parameter settings can be changed during running

    Sn- System parameter settings (can be changes only after
    stop)

    Cn- Control parameter settings (can be changed only after
    stop)

    The parameter setting of Sn-03 (operation status) will determine
    if the setting valueof different parameter groups are allowed to be
    changed or only to be monitored, asshown below:

    DRIVE mode PRGM modeSn-03

    To be set To be monitored To be set To be monitored

    0000*1 An, bn Sn, Cn An, bn, Sn, Cn

    0101*3 An bn, Sn, Cn An bn, Sn, Cn

    *1 : Factory setting

    *2 : When in DRIVE mode, the parameter group Sn-, Cn- can only
    be monitored if the

    RESET key and the DSPL key are to be pressed at the same
    time,

    *3 : After a few trial operation and adjustment, the setting
    value Sn-03 is set to be0101″ so as not be modified again.

    *4 : The 7200GS has one group of monitoring parameters in
    addition to the above 4groups of user parameters.

    Un- : Can be monitored by the users under the DRIVE mode.

    *2

  • 40

    1.4 Sample example of using LCD digital operator

    Note :

    Before operation: Control parameter Cn-01 value must be set as
    the input ACvoltage value. For example, Cn-01=380 if AC input
    voltage is380.

    This sample example will explain the operating of 7200GAS
    according to the followingtime chart.

    OPERATION MODE

    Sample operation

    Description Key Sequence Digital OperatorDisplay Remarks

    Sect frequency referencevalue displayed

    Select PRGM mode

    Select CONTROL

    LED DRIVE OFF

    (1)

    REV60Hz

    FWD60Hz

    (2) (4) (5) (6) (7) (8)(3)

    SET INPUTVOLTAGE

    FREQUENCYSETTING

    FREQ REF.VALUE CHANGE

    POWERON

    FWD JOGOPERATION FWD RUN REV RUN

    STOP

    (1) When POWER ON

    (2) Input voltagesetting (e.g. ACinput voltage is

    380V)

  • 41

    PARAMETER

    Display Cn-01 setting

    Input Voltage 380V

    Display for 0.5sec

    Description Key Sequence Digital OperatorDisplay Remarks

    Select DRIVE mode

    Select output frequencydisplayed

    Select direction of rotation(When power on, initiallydefaulted
    FWD)

    Jog operation

    Select frequency cmddisplayed

    Change frequency cmd

    Set new frequency cmd

    Select O/P frequencydisplayed

    Running operation

    LED DRIVEON

    LED FWDON

    Display for 0.5 secConfirm the display.

    LEDON

    EDITENTER

    RESET

    PRGMDRIVE

    Freq. Cmd. 00.00HzTECO

    EDITENTER

    DSPL Press 3times

    An-01Freq. Cmd. 1

    Cn-01-Input Voltage

    Entry Accepted

    Cn-01=440.0VInput Voltage

    Cn-01=380.0VInput Voltage

    (continued)

    (3) FWD JOG

    (4) Frequency setting15Hz(5) FWD run

    (6) Frequencycommand change

  • 42

    Select frequency cmddisplayed

    Change reference value

    Enter new frequency cmdsetting

    Select frequency cmddisplayed

    Change to REV

    Decrement to STOP

    Display for 0.5 secConfirm the display.

    LED REVON

    LEDON

    (Blinkingwhiledecel.)

    Freq. Cmd. 00.00HzTECO

    Freq. Cmd. .0 HzTECO

    Entry Accepted

    O/P Freq. 6.00 HzTECO

    PRGMDRIVE

    DSPL

    JOG

    EDITENTER

    RESET

    RUN

    FWDREV

    STOP

    DSPL

    EDITENTER

    RESET

    DSPL

    60Hz(7) REV RUN

    (8) STOP

    Press 5timesDSPL

    Press 5timesDSPL

    Freq. Cmd. 00.00HzTECO

    Freq. Cmd. 15.00HzTECO

    Freq. Cmd. 15.00HzTECO

    O/P Freq. .0 HzTECO

    O/P Freq. 15.00 HzTECO

    Freq. Cmd. 15.00HzTECO

    Freq. Cmd. 60.00HzTECO

    Freq. Cmd. 60.00HzTECO

    Entry Accepted

    O/P Freq. 60.00 HzTECO

    O/P Freq. -60.00 HzTECO

    O/P Freq. .0 HzTECO

    RUNSTOPRUN

  • 43

    1.5 Control Mode SelectionThe 7200GS standard with four
    selectable control modes:

    1 GP: V/F control mode (General Purpose V/F control mode).

    2 SL: Sensorless Vector Control mode (with motor parameters auto
    tuningfunction).

    3 PID: PID with Auto Energy Saving Control mode.

    4 PG: V/F+PG closed loop Control mode.

    The control mode can be selected by parameter Sn-13:

    Sn-13 setting LCD Display (English) Descriptions

    00Sn-13=00

    V/F Ctrl ModeGP: V/F control mode (factory setting)

    01Sn-13=01

    SL Ctrl ModeSL: Sensorless Vector Control mode

    10Sn-13=10

    PID Ctrl ModePID: PID with Auto Energy Saving

    Control mode

    11Sn-13=11

    PG Ctrl ModePG: V/F+PG closed loop Controlmode

    Caution:

    1. Factory setting as V/F control mode (GP mode), When the
    required controlmode is selected by Sn-13, the selected control
    mode is effective only afterturning off the power supply till the
    display of digital operator (LCD or LEDdigital operator) is off,
    then turn on the power supply again.

    2. The AUTO TUNE feature can be used to identify and store the
    importantmotor parameters in the first time sensorless vector
    operation afterinstallation, and when switching to anyone of the
    other three control modes,then switched back to the sensorless
    vector control mode, the AUTO TUNEfeature has to be used to
    identify and store the motor parameters once again.

  • 44

    2. SETTING USER CONSTANT2.1 Descriptions of constant/function
    list

    Formate

    Valid Access LevelsParameter

    No. Name LCD Display (English)ChangeDuring

    OperationSetting Range SettingUnit

    FactorySetting

    GP SL PID PG

    Ref.Page

    or

    Descriptions

    Parameter NO.: NO. of the parameter group An-, bn-, Sn-, Cn- and
    Un-.

    Name: Parameter function name.

    LCD Display (English): The LCD display contents.

    Change During Operation:

    : The parameter setting can be changed during running.

    : The parameter setting can not be changed during running.

    Setting Range: The allowable setting range of the parameter.

    Setting Unit: The allowable setting unit ( means without
    unit).

    Factory Setting: Some of the parameter have different factory
    setting valueunder different control mode.

    Valid Access Levels:

    1 GP: V/F control mode (General Purpose V/F control mode).

    2 SL: Sensorless Vector Control mode (with auto tuning
    function).

    3 PID: PID with Auto Energy Saving Control mode.

    4 PG: V/F+PG closed loop Control mode.

    : The parameter is access valid under this control mode (i.e.
    the

    parameter group can be monitored or set by the user)

  • 45

    : The parameter is access invalid under this control mode.

    Number (1~3): different number with different function
    definitions.

  • 46

    2.2 Frequency command (in Multi-speed operation) A n — Under the
    DRIVE mode, the user can monitor the parameters and set their
    values.

    Valid Access LevelsParameter

    No. Name LCD Display (English)ChangeDuring

    OperationSetting Range SettingUnit

    FactorySetting

    GP SL PID PG

    Ref.Page

    An-01 FrequencyCommand 1

    An-01=000.00Hz

    Frequency Command 1 0.00~180.00 Hz 0.01Hz 00.00Hz

    An-02 FrequencyCommand 2

    An-02=000.00Hz

    Frequency Command 2 0.00~180.00 Hz 0.01Hz 0.00Hz

    An-03 FrequencyCommand 3

    An-03=000.00Hz

    Frequency Command 3 0.00~180.00 Hz 0.01Hz 0.00Hz

    An-04 FrequencyCommand 4

    An-04=000.00Hz

    Frequency Command 4 0.00~180.00 Hz 0.01Hz 0.00Hz

    An-05 FrequencyCommand 5

    An-05=000.00Hz

    Frequency Command 5 0.00~180.00 Hz 0.01Hz 0.00Hz

    An-06 FrequencyCommand 6

    An-06=000.00Hz

    Frequency Command 6 0.00~180.00 Hz 0.01Hz 0.00Hz

    An-07 FrequencyCommand 7

    An-07=000.00Hz

    Frequency Command 7 0.00~180.00 Hz 0.01Hz 0.00Hz

    An-08 FrequencyCommand 8

    An-08=000.00Hz

    Frequency Command 8 0.00~180.00 Hz 0.01Hz 0.00Hz

    An-09 Jog FrequencyCommand

    An-09=006.00Hz

    Jog Command 0.00~180.00 Hz 0.01Hz 6.00Hz

    *1. The displayed «Setting Unit can be changed through the
    parameter Cn-20.

    *2. At factory setting, the value of «Setting Unit» is
    0.01Hz.

    *3. The setting of An-01~09 should be with the multi-function
    analog terminals 5 ~8 .

  • 47

    2.3 Parameters Can Be Changed during Running b n — Under the
    DRIVE mode, the Parameter group can be monitored and set by
    theusers.

    Valid AccessLevels

    Function ParameterNo. NameLCD Display

    (English)

    ChangeDuring

    OperationSetting Range SettingUnit

    FactorySetting

    GP SL PID PG

    Ref.Page

    bn-01 AccelerationTime 1bn-01=0010.0s

    Acc. Time 1 0.0~6000.0s 0.1s 10.0s

    bn-02 DecelerationTime 1bn-02=0010.0s

    Dec. Time 1 0.0~6000.0s 0.1s 10.0s

    bn-03 AccelerationTime 2bn-03=0010.0s

    Acc. Time 2 0.0~6000.0s 0.1s 10.0s

    Acc/Dectime

    bn-04 DecelerationTime 2bn-04=0010.0s

    Dec. Time 2 0.0~6000.0s 0.1s 10.0s

    45

    bn-05

    AnalogFrequencyCmd. Gain(Voltage)

    bn-05=0100.0%

    ~Freq. Cmd. Gain 0.0~1000.0% 0.1% 100.0%

    AnalogFrequencyCommand

    bn-06

    AnalogFrequencyCmd. Bias(Voltage)

    bn-06=0000.0%

    ~Freq. Cmd. Bias -100.0%~100.0% 0.1% 0.0%

    46

    TorqueBoost bn-07

    Auto TorqueBoost Gain(Ineffective

    in Autoenergy-saving

    mode)

    bn-07=1.0

    Auto_Boost Gain 0.0~2.0 0.1 1.0*1 46

    Motor Slip bn-08 Rated Slip ofMotorbn-08 =0.0%

    Motor Rated Slip 0.0~9.9%*2 0.1% 0.0% 1 2

    47

    48

    EnergySaving bn-09

    Energy SavingGain

    bn-09=080%

    Eg. Saving Gain 0~200% 1% 80% 48

    bn-10 Monitor No.After power ONbn-10=1

    Power On. Contents 1~3 1 1 48

    A01 Gain bn-11Multi-FunctionAnalog Output

    A01 Gain

    bn-11=1.00

    ~Output A01 Gain 0.01~2.55 0.01 1.00 1 1 1 2

    A02 Gain bn-12Multi-FunctionAnalog Output

    A02 Gain

    bn-12=1.00

    ~Output A02 Gain 0.01~2.55 0.01 1.00 1 1 1 2

    48~50

    bn-13 PID DetectionGainbn-13=01.00

    PID Det. Gain 0.01~10.00 0.01 1.00

    bn-14PID

    ProportionalGain

    bn-14=01.0

    PID P-Gain 0.0~10.0 0.1 1.0

    bn-15 PID IntegralGainbn-15=010.0s

    PID I-Time 0.0~100.0s 0.1s 10.0s

    bn-16 PID DifferentialTimebn-16=0.00s

    PID D-Time 0.00~1.00s 0.01s 0.00s

    PIDControl

    bn-17 PID Biasbn-17=000%

    PID Bias 0~109%*2 1% 0%

    50

    147

    *1. The factory setting value is 1.2 for SL control mode.

  • 48

    *2. Cn-04 is to be the 100% level.

  • 49

    (1) Acceleration Time 1 (bn-01)

    (2) Deceleration Time 1 (bn-02)

    (3) Acceleration Time 2 (bn-03)

    (4) Deceleration Time 2 (bn-04)

    Valid Access LevelsParameter

    No. NameLCD Display

    (English)

    ChangeDuring

    OperationSetting Range SettingUnit

    FactorySetting

    GP SL PID PG

    bn-01 Acceleration Time 1bn-01=0010.0s

    Acc. Time 1 0.0~6000.0s 0.1s 10.0s

    bn-02 Deceleration Time 1bn-02=0010.0s

    Dec. Time 1 0.0~6000.0s 0.1s 10.0s

    bn-03 Acceleration Time 2bn-03=0010.0s

    Acc. Time 2 0.0~6000.0s 0.1s 10.0s

    bn-04 Deceleration Time 2bn-04=0010.0s

    Dec. Time 2 0.0~6000.0s 0.1s 10.0s

    Set individual Acceleration / Deceleration times

    Acceleration time: the time required to go from 0% to 100% of
    the maximum outputfrequency.

    Deceleration time: the time required to go from 0% to 100% of
    the maximum outputfrequency.

    If the acceleration / deceleration time sectors 1 and 2 are
    input via the multifunctioninputs terminal 5 ~8 , the acceleration
    / deceleration can be switched between 2sectors even in the running
    status.

    Control circuit terminals 5 ~8

    Open select the 1st sector Acc. / Dec. time(Parameters bn-01,
    bn-02 set)

    Close select the 2nd sector Acc. / Dec. time(Parameters bn-03,
    bn-04 set)

    bn-03

    bn-01

    Cn-02

    bn-04

    bn-02Time

    Output frequency

  • 50

    Note:

    1. To set the S-curve characteristics function, please refer to
    Sn-06.

  • 51

    (5) Analog Frequency Cmd. Gain (Voltage) (bn-05)

    (6) Analog Frequency Cmd. Bias (Voltage) (bn-06)Valid Access
    LevelsParameter

    No. NameLCD Display

    (English)

    ChangeDuring

    OperationSetting Range SettingUnit

    FactorySetting GP SL PID PG

    bn-05 Analog FrequencyCmd. Gain (Voltage)bn-05=0100.0%

    ~Freq. Cmd. Gain 0.0~1000.0% 0.1% 100.0%

    bn-06 Analog FrequencyCmd. Bias (Voltage)bn-06=0000.0%

    ~Freq. Cmd. Bias -100.0%~100.0% 0.1% 0.0%

    bn-05: The input level when frequency reference voltage is 10V
    is set in units of 1%,examples are shown below.

    bn-06: The input level when frequency reference voltage is 0V is
    set in units of 1%

    1 bn-05 = 50.0

    2 a: bn-06 = 10.0

    b: bn-06 = -10.0

    (7) Auto Torque Boost Gain (bn-07)Valid Access
    LevelsParameter

    No. NameLCD Display

    (English)

    ChangeDuring

    OperationSetting Range SettingUnit

    FactorySetting GP SL PID PG

    bn-07Auto Torque Boost Gain

    (Ineffective in Autoenergy-saving mode)

    bn-07=1.0Auto_Boost Gain

    0.0~2.0 0.1 1.0

    The inverter can increase the output torque to compensate the
    load increaseautomatically through the auto torque boost function.
    Then the output voltage willincrease. As a result, the fault trip
    cases can be decreased. The energy efficiency isalso improved. In
    the case that the wiring distance between the inverter and themotor
    is too long (e.g. more than 100m), the motor torque is a little
    short because ofvoltage drop. Increase the value of bn-11 gradually
    and make sure the current willnot increase too much. Normally, no
    adjustment is required.

    INPUT LEVELbn-06 is positive value.%

    bn-05

    bn-06(a)

    10

    bn-06(b) -10

    0 0V 10V

    bn-06 isnegative value.

    FREQUENCYREF.

    100%

    Base frequency

    torquedecrease

    torqueincrease

    Outputvoltage

  • 52

    bn-07 is ineffective when the Auto-Energy Saving function is
    effective (Sn-08=X1XX)in the PID control mode (Sn-13=10).

  • 53

    (8) Rated Slip of Motor (bn-08)

    1. GP

    Valid Access LevelsParameterNo. Name

    LCD Display(English)

    ChangeDuring

    OperationSetting Range SettingUnit

    FactorySetting GP SL PID PG

    bn-08 Rated Slip of Motorbn-08 =0.0%

    Motor Rated Slip 0.0~9.9% 0.1% 0.0% 1 2

    Motor rated slip is set in units of 0.1%

    Simplified speed control is performedwithout encoder (PG or
    TG).With frequency offset f1 to f2, speedfluctuation due to load is
    reduced.

    When the output current of the inverter is larger than motor
    no-load current (Cn-34),the output frequency of the inverter is
    compensated.

    The amount of frequency compensation is determined by the
    formula below. Themaximum voltage frequency (Cn-04) is 100%.

    If the output current is equal to the motor rated current
    (Cn-09), the output frequencyis compensated for by the motor rated
    slip (bn-08).

    If frequency reference is equal to or smaller than minimum
    output frequency (Cn-07)or motor is in a regeneration mode, slip
    compensation is not performed.

    The amount of output frequency compensation in a constant torque
    area and aconstant output area is shown in the figure below.

    Amount of output frequency compensation =

    Motor rated current: Cn-09Motor no-load current: Cn-34

    motor rated slip

    motor ratedcurrent

    motor no-loadcurrent

    motor no-loadcurrent

    outputcurrent

    TORQUE

    LOAD TORQUE

    SMALL LOADf1

    LARGE LOADf2

    SPEED

    Cn-04xbn-08

    Cn-04 Cn-02

    bn-08

  • 54

    Motor rated slip: bn-08 When 0.0 is set in bn-08, output
    frequency compensation is not performed.

  • 55

    2. SL

    Valid Access LevelsParameterNo. Name

    LCD Display(English)

    ChangeDuring

    OperationSetting Range SettingUnit

    FactorySetting GP SL PID PG

    bn-08 Rated Slip of Motorbn-08 =1.7Hz

    Motor Rated Slip 0.0~20.0Hz 0.1Hz 1.7Hz* 1 2

    * Factory setting depending on inverter capacity (Sn-01 set
    value)

    To calculate the motor rated slop by the below equation:

    Motor Rated Slop (Hz)= [rated speed (rpm)nameplate full load
    speed (rpm)]

    120P (Hz)

    P=motor poles

    (9) Energy Saving Gain (bn-09)Valid Access LevelsParameter

    No. NameLCD Display

    (English)

    ChangeDuring

    OperationSetting Range SettingUnit

    FactorySetting GP SL PID PG

    bn-09 Energy Saving Gainbn-09=080%

    Eg. Saving Gain 0~200% 1% 80%

    Input the energy-saving operation command (Sn-15~18=63), While a
    light loadcauses the inverter output voltage to be reduced and save
    energy. Set this valueas a percentage of the V/F pattern. The
    setting range is 0~200%. The energysaving function is disabled when
    energy saving gain (bn-09) is 100%.

    Please refer to page 97, the time chart when energy-saving
    operation command isinput.

    (10) Monitor No. after Power ON (bn-10)Valid Access
    LevelsParameter

    No. Name LCD Display (English)ChangeDuring

    OperationSetting Range SettingUnit

    FactorySetting GP SL PID PG

    bn-10 Monitor No. Afterpower ONbn-10=1

    Power On. Contents 1~3 1 1

    Data to be monitored after turning on power supply is selected
    with constant NO.

    bn-10=1Frequency reference

    bn-10=2Output frequency

    bn-10=3Output current

    (11) Multi-function Analog Output A01 Gain (bn-11)

    (12) Multi-function Analog Output A02 Gain (bn-12)

  • 56

    1. GP, SL, PID

    Valid Access LevelsParameterNo. Name

    LCD Display(English)

    ChangeDuring

    OperationSetting Range SettingUnit

    FactorySetting GP SL PID PG

    bn-11 Multi-Function AnalogOutput A01 Gainbn-11=1.00

    ~Output A01 Gain 0.01~2.55 0.01 1.00 1 1 1 2

    bn-12 Multi-Function AnalogOutput A02 Gainbn-12=1.00

    ~Output A02 Gain 0.01~2.55 0.01 1.00 1 1 1 2

    To set the output voltage level of A01 channel of analog monitor
    optional card (AO-12) by bn-11 and bn-12. The output voltage level
    is set in the form of 10Vbn-11 (orbn-12).

    To set the output voltage level of multi-function analog output
    terminal 21 .The output voltage level is set in the form of
    10Vbn-11

    2. PG

    Valid Access LevelsParameterNo. Name

    LCD Display(English)

    ChangeDuring

    OperationSetting Range SettingUnit

    FactorySetting GP SL PID PG

    bn-11Multi-Function Analog

    Output 21 itemsbn-11=2

    Output Frequency 1~13 2 1 1 1 2

    bn-12Multi-Function Analog

    Output 21 Gainbn-12=

    Output Gain 0.01~2.55 0.01 1.00 1 1 1 2

    bn-11: Select the item to be output from terminal 21

    bn-11 setting LCD Display (English) Functions01 Freq. Cmd.
    Frequency Command (Reference)02 O/P Freq. Output Frequency03 O/P I
    Output Current04 O/P V Output Voltage

    Channel 1(Select item to be outputfrom channel 1 by Sn-28)

    10.0V bn-11Channel 1 (A01)of AO-12 card

    10.0V bn-12Channel 2(Select item to be outputfrom channel 2 by
    Sn-28)

    Channel 2 (A02)of AO-12 card

    Multi-function analog output terminal 21(Select item to be
    output from terminal21 by the 4th digit of Sn-05 and the 2nddigit
    of Sn-09)

    10.0V bn-11 Terminal 21

  • 57

    05 DC Volt DC Voltage06 O/P KW Output Power (KW)

    07-11 Reserved Not used12 Sp. FBK Amount of speed feedback13 Sp.
    Compen. Amount of speed control compensation

    bn-12: To set the output voltage level of multi-function analog
    output terminal 21 .The output voltage level is set in the form of
    10Vbn-12

    The analog monitor optional card (AO-12) can not be used in PG
    control mode.

    (13) PID Control function (bn-13~bn-17)

    Please refer to Appendix C PID CONTROL.

    Multi-function analog output 21(Select item to be output
    fromterminal 21 by bn-11) 10.0V bn-12

    Terminal 21

  • 58

    2.4 System Parameters S n — Valid Access Levels

    Function ParameterNo. NameLCD Display

    (English) DescriptionFactorySetting

    ChangeDuring

    Operation GP SL PID PGRef.Page

    CapacitySetting Sn-01

    InverterCapacitySelection

    Sn-01=29440V 25HP Inverter Capacity Selection *1 1 2 1 1

    55~62

    V/f Curve Sn-02 V/f CurveSelectionSn-02=01V/f Curve V/f pattern
    Selection 01

    63~65

    Display ofOperator

    0000: Setting and reading of An-, Bn-,Cn-, Sn- enabled

    0101: Setting and reading of An-, Readinng of Bn-,Cn-,
    Sn-enabled

    OperatorStatus Sn-03

    ConstantsInitialization

    Sn-03=0000Operate Setting

    1110: Constants Initialigation (2-wire)*2

    1111: Constants Initialigation (3-wire)*2

    0000 66

    — — -0: Frequency Command =Control circuit terminals 13or 14

    — — -1: Frequency Command =Frequency Command 1(An-01)

    Operation ModeSelect

    — -0 -: RUNSTOP Command =Control circuit terminals

    — -1 -: RUNSTOP Command =LCD Digital Operator

    OperationMode

    Select 1Sn-04

    StoppingMethod

    Selection

    Sn-04=0011Stopping Method

    00- -: Stopping method = Ramp tostop

    01- -: Stopping method =Coastingto stop

    10- -: Stopping method =Full-range DC injection brankingstop

    11- -: Stopping method = Coastingstop (timer
    functionprovided)

    0011 67~69

    — — -0: Stop key effective duringoperation from
    controlterminal

    — — -1: Stop key effective duringoperation from
    controlterminal

    — -0 -: Reverse run enabled- -1 -: Reverse run disabled

    — 0- -: Control input terminals 1

    ~8 are scanned twice.- 1- -: Control input terminals 1

    ~8 are scanned once.

    OperationMode

    Select 2Sn-05

    I/O terminalfunctionselection

    Sn-05=0000I/O term. Fct

    0- — -: Selection of item to beanalog output (terminals21 , 22
    )*3

    1- — -: Selection of item to beanalog output (terminals21 , 22
    )*3

    0000 1 1 1 2 70~71

    — -00: S curve=0.2sec- -01: S curve=0.0sec (NO S

    curve)- -10: S curve=0.5sec- -11: S curve=1.0sec

    OperationMode

    Select 3Sn-06

    S-curve andfrequencyCommand

    characteristics

    Sn-06=0000S-curve Cmd. Char.

    -0 — -: Reference command hasforward characteristics(0-10V or
    4-20mA/0~100%)

    -1 — -: Reference command hasreverse characteristics(0-10V or
    4-20mA/100~0%)

    0000 72~74

  • 59

    0- — -: Stop by reference inputwhen frequency referenceis
    missing

    1- — -: Operation to continue with80% of frequence referencewhen
    frequency referenceis missing

  • 60

    Valid Access LevelsFunction ParameterNo. Name

    LCD Display(English) Description

    FactorySetting

    ChangeDuring

    Operation GP SL PID PGRef.Page

    — — -0: Overtorque detection disabled

    — — -1: Overtorque detection enabled

    — -0 -: Enabled only if at agreedfrequency

    — -1 -: Enable during operation(except during DC injection)

    — 0- -: Operation continued afterovertorque is detected

    — 1- -: Coasts to stop if overtorque isdetected

    OperationMode Select 4 Sn-07

    OvertorqueDetection

    Sn-07=0000

    Over Tq. Detect

    0- — -: Overtorque detection withcurrent

    1- — -: Overtorque detection withtorque

    0000 1 2 1 175-

    76

    — — -0: Frequency reference input byoption card (AI-14B, DI-08
    orSI-M)

    — — -1: Frequency reference input bydigital operetor or
    controlcirauit input terminals

    — -0 -: RUN/STOP command input byoption card (AI-14B, DI-08
    orSI-M)

    — -1 -: RUN/STOP command input bydigital operator or
    controlcircuit input terminals

    OperationMode Select 5 Sn-08

    OptionCard/Invater

    FunctionSelection

    Sn-08=0000

    AI/DI & SI-M Card

    00- -: SI-M communication fault,deceleration to stop (bn-02)

    01- -: SI-M communication fault,coast to stop

    10- -: SI-M communication fault,deceleration to stop (bn-04)

    11- -: SI-M communication fault,continue to run

    0000 1 1 2 377-

    78

    — — -0: Analog output (tereminal21 -22 ) depends on Sn-054th
    digit and Sn-09 2nd digit.

    — — -1: Analog output (tereminal21 -22 ) is set by SI-M
    card.

    — -0 -: Analog output (tereminal21 -22 )

    — -1 -: Analog output (tereminal21 -22 )

    — 0- -: Not used

    — 1- -: Not used

    OperationMode Select 6 Sn-09

    Analog OutputSelection and

    SlipCompensetion

    Sn-09=0000

    ~Output Select

    0- — -: No slip compensation duringregenerating

    1- — -: Slip compensation even duringregenerating

    0000 1 2 3 79-

    80

    — — -0: Stall prevention duringacceleration enabled

    — — -1: Stall prevention duringacceleration disabled

    — -0 -: Stall prevention duringdeceleration enabled

    — -1 -: Stall prevention duringdeceleration disabled

    ProtectiveCharacteristic

    Select 1Sn-10 StallPrevention

    Sn-10=0000

    Stall Select

    — 0- -: Stall prevention during runningenabled

    — 1- -: Stall prevention during runningdisabled

    0000 81-

    82

  • 61

    0- — -: Decel time during stallprevention (bn-02 set value)

    1- — -: Decel time during stallprevention (bn-04 set value)

    Valid Access LevelsFunction ParameterNo. Name

    LCD Display(English) Description

    FactorySetting

    ChangeDuring

    Operation GP SL PID PG

    Ref.Page

    — — -0: Not used

    — — -1: Not used

    — -0 -: Fault contact is not energizedduring Retry operation

    — -1 -: Fault contact is energizedduring Retry operation

    -0 — -: Operation stopped bymomentary power lossdetection
    (UV1)

    -1 — -: Operation conticues aftermomentary power loss

    ProtectiveCharacteristic

    Select 2Sn-11

    Retry andmomentarypower lossprotection

    Sn-11=0000

    Retry & Ride -Thru

    0- — -: Not used

    1- — -: Not used

    0000 83

    — — -0: External fault input (terminal3 ) is NO-contact
    input

    — — -1: External fault input: is NC-contact input

    — -0 -: External fault signal: alwaysdetected

    — -1 -: External fault signal: detectedduring running only

    ProtectiveCharacteristic

    Select 3Sn-12

    ExternalFault

    FunctionSelection

    Sn-12=0000

    External Fault00- -: External fault detected: ramp

    to stop (major fault) by bn-02set value

    01- -: External fault detected:Coasting to stop (major
    fault)

    10- -: External fault detected: rampto stop (major fault) by
    bn-04set value

    11- -: External fault detected:opeation to continue
    (majorfault)

    0000 84

    Control ModeSelect Sn-13

    ControlModeSelect

    Sn-13=00

    V/F Ctrl mode

    — -00: GPV/F Control mode

    — -01: SLSensorless Vector Controlmode

    — -10: PIDPID With Auyo EnergySoving Control mode

    — -11: PGV/F+PG closed loopControl mode

    00 85

    — — -0: Motor overload (OL1)protection: effective

    — — -1: Motor overload (OL1)protection: ineffective

    ProtectiveCharacteristic

    Select 4Sn-14

    ElectronicThermalOverloadProtection

    Sn-14=0000

    Over LoadSelect

    — -0 -: Motor overload protection:standard motor

    — -1 -: Motor overload protection:Inverter duty motor

    0000 86

  • 62

    — 0- -: Motor overload protection timeconstants are standard
    time(8 minutes)

    — 1- -: Motor overload protection timeconstants are short-time
    (5minutes)

    0- — -: Inverter overload (OL2)protection 103% continuous,150%
    for one minute*2

    1- — -: Inverter overload (OL2)protection 113% continuous,123%
    for one minute*2

    Valid Access Levels

    Function ParameterNo. NameLCD Display

    (English) DescriptionFactorySetting

    ChangeDuring

    Operation GP SL PID PG

    Ref.Page

    Sn-15 Terminal 5Function

    Sn-15=03

    Term.5 Function

    00~66

    Selects terminal 5 function(factory preset for multi-stepspeed
    reference 1)

    03 87

    Sn-16 Terminal 6Function

    Sn-16=04

    Term.6 Function

    00~66

    Selects terminal 6 function(factory preset for multi-stepspeed
    reference 2)

    04 87

    Sn-17 Terminal 7Function

    Sn-17=06

    Term.7 Function

    00~66

    Selects terminal 7 function(factory preset for jogfrequency
    reference)

    06 87

    Sn-18 Terminal 8Function

    Sn-18=08

    Term.8 Function

    00~66

    Selects terminal 8 function(factory preset for externalbaseblock
    by NO contactinput)

    08 87

    Sn-19Multi-functionanalog input

    (Terminal 16 )

    Sn-19=00

    Multi-Fct Input

    00~

    0B

    Selects terminal 16 function(factory preset for
    auxilaryfrequency command)

    00 98

    Sn-20Multi-functioncontact output

    (Terminal 9 -10 )

    Sn-20=00

    Term. 9 Function

    00~

    0E

    Selects terminal 9 — 10function (factory preset forrunning)

    00 100

    Sn-21Multi-function PHC

    output (Terminal25 -27 )

    Sn-21=01

    Term. 25 Function

    00~

    0E

    Selects terminal 25 — 27function (factory preset forzero
    speed)

    01 100

    Multi-FunctionSelect

    Sn-22Multi-function PHC

    output (Terminal26 -27 )

    Sn-22=02

    Term. 26 Function

    00~

    0E

    Selects terminal 26 — 27function (factory preset forAgreed
    frequency)

    02 100

    Language Sn-23 LCD Languageselection

    Sn-23=0

    Language: English

    0: English

    1: Chinese0 103

    Sn-24 Not usedSn-24=00

    Reserved

    OptionCard

    FunctionSelect

    Sn-25

    ~

    Sn-28

    *3 *3 *3 *3 1 2 3 4104

    154

  • 63

    Auto-tuning Sn-29

    Motor parametersAuto tuningSelection

    Sn-29=0

    Motor Auto Test

    0: Autotuning invalid

    1: Autotuning valid 108

    *1. Differs according to inverter capacity.

    *2. Effective only for inverter models of capacity 220V 40HP
    (30KW) or more, 440V75HP (55KW) or more.

    *3. Differs according to control mode.

  • 64

    Inverter Capacity Selection Sn-01

    Inverter capacity has been preset at the factory. However, if a
    spare control board isused, reset the inverter capacity referring
    to the table below. Control constant Cn- factory setting values
    (initial values) differ according to Sn-01 setting.

    1. GP, PID, PGValid Access LevelsParameter

    No. NameLCD Display

    (English) DescriptionFactorySetting

    Change DuringOperation GP SL PID PG

    Sn-01 Inverter CapacitySelectionSn-01=29

    440V 25HPInverter Capacity Selection *1 1 2 1 1

    Inverter Capacity Selection220V Class

    Data of Sn-01

    Name00 01 02 03 04 05 06 07

    Inverter rating HP 0.5 1 2 3 5 7.5 10 15

    Inverter rated capacity kVA 1.4 2.1 2.7 4.1 6.9 10.3 13.7
    20.6

    Max. applicable motor capacity HP (kW)0.5

    (0.4)

    1

    (0.75)

    2

    (1.5)

    3

    (2.2)

    5

    (3.7)

    7.5

    (5.5)

    10

    (7.5)

    15

    (11)

    Inverter rated current A 3.2 4.8 6.4 9.6 16 24 32 48

    Cn-09 Motor rated current A 1.9 3.4 6.1 8.7 13.5 20.1 25.1
    36.7

    Cn-23 Carrier frequency upperlimit kHz 15.0 15.0 15.0 15.0 15.0
    15.0 15.0 15.0

    Cn-24 Carrier frequency lowerlimit kHz 15.0 15.0 15.0 15.0 15.0
    15.0 15.0 15.0

    Cn-25 Carrier frequencyproportional gain 0 0 0 0 0 0 0 0

    Cn-31 Motor phase-to-phaseresistance 11.760 5.732 2.407 1.583
    0.684 0.444 0.288 0.159

    Cn-32 Torque compensation ironloss W 48 64 108 142 208 252 285
    370

    Cn-33 Torque compensation limit V 50 50 50 50 50 50 50 50

    Cn-37 Momentary power lossassurance time s 0.7 1.0 1.0 1.0 2.0
    2.0 2.0 2.0

    Fact

    Cn-40 Minimum baseblock time s 0.5 0.5 0.5 0.5 0.5 0.7 0.7
    0.7

  • 65

    Cn-41 V/f during speed search % 100 100 100 100 100 100 100
    100

  • 66

    Inverter Capacity Selection220V Class

    Data of Sn-01

    Name08 09 0A 0B 0C 0D 0E 0F

    Inverter rating HP 20 25 30 40 50 60 75 100

    Inverter rated capacity kVA 27.4 34 41 54 68 78 95 130

    Max. applicable motor capacity HP (kW)20

    (15)

    25

    (18.5)

    30

    (22)

    40

    (30)

    50

    (37)

    60

    (45)

    75

    (55)

    100

    (75)

    Inverter rated current A 64 80 96 130 160 183 224 300

    Cn-09 Motor rated current A 50.3 62.9 72.9 96.7 124 143.5 183.5
    230

    Cn-23 Carrier frequency upperlimit kHz 15.0 15.0 15.0 10.0 10.0
    3.0 3.0 3.0

    Cn-24 Carrier frequency lowerlimit kHz 15.0 15.0 15.0 10.0 10.0
    3.0 3.0 3.0

    Cn-25 Carrier frequencyproportional gain 0 0 0 0 0 0 0 0

    Cn-31 Motor phase-to-phaseresistance 0.109 0.077 0.060 0.041
    0.033 0.028 0.019 0.007

    Cn-32 Torque compensation ironloss W 471 425 582 536 641 737 790
    1800

    Cn-33 Torque compensation limit V 50 50 50 50 50 50 50 50

    Cn-37 Momentary power lossassurance time s 2.0 2.0 2.0 2.0 2.0
    2.0 2.0 2.0

    Cn-40 Minimum baseblock time s 0.7 1.0 1.0 1.0 1.0 1.0 1.0
    1.0

    Fact

    ory

    Set

    ting

    Cn-41 V/f during speed search % 100 100 100 80 80 80 80 80

    The allowable maximum carrier frequency is 10kHz

  • 67

    Inverter Capacity Selection440V Class

    Data of Sn-01

    Name20 21 22 23 24 25 26 27 28 29 2A

    Inverter rating HP 0.5 1 2 3 5 7.5 10 15 20 25 30

    Inverter rated capacity kVA 1.4 2.1 3.4 4.1 6.9 10.3 13.7 20.6
    27.4 34 41

    Max. applicable motor capacity HP (kW)0.5

    (0.4)

    1

    (0.75)

    2

    (1.5)

    3

    (2.2)

    5

    (3.7)

    7.5

    (5.5)

    10

    (7.5)

    15

    (11)

    20

    (15)

    25

    (18.5)

    30

    (22)

    Inverter rated current A 1.6 2.6 4.0 4.8 8 12 16 24 32 40 48

    Cn-09 Motor rated current A 1.0 1.7 2.9 4.0 6.8 10.0 12.6 18.6
    24.8 31.1 36.3

    Cn-23 Carrier frequency upperlimit kHz 15.0 15.0 15.0 15.0 15.0
    15.0 15.0 15.0 15.0 10.0 10.0

    Cn-24 Carrier frequency lowerlimit kHz 15.0 15.0 15.0 15.0 15.0
    15.0 15.0 15.0 15.0 10.0 10.0

    Cn-25 Carrier frequencyproportional gain 0 0 0 0 0 0 0 0 0 0
    0

    Cn-31 Motor phase-to-phaseresistance 47.02 22.929 9.629 6.333
    2.735 1.776 1.151 0.634 0.436 0.308 0.239

    Cn-32 Torque compensation ironloss W 48.1 63.9 108 142 208 252
    285 370 471 425 582

    Cn-33 Torque compensation limit V 100 100 100 100 100 100 100
    100 100 100 100

    Cn-37 Momentary power lossassurance time s 1.0 1.0 1.0 1.0 2.0
    2.0 2.0 2.0 2.0 2.0 2.0

    Cn-40 Minimum baseblock time s 0.5 0.5 0.5 0.5 0.5 0.7 0.7 0.7
    1.0 1.0 1.0

    Fact

    ory

    Set

    ting

    Cn-41 V/f during speed search % 100 100 100 100 100 100 100 100
    100 100 100

  • 68

    Inverter Capacity Selection440V Class

    Data of Sn-01

    Name2B 2C 2D 2E 2F 30 31 32 33 34 35 36

    Inverter rating HP 40 50 60 75 100 125 150 175 215 250 300
    400

    Inverter rated capacity kVA 54 68 82 110 138 180 195 230 260 290
    385 514

    Max. applicable motor capacity HP (kW)40

    (30)

    50

    (37)

    60

    (45)

    75

    (55)

    100

    (75)125

    150

    (110)175

    215

    (160)

    250

    (185)

    300

    (220)

    400

    (300)

    Inverter rated current A 64 80 96 128 165 192 224 270 300 340
    450 600

    Cn-09 Motor rated current A 48.7 59.0 70.5 88.0 114 143 175 206
    235 290 348 465

    Cn-23 Carrier frequency upperlimit kHz 10.0 10.0 10.0 10.0 3.0
    3.0 3.0 3.0 3.0 2.0 2.0 2.0

    Cn-24 Carrier frequency lowerlimit kHz 10.0 10.0 10.0 10.0 3.0
    3.0 3.0 3.0 3.0 2.0 2.0 2.0

    Cn-25 Carrier frequencyproportional gain 0 0 0 0 0 0 0 0 0 0 0
    0

    Cn-31 Motor phase-to-phaseresistance 0.164 0.133 0.110 0.074
    0.027 0.051 0.036 0.032 0.023 0.020 0.022 0.014

    Cn-32 Torque compensation ironloss W 536 641 737 790 1800 2900
    2900 2600 2500 2600 1850 3600

    Cn-33 Torque compensation limit V 100 100 100 100 100 100 100
    100 100 100 100 100

    Cn-37 Momentary power lossassurance time s 2.0 2.0 2.0 2.0 2.0
    2.0 2.0 2.0 2.0 2.0 2.0 2.0

    Cn-40 Minimum baseblock time s 1.0 1.0 1.0 1.0 1.0 1.0 2.0 2.0
    2.0 2.0 2.0 2.0

    Fact

    ory

    Set

    ting

    Cn-41 V/f during speed search % 100 100 100 80 80 80 80 80 80 80
    80 80

    The allowable maximum carrier frequency of 440V class 100HP to
    215HP are to beas follows:

    440V Horse Power 100HP 125HP 150HP 175HP 215HP

    Max. Allowable Carrier Frequency 8kHz 6kHz 6kHz 5kHz 10kHz

  • 69

    2. SLValid Access LevelsParameter

    No. NameLCD Display

    (English) DescriptionFactorySetting

    Change DuringOperation GP SL PID PG

    Sn-01 Inverter CapacitySelectionSn-01=29

    440V 25HPInverter Capacity Selection *1 1 2 1 1

    Inverter Capacity Selection220V Class

    Data of Sn-01

    Name00 01 02 03 04 05 06 07

    Inverter rating HP 0.5 1 2 3 5 7.5 10 15

    Inverter rated capacity kVA 1.4 2.1 2.7 4.1 6.9 10.3 13.7
    20.6

    Max. applicable motor capacity HP (kW)0.5

    (0.4)

    1

    (0.75)

    2

    (1.5)

    3

    (2.2)

    5

    (3.7)

    7.5

    (5.5)

    10

    (7.5)

    15

    (11)

    Inverter rated current A 3.2 4.8 6.4 9.6 16 24 32 48

    Cn-09 Motor rated current A 1.9 3.4 6.1 8.7 13.5 20.1 25.1
    36.7

    Cn-23 Carrier frequency upperlimit kHz 15.0 15.0 15.0 15.0 15.0
    15.0 15.0 15.0

    Cn-24 Carrier frequency lowerlimit kHz 15.0 15.0 15.0 15.0 15.0
    15.0 15.0 15.0

    Cn-25 Carrier frequencyproportional gain 0 0 0 0 0 0 0 0

    Cn-31 Motor phase-to-phaseresistance 11.760 5.732 2.466 1.600
    0.707 0.398 0.222 0.230

    Cn-32 Motor leakage inductance mH 42.24 19.07 13.40 9.81 6.34
    4.22 2.65 2.23

    Cn-33 Torque limit % 150 150 150 150 150 150 150 150

    Cn-37 Momentary power lossassurance time s 0.7 1.0 1.0 1.0 2.0
    2.0 2.0 2.0

    Cn-40 Minimum baseblock time s 0.5 0.5 0.5 0.5 0.5 0.7 0.7
    0.7

    Cn-41 V/f during speed search % 100 100 100 100 100 100 100
    100

    Fact

    ory

    Set

    ting

    bn-08 Rated slip of motor Hz 2.9 2.5 2.6 2.9 3.3 1.5 1.3 1.7

  • 70

    Inverter Capacity Selection220V Class

    Data of Sn-01

    Name08 09 0A 0B 0C 0D 0E 0F

    Inverter rating HP 20 25 30 40 50 60 75 100

    Inverter rated capacity kVA 27.4 34 41 54 68 78 95 130

    Max. applicable motor capacity HP (kW)20

    (15)

    25

    (18.5)

    30

    (22)

    40

    (30)

    50

    (37)

    60

    (45)

    75

    (55)

    100

    (75)

    Inverter rated current A 64 80 96 130 160 183 224 300

    Cn-09 Motor rated current A 50.3 62.9 72.9 96.7 124 143.5 183.5
    230

    Cn-23 Carrier frequency upperlimit kHz 15.0 10.0 10.0 10.0 10.0
    3.0 3.0 3.0

    Cn-24 Carrier frequency lowerlimit kHz 15.0 10.0 10.0 10.0 10.0
    3.0 3.0 3.0

    Cn-25 Carrier frequencyproportional gain 0 0 0 0 0 0 0 0

    Cn-31 Motor phase-to-phaseresistance 0.138 0.102 0.080 0.067
    0.045 0.035 0.028 0.019

    Cn-32 Motor leakage inductance mH 1.48 1.39 1.15 1.15 1.15 1.15
    1.15 1.15

    Cn-33 Torque limit % 150 150 150 150 150 150 150 150

    Cn-37 Momentary power lossassurance time s 2.0 2.0 2.0 2.0 2.0
    2.0 2.0 2.0

    Cn-40 Minimum baseblock time s 0.7 1.0 1.0 1.0 1.0 1.0 1.0
    1.0

    Cn-41 V/f during speed search % 100 100 100 80 80 80 80 80

    Fact

    ory

    Set

    ting

    bn-08 Rated slip of motor Hz 1.6 1.7 1.7 1.8 1.3 1.6 1.5 1.4

    The allowable maximum carrier frequency is 10kHz

  • 71

    Inverter Capacity Selection440V Class

    Data of Sn-01

    Name20 21 22 23 24 25 26 27 28 29 2A

    Inverter rating HP 0.5 1 2 3 5 7.5 10 15 20 25 30

    Inverter rated capacity kVA 1.4 2.1 3.4 4.1 6.9 10.3 13.7 20.6
    27.4 34 41

    Max. applicable motor capacity HP (kW)0.5

    (0.4)

    1

    (0.75)

    2

    (1.5)

    3

    (2.2)

    5

    (3.7)

    7.5

    (5.5)

    10

    (7.5)

    15

    (11)

    20

    (15)

    25

    (18.5)

    30

    (22)

    Inverter rated current A 1.6 2.6 4.0 4.8 8 12 16 24 32 40 48

    Cn-09 Motor rated current A 1.0 1.7 2.9 4.0 6.8 10.0 12.6 18.6
    24.8 31.1 36.3

    Cn-23 Carrier frequency upperlimit kHz 15.0 15.0 15.0 15.0 15.0
    15.0 15.0 15.0 15.0 10.0 10.0

    Cn-24 Carrier frequency lowerlimit kHz 15.0 15.0 15.0 15.0 15.0
    15.0 15.0 15.0 15.0 10.0 10.0

    Cn-25 Carrier frequencyproportional gain 0 0 0 0 0 0 0 0 0 0
    0

    Cn-31 Motor phase-to-phaseresistance 47.02 22.929 9.629 6.333
    2.735 1.776 1.151 0.634 0.436 0.308 0.239

    Cn-32 Motor leakage inductance mH 168.7 80.76 53.25 40.03 24.84
    16.87 10.59 8.93 5.90 5.54 4.59

    Cn-33 Torque limit % 150 150 150 150 150 150 150 150 150 150
    150

    Cn-37 Momentary power lossassurance time s 1.0 1.0 1.0 1.0 2.0
    2.0 2.0 2.0 2.0 2.0 2.0

    Cn-40 Minimum baseblock time s 0.5 0.5 0.5 0.5 0.5 0.7 0.7 0.7
    1.0 1.0 1.0

    Cn-41 V/f during speed search % 100 100 100 100 100 100 100 100
    100 100 100

    Fact

    ory

    Set

    ting

    bn-08 Rated slip of motor Hz 2.7 2.6 2.5 3.0 3.2 1.5 1.3 1.7 1.6
    1.7 1.7

  • 72

    Inverter Capacity Selection440V Class

    Data of Sn-01

    Name2B 2C 2D 2E 2F 30 31 32 33 34 35 36

    Inverter rating HP 40 50 60 75 100 125 150 175 215 250 300
    400

    Inverter rated capacity kVA 54 68 82 110 138 180 195 230 260 290
    385 514

    Max. applicable motor capacity HP (kW)40

    (30)

    50

    (37)

    60

    (45)

    75

    (55)

    100

    (75)125

    150

    (110)175

    215

    (160)

    250

    (185)

    300

    (220)

    400

    (300)

    Inverter rated current A 64 80 96 128 165 192 224 270 300 340
    450 600

    Cn-09 Motor rated current A 48.7 59.0 70.5 88.0 114 143 175 206
    235 290 348 465

    Cn-23 Carrier frequency upperlimit kHz 10.0 10.0 10.0 10.0 3.0
    3.0 3.0 3.0 3.0 2.0 2.0 2.0

    Cn-24 Carrier frequency lowerlimit kHz 10.0 10.0 10.0 10.0 3.0
    3.0 3.0 3.0 3.0 2.0 2.0 2.0

    Cn-25 Carrier frequencyproportional gain 0 0 0 0 0 0 0 0 0 0 0
    0

    Cn-31 Motor phase-to-phaseresistance 0.164 0.133 0.110 0.074
    0.027 0.051 0.036 0.032 0.023 0.020 0.022 0.014

    Cn-32 Motor leakage inductance mH 3.59 2.60 2.26 2.26 2.26 2.26
    2.26 2.26 2.26 2.26 2.26 2.26

    Cn-33 Torque limit % 150 150 150 150 150 150 150 150 150 150 150
    150

    Cn-37 Momentary power lossassurance time s 2.0 2.0 2.0 2.0 2.0
    2.0 2.0 2.0 2.0 2.0 2.0 2.0

    Cn-40 Minimum baseblock time s 1.0 1.0 1.0 1.0 1.0 1.0 2.0 2.0
    2.0 2.0 2.0 2.0

    Cn-41 V/f during speed search % 100 100 100 80 80 80 80 80 80 80
    80 80

    Fact

    ory

    Set

    ting

    bn-08 Rated slip of motor Hz 1.8 1.3 1.6 1.5 1.4 1.4 1.4 1.4 1.3
    1.3 1.2 1.2

    The allowable maximum carrier frequency of 440V class 100HP to
    215HP are to beas follows:

    440V Horse Power 100HP 125HP 150HP 175HP 215HP

    Max. Allowable Carrier Frequency 8kHz 6kHz 6kHz 5kHz 10kHz

  • 73

    V/f Pattern Selection Sn-02

    Valid Access LevelsParameterNo. Name

    LCD Display(English) Description

    FactorySetting

    Change DuringOperation GP SL PID PG

    Sn-02 V/f CurveSelectionSn-02=01V/f Curve

    V/f pattern Selection 01

    V/f pattern is selected by the setting of Sn-02. When V/f
    pattern is selected, set inputvoltage of the inverter in Cn-01.

    Data 0 — E (of Sn-02): Change disabled

    Data F (of Sn-02): Change enabled(V/f patterns are shown on the
    following pages).

    The V/f pattern is fixed to Sn-02=0F for the SL control mode;
    The users have to checkthe V/f pattern to meet the load application
    if switched to one of the other threecontrol mode (GP, PID or PG)
    from SL control mode.

    To select the high starting torque V/f pattern for inverter mode
    of capacity 440V100HP (75KW) or more is recommended.

    In the sensorless vector control mode (SL), if sufficient torque
    cannot be obtained at alow speed, change the V/f pattern setting of
    Cn-02 to Cn-08 to high starting V/f.

    [Example]

    1 3 60f (Hz)

    V (v)Standard V/f

    220

    (Cn-06) 11

    (Cn-08) 4.37

    1 3 60f (Hz)

    V (v)

    High starting V/f

    220

    (Cn-06) 13

    (Cn-08) 5

    (Cn-07)(Cn-05)(Cn-07)(Cn-05)

  • 74

    V/f Pattern of 220V Class* 3 to 60 HP (2.2 to 45kW)

    Specifications Sn-02 V/f Pattern Specifications Sn-02 V/f
    Pattern

    LowStartingtorque

    8

    50Hz 0 50Hz

    HighStartingtorque

    9

    60HzSatu-ration

    1F

    LowStartingtorque

    A

    60Hz

    50HzSatu-ration

    2

    Hig

    h St

    artin

    g To

    rque

    60Hz

    HighStartingtorque

    BGen

    eral

    -pur

    pose

    72Hz 3 90Hz C

    Variabletorque 1 4

    50Hz

    Variabletorque 2 5

    120Hz D

    Variabletorque 3 6

    Varia

    ble

    Torq

    ue C

    hara

    cter

    istic

    s

    60Hz

    Variabletorque 4 7

    Rat

    ed O

    utpu

    t Ope

    ratio

    n (M

    achi

    ne to

    ol)

    180Hz E

    * For 440V class, 2 times voltage value shown in table above.
    Consider the following items as conditions for selecting a V/f
    pattern.

    They must be suitable for:(1) The voltage and frequency
    characteristics of the motor.(2) The maximum rotation speed of the
    motor.

    Select high starting torque only in the following conditions.
    Normally, this selection is not required.(1) The wiring distance is
    long [492ft (150m) and above].(2) Voltage drop at startup is
    large.(3) AC reactor is inserted in the input or output of the
    inverter.(4) A motor smaller than the maximum applicable inverter
    is used.

    220(V)

    (Hz)0 1.3 2.5 50

    1611

    0

    220(V)

    (Hz)0 1.5 3 50 60

    1611

    2

    1

    F

    220(V)

    (Hz)0 1.5 3 60 72

    1611

    3

    1.8 3.6

    220(V)

    (Hz)0 1.3 25 50

    5539

    5

    411 9

    220(V)

    (Hz)0 1.5 30 60

    5539

    7

    611 9

    220(V)

    (Hz)0 1.5 3 60 180

    33 1628 11

    E

    4.5 6

    220(V)

    (Hz)0 1.5 3 60 120

    38 1620 11

    D

    3 6

    220(V)

    (Hz)0 1.5 3 60 90

    1611

    C

    2.5 4.5

    220(V)

    (Hz)0 1.5 3 60

    25 2820 22

    2014 13

    B

    A

    220(V)

    (Hz)0 1.3 2.5 50

    25 2820 22 15 13

    9

    8

  • 75

    V/f Pattern of 220V Class* 75 and 100HP (55 and 75kW), (75 to
    400HP for 440V class)

    Specifications Sn-02 V/f Pattern Specifications Sn-02 V/f
    Pattern

    LowStartingtorque

    8

    50Hz 0 50Hz

    HighStartingtorque

    9

    60HzSatu-ration

    1F

    LowStartingtorque

    A

    60Hz

    50HzSatu-ration

    2

    Hig

    h St

    artin

    g To

    rque

    60Hz

    HighStartingtorque

    BGen

    eral

    -pur

    pose

    72Hz 3 90Hz C

    Variabletorque 1 4

    50Hz

    Variabletorque 2 5

    120Hz D

    Variabletorque 3 6

    Varia

    ble

    Torq

    ue C

    hara

    cter

    istic

    s

    60Hz

    Variabletorque 4 7

    Rat

    ed O

    utpu

    t Ope

    ratio

    n (M

    achi

    ne to

    ol)

    180Hz E

    * For 440V class, 2 times voltage value shown in table above.
    Consider the following items as conditions for selecting a V/f
    pattern.

    They must be suitable for:(1) The voltage and frequency
    characteristics of the motor.(2) The maximum rotation speed of the
    motor.

    Select high starting torque only in the following conditions.
    Normally, this selection is not required.(1) The wiring distance is
    long [492ft (150m) and above].(2) Voltage drop at startup is
    large.(3) AC reactor is inserted in the input or output of the
    inverter.(4) A motor smaller than the maximum applicable inverter
    is used.# Up to 100HP (75kW) for 220V class.

    220(V)

    (Hz)0 1.3 2.5 50

    14 8

    0

    220(V)

    (Hz)0 1.5 3 50 60

    14 8

    2

    1

    F

    220(V)

    (Hz)0 1.5 3 60 72

    14 8

    3

    220(V)

    (Hz)0 1.3 25 50

    5538

    5

    410 8

    220(V)

    (Hz)0 1.5 30 60

    5538

    7

    610 8

    220(V)

    (Hz)0 1.5 3 60 180

    14 8

    E

    220(V)

    (Hz)0 1.5 3 60 120

    14 8

    D

    220(V)

    (Hz)0 1.5 3 60 90

    14 8

    C

    220(V)

    (Hz)0 1.3 2.5 50

    25201311

    9

    8

    220(V)

    (Hz)0 1.3 3 60

    2520

    11

    B

    A

  • 76

    Operator Status Sn-03

    Valid Access LevelsParameterNo. Name

    LCD Display(English) Description

    FactorySetting

    ChangeDuring

    Operation GP SL PID PG

    Display ofOperator

    0000: Setting and reading of An-,Bn-,Cn-, Sn-enabled

    0101: Setting and reading of An-,Readinng of Bn-,Cn-,Sn-
    enabled

    Sn-03

    ConstantsInitialization

    Sn-03=0000Operate Setting

    1110: Constants Initialigation (2-wire)*21111: Constants
    Initialigation (3-wire)*2

    0000

    The ability to set or read the different groups of constants is
    determined by Sn-03 asshow below.

    DRIVE Mode PRGM ModeSn-03

    Setting Reading Setting ReadingRemarks

    0000 An, bn Sn, Cn An, bn, Sn, Cn Factory setting

    0101 An bn, Sn, Cn An bn, Sn, Cn *

    * It is recommended that Sn-03 be set to 0101 and reading mode
    entered after test run adjustment.Note: To read the Sn or Cn
    constants while in the DRIVE mode, depress the DSPL key with

    key depressed.

    Initialization (Sn-03=1110, 1111)

    After depressing the ENTER key, input the initial value of An-,
    bn-, Sn-,Cn-, (except Sn-01,Sn-02) into NV-RAM. When the value is
    written in without anerror, Entry accepted (End) is displayed. When
    the value is written in with an error,** Error (Err) alarm is
    displayed. The values of Sn-15 to -18 differ as followsbetween
    initializations with Sn-03 = 1110 and with Sn-03 = 1111.

    Multi-functionTerminal

    1110(2 Wire Sequence)

    1111(3 Wire Sequence)

    Terminal 5 (Sn-15) 3* (Multi-step speed command 1) 0 (FWD/REV
    run select)

    Terminal 6 (Sn-16) 4* (Multi-step speed command 2) 3 (Multi-step
    speed reference 1)

    Terminal 7 (Sn-17) 6* (Jog frequency reference) 4 (Multi-step
    speed reference 2)

    Terminal 8 (Sn-18) 8* (External baseblock command) 6 (Jog
    frequency reference)

    * Values have been factory-set.** contents depend on the
    parameter setting items.

    RESET

  • 77

    Operation Mode Selection 1 Sn-04

    Valid Access LevelsParameterNo. Name

    LCD Display(English) Description

    FactorySetting

    ChangeDuring

    Operation GP SL PID PG

    — — -0: Frequency Command = Controlcircuit terminals 13 or
    14

    — — -1: Frequency Command =Frequency Command 1 (An-01)Operation
    Mode

    Select — -0 -: RUNSTOP Command =Control circuit terminals

    — -1 -: RUNSTOP Command =LCD Digital OperatorSn-04

    StoppingMethod

    Selection

    Sn-04=0011Stopping Method

    00- -: Stopping method = Ramp to stop01- -: Stopping method
    =Coasting

    to stop10- -: Stopping method =Full-range DC

    injection branking stop11- -: Stopping method = Coasting
    stop

    (timer function provided)

    0011

    (1) 1st digit (frequency reference selection)

    1st digit = 0: Reference input from control circuit terminal 13
    or 14 is the masterspeed frequency reference.

    1st digit = 1: Frequency reference 1 (An-01) is the master speed
    frequencyreference.

    Note: For combination of multi-step speed operation, refer to
    pages 90.

    (2) 2nd digit (run command selection)

    2nd digit = 0: Run command from control circuit terminal is
    accepted.

    2nd digit = 1: Run command from the digital operator is
    accepted.

    Valid run command and frequency references differ as shown in
    the table below,depending on the combination of the 1st and 2nd
    digits.

    2nd digit 1st digit 2nd digit 1st digit 2nd digit 1st digit 2nd
    digit 1st digitCONSTANTREFERENCE

    SYSTEM CONSTANTS 40 0 0 1 1 0 1 1

    Master Speed Frequency Reference Control circuitterminal 13, 14
    An-01Control circuitterminal 13, 14 An-01

    FWD Run Command (Terminal 1) REV Run Command (Terminal 2)
    External Fault (Terminal 3) Fault Reset (Terminal 4)Command of
    Terminal 5 Command of Terminal 6 Command of Terminal 7 Command of
    Terminal 8 Aux. Input Fault Contact Output Multi-function Contact
    Output

    ControlTerminal

    Multi-function PHC Output RUN Key JOG Key STOP Key FWD/REV Key
    >/RESET Key

    DRIVE/PRGM Key Valid only wheninverter stoppedValid only
    wheninverter stopped

    Valid only wheninverter stopped

    Valid only wheninverter stopped

    Operator

    REF LED Lit OFF Lit OFF

  • 78

    SEQ LED Lit Lit OFF OFFMonitor display

    Valid only when the inverter stops. (FWD run command, REV run
    command, and DC injection braking command are «open».)

    FWD/REV run command is not accepted.

    When the STOP key is depressed, processing differs as follows,
    depending on the setting of the 1st digit of Sn-05.

    1st digit = 0: During running by signals from control circuit
    terminals, the STOP key from the operator is accepted.

    If the STOP key is depressed, the inverter stops according to
    the setting of 3rd and 4th digits of Sn-04, while the STOP
    LEDindicator blinks. This stop command is held within the inverter
    until both the FWD run command and REV run command of
    controlcircuit terminals become «open», or another frequency
    reference is selected in the multi-step speed command or jog
    frequencyreference section.

    1st digit=1: During running by signals from control circuit
    terminals, the STOP key from the operator is not accepted.

    (3) 3rd digit, 4th digit (stop method selection)

    Stop method differs by the setting of 3rd and 4th digits as
    shown below.

    1 Sn-04 = 00 XX RAMP to stop

    2 Sn-04 = 01 XX Coast to stop

    RUN COMMAND

    OUTPUT FREQUENCY

    DC INJECTION BRAKINGSTART FREQUENCY(Cn-10)

    DC Injection Braking time atStopping (Cn-12)

    DECELERATION TIME

    DC INJECTIONBRAKING

    CLOSEDOPEN

    RUN COMMANDOUTPUT FREQUENCY

    CLOSEDOPEN

    WHEN STOPREFERENCE IS INPUT,INVERTER OUTPUT IS

  • 79

    3 Sn-04 = 10 XX Full-range DC injection braking stop

    DC injection braking time differs by the output frequency when
    stop command isinput as shown below.

    OUTPUT FREQUENCY WHEN STOPREFERENCE IS INPUT

    4 Sn-04 = 11 XX Coasting to a Stop (timer function provided)

    Once stop command is input, run command is disregarded during T1
    time.

    RUN COMMANDOUTPUT FREQUENCY

    CLOSEDOPEN

    0.5s

    CUTOFF OFINVERTEROUTPUT

    DC INJECTIONBRAKING TIME

    DC INJECTIONBRAKING TIME

    DC INJECTION BRAKINGTIME AT STOPPING (Cn-12)

    Cn-12 x 10

    10% SPEED 100% SPEED

    RUN COMMAND

    OUTPUT FREQUENCY

    CLOSEDOPEN

    DECELERATION TIME

    WHEN STOP REF. ISINPUT, INVERTEROUTPUT IS CUTOFF.

    CLOSED

    T1 Time

    T1 Time

  • 80

    OUTPUT FREQUENCY WHENSTOP REFERENCE IS INPUT.

  • 81

    Operation Mode Selection 2 Sn-05

    1. GP, SL, PIDValid Access LevelsParameter

    No. NameLCD Display

    (English) DescriptionFactorySetting

    ChangeDuring

    Operation GP SL PID PG

    — — -0: Stop key effective duringoperation from control
    terminal

    — — -1: Stop key effective duringoperation from control
    terminal

    — -0 -: Reverse run enabled- -1 -: Reverse run disabled- 0- -:
    Control input terminals 1 ~8

    are scanned twice.- 1- -: Control input terminals 1 ~8

    are scanned once.

    Sn-05I/O terminal

    functionselection

    Sn-05=0000I/O term. Fct

    0- — -: Selection of item to be analogoutput (terminals 21 , 22
    )*3

    1- — -: Selection of item to be analogoutput (terminals 21 , 22
    )*3

    0000 1 1 1 2

    (1) 1st digit

    Select processing to be performed when the STOP key of the
    digital operator isdepressed during running by control circuit
    terminals.

    1st digit = 0: During running by signals from control circuit
    terminals, the STOP keyfrom the digital operator is accepted. If
    the STOP key is depressed, theinverter stops according to the
    setting of the 3rd and 4th digits of Sn-04while the STOP LED
    indicator blinks. This stop command is held withinthe inverter
    until both the FWD run command and REV run commandof control
    circuit terminals become «open», or other frequency referenceis
    selected in the multi-step speed command or jog frequencyreference
    section.

    1st digit = 1: During running by signals from control circuit
    terminals, the STOP keyfrom the digital operator is not
    accepted.

    (2) 2nd digit (REV run prohibited)

    2nd digit = 0: REV run command from control circuit terminals or
    the digital operatoris accepted.

    2nd digit = 1: REV run command from control circuit terminals or
    the digital operatoris not accepted.

    (3) 3rd digit (selection of double scanning sequence
    command)

    3rd digit = 0: Sequence command (control circuit terminals 1 to
    8) is scanned twice.

    3rd digit = 1: Sequence command (control circuit terminals 1 to
    8) is scanned once.

    (4) 4th digit (selection of the multi-function analog
    output)

    Multi-function analog output (control circuit terminals 21, 22)
    output signal can beselected by Sn-05 4th digit and Sn-09 2nd
    digit.

    Sn-054th Digit

    Sn-092nd Digit Description

    0 0 Outputs analog signal proportional to inverter output
    frequency.(Max. frequency/100%)

    1 0 Outputs analog signal proportional to inverter
    current.(Rated current/100%)0 1 Outputs analog signal proportional
    to inverter output voltage reference.

  • 82

    (Cn-01/100%)

    1 1 Outputs analog signal proportional to inverter output
    power.(Max motor capacity/100%)

    2. PGValid Access LevelsParameter

    No. NameLCD Display

    (English) DescriptionFactorySetting

    ChangeDuring

    Operation GP SL PID PG

    — — -0: Stop key effective duringoperation from control
    terminal

    — — -1: Stop key effective duringoperation from control
    terminal

    — -0 -: Reverse run enabled- -1 -: Reverse run disabled

    — 0- -: Control input terminals 1 ~8are scanned twice.

    — 1- -: Control input terminals 1 ~8are scanned once.

    Sn-05I/O terminal

    functionselection

    Sn-05=0000I/O term. Fct

    0- — -: Not used1- — -: Not used

    0000 1 1 1 2

    (1) 1st, 2nd, 3rd, digit (functions same as GP, SL, PID control
    mode)

    (2) 4th digit (Not used)

    [Note] The item to be output from multi-function analog output
    (Control circuit terminals21 -22 ) is set by bn-11 in the GP
    control mode. Please refer to bn-11.

  • 83

    Operation Mode Selection 3 Sn-06Valid Access LevelsParameter

    No. NameLCD Display

    (English) DescriptionFactorySetting

    ChangeDuring

    Operation GP SL PID PG

    — -00: S curve=0.2sec- -01: S curve=0.0sec (NO S curve)- -10: S
    curve=0.5sec- -11: S curve=1.0sec-0 — -: Reference command has
    forward

    characteristics(0-10V or 4-20mA/0~100%)

    -1 — -: Reference command has reversecharacteristics(0-10V or
    4-20mA/100~0%)

    Sn-06

    S-curve andfrequencyCommand

    characteristics

    Sn-06=0000S-curve Cmd.

    Char.

    0- — -: Stop by reference input whenfrequency reference is
    missing

    1- — -: Operation to continue with 80% offrequence reference
    whenfrequency reference is missing

    0000

    (1) 1st digit, 2nd digit (S-curve selection of soft starter)

    The S-curve characteristics of the soft starter depend on the
    setting of the 1st and2nd digits as follows:

    2nd digit 1st digit Contents0011

    0101

    The S-curve characteristic is 0.2 second.No S-curve
    characteristics.The S-curve characteristic is 0.5 second.The
    S-curve characteristic is 1 second.

    Note: S-curve characteristic time refers to the time from
    acceleration rate 0 to the time when anormal acceleration rate
    determined by a specified acceleration time is obtained.

    (a) Time chart at FWD/REV run change with S-curve
    characteristicThe figure below shows the time chart at FWD/REV run
    change duringdeceleration and stop.

    FREQUENCYREF.

    OUTPUT FREQUENCY

    TIME

    S-CURVECHARACTERISTICSTIME (TSC)

    FWD RUNCOMMAND

    REV RUNCOMMAND

    ACCELER-ATION

    DECELER-ATION

    DC INJECTIONBRAKING TIMEAT STOPPING(Cn-12)

    ACCELERATION

    OUTPUTFREQUENCY

    MIN. OUTPUTFREQUENCY(Cn-07)

    : S-CURVE CHARACTERISTIC

    MIN. OUTPUTFREQUENCY(Cn-07)

    DECELER-ATION

    DC INJECTION BRAKINGSTART FREQUENCY (Cn-

    10)

  • 84

    (b) The chart at FWD/REV run change without S-curve
    characteristicThe figure below shows the time chart at FWD/REV run
    change duringdeceleration and stop.

    (2) 3rd digit (reverse characteristic selection)

    The input characteristics of the master speed frequency
    reference depend on theset value as follows. For the reverse
    characteristic, only + input is valid.

    3rd digit = 0: Normal characteristic (0-10V or
    4-20mA/0-100%)

    3rd digit = 1: Reverse characteristic (10-0V or
    20-4mA/0-100%)

    FWD RUNCOMMAND

    REV RUNCOMMAND

    ACCELER-ATION

    DECELER-

    ATIONDC INJECTIONBRAKING TIMEAT STOPPING(Cn-12)

    ACCELERATION

    OUTPUTFREQUENCY

    MIN. OUTPUTFREQUENCY(Cn-07)

    DC INJECTION BRAKINCSTART FREQUENCY (Cn-

    10)

    MIN. OUTPUTFREQUENCY(Cn-07)

    DECELER-ATION

    0%

    FREQUENCYREFERENCE

    100%

    4mA 20mA

    CURRENT INPUT (TERMINAL 14)

    3rd digit = 0 3rd digit = 1

    0%

    FREQUENCYREFERENCE

    100%

    0V 10V

    VOLTAGE INPUT (TERMINAL 13)

  • 85

    (3) 4th digit (operation selection when frequency reference is
    missing)

    4th digit = 0: Normal operation (varies with change of
    reference)

    4th digit = 1: Operation continues with 80% frequency.

    When 4th digit = 1 is set, the current master speed frequency
    reference iscompared at all times with the one that occurred 0.4
    second before. When thecurrent master speed frequency reference
    goes below 10% of the one that occurred0.4 second before, operation
    continues with 80% (80% frequency) of the masterspeed frequency
    reference of the prior one. Consequently, the master speedfrequency
    reference of the previous one (0.4 second before) is used as the
    currentfrequency reference.

    In the following cases, this operation is released and the
    inverter returns to normaloperation:

    Master speed frequency reference exceeding 80% frequency is
    input.

    Stop reference is input.

    Reference is missing during operation at less than 5% of
    frequency.

    FWD RUNCOMMAND

    80%MASTER SPEEDFREQUENCYREFERENCE

    INVERTEROUTPUTFREQUENCY TIME CHART

    10%

    80% OFFREQUENCY

    0.4sec.

    0.4sec.

  • 86

    Operation Mode Selection 4 Sn-07

    1. GP, PID, PGValid Access LevelsParameter

    No. NameLCD Display

    (English) DescriptionFactorySetting

    ChangeDuring

    Operation GP SL PID PG

    — — -0: Overtorque detection disabled

    — — -1: Overtorque detection enabled

    — -0 -: Enabled only if at agreedfrequency

    — -1 -: Enable during operation (exceptduring DC injection)

    — 0- -: Operation continued afterovertorque is detected

    — 1- -: Coasts to stop if overtorque isdetected

    Sn-07 OvertorqueDetectionSn-07=0000

    Over Tq. Detect

    0- — -: Overtorque detection with current1- — -: Overtorque
    detection with torque

    0000 1 2 1 1

    Define the operation at overtorque detection. Overtorque is
    detected by the followingformula:

    Inverter output current B overtorque detection level (Cn-26,
    Initial value: 160%)

    (Detection time Cn-27, Initial value: 0.1 second, Hysteresis
    fixed at 10%)

    (1) 1st digit

    1st digit = 0: Overtorque is not detected.

    1st digit = 1: Overtorque is detected.

    (2) 2nd digit

    2nd digit = 0: Overtorque is detected only during agreed
    frequency.

    2nd digit = 1: Overtorque is detected during stop or during
    running except for DB.

    (3) 3rd digit

    3rd digit = 0: When overtorque is detected, Over Torque (OL3)
    Alarm blinks on thedigital operator and the operation
    continues.

    3rd digit = 1: When overtorque is detected, Over Torque (OL3)
    Fault is displayedon the digital operator and the inverter output
    is shut OFF. Fault contactsignal is output. (Treated as a
    fault).

    Setting either Sn-20 or 22 to 0B enables signal to be output at
    overtorque detection.

    MULTI-FUNCTION OUTPUT SIGNAL(OVERTORQUE DETECTION SIGNAL)

    MOTORCURRENT

    HYSTERESIS 10%

    TIME

    ONCn-27

    Cn-26

    ONCn-27

  • 87

    (4) 4th digit (Not used)

    2. SLValid Access LevelsParameter

    No. NameLCD Display

    (English) DescriptionFactorySetting

    ChangeDuring

    Operation GP SL PID PG

    — — -0: Overtorque detection disabled

    — — -1: Overtorque detection enabled

    — -0 -: Enabled only if at agreedfrequency

    — -1 -: Enable during operation (exceptduring DC injection)

    — 0- -: Operation continued afterovertorque is detected

    — 1- -: Coasts to stop if overtorque isdetected

    Sn-07 OvertorqueDetectionSn-07=0000

    Over Tq. Detect

    0- — -: Overtorque detection with current1- — -: Overtorque
    detection with torque

    0000 1 2 1 1

    (1) 1st, 2nd, 3rd digit (functions same as GP, PID,PG control
    mode)

    (2) 4th digit

    4th digit = 0: Overtorque detected with current.

    4th digit = 1: Overtorque detected with torque.

  • 88

    Operation Mode Selection 5 Sn-08

    1. GP, SLValid Access LevelsParameter

    No. NameLCD Display

    (English) DescriptionFactorySetting

    ChangeDuring

    Operation GP SL PID PG

    — — -0: Frequency reference input byoption card (AI-14B, DI-08
    or SI-M)

    — — -1: Frequency reference input bydigital operetor or control
    cirauitinput terminals

    — -0 -: RUN/STOP command input byoption card (AI-14B, DI-08 or
    SI-M)

    — -1 -: RUN/STOP command input bydigital operator or control
    circuitinput terminals

    Sn-08

    OptionCard/Invater

    FunctionSelection

    Sn-08=0000

    AI/DI & SI-M Card

    00- -: SI-M communication fault,deceleration to stop (bn-02)

    01- -: SI-M communication fault, coastto stop

    10- -: SI-M communication fault,deceleration to stop (bn-04)

    11- -: SI-M communication fault,continue to run

    0000 1 1 2 3

    (1) 1st digit (option/inverter change)

    Specify whether option card or inverter frequency reference is
    used for operation.

    1st digit = 0: Option card frequency reference is accepted.

    1st digit = 1: Frequency reference from inverter control circuit
    terminals or the digitaloperator is accepted.

    (2) 2nd digit (run command option/inverter change)

    Select whether operation is performed by the option card or
    inverter run command.

    2nd digit = 0: Run command from option card received.

    2nd digit = 1: Run command from inverter control circuit
    terminal or digital operatorreceived.

    (3) 3rd digit, 4th digit (selection of stopping method at
    communication error detection)

    Stopping method at communication error detection can be selected
    bycommunication interface card (SI-M).

    4th digit 3rd digit Contents

    0

    0

    1

    1

    0

    1

    0

    1

    Ramp to stop by bn-02 (major fault)

    Coast to stop (major fault)

    Ramp to stop by bn-04 (major fault)

    Operation to continue (minor fault)

  • 89

    2. PIDValid Access LevelsParameter

    No. NameLCD Display

    (English) DescriptionFactorySetting

    ChangeDuring

    Operation GP SL PID PG

    — — -0: Frequency reference input byoption card (AI-14B, DI-08
    or SI-M)

    — — -1: Frequency reference input bydigital operetor or control
    cirauitinput terminals

    — -0 -: RUN/STOP command input byoption card (AI-14B, DI-08 or
    SI-M)

    — -1 -: RUN/STOP command input bydigital operator or control
    circuitinput terminals

    -0 — -: Auto Energy Saving functionineffective (nornal V/f
    controlmethod)

    -1 — -: Auto Energy Saving functioneffective

    Sn-08

    OptionCard/InvaterFunction &

    Energy SavingSelection

    Sn-08=0000

    AI/DI & Eg. Saving

    0- — -: Not used1- — -: Not used

    0000 1 1 2 3

    (1) 1st, 2nd, digit (functions same as GP, SL control mode)

    (2) 3rd digit (Auto Energy Saving selection)

    3rd digit = 0: Auto Energy Saving (AES) function ineffective

    3rd digit = 1: Auto Energy Saving function effective. (ref. To
    Appendix B)

    (3) 4th digit (Not used)

    3. PGValid Access LevelsParameter

    No. NameLCD Display

    (English) DescriptionFactorySetting

    ChangeDuring

    Operation GP SL PID PG

    — — -0: Frequency reference input byoption card (AI-14B, DI-08
    or SI-M)

    — — -1: Frequency reference input bydigital operetor or control
    cirauitinput terminals

    Sn-08

    OptionCard/Invater

    FunctionSelection

    Sn-08=0000

    AI/DI Card- -0 — -1 —0 — —1 — — Not used0- — -1- — —

    0000 1 1 2 3

    (1) 1st digit (functions same as GP, SL control mode)

    (2) 2nd, 3rd, 4th digit (Not used)

  • 90

    Operation Mode Selection 6 Sn-09

    1. GPValid Access LevelsParameter

    No. NameLCD Display

    (English) DescriptionFactorySetting

    ChangeDuring

    Operation GP SL PID PG

    — — -0: Analog output (tereminal 21 -22 )depends on Sn-05 4th
    digit andSn-09 2nd digit.

    — — -1: Analog output (tereminal 21 -22 )is set by SI-M
    card.

    — -0 -: Analog output (tereminal 21 -22 )- -1 -: Analog output
    (tereminal 21 -22 )

    Sn-09

    Analog OutputSelection and

    SlipCompensetion

    Sn-09=0000

    ~Output Select

    -0 — —1 — -0- — — Not used1- — —

    0000 1 2 3

    (1) 1st digit (selection of analog output)

    Multi-function analog output signal contents can be set either
    by the inverter oroption card.

    1st digit = 0: Output according to Sn-05 4th digit and Sn-09 2nd
    digit settingcontents.

    1st digit = 1: Output according to contents set by communication
    interface card (SI-M).

    (2) 2nd digit (selection of multi-function analog output
    signal)

    Multi-function analog output (control circuit terminals 21 — 22)
    output signal can beselected according to Sn-05 4th digit and Sn-09
    2nd digit set value. Output signallevel is set by bn-11.

    Sn-054th Digit

    Sn-092nd Digit Description

    0 0 Outputs analog signal proportional to inverter output
    frequency.(Max. frequency/100%)

    1 0 Outputs analog signal proportional to inverter
    current.(Rated current/100%)

    0 1 Outputs analog signal proportional to inverter output
    voltagereference. (Cn-01/100%)

    1 1 Outputs analog signal proportional to inverter output
    power.(Max. applicable motor capacity/100%)

    (3) 3rd, 4th digit (Not used)

  • 91

    2. SLValid Access LevelsParameter

    No. NameLCD Display

    (English) DescriptionFactorySetting

    ChangeDuring

    Operation GP SL PID PG

    — — -0: Analog output (tereminal 21 -22 )depends on Sn-05 4th
    digit andSn-09 2nd digit.

    — — -1: Analog output (tereminal 21 -22 )is set by SI-M
    card.

    — -0 -: Analog output (tereminal 21 -22 )- -1 -: Analog output
    (tereminal 21 -22 )-0 — -: Not used-1 — -: Not used

    Sn-09

    Analog OutputSelection and

    SlipCompensetion

    Sn-09=0000~Output Select

    0- — -: No slip compensation duringregenerating

    1- — -: Slip compensation even duringregenerating

    0000 1 2 3

    (1) 1st digit (functions same as GP control mode)

    (2) 2nd digit (selection of multi-function analog output
    signal)

    Multi-function analog output (control circuit terminals 21 — 22)
    output signal can beselected according to Sn-05 4th digit and Sn-09
    2nd digit set value. Output signallevel is set by bn-11.

    Sn-054th Digit

    Sn-092nd Digit Description

    0 0 Outputs analog signal proportional to inverter output
    frequency.(Max. frequency/100%)

    1 0 Outputs analog signal proportional to inverter
    current.(Rated current/100%)

    0 1 Outputs analog signal proportional to inverter output
    voltagereference. (Cn-01/100%)

    1 1 Outputs analog signal proportional to inverter output
    torque.(10V/250% motor rated torque)

    (3) 3rd digit (Not used)

    (4) 4th digit (Slip compensation during regenerating
    selection)

    4th digit = 0: No slip compensation during regenerating.

    4th digit = 1: Slip compensation even during regenerating.

    3. PIDValid Access LevelsParameter

    No. NameLCD Display

    (English) DescriptionFactorySetting

    ChangeDuring

    Operation GP SL PID PG

    — — -0- — -1 Not used

    — -0 -: Analog output (tereminal 21 -22 )- -1 -: Analog output
    (tereminal 21 -22 )Sn-09

    Analog OutputSelection and

    SlipCompensetion

    Sn-09=0000~Output Select -0 — —

    -1 — -0- — — Not used1- — —

    0000 1 2 3

    (1) 1st digit (Not used)

    (2) 2nd digit (functions same as GP control mode)

  • 92

    (3) 3rd, 4th digit (Not used)

  • 93

    Protective Characteristic Selection 1 Sn-10

    Valid Access LevelsParameterNo. Name

    LCD Display(English) Description

    FactorySetting

    ChangeDuring

    Operation GP SL PID PG

    — — -0: Stall prevention duringacceleration enabled

    — — -1: Stall prevention duringacceleration disabled

    — -0 -: Stall prevention duringdeceleration enabled

    — -1 -: Stall prevention duringdeceleration disabled

    — 0- -: Stall prevention during runningenabled

    — 1- -: Stall prevention during runningdisabled

    Sn-10 Stall PreventionSn-10=0000

    Stall Select

    0- — -: Decel time during stall prevention(bn-02 set value)

    1- — -: Decel time during stall prevention(bn-04 set value)

    0000

    (1) 1st digit (selection of stall prevention during
    acceleration)1st digit = 0: Stall prevention during acceleration is
    enabled.

    1st digit = 1: Stall prevention during acceleration is
    disabled.

    The function of stall prevention during acceleration
    automatically extendsacceleration according to load status
    (inverter output current), thus preventing themotor from stalling
    during acceleration. The stall prevention level duringacceleration
    in a constant output area is reduced as follows:

    Acceleration stallprevention level of =constant output field
    output frequency

    When the 1st digit of Sn-10 is 1, the output frequency increases
    at the ratedetermined by acceleration time:

    (2) 2nd digit (selection of stall prevention during
    deceleration)2nd digit = 0: Stall prevention during deceleration is
    enabled.

    2nd digit = 1: Stall prevention during deceleration is
    disabled.

    The function of stall prevention during deceleration
    automatically extendsdeceleration time according to the magnitude
    of the main circuit DC voltage, thuspreventing overvoltage during
    deceleration.

    When the 2nd digit of Sn-10 is 1, the output frequency decreases
    at the ratedetermined by deceleration time. For positioning
    applications, specify «stallprevention during deceleration not
    provided» (2nd digit = 1) in order to obtainstopping accuracy. With
    large inertia loads, use a braking resistor to
    preventovervoltage.

    acceleration stall preventionlevel (Cn-28) x

    maximum voltage frequency (Cn-04)

  • 94

    (3) 3rd digit (stall prevention during running)3rd digit = 0:
    Stall prevention during running is enabled.

    3rd digit = 1: Stall prevention during running is disabled.

    Stall prevention operation during running starts decelerating
    when the outputcurrent reaches 100ms or greater than the set value
    of Cn-30 during frequencycoincidence (operation level of stall
    prevention during running). The inverterdecelerates as long as the
    output current exceeds the set value of Cn-30(operation level of
    stall prevention during running). When the output current goesbelow
    the set value, the inverter reaccelerates. The deceleration time
    selected inthe 4th digit of Sn-10 is taken. Even during stall
    prevention while running, stallprevention during deceleration and
    stall prevention during acceleration areenabled.

    (4) 4th digit (selection of deceleration time during stall
    prevention while running)4th digit = 0: The inverter decelerates
    for the deceleration time specified in bn-02.

    4th digit = 1: The inverter decelerates for the deceleration
    time specified in bn-04.

    DETECTION LEVEL OFSTALL PREVENTIONDURING RUNNINGRETURN LEVEL

    OUTPUTFREQUENCY DECELERATION TIME

    ACCELERATIONTIME

    HYSTERESIS2%

    STALL PREVENTION DURING RUNNING

    INVERTEROUTPUT CURRENT

    DETECTION TIME: 100 ms

  • 95

    Protective Characteristic Selection 2 Sn-11

    Valid Access LevelsParameterNo. Name

    LCD Display(English) Description

    FactorySetting

    ChangeDuring

    Operation GP SL PID PG

    — — -0: Not used

    — — -1: Not used

    — -0 -: Fault contact is not energizedduring Retry operation

    — -1 -: Fault contact is energized duringRetry operation

    -0 — -: Operation stopped bymomentary power lossdetection
    (UV1)

    -1 — -: Operation conticues aftermomentary power loss

    Sn-11

    Retry andmomentarypower lossprotection

    Sn-11=0000

    Retry & Ride-Thru

    0- — -: Not used

    1- — -: Not used

    0000

    (1) 1st digit (Not used)

    (2) 2nd digit (fault contact signal during auto reset/restart
    operation)

    2nd digit = 0: A fault contact signal is not output during auto
    reset/restart operation.

    2nd digit = 1: A fault contact signal is output during auto
    reset/restart operation.

    (3) 3rd digit (operation continued at momentary power loss)

    3rd digit = 0: When momentary power loss is detected, DC Volt.
    Low (Uv1) Faultoccurs and the inverter output is shut OFF.

    3rd digit = 1: If momentary power loss time is within momentary
    power loss ride-thru time (Cn-37), the operation continues after
    the momentary powerloss. If the momentary power loss ride-thru time
    is exceeded,undervoltage fault DC Volt. Low (Uv1) Fault occurs and
    the inverteroutput is shut OFF.

    Notes:

    1. When the 3rd digit = 1, be sure not to shut OFF the external
    sequence signal.(e.g. FWD, REV)

    2. For lifters, do not use this function. (the 3rd digit =
    0)

    (4) 4th digit (Not used)

  • 96

    Protective Characteristic Selection 3 Sn-12

    Valid Access LevelsParameterNo. Name

    LCD Display(English) Description

    FactorySetting

    ChangeDuring

    Operation GP SL PID PG

    — — -0: External fault input (terminal 3 )is NO-contact
    input

    — — -1: External fault input: is NC-contact input

    — -0 -: External fault signal: alwaysdetected

    — -1 -: External fault signal: detectedduring running only

    Sn-12External Fault

    FunctionSelection

    Sn-12=0000

    External Fault00- -: External fault detected: ramp to

    stop (major fault) by bn-02 setvalue

    01- -: External fault detected: Coastingto stop (major
    fault)

    10- -: External fault detected: ramp tostop (major fault) by
    bn-04 setvalue

    11- -: External fault detected: opeationto continue (major
    fault)

    0000

    When an external fault signal of terminal 3 is input, External
    Fault 3 (EF3) Fault isdisplayed and a fault contact signal is
    output immediately. The inverter stopsaccording to the setting of
    the 3rd and 4th digits. The external fault signal is heldwithin the
    inverter until a fault reset signal is input.

    (1) 1st digit (level selection of external fault signal)1st
    digit = 0: NO contact input (when «closed», external fault
    operation is

    performed).

    1st digit = 1: NC contact input (when «open», external fault
    operation is performed).

    (2) 2nd digit (acceptance of external fault signal)2nd digit =
    0: External fault signals are always accepted.

    2nd digit = 1: External fault signals are accepted only during
    running.(Not accepted during baseblock).

    (3) 3rd digit, 4th digit (selection of processing at external
    fault detection)

    4th digit 3rd digit Contents

    0

    0

    1

    1

    0

    1

    0

    1

    Ramp to stop by bn-02 (major fault)

    Coast to stop (major fault)

    Ramp to stop by bn-04 (major fault)

    Operation to continue (minor fault)

  • 97

    Control Mode Selection Sn-13

    Valid Access LevelsParameterNo. Name

    LCD Display(English) Description

    FactorySetting

    ChangeDuring

    Operation GP SL PID PG

    Sn-13 Control ModeSelect

    Sn-13=00

    V/F Ctrl mode

    00: GPV/F Control mode

    01: SLSensorless Vector Controlmode

    10: PIDPID With Auyo EnergySoving Control mode

    11: PGV/F+PG closed loop Controlmode

    00

    The four control mode can be selected by parameter Sn-13 as
    below.

    Sn-13setting

    LCD Display(English) Descriptions

    00Sn-13=00

    V/F Ctrl ModeGP: V/F Control mode (factory setting)

    01Sn-13=01

    SL Ctrl ModeSL: Sensorless Vector Control mode

    10Sn-13=10

    PID Ctrl ModePID: PID With Auyo Energy Soving

    Control mode

    11Sn-13=11

    PG Ctrl ModePG: V/F+PG closed loop Controlmode

    When the required control mode is selected by Sn-13 setting, the
    selected controlmode functions are effective only after turning off
    power supply till the display ofdigital operator (LCD or LED
    digital operator) is off, then turn on the powersupply again.

  • 98

    Protective Characteristic Selection 5 Sn-14

    Valid Access LevelsParameterNo. Name

    LCD Display(En

80,00 $ — 230,00 $/ шт. |1 шт./шт.(Мин. заказ)

Преимущества:
Быстрый возврат средств по заказам на сумму менее 1000 USDПолучить сейчас

Время выполнения заказа:

Quantity (шт.) 1 — 10 > 10
Примерное время (в днях) 5 Подлежит согласованию

Сведения о покупке

Защита с помощью

Транспортировка:

Связаться с поставщиком для согласования деталей доставки

Для вас Гарантия своевременной отправки

Платежи:

Шифрование и повышенная безопасность платежей Подробнее

Возврат товаров и возмещение средств

Доступны возврат товаров и возмещение средств Подробнее

Для получения информации касательно цен, индивидуальных заказов и других вопросов:

Trading Company,Agent,Distributor/Wholesaler

CN

8

Понравилась статья? Поделить с друзьями:
  • Инструкция по поклейке защитного стекла на телефон
  • Инструкция imperial 220 пуско зарядное устройство
  • Руководства по ремонту eberspacher
  • Grundfos pmu 2000 инструкция по эксплуатации на русском языке
  • Telefunken телевизор инструкция на русском языке как управлять