■ Functions of LCD digital operator
JNEP-31 LCD digital operator has 2 modes: DRIVE mode and PRGM mode.
When the inverter is stopped, DRIVE mode or PRGM mode can be selected by
pressing the key
the PRGM mode, the parameter settings for operation can be changed but the
operation is not enabled. The component names and function are shown as below:
DRIVE FWD
REV
REMOTE
SEQ
DIGITAL OPERATOR JNEP-31
PRGM
DSPL
DRIVE
JOG
FWD
REV
RUN
STOP
PRGM
. In DRIVE mode, the operation is enabled. Instead, in
DRIVE
operation mode indicators
DRIVE : lit when in DRIVE mode
FWD : lit when there is a forward run command input
REF
REV
SEQ
REF
LCD Display
EDIT
Chinese Display : 2-line by 8-character
ENTER
English Display: 2-line by 20-character
RESET
Keys (Key functions are defined in Table 7)
Fig. 10 LCD Digital operator
: lit when there is a reverse run command input
: lit when the run command is enabled from the
control circuit terminal or RS-485 port
(REMOTE mode)
: lit when the frequency reference from the control
circuit terminals (VIN or AIN) or RS-485 port is
enabled (REMOTE mode)
28
-
34
PART II
OPERATION MANUAL
-
35
1. DESCRIPTION OF USING 7200GS1.1 Using LCD (or LED) digital
operator7200GS are standard with LCD digital operator JNEP-34. Moreover,
an LED digitaloperator JNEP-33 is also available. Three two digital
operator have the sameoperation functions except the LCD and
7-segments LED display difference.The LCD and LED digital operator has 2 modes: DRIVE mode and
PRGM mode.When the inverter is stopped, DRIVE mode or PRGM mode can
be selected bypressing the key PRGMDRIVE . In DRIVE mode, the
operation is enabled. Instead, in thePRGM mode, the parameter
settings for operation can be changed but theoperation is not
enabled.a> The LCD digital operator component names and functions
shown as below:RUN STOP
PRGMDRIVE DSPL
EDITENTER
DIGITAL OPERATOR JNEP-31
DRIVE FWD REV REMOTESEQ REF
FWDREV
JOG
RESET
operation mode indicatorsDRIVE : lit when in DRIVE modeFWD : lit
when there is a forward run command inputREV : lit when there is a
reverse run command inputSEQ : lit when the run command is enabled
from the controlcircuit terminal or option card (REMOTE mode)REF : lit when the
frequency reference from the controlcircuit terminals (VIN or AIN) or option card enabled(REMOTE
mode)LCD DisplayChinese Display: 2 row, each row has 8 characters at
mostEnglish Display: 2 row, each row has 20 characters at mostKeys (Key functions are defined in Table 11)
Fig 9 LCD Digital operator component names and functions
b> The LED digital operator component names and functions
shown as below:RUN STOP
PRGMDRIVE DSPL
EDITENTER
DIGITAL OPERATOR JNEP-31
DRIVE FWD REV REMOTESEQ REF
FWDREV
JOG
RESET
operation mode indicatorsDRIVE : lit when in DRIVE modeFWD : lit
when there is a forward run command inputREV : lit when there is a
reverse run command inputSEQ : lit when the run command is enabled
from the controlcircuit terminal or option card (REMOTE mode)REF : lit when the
frequency reference from the controlcircuit terminals (VIN or AIN) or option card enabled(REMOTE
mode)LED Display5 digitals 7-degment LED.
Keys (Key functions are defined in Table 11)
34
3233
-
36
Fig 10 LED Digital operator component names and functions
Table 11 Keys functions
Key Name Function
PRGMDRIVE PRGM/DRIVE key
Switches between operation (PRGM) and operation(DRIVE).
DSPL DSPL key Display operation status
JOG JOG keyEnable jog operation from digital operator in
operation(DRIVE).FWDREV FWD/REV key Select the rotation direction from digital
operator.RESETRESET key
Set the number of digital for user constant settings.Also it
acts as the reset key when a fault hasoccurred.INCRENMNT key Select the menu items, groups, functions, and
userconstant name, and increment set values.DECRENENT key Select the menu items, groups, functions, and
userconstant name, and decrement set values.EDITENTER EDIT/ENTER key
Select the menu items, groups, functions, and userconstants
name, and set values (EDIT). After finishingthe above action, press
the key (ENTER).RUN RUN keyStart inverter operation in (DRIVE) mode whenoperator
is used. The led will light.STOP STOP key
Stop 7200GS operation from LCD digital operator. Thekey can be
enable or disabled by setting a constantSn-05 when operating from
the control circuit terminal(in this case, the LED will light).RUN, STOP indicator lights or blinks to indicate the 3 operating
status:STOPRUN
STOP
RUN
STOP
Inverter output frequency
Frequency Setting
ON Blink OFF
-
37
1.2 DRIVE mode and PRGM mode displayed contents
*1 : When the inverter is put into operation,
the inverter system immediately enters into
DRIVE mode. Press the PRGMDRIVE key,
the system will switch into PRGM mode.
*2 : If the fault occurred before power
supply was turned off, the fault contents
are displayed when power ON.
Fault occurrence order and display are
provided by or key.
Un fault : n =1~4,the fault occurrence
Order, fault :the fault contents,
please refer to page 131~138,the fault display.
Power on
PRGM mode DRIVE modePRGMDRIVE *1
DSPL
An- monitorset
DSPL
bn- monitorset
DSPL
Sn- monitorset
DSPL
Cn- monitorset
When faultsOccurred beforepower supplywas turned off
*2DSPL
Frequency reference
DSPL
Un- monitor
DSPL
An- monitorset
DSPL
bn- monitorset
DSPL
Sn- monitor
DSPL
Cn- monitor
*4
DSPL *5
RESET
DSPL
Output Frequency
Output Current
Display of faults which occurred before power supply
was turned off
*3
-
38
*3 : If no fault occurred before power supply
was turned off , display the monitored data
according to the bn-10 setting
*4 : This block will be by passed if no fault occurred before
power supply was turned off or afault occurs and was reset by RESET
*5 : When in the DRIVE mode, press the DSPL key and RESET key,
the setting values of Sn-and Cn- will only be displayed for
monitoring but not for changing or setting. -
39
1.3 Parameter Description
The 7200GS has 4 groups of user parameters:
Parameters*4 Description
An- Frequency command
bn- Parameter settings can be changed during running
Sn- System parameter settings (can be changes only after
stop)Cn- Control parameter settings (can be changed only after
stop)The parameter setting of Sn-03 (operation status) will determine
if the setting valueof different parameter groups are allowed to be
changed or only to be monitored, asshown below:DRIVE mode PRGM modeSn-03
To be set To be monitored To be set To be monitored
0000*1 An, bn Sn, Cn An, bn, Sn, Cn
0101*3 An bn, Sn, Cn An bn, Sn, Cn
*1 : Factory setting
*2 : When in DRIVE mode, the parameter group Sn-, Cn- can only
be monitored if theRESET key and the DSPL key are to be pressed at the same
time,*3 : After a few trial operation and adjustment, the setting
value Sn-03 is set to be0101″ so as not be modified again.*4 : The 7200GS has one group of monitoring parameters in
addition to the above 4groups of user parameters.Un- : Can be monitored by the users under the DRIVE mode.
*2
-
40
1.4 Sample example of using LCD digital operator
Note :
Before operation: Control parameter Cn-01 value must be set as
the input ACvoltage value. For example, Cn-01=380 if AC input
voltage is380.This sample example will explain the operating of 7200GAS
according to the followingtime chart.OPERATION MODE
Sample operation
Description Key Sequence Digital OperatorDisplay Remarks
Sect frequency referencevalue displayed
Select PRGM mode
Select CONTROL
LED DRIVE OFF
(1)
REV60Hz
FWD60Hz
(2) (4) (5) (6) (7) (8)(3)
SET INPUTVOLTAGE
FREQUENCYSETTING
FREQ REF.VALUE CHANGE
POWERON
FWD JOGOPERATION FWD RUN REV RUN
STOP
(1) When POWER ON
(2) Input voltagesetting (e.g. ACinput voltage is
380V)
-
41
PARAMETER
Display Cn-01 setting
Input Voltage 380V
Display for 0.5sec
Description Key Sequence Digital OperatorDisplay Remarks
Select DRIVE mode
Select output frequencydisplayed
Select direction of rotation(When power on, initiallydefaulted
FWD)Jog operation
Select frequency cmddisplayed
Change frequency cmd
Set new frequency cmd
Select O/P frequencydisplayed
Running operation
LED DRIVEON
LED FWDON
Display for 0.5 secConfirm the display.
LEDON
EDITENTER
RESET
PRGMDRIVE
Freq. Cmd. 00.00HzTECO
EDITENTER
DSPL Press 3times
An-01Freq. Cmd. 1
Cn-01-Input Voltage
Entry Accepted
Cn-01=440.0VInput Voltage
Cn-01=380.0VInput Voltage
(continued)
(3) FWD JOG
(4) Frequency setting15Hz(5) FWD run
(6) Frequencycommand change
-
42
Select frequency cmddisplayed
Change reference value
Enter new frequency cmdsetting
Select frequency cmddisplayed
Change to REV
Decrement to STOP
Display for 0.5 secConfirm the display.
LED REVON
LEDON
(Blinkingwhiledecel.)
Freq. Cmd. 00.00HzTECO
Freq. Cmd. .0 HzTECO
Entry Accepted
O/P Freq. 6.00 HzTECO
PRGMDRIVE
DSPL
JOG
EDITENTER
RESET
RUN
FWDREV
STOP
DSPL
EDITENTER
RESET
DSPL
60Hz(7) REV RUN
(8) STOP
Press 5timesDSPL
Press 5timesDSPL
Freq. Cmd. 00.00HzTECO
Freq. Cmd. 15.00HzTECO
Freq. Cmd. 15.00HzTECO
O/P Freq. .0 HzTECO
O/P Freq. 15.00 HzTECO
Freq. Cmd. 15.00HzTECO
Freq. Cmd. 60.00HzTECO
Freq. Cmd. 60.00HzTECO
Entry Accepted
O/P Freq. 60.00 HzTECO
O/P Freq. -60.00 HzTECO
O/P Freq. .0 HzTECO
RUNSTOPRUN
-
43
1.5 Control Mode SelectionThe 7200GS standard with four
selectable control modes:1 GP: V/F control mode (General Purpose V/F control mode).
2 SL: Sensorless Vector Control mode (with motor parameters auto
tuningfunction).3 PID: PID with Auto Energy Saving Control mode.
4 PG: V/F+PG closed loop Control mode.
The control mode can be selected by parameter Sn-13:
Sn-13 setting LCD Display (English) Descriptions
00Sn-13=00
V/F Ctrl ModeGP: V/F control mode (factory setting)
01Sn-13=01
SL Ctrl ModeSL: Sensorless Vector Control mode
10Sn-13=10
PID Ctrl ModePID: PID with Auto Energy Saving
Control mode
11Sn-13=11
PG Ctrl ModePG: V/F+PG closed loop Controlmode
Caution:
1. Factory setting as V/F control mode (GP mode), When the
required controlmode is selected by Sn-13, the selected control
mode is effective only afterturning off the power supply till the
display of digital operator (LCD or LEDdigital operator) is off,
then turn on the power supply again.2. The AUTO TUNE feature can be used to identify and store the
importantmotor parameters in the first time sensorless vector
operation afterinstallation, and when switching to anyone of the
other three control modes,then switched back to the sensorless
vector control mode, the AUTO TUNEfeature has to be used to
identify and store the motor parameters once again. -
44
2. SETTING USER CONSTANT2.1 Descriptions of constant/function
listFormate
Valid Access LevelsParameter
No. Name LCD Display (English)ChangeDuring
OperationSetting Range SettingUnit
FactorySetting
GP SL PID PG
Ref.Page
or
Descriptions
Parameter NO.: NO. of the parameter group An-, bn-, Sn-, Cn- and
Un-.Name: Parameter function name.
LCD Display (English): The LCD display contents.
Change During Operation:
: The parameter setting can be changed during running.
: The parameter setting can not be changed during running.
Setting Range: The allowable setting range of the parameter.
Setting Unit: The allowable setting unit ( means without
unit).Factory Setting: Some of the parameter have different factory
setting valueunder different control mode.Valid Access Levels:
1 GP: V/F control mode (General Purpose V/F control mode).
2 SL: Sensorless Vector Control mode (with auto tuning
function).3 PID: PID with Auto Energy Saving Control mode.
4 PG: V/F+PG closed loop Control mode.
: The parameter is access valid under this control mode (i.e.
theparameter group can be monitored or set by the user)
-
45
: The parameter is access invalid under this control mode.
Number (1~3): different number with different function
definitions. -
46
2.2 Frequency command (in Multi-speed operation) A n — Under the
DRIVE mode, the user can monitor the parameters and set their
values.Valid Access LevelsParameter
No. Name LCD Display (English)ChangeDuring
OperationSetting Range SettingUnit
FactorySetting
GP SL PID PG
Ref.Page
An-01 FrequencyCommand 1
An-01=000.00Hz
Frequency Command 1 0.00~180.00 Hz 0.01Hz 00.00Hz
An-02 FrequencyCommand 2
An-02=000.00Hz
Frequency Command 2 0.00~180.00 Hz 0.01Hz 0.00Hz
An-03 FrequencyCommand 3
An-03=000.00Hz
Frequency Command 3 0.00~180.00 Hz 0.01Hz 0.00Hz
An-04 FrequencyCommand 4
An-04=000.00Hz
Frequency Command 4 0.00~180.00 Hz 0.01Hz 0.00Hz
An-05 FrequencyCommand 5
An-05=000.00Hz
Frequency Command 5 0.00~180.00 Hz 0.01Hz 0.00Hz
An-06 FrequencyCommand 6
An-06=000.00Hz
Frequency Command 6 0.00~180.00 Hz 0.01Hz 0.00Hz
An-07 FrequencyCommand 7
An-07=000.00Hz
Frequency Command 7 0.00~180.00 Hz 0.01Hz 0.00Hz
An-08 FrequencyCommand 8
An-08=000.00Hz
Frequency Command 8 0.00~180.00 Hz 0.01Hz 0.00Hz
An-09 Jog FrequencyCommand
An-09=006.00Hz
Jog Command 0.00~180.00 Hz 0.01Hz 6.00Hz
*1. The displayed «Setting Unit can be changed through the
parameter Cn-20.*2. At factory setting, the value of «Setting Unit» is
0.01Hz.*3. The setting of An-01~09 should be with the multi-function
analog terminals 5 ~8 . -
47
2.3 Parameters Can Be Changed during Running b n — Under the
DRIVE mode, the Parameter group can be monitored and set by
theusers.Valid AccessLevels
Function ParameterNo. NameLCD Display
(English)
ChangeDuring
OperationSetting Range SettingUnit
FactorySetting
GP SL PID PG
Ref.Page
bn-01 AccelerationTime 1bn-01=0010.0s
Acc. Time 1 0.0~6000.0s 0.1s 10.0s
bn-02 DecelerationTime 1bn-02=0010.0s
Dec. Time 1 0.0~6000.0s 0.1s 10.0s
bn-03 AccelerationTime 2bn-03=0010.0s
Acc. Time 2 0.0~6000.0s 0.1s 10.0s
Acc/Dectime
bn-04 DecelerationTime 2bn-04=0010.0s
Dec. Time 2 0.0~6000.0s 0.1s 10.0s
45
bn-05
AnalogFrequencyCmd. Gain(Voltage)
bn-05=0100.0%
~Freq. Cmd. Gain 0.0~1000.0% 0.1% 100.0%
AnalogFrequencyCommand
bn-06
AnalogFrequencyCmd. Bias(Voltage)
bn-06=0000.0%
~Freq. Cmd. Bias -100.0%~100.0% 0.1% 0.0%
46
TorqueBoost bn-07
Auto TorqueBoost Gain(Ineffective
in Autoenergy-saving
mode)
bn-07=1.0
Auto_Boost Gain 0.0~2.0 0.1 1.0*1 46
Motor Slip bn-08 Rated Slip ofMotorbn-08 =0.0%
Motor Rated Slip 0.0~9.9%*2 0.1% 0.0% 1 2
47
48
EnergySaving bn-09
Energy SavingGain
bn-09=080%
Eg. Saving Gain 0~200% 1% 80% 48
bn-10 Monitor No.After power ONbn-10=1
Power On. Contents 1~3 1 1 48
A01 Gain bn-11Multi-FunctionAnalog Output
A01 Gain
bn-11=1.00
~Output A01 Gain 0.01~2.55 0.01 1.00 1 1 1 2
A02 Gain bn-12Multi-FunctionAnalog Output
A02 Gain
bn-12=1.00
~Output A02 Gain 0.01~2.55 0.01 1.00 1 1 1 2
48~50
bn-13 PID DetectionGainbn-13=01.00
PID Det. Gain 0.01~10.00 0.01 1.00
bn-14PID
ProportionalGain
bn-14=01.0
PID P-Gain 0.0~10.0 0.1 1.0
bn-15 PID IntegralGainbn-15=010.0s
PID I-Time 0.0~100.0s 0.1s 10.0s
bn-16 PID DifferentialTimebn-16=0.00s
PID D-Time 0.00~1.00s 0.01s 0.00s
PIDControl
bn-17 PID Biasbn-17=000%
PID Bias 0~109%*2 1% 0%
50
147
*1. The factory setting value is 1.2 for SL control mode.
-
48
*2. Cn-04 is to be the 100% level.
-
49
(1) Acceleration Time 1 (bn-01)
(2) Deceleration Time 1 (bn-02)
(3) Acceleration Time 2 (bn-03)
(4) Deceleration Time 2 (bn-04)
Valid Access LevelsParameter
No. NameLCD Display
(English)
ChangeDuring
OperationSetting Range SettingUnit
FactorySetting
GP SL PID PG
bn-01 Acceleration Time 1bn-01=0010.0s
Acc. Time 1 0.0~6000.0s 0.1s 10.0s
bn-02 Deceleration Time 1bn-02=0010.0s
Dec. Time 1 0.0~6000.0s 0.1s 10.0s
bn-03 Acceleration Time 2bn-03=0010.0s
Acc. Time 2 0.0~6000.0s 0.1s 10.0s
bn-04 Deceleration Time 2bn-04=0010.0s
Dec. Time 2 0.0~6000.0s 0.1s 10.0s
Set individual Acceleration / Deceleration times
Acceleration time: the time required to go from 0% to 100% of
the maximum outputfrequency.Deceleration time: the time required to go from 0% to 100% of
the maximum outputfrequency.If the acceleration / deceleration time sectors 1 and 2 are
input via the multifunctioninputs terminal 5 ~8 , the acceleration
/ deceleration can be switched between 2sectors even in the running
status.Control circuit terminals 5 ~8
Open select the 1st sector Acc. / Dec. time(Parameters bn-01,
bn-02 set)Close select the 2nd sector Acc. / Dec. time(Parameters bn-03,
bn-04 set)bn-03
bn-01
Cn-02
bn-04
bn-02Time
Output frequency
-
50
Note:
1. To set the S-curve characteristics function, please refer to
Sn-06. -
51
(5) Analog Frequency Cmd. Gain (Voltage) (bn-05)
(6) Analog Frequency Cmd. Bias (Voltage) (bn-06)Valid Access
LevelsParameterNo. NameLCD Display
(English)
ChangeDuring
OperationSetting Range SettingUnit
FactorySetting GP SL PID PG
bn-05 Analog FrequencyCmd. Gain (Voltage)bn-05=0100.0%
~Freq. Cmd. Gain 0.0~1000.0% 0.1% 100.0%
bn-06 Analog FrequencyCmd. Bias (Voltage)bn-06=0000.0%
~Freq. Cmd. Bias -100.0%~100.0% 0.1% 0.0%
bn-05: The input level when frequency reference voltage is 10V
is set in units of 1%,examples are shown below.bn-06: The input level when frequency reference voltage is 0V is
set in units of 1%1 bn-05 = 50.0
2 a: bn-06 = 10.0
b: bn-06 = -10.0
(7) Auto Torque Boost Gain (bn-07)Valid Access
LevelsParameterNo. NameLCD Display
(English)
ChangeDuring
OperationSetting Range SettingUnit
FactorySetting GP SL PID PG
bn-07Auto Torque Boost Gain
(Ineffective in Autoenergy-saving mode)
bn-07=1.0Auto_Boost Gain
0.0~2.0 0.1 1.0
The inverter can increase the output torque to compensate the
load increaseautomatically through the auto torque boost function.
Then the output voltage willincrease. As a result, the fault trip
cases can be decreased. The energy efficiency isalso improved. In
the case that the wiring distance between the inverter and themotor
is too long (e.g. more than 100m), the motor torque is a little
short because ofvoltage drop. Increase the value of bn-11 gradually
and make sure the current willnot increase too much. Normally, no
adjustment is required.INPUT LEVELbn-06 is positive value.%
bn-05
bn-06(a)
10
bn-06(b) -10
0 0V 10V
bn-06 isnegative value.
FREQUENCYREF.
100%
Base frequency
torquedecrease
torqueincrease
Outputvoltage
-
52
bn-07 is ineffective when the Auto-Energy Saving function is
effective (Sn-08=X1XX)in the PID control mode (Sn-13=10). -
53
(8) Rated Slip of Motor (bn-08)
1. GP
Valid Access LevelsParameterNo. Name
LCD Display(English)
ChangeDuring
OperationSetting Range SettingUnit
FactorySetting GP SL PID PG
bn-08 Rated Slip of Motorbn-08 =0.0%
Motor Rated Slip 0.0~9.9% 0.1% 0.0% 1 2
Motor rated slip is set in units of 0.1%
Simplified speed control is performedwithout encoder (PG or
TG).With frequency offset f1 to f2, speedfluctuation due to load is
reduced.When the output current of the inverter is larger than motor
no-load current (Cn-34),the output frequency of the inverter is
compensated.The amount of frequency compensation is determined by the
formula below. Themaximum voltage frequency (Cn-04) is 100%.If the output current is equal to the motor rated current
(Cn-09), the output frequencyis compensated for by the motor rated
slip (bn-08).If frequency reference is equal to or smaller than minimum
output frequency (Cn-07)or motor is in a regeneration mode, slip
compensation is not performed.The amount of output frequency compensation in a constant torque
area and aconstant output area is shown in the figure below.Amount of output frequency compensation =
Motor rated current: Cn-09Motor no-load current: Cn-34
motor rated slip
motor ratedcurrent
motor no-loadcurrent
motor no-loadcurrent
outputcurrent
TORQUE
LOAD TORQUE
SMALL LOADf1
LARGE LOADf2
SPEED
Cn-04xbn-08
Cn-04 Cn-02
bn-08
-
54
Motor rated slip: bn-08 When 0.0 is set in bn-08, output
frequency compensation is not performed. -
55
2. SL
Valid Access LevelsParameterNo. Name
LCD Display(English)
ChangeDuring
OperationSetting Range SettingUnit
FactorySetting GP SL PID PG
bn-08 Rated Slip of Motorbn-08 =1.7Hz
Motor Rated Slip 0.0~20.0Hz 0.1Hz 1.7Hz* 1 2
* Factory setting depending on inverter capacity (Sn-01 set
value)To calculate the motor rated slop by the below equation:
Motor Rated Slop (Hz)= [rated speed (rpm)nameplate full load
speed (rpm)]120P (Hz)
P=motor poles
(9) Energy Saving Gain (bn-09)Valid Access LevelsParameter
No. NameLCD Display
(English)
ChangeDuring
OperationSetting Range SettingUnit
FactorySetting GP SL PID PG
bn-09 Energy Saving Gainbn-09=080%
Eg. Saving Gain 0~200% 1% 80%
Input the energy-saving operation command (Sn-15~18=63), While a
light loadcauses the inverter output voltage to be reduced and save
energy. Set this valueas a percentage of the V/F pattern. The
setting range is 0~200%. The energysaving function is disabled when
energy saving gain (bn-09) is 100%.Please refer to page 97, the time chart when energy-saving
operation command isinput.(10) Monitor No. after Power ON (bn-10)Valid Access
LevelsParameterNo. Name LCD Display (English)ChangeDuring
OperationSetting Range SettingUnit
FactorySetting GP SL PID PG
bn-10 Monitor No. Afterpower ONbn-10=1
Power On. Contents 1~3 1 1
Data to be monitored after turning on power supply is selected
with constant NO.bn-10=1Frequency reference
bn-10=2Output frequency
bn-10=3Output current
(11) Multi-function Analog Output A01 Gain (bn-11)
(12) Multi-function Analog Output A02 Gain (bn-12)
-
56
1. GP, SL, PID
Valid Access LevelsParameterNo. Name
LCD Display(English)
ChangeDuring
OperationSetting Range SettingUnit
FactorySetting GP SL PID PG
bn-11 Multi-Function AnalogOutput A01 Gainbn-11=1.00
~Output A01 Gain 0.01~2.55 0.01 1.00 1 1 1 2
bn-12 Multi-Function AnalogOutput A02 Gainbn-12=1.00
~Output A02 Gain 0.01~2.55 0.01 1.00 1 1 1 2
To set the output voltage level of A01 channel of analog monitor
optional card (AO-12) by bn-11 and bn-12. The output voltage level
is set in the form of 10Vbn-11 (orbn-12).To set the output voltage level of multi-function analog output
terminal 21 .The output voltage level is set in the form of
10Vbn-112. PG
Valid Access LevelsParameterNo. Name
LCD Display(English)
ChangeDuring
OperationSetting Range SettingUnit
FactorySetting GP SL PID PG
bn-11Multi-Function Analog
Output 21 itemsbn-11=2
Output Frequency 1~13 2 1 1 1 2
bn-12Multi-Function Analog
Output 21 Gainbn-12=
Output Gain 0.01~2.55 0.01 1.00 1 1 1 2
bn-11: Select the item to be output from terminal 21
bn-11 setting LCD Display (English) Functions01 Freq. Cmd.
Frequency Command (Reference)02 O/P Freq. Output Frequency03 O/P I
Output Current04 O/P V Output VoltageChannel 1(Select item to be outputfrom channel 1 by Sn-28)
10.0V bn-11Channel 1 (A01)of AO-12 card
10.0V bn-12Channel 2(Select item to be outputfrom channel 2 by
Sn-28)Channel 2 (A02)of AO-12 card
Multi-function analog output terminal 21(Select item to be
output from terminal21 by the 4th digit of Sn-05 and the 2nddigit
of Sn-09)10.0V bn-11 Terminal 21
-
57
05 DC Volt DC Voltage06 O/P KW Output Power (KW)
07-11 Reserved Not used12 Sp. FBK Amount of speed feedback13 Sp.
Compen. Amount of speed control compensationbn-12: To set the output voltage level of multi-function analog
output terminal 21 .The output voltage level is set in the form of
10Vbn-12The analog monitor optional card (AO-12) can not be used in PG
control mode.(13) PID Control function (bn-13~bn-17)
Please refer to Appendix C PID CONTROL.
Multi-function analog output 21(Select item to be output
fromterminal 21 by bn-11) 10.0V bn-12Terminal 21
-
58
2.4 System Parameters S n — Valid Access Levels
Function ParameterNo. NameLCD Display
(English) DescriptionFactorySetting
ChangeDuring
Operation GP SL PID PGRef.Page
CapacitySetting Sn-01
InverterCapacitySelection
Sn-01=29440V 25HP Inverter Capacity Selection *1 1 2 1 1
55~62
V/f Curve Sn-02 V/f CurveSelectionSn-02=01V/f Curve V/f pattern
Selection 0163~65
Display ofOperator
0000: Setting and reading of An-, Bn-,Cn-, Sn- enabled
0101: Setting and reading of An-, Readinng of Bn-,Cn-,
Sn-enabledOperatorStatus Sn-03
ConstantsInitialization
Sn-03=0000Operate Setting
1110: Constants Initialigation (2-wire)*2
1111: Constants Initialigation (3-wire)*2
0000 66
— — -0: Frequency Command =Control circuit terminals 13or 14
— — -1: Frequency Command =Frequency Command 1(An-01)
Operation ModeSelect
— -0 -: RUNSTOP Command =Control circuit terminals
— -1 -: RUNSTOP Command =LCD Digital Operator
OperationMode
Select 1Sn-04
StoppingMethod
Selection
Sn-04=0011Stopping Method
00- -: Stopping method = Ramp tostop
01- -: Stopping method =Coastingto stop
10- -: Stopping method =Full-range DC injection brankingstop
11- -: Stopping method = Coastingstop (timer
functionprovided)0011 67~69
— — -0: Stop key effective duringoperation from
controlterminal— — -1: Stop key effective duringoperation from
controlterminal— -0 -: Reverse run enabled- -1 -: Reverse run disabled
— 0- -: Control input terminals 1
~8 are scanned twice.- 1- -: Control input terminals 1
~8 are scanned once.
OperationMode
Select 2Sn-05
I/O terminalfunctionselection
Sn-05=0000I/O term. Fct
0- — -: Selection of item to beanalog output (terminals21 , 22
)*31- — -: Selection of item to beanalog output (terminals21 , 22
)*30000 1 1 1 2 70~71
— -00: S curve=0.2sec- -01: S curve=0.0sec (NO S
curve)- -10: S curve=0.5sec- -11: S curve=1.0sec
OperationMode
Select 3Sn-06
S-curve andfrequencyCommand
characteristics
Sn-06=0000S-curve Cmd. Char.
-0 — -: Reference command hasforward characteristics(0-10V or
4-20mA/0~100%)-1 — -: Reference command hasreverse characteristics(0-10V or
4-20mA/100~0%)0000 72~74
-
59
0- — -: Stop by reference inputwhen frequency referenceis
missing1- — -: Operation to continue with80% of frequence referencewhen
frequency referenceis missing -
60
Valid Access LevelsFunction ParameterNo. Name
LCD Display(English) Description
FactorySetting
ChangeDuring
Operation GP SL PID PGRef.Page
— — -0: Overtorque detection disabled
— — -1: Overtorque detection enabled
— -0 -: Enabled only if at agreedfrequency
— -1 -: Enable during operation(except during DC injection)
— 0- -: Operation continued afterovertorque is detected
— 1- -: Coasts to stop if overtorque isdetected
OperationMode Select 4 Sn-07
OvertorqueDetection
Sn-07=0000
Over Tq. Detect
0- — -: Overtorque detection withcurrent
1- — -: Overtorque detection withtorque
0000 1 2 1 175-
76
— — -0: Frequency reference input byoption card (AI-14B, DI-08
orSI-M)— — -1: Frequency reference input bydigital operetor or
controlcirauit input terminals— -0 -: RUN/STOP command input byoption card (AI-14B, DI-08
orSI-M)— -1 -: RUN/STOP command input bydigital operator or
controlcircuit input terminalsOperationMode Select 5 Sn-08
OptionCard/Invater
FunctionSelection
Sn-08=0000
AI/DI & SI-M Card
00- -: SI-M communication fault,deceleration to stop (bn-02)
01- -: SI-M communication fault,coast to stop
10- -: SI-M communication fault,deceleration to stop (bn-04)
11- -: SI-M communication fault,continue to run
0000 1 1 2 377-
78
— — -0: Analog output (tereminal21 -22 ) depends on Sn-054th
digit and Sn-09 2nd digit.— — -1: Analog output (tereminal21 -22 ) is set by SI-M
card.— -0 -: Analog output (tereminal21 -22 )
— -1 -: Analog output (tereminal21 -22 )
— 0- -: Not used
— 1- -: Not used
OperationMode Select 6 Sn-09
Analog OutputSelection and
SlipCompensetion
Sn-09=0000
~Output Select
0- — -: No slip compensation duringregenerating
1- — -: Slip compensation even duringregenerating
0000 1 2 3 79-
80
— — -0: Stall prevention duringacceleration enabled
— — -1: Stall prevention duringacceleration disabled
— -0 -: Stall prevention duringdeceleration enabled
— -1 -: Stall prevention duringdeceleration disabled
ProtectiveCharacteristic
Select 1Sn-10 StallPrevention
Sn-10=0000
Stall Select
— 0- -: Stall prevention during runningenabled
— 1- -: Stall prevention during runningdisabled
0000 81-
82
-
61
0- — -: Decel time during stallprevention (bn-02 set value)
1- — -: Decel time during stallprevention (bn-04 set value)
Valid Access LevelsFunction ParameterNo. Name
LCD Display(English) Description
FactorySetting
ChangeDuring
Operation GP SL PID PG
Ref.Page
— — -0: Not used
— — -1: Not used
— -0 -: Fault contact is not energizedduring Retry operation
— -1 -: Fault contact is energizedduring Retry operation
-0 — -: Operation stopped bymomentary power lossdetection
(UV1)-1 — -: Operation conticues aftermomentary power loss
ProtectiveCharacteristic
Select 2Sn-11
Retry andmomentarypower lossprotection
Sn-11=0000
Retry & Ride -Thru
0- — -: Not used
1- — -: Not used
0000 83
— — -0: External fault input (terminal3 ) is NO-contact
input— — -1: External fault input: is NC-contact input
— -0 -: External fault signal: alwaysdetected
— -1 -: External fault signal: detectedduring running only
ProtectiveCharacteristic
Select 3Sn-12
ExternalFault
FunctionSelection
Sn-12=0000
External Fault00- -: External fault detected: ramp
to stop (major fault) by bn-02set value
01- -: External fault detected:Coasting to stop (major
fault)10- -: External fault detected: rampto stop (major fault) by
bn-04set value11- -: External fault detected:opeation to continue
(majorfault)0000 84
Control ModeSelect Sn-13
ControlModeSelect
Sn-13=00
V/F Ctrl mode
— -00: GPV/F Control mode
— -01: SLSensorless Vector Controlmode
— -10: PIDPID With Auyo EnergySoving Control mode
— -11: PGV/F+PG closed loopControl mode
00 85
— — -0: Motor overload (OL1)protection: effective
— — -1: Motor overload (OL1)protection: ineffective
ProtectiveCharacteristic
Select 4Sn-14
ElectronicThermalOverloadProtection
Sn-14=0000
Over LoadSelect
— -0 -: Motor overload protection:standard motor
— -1 -: Motor overload protection:Inverter duty motor
0000 86
-
62
— 0- -: Motor overload protection timeconstants are standard
time(8 minutes)— 1- -: Motor overload protection timeconstants are short-time
(5minutes)0- — -: Inverter overload (OL2)protection 103% continuous,150%
for one minute*21- — -: Inverter overload (OL2)protection 113% continuous,123%
for one minute*2Valid Access Levels
Function ParameterNo. NameLCD Display
(English) DescriptionFactorySetting
ChangeDuring
Operation GP SL PID PG
Ref.Page
Sn-15 Terminal 5Function
Sn-15=03
Term.5 Function
00~66
Selects terminal 5 function(factory preset for multi-stepspeed
reference 1)03 87
Sn-16 Terminal 6Function
Sn-16=04
Term.6 Function
00~66
Selects terminal 6 function(factory preset for multi-stepspeed
reference 2)04 87
Sn-17 Terminal 7Function
Sn-17=06
Term.7 Function
00~66
Selects terminal 7 function(factory preset for jogfrequency
reference)06 87
Sn-18 Terminal 8Function
Sn-18=08
Term.8 Function
00~66
Selects terminal 8 function(factory preset for externalbaseblock
by NO contactinput)08 87
Sn-19Multi-functionanalog input
(Terminal 16 )
Sn-19=00
Multi-Fct Input
00~
0B
Selects terminal 16 function(factory preset for
auxilaryfrequency command)00 98
Sn-20Multi-functioncontact output
(Terminal 9 -10 )
Sn-20=00
Term. 9 Function
00~
0E
Selects terminal 9 — 10function (factory preset forrunning)
00 100
Sn-21Multi-function PHC
output (Terminal25 -27 )
Sn-21=01
Term. 25 Function
00~
0E
Selects terminal 25 — 27function (factory preset forzero
speed)01 100
Multi-FunctionSelect
Sn-22Multi-function PHC
output (Terminal26 -27 )
Sn-22=02
Term. 26 Function
00~
0E
Selects terminal 26 — 27function (factory preset forAgreed
frequency)02 100
Language Sn-23 LCD Languageselection
Sn-23=0
Language: English
0: English
1: Chinese0 103
Sn-24 Not usedSn-24=00
Reserved
OptionCard
FunctionSelect
Sn-25
~
Sn-28
*3 *3 *3 *3 1 2 3 4104
154
-
63
Auto-tuning Sn-29
Motor parametersAuto tuningSelection
Sn-29=0
Motor Auto Test
0: Autotuning invalid
1: Autotuning valid 108
*1. Differs according to inverter capacity.
*2. Effective only for inverter models of capacity 220V 40HP
(30KW) or more, 440V75HP (55KW) or more.*3. Differs according to control mode.
-
64
Inverter Capacity Selection Sn-01
Inverter capacity has been preset at the factory. However, if a
spare control board isused, reset the inverter capacity referring
to the table below. Control constant Cn- factory setting values
(initial values) differ according to Sn-01 setting.1. GP, PID, PGValid Access LevelsParameter
No. NameLCD Display
(English) DescriptionFactorySetting
Change DuringOperation GP SL PID PG
Sn-01 Inverter CapacitySelectionSn-01=29
440V 25HPInverter Capacity Selection *1 1 2 1 1
Inverter Capacity Selection220V Class
Data of Sn-01
Name00 01 02 03 04 05 06 07
Inverter rating HP 0.5 1 2 3 5 7.5 10 15
Inverter rated capacity kVA 1.4 2.1 2.7 4.1 6.9 10.3 13.7
20.6Max. applicable motor capacity HP (kW)0.5
(0.4)
1
(0.75)
2
(1.5)
3
(2.2)
5
(3.7)
7.5
(5.5)
10
(7.5)
15
(11)
Inverter rated current A 3.2 4.8 6.4 9.6 16 24 32 48
Cn-09 Motor rated current A 1.9 3.4 6.1 8.7 13.5 20.1 25.1
36.7Cn-23 Carrier frequency upperlimit kHz 15.0 15.0 15.0 15.0 15.0
15.0 15.0 15.0Cn-24 Carrier frequency lowerlimit kHz 15.0 15.0 15.0 15.0 15.0
15.0 15.0 15.0Cn-25 Carrier frequencyproportional gain 0 0 0 0 0 0 0 0
Cn-31 Motor phase-to-phaseresistance 11.760 5.732 2.407 1.583
0.684 0.444 0.288 0.159Cn-32 Torque compensation ironloss W 48 64 108 142 208 252 285
370Cn-33 Torque compensation limit V 50 50 50 50 50 50 50 50
Cn-37 Momentary power lossassurance time s 0.7 1.0 1.0 1.0 2.0
2.0 2.0 2.0Fact
Cn-40 Minimum baseblock time s 0.5 0.5 0.5 0.5 0.5 0.7 0.7
0.7 -
65
Cn-41 V/f during speed search % 100 100 100 100 100 100 100
100 -
66
Inverter Capacity Selection220V Class
Data of Sn-01
Name08 09 0A 0B 0C 0D 0E 0F
Inverter rating HP 20 25 30 40 50 60 75 100
Inverter rated capacity kVA 27.4 34 41 54 68 78 95 130
Max. applicable motor capacity HP (kW)20
(15)
25
(18.5)
30
(22)
40
(30)
50
(37)
60
(45)
75
(55)
100
(75)
Inverter rated current A 64 80 96 130 160 183 224 300
Cn-09 Motor rated current A 50.3 62.9 72.9 96.7 124 143.5 183.5
230Cn-23 Carrier frequency upperlimit kHz 15.0 15.0 15.0 10.0 10.0
3.0 3.0 3.0Cn-24 Carrier frequency lowerlimit kHz 15.0 15.0 15.0 10.0 10.0
3.0 3.0 3.0Cn-25 Carrier frequencyproportional gain 0 0 0 0 0 0 0 0
Cn-31 Motor phase-to-phaseresistance 0.109 0.077 0.060 0.041
0.033 0.028 0.019 0.007Cn-32 Torque compensation ironloss W 471 425 582 536 641 737 790
1800Cn-33 Torque compensation limit V 50 50 50 50 50 50 50 50
Cn-37 Momentary power lossassurance time s 2.0 2.0 2.0 2.0 2.0
2.0 2.0 2.0Cn-40 Minimum baseblock time s 0.7 1.0 1.0 1.0 1.0 1.0 1.0
1.0Fact
ory
Set
ting
Cn-41 V/f during speed search % 100 100 100 80 80 80 80 80
The allowable maximum carrier frequency is 10kHz
-
67
Inverter Capacity Selection440V Class
Data of Sn-01
Name20 21 22 23 24 25 26 27 28 29 2A
Inverter rating HP 0.5 1 2 3 5 7.5 10 15 20 25 30
Inverter rated capacity kVA 1.4 2.1 3.4 4.1 6.9 10.3 13.7 20.6
27.4 34 41Max. applicable motor capacity HP (kW)0.5
(0.4)
1
(0.75)
2
(1.5)
3
(2.2)
5
(3.7)
7.5
(5.5)
10
(7.5)
15
(11)
20
(15)
25
(18.5)
30
(22)
Inverter rated current A 1.6 2.6 4.0 4.8 8 12 16 24 32 40 48
Cn-09 Motor rated current A 1.0 1.7 2.9 4.0 6.8 10.0 12.6 18.6
24.8 31.1 36.3Cn-23 Carrier frequency upperlimit kHz 15.0 15.0 15.0 15.0 15.0
15.0 15.0 15.0 15.0 10.0 10.0Cn-24 Carrier frequency lowerlimit kHz 15.0 15.0 15.0 15.0 15.0
15.0 15.0 15.0 15.0 10.0 10.0Cn-25 Carrier frequencyproportional gain 0 0 0 0 0 0 0 0 0 0
0Cn-31 Motor phase-to-phaseresistance 47.02 22.929 9.629 6.333
2.735 1.776 1.151 0.634 0.436 0.308 0.239Cn-32 Torque compensation ironloss W 48.1 63.9 108 142 208 252
285 370 471 425 582Cn-33 Torque compensation limit V 100 100 100 100 100 100 100
100 100 100 100Cn-37 Momentary power lossassurance time s 1.0 1.0 1.0 1.0 2.0
2.0 2.0 2.0 2.0 2.0 2.0Cn-40 Minimum baseblock time s 0.5 0.5 0.5 0.5 0.5 0.7 0.7 0.7
1.0 1.0 1.0Fact
ory
Set
ting
Cn-41 V/f during speed search % 100 100 100 100 100 100 100 100
100 100 100 -
68
Inverter Capacity Selection440V Class
Data of Sn-01
Name2B 2C 2D 2E 2F 30 31 32 33 34 35 36
Inverter rating HP 40 50 60 75 100 125 150 175 215 250 300
400Inverter rated capacity kVA 54 68 82 110 138 180 195 230 260 290
385 514Max. applicable motor capacity HP (kW)40
(30)
50
(37)
60
(45)
75
(55)
100
(75)125
150
(110)175
215
(160)
250
(185)
300
(220)
400
(300)
Inverter rated current A 64 80 96 128 165 192 224 270 300 340
450 600Cn-09 Motor rated current A 48.7 59.0 70.5 88.0 114 143 175 206
235 290 348 465Cn-23 Carrier frequency upperlimit kHz 10.0 10.0 10.0 10.0 3.0
3.0 3.0 3.0 3.0 2.0 2.0 2.0Cn-24 Carrier frequency lowerlimit kHz 10.0 10.0 10.0 10.0 3.0
3.0 3.0 3.0 3.0 2.0 2.0 2.0Cn-25 Carrier frequencyproportional gain 0 0 0 0 0 0 0 0 0 0 0
0Cn-31 Motor phase-to-phaseresistance 0.164 0.133 0.110 0.074
0.027 0.051 0.036 0.032 0.023 0.020 0.022 0.014Cn-32 Torque compensation ironloss W 536 641 737 790 1800 2900
2900 2600 2500 2600 1850 3600Cn-33 Torque compensation limit V 100 100 100 100 100 100 100
100 100 100 100 100Cn-37 Momentary power lossassurance time s 2.0 2.0 2.0 2.0 2.0
2.0 2.0 2.0 2.0 2.0 2.0 2.0Cn-40 Minimum baseblock time s 1.0 1.0 1.0 1.0 1.0 1.0 2.0 2.0
2.0 2.0 2.0 2.0Fact
ory
Set
ting
Cn-41 V/f during speed search % 100 100 100 80 80 80 80 80 80 80
80 80The allowable maximum carrier frequency of 440V class 100HP to
215HP are to beas follows:440V Horse Power 100HP 125HP 150HP 175HP 215HP
Max. Allowable Carrier Frequency 8kHz 6kHz 6kHz 5kHz 10kHz
-
69
2. SLValid Access LevelsParameter
No. NameLCD Display
(English) DescriptionFactorySetting
Change DuringOperation GP SL PID PG
Sn-01 Inverter CapacitySelectionSn-01=29
440V 25HPInverter Capacity Selection *1 1 2 1 1
Inverter Capacity Selection220V Class
Data of Sn-01
Name00 01 02 03 04 05 06 07
Inverter rating HP 0.5 1 2 3 5 7.5 10 15
Inverter rated capacity kVA 1.4 2.1 2.7 4.1 6.9 10.3 13.7
20.6Max. applicable motor capacity HP (kW)0.5
(0.4)
1
(0.75)
2
(1.5)
3
(2.2)
5
(3.7)
7.5
(5.5)
10
(7.5)
15
(11)
Inverter rated current A 3.2 4.8 6.4 9.6 16 24 32 48
Cn-09 Motor rated current A 1.9 3.4 6.1 8.7 13.5 20.1 25.1
36.7Cn-23 Carrier frequency upperlimit kHz 15.0 15.0 15.0 15.0 15.0
15.0 15.0 15.0Cn-24 Carrier frequency lowerlimit kHz 15.0 15.0 15.0 15.0 15.0
15.0 15.0 15.0Cn-25 Carrier frequencyproportional gain 0 0 0 0 0 0 0 0
Cn-31 Motor phase-to-phaseresistance 11.760 5.732 2.466 1.600
0.707 0.398 0.222 0.230Cn-32 Motor leakage inductance mH 42.24 19.07 13.40 9.81 6.34
4.22 2.65 2.23Cn-33 Torque limit % 150 150 150 150 150 150 150 150
Cn-37 Momentary power lossassurance time s 0.7 1.0 1.0 1.0 2.0
2.0 2.0 2.0Cn-40 Minimum baseblock time s 0.5 0.5 0.5 0.5 0.5 0.7 0.7
0.7Cn-41 V/f during speed search % 100 100 100 100 100 100 100
100Fact
ory
Set
ting
bn-08 Rated slip of motor Hz 2.9 2.5 2.6 2.9 3.3 1.5 1.3 1.7
-
70
Inverter Capacity Selection220V Class
Data of Sn-01
Name08 09 0A 0B 0C 0D 0E 0F
Inverter rating HP 20 25 30 40 50 60 75 100
Inverter rated capacity kVA 27.4 34 41 54 68 78 95 130
Max. applicable motor capacity HP (kW)20
(15)
25
(18.5)
30
(22)
40
(30)
50
(37)
60
(45)
75
(55)
100
(75)
Inverter rated current A 64 80 96 130 160 183 224 300
Cn-09 Motor rated current A 50.3 62.9 72.9 96.7 124 143.5 183.5
230Cn-23 Carrier frequency upperlimit kHz 15.0 10.0 10.0 10.0 10.0
3.0 3.0 3.0Cn-24 Carrier frequency lowerlimit kHz 15.0 10.0 10.0 10.0 10.0
3.0 3.0 3.0Cn-25 Carrier frequencyproportional gain 0 0 0 0 0 0 0 0
Cn-31 Motor phase-to-phaseresistance 0.138 0.102 0.080 0.067
0.045 0.035 0.028 0.019Cn-32 Motor leakage inductance mH 1.48 1.39 1.15 1.15 1.15 1.15
1.15 1.15Cn-33 Torque limit % 150 150 150 150 150 150 150 150
Cn-37 Momentary power lossassurance time s 2.0 2.0 2.0 2.0 2.0
2.0 2.0 2.0Cn-40 Minimum baseblock time s 0.7 1.0 1.0 1.0 1.0 1.0 1.0
1.0Cn-41 V/f during speed search % 100 100 100 80 80 80 80 80
Fact
ory
Set
ting
bn-08 Rated slip of motor Hz 1.6 1.7 1.7 1.8 1.3 1.6 1.5 1.4
The allowable maximum carrier frequency is 10kHz
-
71
Inverter Capacity Selection440V Class
Data of Sn-01
Name20 21 22 23 24 25 26 27 28 29 2A
Inverter rating HP 0.5 1 2 3 5 7.5 10 15 20 25 30
Inverter rated capacity kVA 1.4 2.1 3.4 4.1 6.9 10.3 13.7 20.6
27.4 34 41Max. applicable motor capacity HP (kW)0.5
(0.4)
1
(0.75)
2
(1.5)
3
(2.2)
5
(3.7)
7.5
(5.5)
10
(7.5)
15
(11)
20
(15)
25
(18.5)
30
(22)
Inverter rated current A 1.6 2.6 4.0 4.8 8 12 16 24 32 40 48
Cn-09 Motor rated current A 1.0 1.7 2.9 4.0 6.8 10.0 12.6 18.6
24.8 31.1 36.3Cn-23 Carrier frequency upperlimit kHz 15.0 15.0 15.0 15.0 15.0
15.0 15.0 15.0 15.0 10.0 10.0Cn-24 Carrier frequency lowerlimit kHz 15.0 15.0 15.0 15.0 15.0
15.0 15.0 15.0 15.0 10.0 10.0Cn-25 Carrier frequencyproportional gain 0 0 0 0 0 0 0 0 0 0
0Cn-31 Motor phase-to-phaseresistance 47.02 22.929 9.629 6.333
2.735 1.776 1.151 0.634 0.436 0.308 0.239Cn-32 Motor leakage inductance mH 168.7 80.76 53.25 40.03 24.84
16.87 10.59 8.93 5.90 5.54 4.59Cn-33 Torque limit % 150 150 150 150 150 150 150 150 150 150
150Cn-37 Momentary power lossassurance time s 1.0 1.0 1.0 1.0 2.0
2.0 2.0 2.0 2.0 2.0 2.0Cn-40 Minimum baseblock time s 0.5 0.5 0.5 0.5 0.5 0.7 0.7 0.7
1.0 1.0 1.0Cn-41 V/f during speed search % 100 100 100 100 100 100 100 100
100 100 100Fact
ory
Set
ting
bn-08 Rated slip of motor Hz 2.7 2.6 2.5 3.0 3.2 1.5 1.3 1.7 1.6
1.7 1.7 -
72
Inverter Capacity Selection440V Class
Data of Sn-01
Name2B 2C 2D 2E 2F 30 31 32 33 34 35 36
Inverter rating HP 40 50 60 75 100 125 150 175 215 250 300
400Inverter rated capacity kVA 54 68 82 110 138 180 195 230 260 290
385 514Max. applicable motor capacity HP (kW)40
(30)
50
(37)
60
(45)
75
(55)
100
(75)125
150
(110)175
215
(160)
250
(185)
300
(220)
400
(300)
Inverter rated current A 64 80 96 128 165 192 224 270 300 340
450 600Cn-09 Motor rated current A 48.7 59.0 70.5 88.0 114 143 175 206
235 290 348 465Cn-23 Carrier frequency upperlimit kHz 10.0 10.0 10.0 10.0 3.0
3.0 3.0 3.0 3.0 2.0 2.0 2.0Cn-24 Carrier frequency lowerlimit kHz 10.0 10.0 10.0 10.0 3.0
3.0 3.0 3.0 3.0 2.0 2.0 2.0Cn-25 Carrier frequencyproportional gain 0 0 0 0 0 0 0 0 0 0 0
0Cn-31 Motor phase-to-phaseresistance 0.164 0.133 0.110 0.074
0.027 0.051 0.036 0.032 0.023 0.020 0.022 0.014Cn-32 Motor leakage inductance mH 3.59 2.60 2.26 2.26 2.26 2.26
2.26 2.26 2.26 2.26 2.26 2.26Cn-33 Torque limit % 150 150 150 150 150 150 150 150 150 150 150
150Cn-37 Momentary power lossassurance time s 2.0 2.0 2.0 2.0 2.0
2.0 2.0 2.0 2.0 2.0 2.0 2.0Cn-40 Minimum baseblock time s 1.0 1.0 1.0 1.0 1.0 1.0 2.0 2.0
2.0 2.0 2.0 2.0Cn-41 V/f during speed search % 100 100 100 80 80 80 80 80 80 80
80 80Fact
ory
Set
ting
bn-08 Rated slip of motor Hz 1.8 1.3 1.6 1.5 1.4 1.4 1.4 1.4 1.3
1.3 1.2 1.2The allowable maximum carrier frequency of 440V class 100HP to
215HP are to beas follows:440V Horse Power 100HP 125HP 150HP 175HP 215HP
Max. Allowable Carrier Frequency 8kHz 6kHz 6kHz 5kHz 10kHz
-
73
V/f Pattern Selection Sn-02
Valid Access LevelsParameterNo. Name
LCD Display(English) Description
FactorySetting
Change DuringOperation GP SL PID PG
Sn-02 V/f CurveSelectionSn-02=01V/f Curve
V/f pattern Selection 01
V/f pattern is selected by the setting of Sn-02. When V/f
pattern is selected, set inputvoltage of the inverter in Cn-01.Data 0 — E (of Sn-02): Change disabled
Data F (of Sn-02): Change enabled(V/f patterns are shown on the
following pages).The V/f pattern is fixed to Sn-02=0F for the SL control mode;
The users have to checkthe V/f pattern to meet the load application
if switched to one of the other threecontrol mode (GP, PID or PG)
from SL control mode.To select the high starting torque V/f pattern for inverter mode
of capacity 440V100HP (75KW) or more is recommended.In the sensorless vector control mode (SL), if sufficient torque
cannot be obtained at alow speed, change the V/f pattern setting of
Cn-02 to Cn-08 to high starting V/f.[Example]
1 3 60f (Hz)
V (v)Standard V/f
220
(Cn-06) 11
(Cn-08) 4.37
1 3 60f (Hz)
V (v)
High starting V/f
220
(Cn-06) 13
(Cn-08) 5
(Cn-07)(Cn-05)(Cn-07)(Cn-05)
-
74
V/f Pattern of 220V Class* 3 to 60 HP (2.2 to 45kW)
Specifications Sn-02 V/f Pattern Specifications Sn-02 V/f
PatternLowStartingtorque
8
50Hz 0 50Hz
HighStartingtorque
9
60HzSatu-ration
1F
LowStartingtorque
A
60Hz
50HzSatu-ration
2
Hig
h St
artin
g To
rque
60Hz
HighStartingtorque
BGen
eral
-pur
pose
72Hz 3 90Hz C
Variabletorque 1 4
50Hz
Variabletorque 2 5
120Hz D
Variabletorque 3 6
Varia
ble
Torq
ue C
hara
cter
istic
s
60Hz
Variabletorque 4 7
Rat
ed O
utpu
t Ope
ratio
n (M
achi
ne to
ol)
180Hz E
* For 440V class, 2 times voltage value shown in table above.
Consider the following items as conditions for selecting a V/f
pattern.They must be suitable for:(1) The voltage and frequency
characteristics of the motor.(2) The maximum rotation speed of the
motor.Select high starting torque only in the following conditions.
Normally, this selection is not required.(1) The wiring distance is
long [492ft (150m) and above].(2) Voltage drop at startup is
large.(3) AC reactor is inserted in the input or output of the
inverter.(4) A motor smaller than the maximum applicable inverter
is used.220(V)
(Hz)0 1.3 2.5 50
1611
0
220(V)
(Hz)0 1.5 3 50 60
1611
2
1
F
220(V)
(Hz)0 1.5 3 60 72
1611
3
1.8 3.6
220(V)
(Hz)0 1.3 25 50
5539
5
411 9
220(V)
(Hz)0 1.5 30 60
5539
7
611 9
220(V)
(Hz)0 1.5 3 60 180
33 1628 11
E
4.5 6
220(V)
(Hz)0 1.5 3 60 120
38 1620 11
D
3 6
220(V)
(Hz)0 1.5 3 60 90
1611
C
2.5 4.5
220(V)
(Hz)0 1.5 3 60
25 2820 22
2014 13
B
A
220(V)
(Hz)0 1.3 2.5 50
25 2820 22 15 13
9
8
-
75
V/f Pattern of 220V Class* 75 and 100HP (55 and 75kW), (75 to
400HP for 440V class)Specifications Sn-02 V/f Pattern Specifications Sn-02 V/f
PatternLowStartingtorque
8
50Hz 0 50Hz
HighStartingtorque
9
60HzSatu-ration
1F
LowStartingtorque
A
60Hz
50HzSatu-ration
2
Hig
h St
artin
g To
rque
60Hz
HighStartingtorque
BGen
eral
-pur
pose
72Hz 3 90Hz C
Variabletorque 1 4
50Hz
Variabletorque 2 5
120Hz D
Variabletorque 3 6
Varia
ble
Torq
ue C
hara
cter
istic
s
60Hz
Variabletorque 4 7
Rat
ed O
utpu
t Ope
ratio
n (M
achi
ne to
ol)
180Hz E
* For 440V class, 2 times voltage value shown in table above.
Consider the following items as conditions for selecting a V/f
pattern.They must be suitable for:(1) The voltage and frequency
characteristics of the motor.(2) The maximum rotation speed of the
motor.Select high starting torque only in the following conditions.
Normally, this selection is not required.(1) The wiring distance is
long [492ft (150m) and above].(2) Voltage drop at startup is
large.(3) AC reactor is inserted in the input or output of the
inverter.(4) A motor smaller than the maximum applicable inverter
is used.# Up to 100HP (75kW) for 220V class.220(V)
(Hz)0 1.3 2.5 50
14 8
0
220(V)
(Hz)0 1.5 3 50 60
14 8
2
1
F
220(V)
(Hz)0 1.5 3 60 72
14 8
3
220(V)
(Hz)0 1.3 25 50
5538
5
410 8
220(V)
(Hz)0 1.5 30 60
5538
7
610 8
220(V)
(Hz)0 1.5 3 60 180
14 8
E
220(V)
(Hz)0 1.5 3 60 120
14 8
D
220(V)
(Hz)0 1.5 3 60 90
14 8
C
220(V)
(Hz)0 1.3 2.5 50
25201311
9
8
220(V)
(Hz)0 1.3 3 60
2520
11
B
A
-
76
Operator Status Sn-03
Valid Access LevelsParameterNo. Name
LCD Display(English) Description
FactorySetting
ChangeDuring
Operation GP SL PID PG
Display ofOperator
0000: Setting and reading of An-,Bn-,Cn-, Sn-enabled
0101: Setting and reading of An-,Readinng of Bn-,Cn-,Sn-
enabledSn-03
ConstantsInitialization
Sn-03=0000Operate Setting
1110: Constants Initialigation (2-wire)*21111: Constants
Initialigation (3-wire)*20000
The ability to set or read the different groups of constants is
determined by Sn-03 asshow below.DRIVE Mode PRGM ModeSn-03
Setting Reading Setting ReadingRemarks
0000 An, bn Sn, Cn An, bn, Sn, Cn Factory setting
0101 An bn, Sn, Cn An bn, Sn, Cn *
* It is recommended that Sn-03 be set to 0101 and reading mode
entered after test run adjustment.Note: To read the Sn or Cn
constants while in the DRIVE mode, depress the DSPL key withkey depressed.
Initialization (Sn-03=1110, 1111)
After depressing the ENTER key, input the initial value of An-,
bn-, Sn-,Cn-, (except Sn-01,Sn-02) into NV-RAM. When the value is
written in without anerror, Entry accepted (End) is displayed. When
the value is written in with an error,** Error (Err) alarm is
displayed. The values of Sn-15 to -18 differ as followsbetween
initializations with Sn-03 = 1110 and with Sn-03 = 1111.Multi-functionTerminal
1110(2 Wire Sequence)
1111(3 Wire Sequence)
Terminal 5 (Sn-15) 3* (Multi-step speed command 1) 0 (FWD/REV
run select)Terminal 6 (Sn-16) 4* (Multi-step speed command 2) 3 (Multi-step
speed reference 1)Terminal 7 (Sn-17) 6* (Jog frequency reference) 4 (Multi-step
speed reference 2)Terminal 8 (Sn-18) 8* (External baseblock command) 6 (Jog
frequency reference)* Values have been factory-set.** contents depend on the
parameter setting items.RESET
-
77
Operation Mode Selection 1 Sn-04
Valid Access LevelsParameterNo. Name
LCD Display(English) Description
FactorySetting
ChangeDuring
Operation GP SL PID PG
— — -0: Frequency Command = Controlcircuit terminals 13 or
14— — -1: Frequency Command =Frequency Command 1 (An-01)Operation
ModeSelect — -0 -: RUNSTOP Command =Control circuit terminals
— -1 -: RUNSTOP Command =LCD Digital OperatorSn-04
StoppingMethod
Selection
Sn-04=0011Stopping Method
00- -: Stopping method = Ramp to stop01- -: Stopping method
=Coastingto stop10- -: Stopping method =Full-range DC
injection branking stop11- -: Stopping method = Coasting
stop(timer function provided)
0011
(1) 1st digit (frequency reference selection)
1st digit = 0: Reference input from control circuit terminal 13
or 14 is the masterspeed frequency reference.1st digit = 1: Frequency reference 1 (An-01) is the master speed
frequencyreference.Note: For combination of multi-step speed operation, refer to
pages 90.(2) 2nd digit (run command selection)
2nd digit = 0: Run command from control circuit terminal is
accepted.2nd digit = 1: Run command from the digital operator is
accepted.Valid run command and frequency references differ as shown in
the table below,depending on the combination of the 1st and 2nd
digits.2nd digit 1st digit 2nd digit 1st digit 2nd digit 1st digit 2nd
digit 1st digitCONSTANTREFERENCESYSTEM CONSTANTS 40 0 0 1 1 0 1 1
Master Speed Frequency Reference Control circuitterminal 13, 14
An-01Control circuitterminal 13, 14 An-01FWD Run Command (Terminal 1) REV Run Command (Terminal 2)
External Fault (Terminal 3) Fault Reset (Terminal 4)Command of
Terminal 5 Command of Terminal 6 Command of Terminal 7 Command of
Terminal 8 Aux. Input Fault Contact Output Multi-function Contact
OutputControlTerminal
Multi-function PHC Output RUN Key JOG Key STOP Key FWD/REV Key
>/RESET KeyDRIVE/PRGM Key Valid only wheninverter stoppedValid only
wheninverter stoppedValid only wheninverter stopped
Valid only wheninverter stopped
Operator
REF LED Lit OFF Lit OFF
-
78
SEQ LED Lit Lit OFF OFFMonitor display
Valid only when the inverter stops. (FWD run command, REV run
command, and DC injection braking command are «open».)FWD/REV run command is not accepted.
When the STOP key is depressed, processing differs as follows,
depending on the setting of the 1st digit of Sn-05.1st digit = 0: During running by signals from control circuit
terminals, the STOP key from the operator is accepted.If the STOP key is depressed, the inverter stops according to
the setting of 3rd and 4th digits of Sn-04, while the STOP
LEDindicator blinks. This stop command is held within the inverter
until both the FWD run command and REV run command of
controlcircuit terminals become «open», or another frequency
reference is selected in the multi-step speed command or jog
frequencyreference section.1st digit=1: During running by signals from control circuit
terminals, the STOP key from the operator is not accepted.(3) 3rd digit, 4th digit (stop method selection)
Stop method differs by the setting of 3rd and 4th digits as
shown below.1 Sn-04 = 00 XX RAMP to stop
2 Sn-04 = 01 XX Coast to stop
RUN COMMAND
OUTPUT FREQUENCY
DC INJECTION BRAKINGSTART FREQUENCY(Cn-10)
DC Injection Braking time atStopping (Cn-12)
DECELERATION TIME
DC INJECTIONBRAKING
CLOSEDOPEN
RUN COMMANDOUTPUT FREQUENCY
CLOSEDOPEN
WHEN STOPREFERENCE IS INPUT,INVERTER OUTPUT IS
-
79
3 Sn-04 = 10 XX Full-range DC injection braking stop
DC injection braking time differs by the output frequency when
stop command isinput as shown below.OUTPUT FREQUENCY WHEN STOPREFERENCE IS INPUT
4 Sn-04 = 11 XX Coasting to a Stop (timer function provided)
Once stop command is input, run command is disregarded during T1
time.RUN COMMANDOUTPUT FREQUENCY
CLOSEDOPEN
0.5s
CUTOFF OFINVERTEROUTPUT
DC INJECTIONBRAKING TIME
DC INJECTIONBRAKING TIME
DC INJECTION BRAKINGTIME AT STOPPING (Cn-12)
Cn-12 x 10
10% SPEED 100% SPEED
RUN COMMAND
OUTPUT FREQUENCY
CLOSEDOPEN
DECELERATION TIME
WHEN STOP REF. ISINPUT, INVERTEROUTPUT IS CUTOFF.
CLOSED
T1 Time
T1 Time
-
80
OUTPUT FREQUENCY WHENSTOP REFERENCE IS INPUT.
-
81
Operation Mode Selection 2 Sn-05
1. GP, SL, PIDValid Access LevelsParameter
No. NameLCD Display
(English) DescriptionFactorySetting
ChangeDuring
Operation GP SL PID PG
— — -0: Stop key effective duringoperation from control
terminal— — -1: Stop key effective duringoperation from control
terminal— -0 -: Reverse run enabled- -1 -: Reverse run disabled- 0- -:
Control input terminals 1 ~8are scanned twice.- 1- -: Control input terminals 1 ~8
are scanned once.
Sn-05I/O terminal
functionselection
Sn-05=0000I/O term. Fct
0- — -: Selection of item to be analogoutput (terminals 21 , 22
)*31- — -: Selection of item to be analogoutput (terminals 21 , 22
)*30000 1 1 1 2
(1) 1st digit
Select processing to be performed when the STOP key of the
digital operator isdepressed during running by control circuit
terminals.1st digit = 0: During running by signals from control circuit
terminals, the STOP keyfrom the digital operator is accepted. If
the STOP key is depressed, theinverter stops according to the
setting of the 3rd and 4th digits of Sn-04while the STOP LED
indicator blinks. This stop command is held withinthe inverter
until both the FWD run command and REV run commandof control
circuit terminals become «open», or other frequency referenceis
selected in the multi-step speed command or jog frequencyreference
section.1st digit = 1: During running by signals from control circuit
terminals, the STOP keyfrom the digital operator is not
accepted.(2) 2nd digit (REV run prohibited)
2nd digit = 0: REV run command from control circuit terminals or
the digital operatoris accepted.2nd digit = 1: REV run command from control circuit terminals or
the digital operatoris not accepted.(3) 3rd digit (selection of double scanning sequence
command)3rd digit = 0: Sequence command (control circuit terminals 1 to
is scanned twice.3rd digit = 1: Sequence command (control circuit terminals 1 to
is scanned once.(4) 4th digit (selection of the multi-function analog
output)Multi-function analog output (control circuit terminals 21, 22)
output signal can beselected by Sn-05 4th digit and Sn-09 2nd
digit.Sn-054th Digit
Sn-092nd Digit Description
0 0 Outputs analog signal proportional to inverter output
frequency.(Max. frequency/100%)1 0 Outputs analog signal proportional to inverter
current.(Rated current/100%)0 1 Outputs analog signal proportional
to inverter output voltage reference. -
82
(Cn-01/100%)
1 1 Outputs analog signal proportional to inverter output
power.(Max motor capacity/100%)2. PGValid Access LevelsParameter
No. NameLCD Display
(English) DescriptionFactorySetting
ChangeDuring
Operation GP SL PID PG
— — -0: Stop key effective duringoperation from control
terminal— — -1: Stop key effective duringoperation from control
terminal— -0 -: Reverse run enabled- -1 -: Reverse run disabled
— 0- -: Control input terminals 1 ~8are scanned twice.
— 1- -: Control input terminals 1 ~8are scanned once.
Sn-05I/O terminal
functionselection
Sn-05=0000I/O term. Fct
0- — -: Not used1- — -: Not used
0000 1 1 1 2
(1) 1st, 2nd, 3rd, digit (functions same as GP, SL, PID control
mode)(2) 4th digit (Not used)
[Note] The item to be output from multi-function analog output
(Control circuit terminals21 -22 ) is set by bn-11 in the GP
control mode. Please refer to bn-11. -
83
Operation Mode Selection 3 Sn-06Valid Access LevelsParameter
No. NameLCD Display
(English) DescriptionFactorySetting
ChangeDuring
Operation GP SL PID PG
— -00: S curve=0.2sec- -01: S curve=0.0sec (NO S curve)- -10: S
curve=0.5sec- -11: S curve=1.0sec-0 — -: Reference command has
forwardcharacteristics(0-10V or 4-20mA/0~100%)
-1 — -: Reference command has reversecharacteristics(0-10V or
4-20mA/100~0%)Sn-06
S-curve andfrequencyCommand
characteristics
Sn-06=0000S-curve Cmd.
Char.
0- — -: Stop by reference input whenfrequency reference is
missing1- — -: Operation to continue with 80% offrequence reference
whenfrequency reference is missing0000
(1) 1st digit, 2nd digit (S-curve selection of soft starter)
The S-curve characteristics of the soft starter depend on the
setting of the 1st and2nd digits as follows:2nd digit 1st digit Contents0011
0101
The S-curve characteristic is 0.2 second.No S-curve
characteristics.The S-curve characteristic is 0.5 second.The
S-curve characteristic is 1 second.Note: S-curve characteristic time refers to the time from
acceleration rate 0 to the time when anormal acceleration rate
determined by a specified acceleration time is obtained.(a) Time chart at FWD/REV run change with S-curve
characteristicThe figure below shows the time chart at FWD/REV run
change duringdeceleration and stop.FREQUENCYREF.
OUTPUT FREQUENCY
TIME
S-CURVECHARACTERISTICSTIME (TSC)
FWD RUNCOMMAND
REV RUNCOMMAND
ACCELER-ATION
DECELER-ATION
DC INJECTIONBRAKING TIMEAT STOPPING(Cn-12)
ACCELERATION
OUTPUTFREQUENCY
MIN. OUTPUTFREQUENCY(Cn-07)
: S-CURVE CHARACTERISTIC
MIN. OUTPUTFREQUENCY(Cn-07)
DECELER-ATION
DC INJECTION BRAKINGSTART FREQUENCY (Cn-
10)
-
84
(b) The chart at FWD/REV run change without S-curve
characteristicThe figure below shows the time chart at FWD/REV run
change duringdeceleration and stop.(2) 3rd digit (reverse characteristic selection)
The input characteristics of the master speed frequency
reference depend on theset value as follows. For the reverse
characteristic, only + input is valid.3rd digit = 0: Normal characteristic (0-10V or
4-20mA/0-100%)3rd digit = 1: Reverse characteristic (10-0V or
20-4mA/0-100%)FWD RUNCOMMAND
REV RUNCOMMAND
ACCELER-ATION
DECELER-
ATIONDC INJECTIONBRAKING TIMEAT STOPPING(Cn-12)
ACCELERATION
OUTPUTFREQUENCY
MIN. OUTPUTFREQUENCY(Cn-07)
DC INJECTION BRAKINCSTART FREQUENCY (Cn-
10)
MIN. OUTPUTFREQUENCY(Cn-07)
DECELER-ATION
0%
FREQUENCYREFERENCE
100%
4mA 20mA
CURRENT INPUT (TERMINAL 14)
3rd digit = 0 3rd digit = 1
0%
FREQUENCYREFERENCE
100%
0V 10V
VOLTAGE INPUT (TERMINAL 13)
-
85
(3) 4th digit (operation selection when frequency reference is
missing)4th digit = 0: Normal operation (varies with change of
reference)4th digit = 1: Operation continues with 80% frequency.
When 4th digit = 1 is set, the current master speed frequency
reference iscompared at all times with the one that occurred 0.4
second before. When thecurrent master speed frequency reference
goes below 10% of the one that occurred0.4 second before, operation
continues with 80% (80% frequency) of the masterspeed frequency
reference of the prior one. Consequently, the master speedfrequency
reference of the previous one (0.4 second before) is used as the
currentfrequency reference.In the following cases, this operation is released and the
inverter returns to normaloperation:Master speed frequency reference exceeding 80% frequency is
input.Stop reference is input.
Reference is missing during operation at less than 5% of
frequency.FWD RUNCOMMAND
80%MASTER SPEEDFREQUENCYREFERENCE
INVERTEROUTPUTFREQUENCY TIME CHART
10%
80% OFFREQUENCY
0.4sec.
0.4sec.
-
86
Operation Mode Selection 4 Sn-07
1. GP, PID, PGValid Access LevelsParameter
No. NameLCD Display
(English) DescriptionFactorySetting
ChangeDuring
Operation GP SL PID PG
— — -0: Overtorque detection disabled
— — -1: Overtorque detection enabled
— -0 -: Enabled only if at agreedfrequency
— -1 -: Enable during operation (exceptduring DC injection)
— 0- -: Operation continued afterovertorque is detected
— 1- -: Coasts to stop if overtorque isdetected
Sn-07 OvertorqueDetectionSn-07=0000
Over Tq. Detect
0- — -: Overtorque detection with current1- — -: Overtorque
detection with torque0000 1 2 1 1
Define the operation at overtorque detection. Overtorque is
detected by the followingformula:Inverter output current B overtorque detection level (Cn-26,
Initial value: 160%)(Detection time Cn-27, Initial value: 0.1 second, Hysteresis
fixed at 10%)(1) 1st digit
1st digit = 0: Overtorque is not detected.
1st digit = 1: Overtorque is detected.
(2) 2nd digit
2nd digit = 0: Overtorque is detected only during agreed
frequency.2nd digit = 1: Overtorque is detected during stop or during
running except for DB.(3) 3rd digit
3rd digit = 0: When overtorque is detected, Over Torque (OL3)
Alarm blinks on thedigital operator and the operation
continues.3rd digit = 1: When overtorque is detected, Over Torque (OL3)
Fault is displayedon the digital operator and the inverter output
is shut OFF. Fault contactsignal is output. (Treated as a
fault).Setting either Sn-20 or 22 to 0B enables signal to be output at
overtorque detection.MULTI-FUNCTION OUTPUT SIGNAL(OVERTORQUE DETECTION SIGNAL)
MOTORCURRENT
HYSTERESIS 10%
TIME
ONCn-27
Cn-26
ONCn-27
-
87
(4) 4th digit (Not used)
2. SLValid Access LevelsParameter
No. NameLCD Display
(English) DescriptionFactorySetting
ChangeDuring
Operation GP SL PID PG
— — -0: Overtorque detection disabled
— — -1: Overtorque detection enabled
— -0 -: Enabled only if at agreedfrequency
— -1 -: Enable during operation (exceptduring DC injection)
— 0- -: Operation continued afterovertorque is detected
— 1- -: Coasts to stop if overtorque isdetected
Sn-07 OvertorqueDetectionSn-07=0000
Over Tq. Detect
0- — -: Overtorque detection with current1- — -: Overtorque
detection with torque0000 1 2 1 1
(1) 1st, 2nd, 3rd digit (functions same as GP, PID,PG control
mode)(2) 4th digit
4th digit = 0: Overtorque detected with current.
4th digit = 1: Overtorque detected with torque.
-
88
Operation Mode Selection 5 Sn-08
1. GP, SLValid Access LevelsParameter
No. NameLCD Display
(English) DescriptionFactorySetting
ChangeDuring
Operation GP SL PID PG
— — -0: Frequency reference input byoption card (AI-14B, DI-08
or SI-M)— — -1: Frequency reference input bydigital operetor or control
cirauitinput terminals— -0 -: RUN/STOP command input byoption card (AI-14B, DI-08 or
SI-M)— -1 -: RUN/STOP command input bydigital operator or control
circuitinput terminalsSn-08
OptionCard/Invater
FunctionSelection
Sn-08=0000
AI/DI & SI-M Card
00- -: SI-M communication fault,deceleration to stop (bn-02)
01- -: SI-M communication fault, coastto stop
10- -: SI-M communication fault,deceleration to stop (bn-04)
11- -: SI-M communication fault,continue to run
0000 1 1 2 3
(1) 1st digit (option/inverter change)
Specify whether option card or inverter frequency reference is
used for operation.1st digit = 0: Option card frequency reference is accepted.
1st digit = 1: Frequency reference from inverter control circuit
terminals or the digitaloperator is accepted.(2) 2nd digit (run command option/inverter change)
Select whether operation is performed by the option card or
inverter run command.2nd digit = 0: Run command from option card received.
2nd digit = 1: Run command from inverter control circuit
terminal or digital operatorreceived.(3) 3rd digit, 4th digit (selection of stopping method at
communication error detection)Stopping method at communication error detection can be selected
bycommunication interface card (SI-M).4th digit 3rd digit Contents
0
0
1
1
0
1
0
1
Ramp to stop by bn-02 (major fault)
Coast to stop (major fault)
Ramp to stop by bn-04 (major fault)
Operation to continue (minor fault)
-
89
2. PIDValid Access LevelsParameter
No. NameLCD Display
(English) DescriptionFactorySetting
ChangeDuring
Operation GP SL PID PG
— — -0: Frequency reference input byoption card (AI-14B, DI-08
or SI-M)— — -1: Frequency reference input bydigital operetor or control
cirauitinput terminals— -0 -: RUN/STOP command input byoption card (AI-14B, DI-08 or
SI-M)— -1 -: RUN/STOP command input bydigital operator or control
circuitinput terminals-0 — -: Auto Energy Saving functionineffective (nornal V/f
controlmethod)-1 — -: Auto Energy Saving functioneffective
Sn-08
OptionCard/InvaterFunction &
Energy SavingSelection
Sn-08=0000
AI/DI & Eg. Saving
0- — -: Not used1- — -: Not used
0000 1 1 2 3
(1) 1st, 2nd, digit (functions same as GP, SL control mode)
(2) 3rd digit (Auto Energy Saving selection)
3rd digit = 0: Auto Energy Saving (AES) function ineffective
3rd digit = 1: Auto Energy Saving function effective. (ref. To
Appendix B)(3) 4th digit (Not used)
3. PGValid Access LevelsParameter
No. NameLCD Display
(English) DescriptionFactorySetting
ChangeDuring
Operation GP SL PID PG
— — -0: Frequency reference input byoption card (AI-14B, DI-08
or SI-M)— — -1: Frequency reference input bydigital operetor or control
cirauitinput terminalsSn-08
OptionCard/Invater
FunctionSelection
Sn-08=0000
AI/DI Card- -0 — -1 —0 — —1 — — Not used0- — -1- — —
0000 1 1 2 3
(1) 1st digit (functions same as GP, SL control mode)
(2) 2nd, 3rd, 4th digit (Not used)
-
90
Operation Mode Selection 6 Sn-09
1. GPValid Access LevelsParameter
No. NameLCD Display
(English) DescriptionFactorySetting
ChangeDuring
Operation GP SL PID PG
— — -0: Analog output (tereminal 21 -22 )depends on Sn-05 4th
digit andSn-09 2nd digit.— — -1: Analog output (tereminal 21 -22 )is set by SI-M
card.— -0 -: Analog output (tereminal 21 -22 )- -1 -: Analog output
(tereminal 21 -22 )Sn-09
Analog OutputSelection and
SlipCompensetion
Sn-09=0000
~Output Select
-0 — —1 — -0- — — Not used1- — —
0000 1 2 3
(1) 1st digit (selection of analog output)
Multi-function analog output signal contents can be set either
by the inverter oroption card.1st digit = 0: Output according to Sn-05 4th digit and Sn-09 2nd
digit settingcontents.1st digit = 1: Output according to contents set by communication
interface card (SI-M).(2) 2nd digit (selection of multi-function analog output
signal)Multi-function analog output (control circuit terminals 21 — 22)
output signal can beselected according to Sn-05 4th digit and Sn-09
2nd digit set value. Output signallevel is set by bn-11.Sn-054th Digit
Sn-092nd Digit Description
0 0 Outputs analog signal proportional to inverter output
frequency.(Max. frequency/100%)1 0 Outputs analog signal proportional to inverter
current.(Rated current/100%)0 1 Outputs analog signal proportional to inverter output
voltagereference. (Cn-01/100%)1 1 Outputs analog signal proportional to inverter output
power.(Max. applicable motor capacity/100%)(3) 3rd, 4th digit (Not used)
-
91
2. SLValid Access LevelsParameter
No. NameLCD Display
(English) DescriptionFactorySetting
ChangeDuring
Operation GP SL PID PG
— — -0: Analog output (tereminal 21 -22 )depends on Sn-05 4th
digit andSn-09 2nd digit.— — -1: Analog output (tereminal 21 -22 )is set by SI-M
card.— -0 -: Analog output (tereminal 21 -22 )- -1 -: Analog output
(tereminal 21 -22 )-0 — -: Not used-1 — -: Not usedSn-09
Analog OutputSelection and
SlipCompensetion
Sn-09=0000~Output Select
0- — -: No slip compensation duringregenerating
1- — -: Slip compensation even duringregenerating
0000 1 2 3
(1) 1st digit (functions same as GP control mode)
(2) 2nd digit (selection of multi-function analog output
signal)Multi-function analog output (control circuit terminals 21 — 22)
output signal can beselected according to Sn-05 4th digit and Sn-09
2nd digit set value. Output signallevel is set by bn-11.Sn-054th Digit
Sn-092nd Digit Description
0 0 Outputs analog signal proportional to inverter output
frequency.(Max. frequency/100%)1 0 Outputs analog signal proportional to inverter
current.(Rated current/100%)0 1 Outputs analog signal proportional to inverter output
voltagereference. (Cn-01/100%)1 1 Outputs analog signal proportional to inverter output
torque.(10V/250% motor rated torque)(3) 3rd digit (Not used)
(4) 4th digit (Slip compensation during regenerating
selection)4th digit = 0: No slip compensation during regenerating.
4th digit = 1: Slip compensation even during regenerating.
3. PIDValid Access LevelsParameter
No. NameLCD Display
(English) DescriptionFactorySetting
ChangeDuring
Operation GP SL PID PG
— — -0- — -1 Not used
— -0 -: Analog output (tereminal 21 -22 )- -1 -: Analog output
(tereminal 21 -22 )Sn-09Analog OutputSelection and
SlipCompensetion
Sn-09=0000~Output Select -0 — —
-1 — -0- — — Not used1- — —
0000 1 2 3
(1) 1st digit (Not used)
(2) 2nd digit (functions same as GP control mode)
-
92
(3) 3rd, 4th digit (Not used)
-
93
Protective Characteristic Selection 1 Sn-10
Valid Access LevelsParameterNo. Name
LCD Display(English) Description
FactorySetting
ChangeDuring
Operation GP SL PID PG
— — -0: Stall prevention duringacceleration enabled
— — -1: Stall prevention duringacceleration disabled
— -0 -: Stall prevention duringdeceleration enabled
— -1 -: Stall prevention duringdeceleration disabled
— 0- -: Stall prevention during runningenabled
— 1- -: Stall prevention during runningdisabled
Sn-10 Stall PreventionSn-10=0000
Stall Select
0- — -: Decel time during stall prevention(bn-02 set value)
1- — -: Decel time during stall prevention(bn-04 set value)
0000
(1) 1st digit (selection of stall prevention during
acceleration)1st digit = 0: Stall prevention during acceleration is
enabled.1st digit = 1: Stall prevention during acceleration is
disabled.The function of stall prevention during acceleration
automatically extendsacceleration according to load status
(inverter output current), thus preventing themotor from stalling
during acceleration. The stall prevention level duringacceleration
in a constant output area is reduced as follows:Acceleration stallprevention level of =constant output field
output frequencyWhen the 1st digit of Sn-10 is 1, the output frequency increases
at the ratedetermined by acceleration time:(2) 2nd digit (selection of stall prevention during
deceleration)2nd digit = 0: Stall prevention during deceleration is
enabled.2nd digit = 1: Stall prevention during deceleration is
disabled.The function of stall prevention during deceleration
automatically extendsdeceleration time according to the magnitude
of the main circuit DC voltage, thuspreventing overvoltage during
deceleration.When the 2nd digit of Sn-10 is 1, the output frequency decreases
at the ratedetermined by deceleration time. For positioning
applications, specify «stallprevention during deceleration not
provided» (2nd digit = 1) in order to obtainstopping accuracy. With
large inertia loads, use a braking resistor to
preventovervoltage.acceleration stall preventionlevel (Cn-28) x
maximum voltage frequency (Cn-04)
-
94
(3) 3rd digit (stall prevention during running)3rd digit = 0:
Stall prevention during running is enabled.3rd digit = 1: Stall prevention during running is disabled.
Stall prevention operation during running starts decelerating
when the outputcurrent reaches 100ms or greater than the set value
of Cn-30 during frequencycoincidence (operation level of stall
prevention during running). The inverterdecelerates as long as the
output current exceeds the set value of Cn-30(operation level of
stall prevention during running). When the output current goesbelow
the set value, the inverter reaccelerates. The deceleration time
selected inthe 4th digit of Sn-10 is taken. Even during stall
prevention while running, stallprevention during deceleration and
stall prevention during acceleration areenabled.(4) 4th digit (selection of deceleration time during stall
prevention while running)4th digit = 0: The inverter decelerates
for the deceleration time specified in bn-02.4th digit = 1: The inverter decelerates for the deceleration
time specified in bn-04.DETECTION LEVEL OFSTALL PREVENTIONDURING RUNNINGRETURN LEVEL
OUTPUTFREQUENCY DECELERATION TIME
ACCELERATIONTIME
HYSTERESIS2%
STALL PREVENTION DURING RUNNING
INVERTEROUTPUT CURRENT
DETECTION TIME: 100 ms
-
95
Protective Characteristic Selection 2 Sn-11
Valid Access LevelsParameterNo. Name
LCD Display(English) Description
FactorySetting
ChangeDuring
Operation GP SL PID PG
— — -0: Not used
— — -1: Not used
— -0 -: Fault contact is not energizedduring Retry operation
— -1 -: Fault contact is energized duringRetry operation
-0 — -: Operation stopped bymomentary power lossdetection
(UV1)-1 — -: Operation conticues aftermomentary power loss
Sn-11
Retry andmomentarypower lossprotection
Sn-11=0000
Retry & Ride-Thru
0- — -: Not used
1- — -: Not used
0000
(1) 1st digit (Not used)
(2) 2nd digit (fault contact signal during auto reset/restart
operation)2nd digit = 0: A fault contact signal is not output during auto
reset/restart operation.2nd digit = 1: A fault contact signal is output during auto
reset/restart operation.(3) 3rd digit (operation continued at momentary power loss)
3rd digit = 0: When momentary power loss is detected, DC Volt.
Low (Uv1) Faultoccurs and the inverter output is shut OFF.3rd digit = 1: If momentary power loss time is within momentary
power loss ride-thru time (Cn-37), the operation continues after
the momentary powerloss. If the momentary power loss ride-thru time
is exceeded,undervoltage fault DC Volt. Low (Uv1) Fault occurs and
the inverteroutput is shut OFF.Notes:
1. When the 3rd digit = 1, be sure not to shut OFF the external
sequence signal.(e.g. FWD, REV)2. For lifters, do not use this function. (the 3rd digit =
0)(4) 4th digit (Not used)
-
96
Protective Characteristic Selection 3 Sn-12
Valid Access LevelsParameterNo. Name
LCD Display(English) Description
FactorySetting
ChangeDuring
Operation GP SL PID PG
— — -0: External fault input (terminal 3 )is NO-contact
input— — -1: External fault input: is NC-contact input
— -0 -: External fault signal: alwaysdetected
— -1 -: External fault signal: detectedduring running only
Sn-12External Fault
FunctionSelection
Sn-12=0000
External Fault00- -: External fault detected: ramp to
stop (major fault) by bn-02 setvalue
01- -: External fault detected: Coastingto stop (major
fault)10- -: External fault detected: ramp tostop (major fault) by
bn-04 setvalue11- -: External fault detected: opeationto continue (major
fault)0000
When an external fault signal of terminal 3 is input, External
Fault 3 (EF3) Fault isdisplayed and a fault contact signal is
output immediately. The inverter stopsaccording to the setting of
the 3rd and 4th digits. The external fault signal is heldwithin the
inverter until a fault reset signal is input.(1) 1st digit (level selection of external fault signal)1st
digit = 0: NO contact input (when «closed», external fault
operation isperformed).
1st digit = 1: NC contact input (when «open», external fault
operation is performed).(2) 2nd digit (acceptance of external fault signal)2nd digit =
0: External fault signals are always accepted.2nd digit = 1: External fault signals are accepted only during
running.(Not accepted during baseblock).(3) 3rd digit, 4th digit (selection of processing at external
fault detection)4th digit 3rd digit Contents
0
0
1
1
0
1
0
1
Ramp to stop by bn-02 (major fault)
Coast to stop (major fault)
Ramp to stop by bn-04 (major fault)
Operation to continue (minor fault)
-
97
Control Mode Selection Sn-13
Valid Access LevelsParameterNo. Name
LCD Display(English) Description
FactorySetting
ChangeDuring
Operation GP SL PID PG
Sn-13 Control ModeSelect
Sn-13=00
V/F Ctrl mode
00: GPV/F Control mode
01: SLSensorless Vector Controlmode
10: PIDPID With Auyo EnergySoving Control mode
11: PGV/F+PG closed loop Controlmode
00
The four control mode can be selected by parameter Sn-13 as
below.Sn-13setting
LCD Display(English) Descriptions
00Sn-13=00
V/F Ctrl ModeGP: V/F Control mode (factory setting)
01Sn-13=01
SL Ctrl ModeSL: Sensorless Vector Control mode
10Sn-13=10
PID Ctrl ModePID: PID With Auyo Energy Soving
Control mode
11Sn-13=11
PG Ctrl ModePG: V/F+PG closed loop Controlmode
When the required control mode is selected by Sn-13 setting, the
selected controlmode functions are effective only after turning off
power supply till the display ofdigital operator (LCD or LED
digital operator) is off, then turn on the powersupply again. -
98
Protective Characteristic Selection 5 Sn-14
Valid Access LevelsParameterNo. Name
LCD Display(En
80,00 $ — 230,00 $/ шт. |1 шт./шт.(Мин. заказ)
- Преимущества:
- Быстрый возврат средств по заказам на сумму менее 1000 USDПолучить сейчас
Время выполнения заказа:
Quantity (шт.) | 1 — 10 | > 10 |
Примерное время (в днях) | 5 | Подлежит согласованию |
Сведения о покупке
Защита с помощью
Транспортировка:
Связаться с поставщиком для согласования деталей доставки
Для вас Гарантия своевременной отправки
Платежи:
Шифрование и повышенная безопасность платежей Подробнее
Возврат товаров и возмещение средств
Доступны возврат товаров и возмещение средств Подробнее
Для получения информации касательно цен, индивидуальных заказов и других вопросов:
Trading Company,Agent,Distributor/Wholesaler
CN
8