Easygen 2000 руководство

Woodward easYgen-2000 Series Application Manual

  • Contents

  • Table of Contents

  • Bookmarks

Quick Links

37429

easYgen-2000 Series

Genset Control

Application

Software Version 1.xxxx

Manual 37429

loading

Related Manuals for Woodward easYgen-2000 Series

Summary of Contents for Woodward easYgen-2000 Series

  • Page 1
    37429 easYgen-2000 Series Genset Control Application Software Version 1.xxxx Manual 37429…
  • Page 2
    Provides other helpful information that does not fall under the warning or caution categories. Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is believed to be correct and reliable. However, Woodward assumes no responsibility unless otherwise expressly undertaken.
  • Page 3: Table Of Contents

    Manual 37429 easYgen-2000 Series — Genset Control Revision History Rev. Date Editor Changes NEW 09-06-09 Release Content 1. G ………………7 HAPTER ENERAL NFORMATION 2. B ………………. 8 HAPTER ASIC PPLICATIONS Overview …………………………8 Application Mode {0} ……………………..9 Application Mode {1o} ……………………..10 Application Mode {1oc} ……………………..

  • Page 4
    Manual 37429 easYgen-2000 Series — Genset Control Connecting a Landline Modem ………………….36 Function ……………………….36 Preconditions for this Example ………………..36 Connection ……………………..37 easYgen Settings ……………………37 ToolKit Settings ……………………… 38 Phoenix Modem Settings ………………….38 Wiring Self-Powered DIs……………………40 Page 4/41 ©…
  • Page 5
    Manual 37429 easYgen-2000 Series — Genset Control Figures and Tables Figures Figure 2-1: Application mode {0} ………………………… 9 Figure 2-2: Application mode {1o} ……………………….10 Figure 2-3: Application mode {1oc} ……………………….11 Figure 2-4: Application mode {2oc} ……………………….12 Figure 3-1: Multiple genset application mode……………………… 13 Figure 3-2: Example — configuring load-dependent start stop (LM) ………………
  • Page 6
    Manual 37429 easYgen-2000 Series — Genset Control Tables Table 1-1: Manual — overview …………………………7 Table 3-1: Configuration of load-dependent start/stop………………….14 Table 3-2: Configuration of load-dependent start/stop IOP …………………. 15 Table 3-3: Configuration of load-dependent start/stop MOP ………………..15 Table 3-4: Configuration of emergency operation ……………………
  • Page 7: Chapter 1. General Information

    Series — Interfaces 37430 easYgen-2000 Series — Parameter List 37431 DE37431 easYgen-2000 Series — Brief Operation Informa- 37432 DE37332 tion Table 1-1: Manual — overview Intended Use The unit must only be operated in the manner described by this manual. The prerequisite for a proper and safe operation of the product is correct transportation, storage, and installation as well as careful oper- ation and maintenance.

  • Page 8: Chapter 2. Basic Applications

    Manual 37429 easYgen-2000 Series — Genset Control Chapter 2. Basic Applications Overview ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ NOTE Please refer to the Configuration Manual 37427 for selection of the application mode. Depending on the application, different application modes are possible. • Application mode {0} — [start/stop] — engine control — refer to page 9 — Measuring of engine/generator parameters (i.e.

  • Page 9: Application Mode {0

    Manual 37429 easYgen-2000 Series — Genset Control Application Mode {0} ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ This application mode may be used for isolated operation applications. In this case, the easYgen will function as an engine control. Figure 2-1: Application mode {0} The easYgen requires in all application modes the feedback reply from the circuit breakers. These replies are used to define, whether it controls frequency, shares the load with other gensets, or performs active load control.

  • Page 10: Application Mode {1O

    Manual 37429 easYgen-2000 Series — Genset Control Application Mode {1o} ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ This application mode may be used for isolated operation applications. In this case, the easYgen will function as an engine control with generator and engine protection. The control unit can only open the GCB.

  • Page 11: Application Mode {1Oc

    Manual 37429 easYgen-2000 Series — Genset Control Application Mode {1oc} ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ This application mode may be used in applications, where only the GCB is operated by the easYgen. If it is used for isolated or mains parallel operations, mains decoupling should be performed by the GCB or an external provi- sion.

  • Page 12: Application Mode {2Oc

    Manual 37429 easYgen-2000 Series — Genset Control Application Mode {2oc} ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ This application mode may be used for mains parallel operation. In this case, the easYgen will function as an en- gine control with generator, mains and engine protection. The control unit can open and close the GCB and the MCB.

  • Page 13: Chapter 3. Multiple Genset Applications

    Manual 37429 easYgen-2000 Series — Genset Control Chapter 3. Multiple Genset Applications Overview ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Figure 3-1: Multiple genset application mode In a multiple-unit mains parallel application, all easYgens need the same signals for: — mains voltage and current — reply signal of the MCB The open and close contacts from all controls must be wired in parallel.

  • Page 14: Configuration Example

    Manual 37429 easYgen-2000 Series — Genset Control Configuration Example ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Mains Parallel Operation (mains interchange (import/export) power control) The following example describes the configuration of a typical mains parallel operation with import/export power control at the interchange point and load-dependent start/stop.

  • Page 15: Table 3-2: Configuration Of Load-Dependent Start/Stop Iop

    Manual 37429 easYgen-2000 Series — Genset Control Configuring Load-Dependent Start/Stop Isolated Operation Additional assumptions are valid for isolated operation (IOP), i.e. in case of an emergency operation: • A reserve power of 80 kW on the busbar shall be maintained, i.e. at least 2 generators are available in iso- lated operation for redundancy because no supporting mains are present.

  • Page 16: Figure 3-3: Example — Configuring Start In Auto (Lm)

    Manual 37429 easYgen-2000 Series — Genset Control Configuring Automatic Operation From the main screen on the unit select Parameter -> Configuration -> Application config. -> Automatic run con- LogicsManager fig. and configure the function «Start req in AUTO» as shown in Figure 4-2 on page 19 to start the generator in Automatic operating mode if discrete input [DI 02] («09.02 Discrete input 2») is energized or a…

  • Page 17: Chapter 4. Special Application Examples

    Generator Excitation Protection ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The easYgen-2000 Series provides the user with power factor monitoring. These monitoring functions permit for protection of the generator over- and under-excitation. The power factor monitoring consists of a warning alarm and/or a shutdown alarm when enabled. An alarm and the specified action will be initiated if the monitored pow- er factor surpasses the defined limits.

  • Page 18: Configuring A Set Point Control Via Analog Input

    Manual 37429 easYgen-2000 Series — Genset Control Configuring a Set Point Control via Analog Input ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The following example illustrates how to configure an easYgen for using an external load set point via analog in- put [AI 03]. The external set point may be enabled using a switch, wired to discrete input [DI 04] (configure pa- rameter 1262 “Alarm class”…

  • Page 19: Viewing The Load Set Point On The Easygen

    Manual 37429 easYgen-2000 Series — Genset Control LogicsManager Configure the function «Setp. 2 load» as shown in Figure 4-2 on page 19 to enable load setpoint 2 if discrete input [DI 04] is energized. Figure 4-2: Example — configuring load setpoint 2 for [DI 04] Viewing the Load Set Point on the easYgen After the unit is configured as described above, the «Setpoint»…

  • Page 20: Creating Self-Toggling (Pulsing) Relays Using Logicsmanager

    Manual 37429 easYgen-2000 Series — Genset Control Creating Self-Toggling (Pulsing) Relays Using LogicsManager ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Various functions are possible with the LogicsManager. This is a simple example of a relay output that toggles from energized to de-energized in automatic mode with adjustable on and off time. This pulsing relay may be combined with a flexible limit, which can be programmed with a function like low battery voltage to get a blink- ing warning light.

  • Page 21: Performing Remote Start/Stop And Acknowledgement

    Series — Genset Control Performing Remote Start/Stop and Acknowledgement ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The easYgen-2000 Series controller can be configured to perform start/stop/acknowledgement functions remotely through the CAN bus or Modbus. The required procedure is described in the following steps. NOTE Refer to the operation manual 37428 for a detailed description of the navigation through the various display screens.

  • Page 22: Setting Up A Test With Or Without Load

    Setting Up a Test With or Without Load There are a lot of different opinions of the behavior of a proper test mode. The easYgen-2000 Series can support the following two modes: Test with load and test without load. Both modes work only in automatic mode. The correct test mode depends on your local specifications.

  • Page 23: Figure 4-10: Configuration — Flag 2 (Timer)

    Manual 37429 easYgen-2000 Series — Genset Control Example for test without load: The engine shall start once a month and run for one hour without overtaking the load. The test day shall be every fifteenth of a month (with flag 2). A relay output can be configured that this test is running, e.g.

  • Page 24: Remote Start/Stop And Acknowledgement

    Manual 37429 easYgen-2000 Series — Genset Control Remote Start/Stop and Acknowledgement The easYgen may be started, stopped, or acknowledged with Modbus or CAN protocol via the interface. Two logical command variables are available for this in the LogicsManager: 04.13 Remote request 04.14…

  • Page 25: Figure 4-13: Example — Remote Acknowledgement

    Manual 37429 easYgen-2000 Series — Genset Control External Acknowledgement Navigate to the «Configure automatic run» screen by pressing the following softkeys in this sequence: Parameter -> Configuration -> Monitoring config. -> Miscellaneous Navigate to the entry «Ext. acknowledge» by using the softkeys and press to enter the «Ext.

  • Page 26: Bit Enabling Via Modbus Protocol And Rs-485 Interface

    Manual 37429 easYgen-2000 Series — Genset Control The following figure shows the reaction of the command variable on the various changes of the bits: Start bit Stop bit Com. var. 04.13 Remote request no reaction, stops, because because simultanous higher prioritized…

  • Page 27: Connecting An Ikd 1 On Can Bus 1

    Connecting an IKD 1 on CAN Bus 1 ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ We recommend to connect external expansion boards, like the Woodward IKD 1 to CAN bus 2. This CAN bus offers preconfigured settings for operating several expansion boards including the IKD 1.

  • Page 28: Ikd 1 Configuration

    Manual 37429 easYgen-2000 Series — Genset Control Receive PDO The easYgen must be configured for receiving data on an RPDO. The data received on CAN ID 201h is inter- preted as object with the index 8011 (external DIs 1 to 8). For this, RPDO1 must be configured as follows:…

  • Page 29: Baudrate Configuration

    Manual 37429 easYgen-2000 Series — Genset Control Baudrate Configuration The baud rate must be configured identical in the easYgen and the IKD 1. The following example shows the con- figuration of both units to 250 kBd: Figure 4-18: Configuration of the baud rate ©…

  • Page 30: Configuration For A Second Ikd 1

    Manual 37429 easYgen-2000 Series — Genset Control Configuration for a Second IKD 1 If a second IKD 1 shall be connected to the easYgen, the following settings must be made to TPDO2 and RPDO2 in the easYgen: Figure 4-19: Configuration of the easYgen for a second IKD 1…

  • Page 31: Configuring A Pwm Duty Cycle For A Cat Adem Controller

    Manual 37429 easYgen-2000 Series — Genset Control Configuring a PWM Duty Cycle for a CAT ADEM Controller ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ If a PWM signal shall be used with a CAT ADEM speed controller, the duty cycle must be limited between 10% and 85%. For this, the following settings must be made to the respective analog output (the following parameter IDs and figures refer to analog output 1;…

  • Page 32: Connecting A Gsm Modem

    Manual 37429 easYgen-2000 Series — Genset Control Connecting a GSM Modem ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Figure 4-22: Connecting a GSM modem Function It is possible to establish a cellular connection to the system using a GSM modem. This application is intended for mobile use. It is also interesting to trigger a call in case of an alarm with this application. The GSM modem provides a discrete input for this, which can trigger e.g.

  • Page 33: Connection

    Manual 37429 easYgen-2000 Series — Genset Control If a different modem is used, this has to accept incoming calls automatically and establish a connec- tion between calling PC and easYgen. Connection It is possible to issue an active call in case of a malfunction using a relay of the relay manager. Connect the ea- sYgen and the modem with the power supply as directed.

  • Page 34: Toolkit Settings

    Manual 37429 easYgen-2000 Series — Genset Control ToolKit Settings In ToolKit, select Connect… from the Device menu to open the Communications window. Select the modem (this must be installed and configured under Windows) from the network list, enter the phone number and click the Connect button to establish a connection with the modem.

  • Page 35: Figure 4-26: Configuring Alarm Input 1 In The Gsm Modem Software

    Manual 37429 easYgen-2000 Series — Genset Control Make the following settings on the Alarm/Output 1 tab. The phone number and the text can be set as required. Figure 4-26: Configuring alarm input 1 in the GSM modem software Make the following settings on the Alarm/Output 2 tab. The phone number and the text can be set as required.

  • Page 36: Connecting A Landline Modem

    Manual 37429 easYgen-2000 Series — Genset Control Connecting a Landline Modem ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Figure 4-28: Connecting a landline modem Function It is possible to establish a phone connection to the system using a modem. This application is intended for sta- tionary use, where a steady remote control is required.

  • Page 37: Connection

    Manual 37429 easYgen-2000 Series — Genset Control Connection It is possible to issue an active call in case of a malfunction using a relay of the relay manager. Connect the ea- sYgen and the modem with the power supply as directed.

  • Page 38: Toolkit Settings

    Manual 37429 easYgen-2000 Series — Genset Control ToolKit Settings In ToolKit, select Connect… from the Device menu to open the Communications window. Select the modem (this must be installed and configured under Windows) from the network list, enter the phone number and click the Connect button to establish a connection with the modem.

  • Page 39
    Manual 37429 easYgen-2000 Series — Genset Control To configure the modem, proceed as follows. Configure the COM port The phone number and the text can be set as required. These settings configure the modem to accept an incoming call for remote configuration.
  • Page 40: Wiring Self-Powered Dis

    Manual 37429 easYgen-2000 Series — Genset Control Wiring Self-Powered DIs ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ In order to create self-powered discrete inputs, it is required to connect battery negative (B-) to ground and func- tion earth (terminal 55). Moreover, DI common (terminal 43) must be connected to Power supply 12/24 V (ter- minal 53, minimum wire size 0.5 mm²…

  • Page 41
    Phone +49 (0) 711 789 54-0 • Fax +49 (0) 711 789 54-100 stgt-info@woodward.com Homepage http://www.woodward.com/power Woodward has company-owned plants, subsidiaries, and branches, as well as authorized distributors and other authorized service and sales facilities throughout the world. Complete address/phone/fax/e-mail information for all locations is available on our website (www.woodward.com).

Manual 37427

WARNING

Read this entire manual and all other publications pertaining to the work to be performed before

installing, operating, or servicing this equipment. Practice all plant and safety instructions and

precautions. Failure to follow instructions can cause personal injury and/or property damage.

The engine, turbine, or other type of prime mover should be equipped with an overspeed

(overtemperature, or overpressure, where applicable) shutdown device(s), that operates totally

independently of the prime mover control device(s) to protect against runaway or damage to the

engine, turbine, or other type of prime mover with possible personal injury or loss of life should the

mechanical-hydraulic governor(s) or electric control(s), the actuator(s), fuel control(s), the driving

mechanism(s), the linkage(s), or the controlled device(s) fail.

Any unauthorized modifications to or use of this equipment outside its specified mechanical, electrical,

or other operating limits may cause personal injury and/or property damage, including damage to the

equipment. Any such unauthorized modifications: (i) constitute «misuse» and/or «negligence» within

the meaning of the product warranty thereby excluding warranty coverage for any resulting damage,

and (ii) invalidate product certifications or listings.

CAUTION

To prevent damage to a control system that uses an alternator or battery-charging device, make sure

the charging device is turned off before disconnecting the battery from the system.

Electronic controls contain static-sensitive parts. Observe the following precautions to prevent

damage to these parts.

Discharge body static before handling the control (with power to the control turned off, contact a

grounded surface and maintain contact while handling the control).

Avoid all plastic, vinyl, and Styrofoam (except antistatic versions) around printed circuit boards.

Do not touch the components or conductors on a printed circuit board with your hands or with

conductive devices.

OUT-OF-DATE PUBLICATION

This publication may have been revised or updated since this copy was produced. To verify that you

have the latest revision, be sure to check the Woodward website:

http://www.woodward.com/pubs/current.pdf

The revision level is shown at the bottom of the front cover after the publication number. The latest

version of most publications is available at:

http://www.woodward.com/publications

If your publication is not there, please contact your customer service representative to get the latest

copy.

Important definitions

WARNING

Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.

CAUTION

Indicates a potentially hazardous situation that, if not avoided, could result in damage to equipment.

NOTE

Provides other helpful information that does not fall under the warning or caution categories.

Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is believed to be

correct and reliable. However, Woodward assumes no responsibility unless otherwise expressly undertaken.

Page 2/339

© Woodward

All Rights Reserved.

easYgen-2000 Series — Genset Control

© Woodward

Woodward easYgen-2000 Series: Available Instructions

Note for Owners:

Guidesimo.com webproject is not a service center of Woodward trademark and does not carries out works for diagnosis and repair of faulty Woodward easYgen-2000 Series equipment. For quality services, please contact an official service center of Woodward company. On our website you can read and download documentation for your Woodward easYgen-2000 Series device for free and familiarize yourself with the technical specifications of device.

  • Penn P545 Series

    Product/Technical Bulletin Issue Date September 2018 © 2018 Johnson Controls 1 Code No. LIT-12011012 www.penncontrols.com Part No. 24-7664-2616, Rev. D P545 Series Electronic Lube Oil Control The P545 Series Electronic Lube Oil Control is designed for use on refrigeration compressors equipped with an oil pump that accepts a single-point differential pressure switch. The P400 switch cont …

    P545 Series Control Panel, 13

  • REMEHA Gas 310 ECO

    1• Gebruikersvoorschrift• User guidelines• Notice d’utilisation• BedienungsanleitungRemeha Gas 310/610 ECOGebruikersvoorschriftUser guidelinesNotice d’utilisationBedienungsanleitungRemeha Gas 310/610 ECO …

    Gas 310 ECO Boiler, 20

  • Chamberlain 935EV

    1To prevent possible SERIOUS INJURY or DEATH from electrocution:• Be sure power is NOT connected BEFORE installing door control.• Connect ONLY to 24 VOLT low voltage wires. To prevent possible SERIOUS INJURY or DEATH from a closing garage door:• Install door control within sight of garage door, out of reach of children at a minimum height of 5 feet (1.5 m), and away from ALL moving par …

    935EV Control Panel, 4

  • Siemens F IWLAN

    Wireless Teach Pendant F IWLAN V2 ________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ SIMATIC HMIHMI device Wireless Teach Pendant F IWLAN V …

    F IWLAN Telephone Accessories, 100

  • BFT P7

    ISTRUZIONI D’USO E DI INSTALLAZIONEINSTALLATION AND USER’S MANUALINSTRUCTIONS D’UTILISATION ET D’INSTALLATIONINSTALLATIONS-UND GEBRAUCHSANLEITUNGINSTRUCCIONES DE USO Y DE INSTALACIONINSTRUÇÕES DE USO E DE INSTALAÇÃOAttenzione! Leggere attentamente le “Avvertenze” all’interno! Caution! Read “Warnings” inside carefully! Attention! Veuillez lire attentivement les Avertissements …

    P7 Gate Opener, 32

Popular Control Panel User Guides:

5 docs – User Manuals, Help Guides and Specs – for the Woodward easYgen-2000 Series product are present in our data base.

Tips for Finding Manuals:

This web-page provides a list of 5 accessible operating manuals and information books describing Woodward easYgen-2000 Series.
All manuals and instructions for Woodward easYgen-2000 Series are introduced in an easy-to-use PDF format and may be gratuitously downloaded or looked through directly from the site.

The page offers the following types of manuals: Control Panel, Control Unit.

Helpful hints: While selecting a necessary guide for Woodward easYgen-2000 Series one should pay special attention to the type of the document.
We try to supply you with the fullest possible set of papers we or our users are able to find. These may be overviews and specifications of the device, mounting and installing instructions, the unit operating rules and maintenance regulations and much more.

Haven’t found a required manual for your Woodward easYgen-2000 Series?

Check in a while. We update our guides collection and add new documents on a daily basis for you to be always able to find the very paper you need on our web-site. In case you own a directory or an instruction for Woodward easYgen-2000 Series, which is absent on our site, and you’d like to share it with the public, please send it to us as a scanned copy or a PDF file, and we’ll definitely place it on our page while providing your name as a supplier of the doc. Lots of our users will be grateful for your assistance!

Контроллеры управления генераторами easYgen-2000 — это серия контроллеров, которая предназначена для контроля и защиты генераторных установок, распределения нагрузки между генераторными установками (до 16 шт.) в режиме изолированной сети или с параллельным подключением одного модуля к промышленной сети. Серия easYgen-2000 позволяет пользователю программировать запуск и остановку в зависимости от нагрузки, а так же позволяет пользователю определять принцип подключения генераторных установок к сети и их отключения с целью реагирования на изменение нагрузки. Обеспечивает нужный вращающий момент, для оптимизации расхода топлива. Расширенные возможности интерфейса обеспечивают обмен данными управления генераторной установки и связь с ПК в любой точки мира.

Основные преимущества:

  • Распределение нагрузки между генераторными установками (до 16 шт.);
  • Контроль 0, 1 или 2 выключателей, переключение с разрывом и без разрыва цепи, обеспечивает синхронизацию генератора с сетью и обеспечивает плавный пуск;
  • Сертификаты: CE, UL/cUL & LR Marine, ГОСТ Р;
  • Доступно программирование логики для контроля сложных схем;
  • Поддерживает русский язык;
  • Полная защита питания и мониторинг основного источника питания;
  • Поддержка асинхронных и синхронных генераторов;
  • Позволяет выставлять требующиеся значения оборотов, частоты, напряжения, активной мощности, реактивной мощности и коэффициента мощности с помощью аналоговых входов или интерфейса;
  • Удалённое управление по средствам интерфейса или дискретных выходов;
  • Измерения 120 В и 480 В действующего напряжения, измерение действующего тока, счётчик кВт/ч генератора;
  • Возможность подключения дополнительных элементов таких как: прибор контроля температур; карта расширения IKD-1; зарядные устройства BL; модуль распределения нагрузки с генераторными установками оборудованными панелями других производителей.

Технические характеристики:

Наименование характеристики Значение
Напряжение питания, VDC 12/24 (от 8 до 40)
Потребляемая мощность (2200/2500), Вт макс 8/12
Температура хранения, °С от -30 до +80
Температура использования, °С от -20 до +70
Влажность, % не более 95
Входное переменное напряжение, VАС 120 и 480
Точность Класс 1
Входной ток, А 1 или 5
Дискретные входы, В DC 12/24 (от 8 до 40)
Ток активной нагрузки (при 24 DС и 250 V АС), A 2
Аналоговые входы От 0 до 500 Ом, от 0 до 20 мА
Аналоговые выходы ± 10 В / ± 20 мА / ШИМ
Релейные выходы Сухие контакты
Корпус Пластиковый
Степень защиты IP65/IP20
Размеры (Ш/В/Г) (2200/2500), мм 219/171/61 / 219/171/98
Вес (2200/2500), г 800/1100
Модель easYgen-2200 (P1/P2) easYgen-2500
Блок защиты памяти +/- +
Дискретные входы 8/8 10
Релейные выходы 6/6 11
Аналоговые входы 3/3 4
Аналоговые выходы 1/1 4
Шина CAN интерфейса 1/1 2
RS-485 интерфейс -/-т +
Номер заказа
1 А 8440-1856/8440-1858 8440-1860
5 А 8440-1855/8440-1857 8440-1884

Понравилась статья? Поделить с друзьями:
  • Мануал по рейке мерседес
  • Окко отменить подписку пошаговая инструкция на телефоне
  • Инструкция пылесоса ilife v50 по эксплуатации робота
  • Аскорил инструкция по применению для детей аналоги
  • Нош па инструкция по применению цена отзывы аналоги таблетки цена