ECL Comfort 110
Application 130
Weather compensated flow temperature
control of heating and boiler systems
User guide,
Installation & Maintenance
VI.KT.G2.02
DH-SMT/DK
© Danfoss 05/2007
Related Manuals for Danfoss ECL Comfort 110
Summary of Contents for Danfoss ECL Comfort 110
-
Page 1
Instructions ECL Comfort 110 Application 130 Weather compensated flow temperature control of heating and boiler systems User guide, Installation & Maintenance VI.KT.G2.02 DH-SMT/DK © Danfoss 05/2007… -
Page 2
The warning sign is used to emphasize special conditions that should be taken into consideration. This symbol indicates that this particular piece of information should be read with special attention. VI.KT.G2.02 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK DH-SMT/DK © Danfoss 05/2007… -
Page 3: Table Of Contents
Electrical connections — 24 V a.c. — in general Connecting the temperature sensors and the ECL BUS How to identify your system type Adapting the ECL Comfort 110 controller Manual control Placing the temperature sensors Connecting the room panel / remote control Checklist, electrical connections …………..45…
-
Page 4: Vi.kt.g2.02 © Danfoss
3183 Limit (return temp. limitation) 4030 18 50 °C Basic principles of application 130 for ECL Comfort 110 Gain — max. (return temp. limitation — max. influence) 4035 19 -2.0 Typically, the flow temperature is always adjusted according to your requirements.
-
Page 5: Vi.kt.g2.02 © Danfoss
Temperature overview 2 sec. Push the button to see the sensor (S1-S4) temperatures. It is only possible to set the personal schedules if the ECL Comfort 110 controller has a built-in ECA 110 timer program. Change between the temperature displays: ����������������…
-
Page 6
It is only necessary to set the correct date and time in connection with the first use of the change the start of this period. ECL Comfort 110 controller or after a power break of more than 36 hours (see the chapter Adapting the ECL Comfort 110 controller). -
Page 7
For quick setting, the graph can be used. The graph is intended for a T of 20 °C. If the room design data from example I is used, the slope will be approx. 1.7. VI.KT.G2.02 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK DH-SMT/DK © Danfoss 05/2007… -
Page 8
The ‘Gain — max.’ is set to -4.0. The ‘Gain — min.’ is set to 0.0. The ‘Slope’ is 1.8. Result: The desired flow temperature is changed by 2 x -4.0 x 1.8 = -14.4 degrees. VI.KT.G2.02 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK DH-SMT/DK © Danfoss 05/2007… -
Page 9
The ‘Gain — max.’ is set to -3.5. The ‘Gain — min.’ is set to 2.0. The ‘Slope’ is 1.8. Result: The desired flow temperature is changed by 2 x (-3.5) x 1.8 = -12.6 degrees. VI.KT.G2.02 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK DH-SMT/DK © Danfoss 05/2007… -
Page 10
The desired flow temperature is increased, when the return temperature gets below the set limit. Influence lower than 0: The desired flow temperature is decreased, when the return temperature gets below the set limit. VI.KT.G2.02 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK DH-SMT/DK © Danfoss 05/2007… -
Page 11
(line 5014). If a room temperature sensor or a room panel / remote control is connected, the boost stops when the room temperature is reached. VI.KT.G2.02 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK DH-SMT/DK © Danfoss 05/2007… -
Page 12
5014 Setting range Factory setting It is only possible make use of ‘Optimize’ if the ECL Comfort 110 controller has a built-in ECA OFF / 10 … 59 110 timer program or is connected to an ECA 61 / 63. -
Page 13
S1 T filter (outdoor temp. filter) 5081 Setting range Factory setting 1 … 200 Dampens the measured outdoor temperatures by the set factor. Fast (low filter constant) 200: Slow (high filter constant) VI.KT.G2.02 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK DH-SMT/DK © Danfoss 05/2007… -
Page 14
5 … 250 sec. 35 sec. ‘M1 run’ is the time it takes the controlled unit to move from fully closed to fully open position. Set the ‘M1 run’ according to the example. VI.KT.G2.02 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK DH-SMT/DK © Danfoss 05/2007… -
Page 15: Application
Factory setting GEAR / ABV GEAR Choose the actuator type for your valve. GEAR: Gear motor ABV: Thermo actuator (Danfoss type ABV) Control parameters (lines 6174-6187) are overruled if thermo actuator is chosen (ABV). VI.KT.G2.02 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK DH-SMT/DK…
-
Page 16: Dhw Prior. (Closed Valve / Normal Operation) 7052
SETBACK: The controller is in setback mode when terminals 11 and 12 are short- circuited. COMFORT: The controller is in comfort mode when terminals 11 and 12 are short- circuited. VI.KT.G2.02 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK DH-SMT/DK © Danfoss 05/2007…
-
Page 17: Knee Point 7162
Start the chosen application. Factory settings are restored. All personal settings will be deleted. It is recommended to make a note of your personal settings in the ‘Settings overview’ for future use. VI.KT.G2.02 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK DH-SMT/DK © Danfoss 05/2007…
-
Page 18: Service 8000
OFF: No backlight. Weak backlight. Strong backlight. Contrast (display contrast) 8311 Setting range Factory setting 0 … 20 The contrast of the display can be adjusted. High contrast Low contrast VI.KT.G2.02 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK DH-SMT/DK © Danfoss 05/2007…
-
Page 19: Installation
93 x 139 mm. Insert the controller into the panel cut-out and fix it with the clamp which Incorrect connection can damage the TRIAC outputs. is placed horisontally on the controller. Establish the electrical connections. For further details on mounting, see the mounting guide. VI.KT.G2.02 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK DH-SMT/DK © Danfoss 05/2007…
-
Page 20: Electrical Connections — 24 V A.c. — In General
Relay R2 4 (2) A Cable lengths of more than 125 m may cause noise sensibility (EMC). Wire cross section: 0.5 — 1.5 mm Incorrect connection can damage the TRIAC outputs. VI.KT.G2.02 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK DH-SMT/DK © Danfoss 05/2007…
-
Page 21: How To Identify Your System Type
How to identify your system type Adapting the ECL Comfort 110 controller When you switch on the controller the first time, it will ask you to choose language The ECL Comfort controller is a universal controller that can be used for various systems.
-
Page 22: Manual Control
Flow temperature sensor (ESMU, ESM-11 or ESMC) Place the sensor max. 15 cm from the mixing point. In systems with heat exchanger, 5 sec. Danfoss recommends that the ESMU-type to be inserted into the exchanger flow outlet. Go to manual mode. Actuator M1 is opening ( �����������…
-
Page 23: Connecting The Room Panel / Remote Control
The BUS is activated by setting the controller address to 15 (line 7199). etc.) start and stop when operated manually. Check that the temperatures shown in the display match the actual sensors. VI.KT.G2.02 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK DH-SMT/DK © Danfoss 05/2007…
-
Page 24: Frequently Asked Questions
Humidity, relative This value (stated in %) refers to the indoor moisture content compared to the max. moisture content. The relative humidity is measured by the ECA 62 / 63. VI.KT.G2.02 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK DH-SMT/DK © Danfoss 05/2007…
-
Page 25: Definitions
The definitions apply to the Comfort 110 series. Consequently, you might come across It must be collected separately with other electrical and electronic waste according to expressions that are not mentioned in your guide. local legislation. VI.KT.G2.02 VI.KT.G2.02 © Danfoss 05/2007 DH-SMT/DK DH-SMT/DK © Danfoss 05/2007…
-
Page 26
*VIKTG202* Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
Архивная серия
Товары серии сняты с продажи
ECL Comfort 110 — это электронный одноконтурный регулятор, предназначенный для регулирования температуры подачи в системе теплоснабжения или регулирования постоянной температуры в системе ГВС.
Помимо регулирования температуры ECL 110 позволяет оптимизировать систему, ограничить температуру возвращаемого теплоносителя, а при помощи встроенного таймера значительно увеличить энергосбережение. Также имеются защитные функции, такие как защита от замерзания или защита от блокировки регулирующего клапана и насоса.
Регулятор имеет симисторные выходы для электроприводов регулирующих клапанов и релейные выходы для управления насосом, а также текстовый дисплей с подсветкой.
ECL Comfort 110 не требует отдельной клеммной панели, регулятор может быть смонтирован на DIN-рейке или на стене, а при помощи комплекта для монтажа его можно установить в вырез шкафа автоматизации.
Также нет нужды приобретать ключи управления для ECL Comfort 110, в регуляторе уже предустановлены приложения для управления системой отопления (приложение 130) и управления системой ГВС с емкостным или скоростным подогревателем (приложение 116).
Документация>>
Бренд:
Danfoss
Обсудить в Community
Товары серии
Название и артикул |
---|
087B1249 Комплект для монтажа ECL 110 в вырезе шкафа |
||
|
Подпишитесь на наши новости
Первыми получайте уведомления о наших новостях в рассылке
перейти к содержанию
Руководство по установке приводов переменного тока и органов управления Danfoss ECL Comfort 110
Руководство по установке
ЭКЛ Комфорт 110
ЭКЛ Комфорт 110
Руководство по установке, ECL Comfort 110
230 В переменного тока
24 В переменного тока
ЕС-декларация соответствия
Перейти к:
https://store.danfoss.com/en/
Выберите: ECL Comfort 110 > Документы > Декларация ЕС:
https://assets.danfoss.com/approvals/188967/ID389638298581-0101.pdf or
Декларация Великобритании:
https://assets.danfoss.com/approvals/188970/ID389638299582-0101.pdf
?ECL Комфорт 110: www.heating.danfoss.com
?https://www.youtube.com/user/DanfossHeating -> Плейлисты -> Видео с практическими рекомендациями -> Видео по установке районного энергоснабжения
БАРНЫЙ КОД
Документы / Ресурсы
Рекомендации