Emotron tsa руководство по эксплуатации

CG emotron TSA Series Instruction Manual

  1. Manuals
  2. Brands
  3. CG Manuals
  4. Controller
  5. emotron TSA Series
  6. Instruction manual

  • Contents

  • Table of Contents

  • Troubleshooting

  • Bookmarks

Quick Links

Emotron TSA

Softstarter

Instruction manual

English

Valid from Software version 1.27

loading

Related Manuals for CG emotron TSA Series

Summary of Contents for CG emotron TSA Series

  • Page 1
    Emotron TSA Softstarter Instruction manual English Valid from Software version 1.27…
  • Page 3
    Date of release: 28-01-2017 © Copyright CG Drives & Automation Sweden AB 2013-2017 CG Drives & Automation Sweden AB retains the right to change specifications and illustrations in the text, without prior notification. The contents of this document may not be copied without the explicit…
  • Page 5: Safety Instructions

    Safety instructions Phase compensation capacitor Congratulations for choosing a product from CG Drives & Automation! If a phase compensation capacitor is to be used, it must be Before you begin with the installation, commissioning or connected at the inlet of the softstarter, not between the powering up the unit for the first time it is very important motor and the softstarter.

  • Page 6
    CG Drives & Automation 01-5980-01r2…
  • Page 7: Table Of Contents

    4.4.13 Other control voltage ……….37 8.1.1 1st Line [110]…………69 8.1.2 2nd Line [120] …………69 Getting started……….39 Main Setup [200]………… 69 Check list …………..39 8.2.1 Operation setup [210] ……….69 Mains and motor connection ……… 39 CG Drives & Automation 01-5980-01r2…

  • Page 8
    Process value …………140 Description of the EInt formats ……141 Softstarter theory ……..143 10.1 Background theory……….143 10.2 Reduced voltage starting……..145 10.3 Other starting methods……… 147 10.4 Use of softstarters with torque control ….148 CG Drives & Automation 01-5980-01r2…
  • Page 9: Introduction

    The Quick Start Guide can be put in a cabinet so that it is always easy to access in case of an emergency. — =Standard (Grounded Supply type net) I=IT-net (EMC not fulfilled) Brand label A=Standard Software A=Standard software — =CE approved Standard U=UL/cUL approved CG Drives & Automation 01-5980-01r2 Introduction…

  • Page 10: Standards

    The recycling of materials will help to conserve natural resources. For more detailed information about recycling this product, please contact the local distributor of the product. Introduction CG Drives & Automation 01-5980-01r2…

  • Page 11: Glossary

    ——————————————— — lb ft UInt Communication format (Unsigned Integer) n mot Communication format (Integer) Long Communication format (Integer Long) SELV Safety Extra Low Voltage The function cannot be changed in run mode CG Drives & Automation 01-5980-01r2 Introduction…

  • Page 12
    Introduction CG Drives & Automation 01-5980-01r2…
  • Page 13: Mounting

    Minimum free space WARNING! Never operate the softstarter with the front Minimum free space cover removed. mm (in) Frame size above* below at side (3.9) (3.9) *) Above: Cabinet roof to softstarter or softstarter to softstarter CG Drives & Automation 01-5980-01r2 Mounting…

  • Page 14: Mechanical Specifications And Drawings

    H3 = Total height including Cable covers. Emotron TSA frame size 1 — 2 Fig. 3 Dimensions for Emotron TSA frame size 1 and 2, bottom view. Fig. 2 Dimensions for Emotron TSA frame size 1 and 2. Mounting CG Drives & Automation 01-5980-01r2…

  • Page 15
    Emotron TSA frame size 3 196 (7.7) 235 (9.3) Fig. 4 Dimensions for Emotron TSA frame size 3. Fig. 5 Dimensions for Emotron TSA frame size 3, bottom view. CG Drives & Automation 01-5980-01r2 Mounting…
  • Page 16
    Emotron TSA frame size 4 254 (10) 260 (10.3) Fig. 6 Dimensions for Emotron TSA frame size 4 . Fig. 7 Dimensions for Emotron TSA frame size 4, bottom view. Mounting CG Drives & Automation 01-5980-01r2…
  • Page 17: Mounting Schemes

    On our websites www.cgglobal.com and www.emotron.com Ø 13 it is possible to download a full-size template for positioning of the fixing holes. Ø 7 (x 4) Fig. 9 Hole pattern for Emotron TSA frame size 3. CG Drives & Automation 01-5980-01r2 Mounting…

  • Page 18
    Mounting CG Drives & Automation 01-5980-01r2…
  • Page 19: Connections

    Fig. 11 Mains, motor and control supply voltage connection NOTE: The Emotron TSA control-board is equipped with a ground plane to which shielded cables can be connected (see Fig. 17 on page 21). NOTE: For UL-approval use 75°C copper wire only. CG Drives & Automation 01-5980-01r2 Connections…

  • Page 20
    Full voltage can be detected if no motor is connected. Table 7 Tightening torque for bolts [Nm (Lb-in)]. Tightening torque for bolts [Nm (Lb-in)] Frame size Motor or mains PE cable cables 8 (70) 5 (44) 8 (70) 5(44) Connections CG Drives & Automation 01-5980-01r2…
  • Page 21
    Full voltage can be detected if no motor is connected. Table 8 Tightening torque for bolts [Nm (Lb-in)]. Tightening torque for bolts [Nm (Lb-in)] Frame size Motor or mains PE cable cables 20 (177) 12 (106) CG Drives & Automation 01-5980-01r2 Connections…
  • Page 22
    Full voltage can be detected if no motor is connected. Table 9 Tightening torque for bolts [[Nm (Lb-in)]. Tightening torque for bolts [Nm (Lb-in)] Frame size Motor or mains PE cable cables 50 (442) 12 (106) Connections CG Drives & Automation 01-5980-01r2…
  • Page 23: Busbar Distances On Emotron Tsa Softatarter

    44 (0.9) 83 (3.27) 83 (3.27) 3.1.2 Cable covers When the Mains and motor cables are connected, mount the cable covers according to Fig. 16. Fig. 16 How to mount the cable covers general drawing. CG Drives & Automation 01-5980-01r2 Connections…

  • Page 24: Board Layout And Connectors

    WARNING! For softstarters rated higher than 525 VAC, it is mandatory to have at least basic insulation from the temperature sensor towards live voltage. Connections CG Drives & Automation 01-5980-01r2…

  • Page 25
    Solid: 2.5 (27) 8. Terminals for DigIn/AnIn/AnOut signals (control board) * When using Ferrules, suitable Ferrule length is 10-12 mm/ 0.39 — 0.47 in. 9. Terminals for relay output signals and PTC connection (power board) CG Drives & Automation 01-5980-01r2 Connections…
  • Page 26: Control Signal Connections

    Analogue output. Factory setting is “Current”. 0-20 mA and 4-20 mA; max load impedance 500 Ω +24 VDC ±5%. Max. current from +24 VDC = 50 mA. Control signal supply 2, voltage to digital input. Short circuit-proof and overload-proof. Connections CG Drives & Automation 01-5980-01r2…

  • Page 27: Wiring Examples

    • If required, connect relay R1 (terminals 21 and 22) to the contactor – the softstarter then controls the mains contactor (for factory configuration of R1 see menu [551]). Always ensure the installation complies with the appropriate local regulations. CG Drives & Automation 01-5980-01r2 Connections…

  • Page 28
    Relay 2 Relay 3 Run FWD Stop DigIn 1 DigIn 2 +10 V AnIn DigIn 3 DigIn 4 +24 V AnOut +24 V Fig. 20 Separate Start- Stop-signals ( 3-wire connection) wir- ing example. Connections CG Drives & Automation 01-5980-01r2…
  • Page 29
    Relay 2 Relay 3 Stop Run FWD DigIn 1 DigIn 2 +10 V AnIn DigIn 3 DigIn 4 +24 V AnOut +24 V Fig. 21 Common Start- Stop-signals ( 2-wire connection) wir- ing example. CG Drives & Automation 01-5980-01r2 Connections…
  • Page 30
    Relay 2 Relay 3 Run FWD DigIn 1 DigIn 2 +10 V AnIn DigIn 3 DigIn 4 +24 V AnOut +24 V Fig. 22 Common Start- Stop-signals ( 2-wire connection) wir- ing example, Level control. Connections CG Drives & Automation 01-5980-01r2…
  • Page 31
    +24 V Reset Run FWD Pressure 0 — 10 bar Current 0 — I 4 — 20 mA 4 — 20 mA Fig. 23 Extended wiring example, using digital and analogue inputs and outputs. CG Drives & Automation 01-5980-01r2 Connections…
  • Page 32
    Relay 1 Relay 2 Relay 3 DigIn 1 DigIn 2 +10 V AnIn DigIn 3 DigIn 4 +24 V AnOut +24 V Run FWD Stop Fig. 24 Reverse current brake wiring example. Connections CG Drives & Automation 01-5980-01r2…
  • Page 33
    Relay 2 OperationREV avoided. Relay 1 Relay 2 DigIn 1 DigIn 2 +10 V AnIn DigIn 3 DigIn 4 +24 V AnOut +24 V Run FWD Stop Run REV Fig. 25 Connection for start forward/reverse. CG Drives & Automation 01-5980-01r2 Connections…
  • Page 34
    If both DigIn 1 “RunFWD” and DigIn 3 “RunREV” are closed at the same time, a stop is performed according to the stop settings in menu group [340]. In this case no start will be allowed. Connections CG Drives & Automation 01-5980-01r2…
  • Page 35: Application Guidelines

    70 A with a start current ratio of 3.0 x FLC (210 A) for 30 seconds, and with a 330 seconds (5.5 minutes) interval between starts (current via bypass contactors). CG Drives & Automation 01-5980-01r2 Application guidelines…

  • Page 36
    Bandsaw Chipper Circular saw Lumber & Wood Debarker Planer Sander Ball mill Centrifuge Petrochemical Extruder Screw conveyor Ball mill Grinder Material conveyor Palletiser Transport & Machine Press Roller mill Rotary table Trolley Escalator Application guidelines CG Drives & Automation 01-5980-01r2…
  • Page 37: The Application Functions List

    This column guides you to the menu, menu group, or manual section where you find a description of the settings for the function. For instance «331=Sqr Torq Ctr», means: set menu [331] to “Sqr Torq Ctr.” CG Drives & Automation 01-5980-01r2 Application guidelines…

  • Page 38
    344=Rev Curr Brk Conveyor speed set from planer shaft High speed lines power analogue output. Worn out tool Use load monitor maximum alarm Broken coupling Use load monitor minimum alarm Application guidelines CG Drives & Automation 01-5980-01r2…
  • Page 39
    Torque boost in beginning of ramp. Jamming Use load monitor maximum alarm HAMMER MILL Reverse current brake with reversing 341=Brake Fast stop contactor for heavy loads. 344=Rev Curr Brk Motor blocked Locked rotor function CG Drives & Automation 01-5980-01r2 Application guidelines…
  • Page 40: Special Conditions

    For instance, the start ramp can only be set for an average starting ramp for all the connected motors. This means that the start time may differ from motor to motor. Similarly, the load monitor alarm levels/margins are applied for the Application guidelines CG Drives & Automation 01-5980-01r2…

  • Page 41: Earthing System

    Emotron TSA should be configured for IT-net supply type. The unit will then not fulfil the EMC requirements. If you have a softstarter without IT net supply type, the softstarter can be rebuilt. Contact your local CG Drives & Automation service partner. 4.4.12 Earth fault relay It is possible to use an earth fault relay to protect motor and cables.

  • Page 42
    Application guidelines CG Drives & Automation 01-5980-01r2…
  • Page 43: Getting Started

    73). • Check / Set real time clock (menu [740], section 8.7.4, page 134) • Select keyboard control (menu [2151], section 7.1.1, page 49). • Perform a test run from the control panel. CG Drives & Automation 01-5980-01r2 Getting started…

  • Page 44: Default Toggle Loop

    Chapter 6. page 43. Menu [100], “Preferred View” is displayed at start. 1. Press to display menu [211] “Language”. NQE1 Select Language using the keys. Confirm with Getting started CG Drives & Automation 01-5980-01r2…

  • Page 45: Control Panel Operation

    To stop the motor, press the key on the control panel. NOTE: For selection of other stop method than the default “Coast”, see section 7.1.2, page 35 and menu [341]. CG Drives & Automation 01-5980-01r2 Getting started…

  • Page 46
    Getting started CG Drives & Automation 01-5980-01r2…
  • Page 47: Operation Via The Control Panel

    Shows the setting or selection in the active Area F: menu (empty at 1st level and 2nd level menus). Shows warnings and alarm messages. CG Drives & Automation, 01-5980-01r2 Operation via the control panel…

  • Page 48: Led Indicators

    Table 18 Control key commands. Start with reversed (left) rotation. START REVERSE RUN (Requires reversing contactor). Stop motor. STOP/RESET Reset softstarter (after a trip). Start with forward START FORWARD RUN (right) rotation. Operation via the control panel CG Drives & Automation, 01-5980-01r2…

  • Page 49: Function Keys

    To activate the jog key function, see instructions in “Jog functions” on page 50. To deactivate the jog key function, unlock the keyboard in menu [218]. CG Drives & Automation, 01-5980-01r2 Operation via the control panel…

  • Page 50: Toggle And Loc/Rem Key

    1. Press the Toggle key and keep it pressed while pressing the ESC key. 2. The message “Clear Loop?” is shown. 3. Confirm with ENTER to delete the menus in the loop. Operation via the control panel CG Drives & Automation, 01-5980-01r2…

  • Page 51: Loc/Rem Function

    Relays [550]. When the softstarter is set to “LOCAL”, the signal on the relay will be active/high. In “REMOTE” the signal will be inactive/low. 3rd level 4th level Fig. 33 Menu structure CG Drives & Automation, 01-5980-01r2 Operation via the control panel…

  • Page 52: The Main Menu

    View Trip Log Here you can see the last 9 trips in the trip memory. System Data This menu contains information on softstarter model and software version. Operation via the control panel CG Drives & Automation, 01-5980-01r2…

  • Page 53: Main Features

    [520], see section 8.5.2, page 108. Spinbrake can only be activated when the TSA is non-operational, i.e that Stp is shown in the display. Fig. 35 Run/Stop decision tree CG Drives & Automation, 01-5980-01r2 Main features…

  • Page 54: Jog Functions

    Jog speed level in menu “[353] Jog Ramp Rate” to achieve smooth Jog start. There are also a couple of examples on how to apply time settings for jog by using logic functions, see page 63. Main features CG Drives & Automation, 01-5980-01r2…

  • Page 55: Working With Parameter Sets

    DigIn running in automatic control mode (i.e. control signals from 3 [523] is set to “Set Ctrl 1” and DigIn 4 [524] is set to “Set PLC, e.g. via fieldbus). Ctrl 2”. CG Drives & Automation, 01-5980-01r2 Main features…

  • Page 56: Configuration Of Parameter Sets

    2. Select motor M1 in menu [212]. 3. Enter motor data and settings for other parameters. 4. Select parameter set B in menu [241]. 5. Select M2 in menu [212]. 6. Enter motor data and settings for other parameters. Main features CG Drives & Automation, 01-5980-01r2…

  • Page 57
    1 to the internal control board of TSA unit 2, using menu [245]. Fig. 38 Copy and load parameters between two Emotron TSA units via the control panel. WARNING! Switch off all power connections before opening the front cover. CG Drives & Automation, 01-5980-01r2 Main features…
  • Page 58
    Fig. 39 Copy and load parameters between two Emotron TSA units using an external control panel (optional). NOTE: Another solution for copying settings and data between different softstarter units is via PC, using the EmoSoftCom PC tool (option). See section 12.2, page 155. Main features CG Drives & Automation, 01-5980-01r2…
  • Page 59: Applying Limitations, Alarms And Autoreset

    • The Trip LED indicator (red triangle) is lit. • The “TRP” status indication is displayed (area D of the display). • The Trip relay or output is active (if selected function in menu [551], [552] or [553]). CG Drives & Automation, 01-5980-01r2 Main features…

  • Page 60: Load Monitor Function

    [223] (being 100%). However, the way to set the levels differs between the two methods: NOTE: When using the load monitor, check that the nominal motor power is set properly in menu [223]. Main features CG Drives & Automation, 01-5980-01r2…

  • Page 61
    (menu [223]). The actual shaft 4112 MaxAlarmLev power is displayed in brackets together with the Alarm Level (104%) 116% value to facilitate setting. See example on the right. Fig. 40 Manually set load monitor alarm levels. CG Drives & Automation, 01-5980-01r2 Main features…
  • Page 62
    Every time a new “Autoset Alarm” command is executed, the actual shaft power value will be updated as the “Normal Load” value, with the alarm levels following this. Fig. 41 Autoset load monitor alarm margins. Main features CG Drives & Automation, 01-5980-01r2…
  • Page 63
    C. The maximum alarm level is exceeded. D. When the set maximum alarm delay time (3 seconds) has passed, the set maximum alarm action is executed, in this case a Hard trip, as set in menu [4111]. CG Drives & Automation, 01-5980-01r2 Main features…
  • Page 64: Reset And Autoreset

    “Autoreset Attempts [251]” on page 83. activated by selecting one of the keyboard alternatives (enabled as default). If controlled by digital input [520], or by virtual I/O [560], this is set by selecting “Reset” signal. Main features CG Drives & Automation, 01-5980-01r2…

  • Page 65: Programmable I/O

    • No digital outputs are available. • 3 relays [550], with the possibility for up to 6 extra relays if extended I/O option boards (max 2) are fitted. • There are also 8 virtual I/Os [560] CG Drives & Automation, 01-5980-01r2 Main features…

  • Page 66: Enable And Stop Functions

    Fig. 44, page 61. Fig. 45 gives an example of a possible RunFWD and RunREV inputs are active, then the sequence. softstarter stops according to the selected stop method in menu [341]. Fig. 46 gives an example of a possible sequence. Main features CG Drives & Automation, 01-5980-01r2…

  • Page 67: Logical Functions

    WARNING! Fig. 46 Input and output status for level control Motor may start instantly! Please verify that parameter settings and I/O connections are according to desired function before switching on mains supply. CG Drives & Automation, 01-5980-01r2 Main features…

  • Page 68
    Number of pulses with Jog speed before run 6521 C2 trig DigIn 2 Pulse input 6522 C2 Reset Counter 2 is blocked until end of deceleration. 6523 C2 Trip Val Number of pulses with Jog speed after run Main features CG Drives & Automation, 01-5980-01r2…
  • Page 69
    Reset Flip Flop 1 and stop the motor 6323 Timer2 Dly 5,0 s Jog time before stop 6411 F1 mode Edge 6412 F1 set Negative flank of “Dec” 6413 F1 reset Reset when “Jog speed after run” has ended CG Drives & Automation, 01-5980-01r2 Main features…
  • Page 70
    Main features CG Drives & Automation, 01-5980-01r2…
  • Page 71: Functionality

    Emotron TSA model, software and hardware version. Service System data 8.9, page 136 information. WARNING! Motor may start instantly! Please verify that parameter settings and I/O connections are according to desired function before switching on mains supply. CG Drives & Automation, 01-5980-01r2 Functionality…

  • Page 72
    For bus communication, the integer value 0 is used to select “Off ” in the example. Integer 1 represents “REV”. To change selection by bus communication refer to the description in Chapter 9. page 139. Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 73: Preferred View [100]

    Sets the content of the lower row in the menu [100] “Preferred View”. Same selection as in menu [110]. Default: 120 2nd Line Motor Data [220] is connected to Current selected motor. Default: Current CG Drives & Automation, 01-5980-01r2 Functionality…

  • Page 74
    Jog command via digital input or Virtual I/O. Int+Ext Jog command via internal or external keyb control panel. Jog command via serial communication. Int keyb Jog command via internal control panel. Ext keyb Jog command via external control panel. Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 75
    Local start/stop command via serial keyboard and the keys are activated. (it is possible to select communication. e.g. Start REV to be Off or REV in menu [2175] above). 218 Lock Code? Default: Range: 0–9999 CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 76: Remote Signal Level/Edge [21A]

    NOTE: Edge controlled inputs can comply with the Machine Directive (see Chapter 1.5.1 page 6) if the inputs are directly used to start and stop the machine. Functionality CG Drives & Automation, 01-5980-01r2…

  • Page 77: Motor Data [220]

    For explanation of the different abbreviations used in this 1 US-units chapter, see Chapter 1.7.2 page 7 WARNING! When the “Units” setting is changed, this will also affect the factory settings of the motor. CG Drives & Automation, 01-5980-01r2 Functionality…

  • Page 78
    . It must be set within the range 25 — 400% of n_soft the softstarter power Pn_soft. If parallel motors, set the sum 221 Motor Volts of the motor power. See nominal data for CG motors in Ta- 400V ble 27. 400 V for SI-units…
  • Page 79
    226 Motor Poles Default: Range: 2-144 Nominal Motor Cos φ [227] Set the nominal Motor cosphi (power factor). 227 Motor Cosφ 0.86 0.86 Default: (see Note 2, page 73) Range: 0.50 — 1.00 CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 80: Motor Protection [230]

    [2311] is performed. The alarm remains active until the I²t value is below 95% before allowing a reset or an autoreset (see more detailed description in menu [2521]). Functionality CG Drives & Automation, 01-5980-01r2…

  • Page 81
    Using motor overload trip class 10 Current: 5 x In_mot Overload trip time (max start time): 20 sec 60 s 20 s Current (x I n_mot 500% x I 300% x I n_mot n_mot Fig. 50 The thermal curve CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 82
    PTC Alarm Action [2331] B 120 ° F 140 F Nema 2331 PTC AA ° No action H 165°C Default: No action No action Hard Trip For a definition, see Table 23, page 55. Soft Trip Warning Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 83
    Counts down from set value in menu [2343]. 2341 StartLim AA No action 2344 TimTNxtStrt Read only Default: No action No action Unit minutes Hard Trip For a definition, see Table 23, page 55 Resolution: 1 min Warning CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 84: Parameter Set Handling [240]

    NOTE: The parameter set cannot be changed No action during run if the parameter set includes change of the motor set (M1-M4). Hard Trip For a definition, see Table 23, page 55. Soft Trip Warning Functionality CG Drives & Automation, 01-5980-01r2…

  • Page 85
    NOTE: The control panel will be temporarily locked while copying or loading data to the internal control panel. If the on-board RS-232 port is connected to a PC or to an external control panel this will also be temporarily locked. CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 86
    Data from motor 4 is loaded. M1M2M3 Data from motor 1, 2, 3 and 4 are loaded. All data is loaded from the control panel. NOTE: Loading or copying will not affect the value in menus for viewing. Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 87: Autoreset [250]

    • Number of allowed autoreset attempts [2511]= 5. • Within 10 minutes 6 trips occur. 1–3600 1–3600 1–3,600 s • At the 6th trip there is no autoreset, because the autoreset counter allows only 5 attempts to autoreset a trip. CG Drives & Automation, 01-5980-01r2 Functionality…

  • Page 88
    When the delay time has [2541] elapsed, the alarm will be reset. The delay counter starts counting immediately. 2524 LockedRotor 2541 MaxAlarm Default: Default: 1–3600 1–3600 1–3,600 s 1–3600 1–3600 1–3,600 s Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 89
    External Alarm 1 autoreset [2549] Default: The delay counter starts counting as soon as the relevant external alarm input is inactive. 1–3600 1–3600 1–3,600 s 2549 Ext Alarm 1 Default: 1–3600 1–3600 1–3,600 s CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 90: Serial Communication [260]

    In this menu the delay time for an autoreset of an Fieldbus module. undervoltage alarm [433] is set. The delay time starts counting when the fault is removed. The undervoltage *) EtherCAT and Bluetooth are future options. Functionality CG Drives & Automation, 01-5980-01r2…

  • Page 91
    Select “RW” in normal Set up the parameters for fieldbus communication. cases to control inverter. 263 Fieldbus Additional Process Values [2634] Define the number of additional process values sent in cyclic messages. 2634 AddPrValues Default: Range: CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 92
    Communication Fault Time [2642] Gateway [2654] Defines the delay time for the trip/warning. 2654 Gateway 2642 ComFlt Time 0.000.000.000 0.5s Default: 0.0.0.0 Default: 0.5 s Range: 0.1-15 s DHCP [2655] 2655 DHCP Default: Selection: On/Off Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 93: Process [300]

    321 Proc Source Default: No process source selected. F(AnIn) Function of analogue input. F(Bus) Function of communication value. NOTE: If F (Bus) is chosen in menu [321], see section 9.5 Process value, page 140. CG Drives & Automation, 01-5980-01r2 Functionality…

  • Page 94
    Confirm the character by moving the cursor to the next position by pressing the NEXT key. No. for serial No. for serial Character Character comm. comm. ° í Space 0–9 1–10 ñ ó ô ü Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 95: Start Setting [330]

    Voltage control is selected when a linear voltage ramp is desired. The thyristor switch on time will be ramped up linearly, from “Initial Voltage”, menu [334], up to full mains voltage. See Fig. 52. CG Drives & Automation, 01-5980-01r2 Functionality…

  • Page 96
    The motor voltage is controlled according torque ramp reactivated. The ramp slope will increase above Voltage Ctr to a linear voltage ramp, menu [334]. Direct online Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 97
    As “Voltage ramp with Current limit” but with fixed ramp 336 Start Time time of 6 seconds. Default: 10 s Range: 1 — 60 s Current limit Ramp time (6 seconds) Fig. 55 Direct on-line start in combination with current limit at start. CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 98: Stop Setting [340]

    Braking may be used in applications where the motor needs to be stopped quickly. When this selection is made, the braking method (“Dynamic Vector Brake” or “Reverse Current Brake”) can be activated in menu [344]. Functionality CG Drives & Automation, 01-5980-01r2…

  • Page 99
    The DC brake will automatically be deactivated when the Stop time motor has stopped or when the stop time has expired. Time Optionally an external rotation sensor can be connected via Fig. 58 Step down voltage at stop. CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 100
    The strength of the DC brake is set here, the value expressed Range: 0 – 120s as a percentage of the maximum available DC braking power. 348 DCB Strength Default: 30 % Range: 20 – 80% Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 101: Jog [350]

    [rpm] Jog speed t [s] t [s] Jog command Fig. 59 Jog command Jog Speed Forward [351] 351 JogSpd FWD Default: Range: 1- 30% of nominal motor speed [225] CG Drives & Automation, 01-5980-01r2 Functionality…

  • Page 102: Load Monitor And Process Protection [400]

    Setting of the wanted alarm behaviour when a “Maximum Alarm” has been detected. 4111 MaxAlarmAct No Action Default: No Action No Action Hard Trip For a definition, see Table 23, page 55. Soft Trip Warning Functionality CG Drives & Automation, 01-5980-01r2…

  • Page 103
    0.5 s period longer than the set “Max Pre-Alarm Delay” time, the Range: 0.1 — 90 s selected “Maximum Pre-Alarm Action” in menu [4121] is activated. 4123 MaxPreAlDel 0.5s Default: 0.5 s Range: 0.1–90 s CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 104
    “Autoset”. See nominal motor power, the alarm delay timer starts counting further information in Fig. 40, page 57. down. 4142 MinAlarmLev shaft Default: Range: 0 — 200% of nominal motor power [223] Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 105
    [4142] MinAlarmLev [4174] MinAlarmMar nominal motor power [223]. NOTE: Changing any alarm margin without performing 4172 MaxPreAlMar Autoset will NOT affect the alarm levels. Default: Range: 0 — of nominal motor power [223] CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 106
    [417] Autoset. A new autoset command will overwrite previously used alarm levels. Autoset can also be triggered by a remote signal, setting the function of any digital input to “Autoset”. Note that this signal is edge-triggered. Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 107: Process Protection [420]

    Hard Trip 4223 LockRotCurr For a definition, see Table 23, page 55. 480% Soft Trip Warning Default: 480% (4.8 x I n_mot Range: 100% — 1000% (1.0 x I — 10.0 x I n_mot n_mot CG Drives & Automation, 01-5980-01r2 Functionality…

  • Page 108: Mains Protection [430]

    Voltage Unbalance Alarm Delay [4313] Default: In this menu the response delay for the voltage unbalance Range: 1 — 90 s alarm, as set in [4311] and [4312], is selected. 4313 VoltUnbDel Default: Range: 1 — 90 s Functionality CG Drives & Automation, 01-5980-01r2…

  • Page 109
    L123 and L321 Under-Voltage Alarm Delay [4333] In this menu the response delay for the voltage unbalance alarm, as set in [4431] and [4432], is selected 4333 UnderV Del Default: Range: 1 — 90 s CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 110: I/O [500]

    S1. When the jumper is in voltage mode only the voltage menu items are selectable. With the jumper in Default: Min (0 V/4.00 mA) current mode only the current menu items are 0.00–20.00 mA selectable. Range: 0–10.00 V Functionality CG Drives & Automation, 01-5980-01r2…

  • Page 111
    With “AnIn Function Max” the physical maximum value is scaled to selected process unit. The default scaling is dependent of the selected function of AnIn [511]. 5136 AnIn FcMax Default: Min value Max value User-defined 2 Define user value in menu [5137] CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 112: Digital Inputs [520]

    Activates other parameter set. See Table Set Ctrl 1 29 for selection possibilities. Activates other parameter set. See Table Set Ctrl 2 29 for selection possibilities. Loc/Rem 10 Activates local mode defined in [2173]. Functionality CG Drives & Automation, 01-5980-01r2…

  • Page 113: Analogue Output [530]

    AnIn Mirror of received signal value on AnIn. Line Voltage 14 Mains supply NOTE: To activate the parameter set selection, menu 241 must be set to DigIn. Used Th Cap 15 Used thermal capacity CG Drives & Automation, 01-5980-01r2 Functionality…

  • Page 114
    [531]. Table 30 AnOut Min Value Max Value Function Process Value Process Min [324] Process Max [325] Shaft Power Motor Power [223] Current Motor Current [224] Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 115
    Min value Max value User defined 2 Define user value in menu [5337 ] NOTE: It is possible to set AnOut up as an inverted output signal by setting “AnOut Min” > “AnOut Max”. CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 116: Relays [550]

    Max pre-alarm condition active (trip or Flip-flop output 4. Max PreAlarm warning). Flip-flop output 4 inverted. Min alarm condition active (trip or Min Alarm CTR1 Counter output 1. warning). !CTR1 Counter output 1 inverted. Functionality CG Drives & Automation, 01-5980-01r2…

  • Page 117
    Fig. 63 Relay function example for start and braking cycle. is active (trip) PTC Alarm 103 PTC alarm active (trip or warning) PT100 Alarm 104 PT100 alarm active (trip or warning) 105 I t alarm active (trip or warning) CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 118
    I/O option board on the option mounting plate. The functions and selections are the same as for “Relay 1” [551]. Default settings are “Off ”. NOTE: Visible only if optional board is detected or if any input/output is activated. Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 119: Virtual I/Os [560]

    “OR logic”. See section 8.5.2, page 108 (Digital Input) for descriptions of the different selections. 561 VIO 1 Dest Default: Same selections as in menu Digital Input 1 Selection: [521], page 108. CG Drives & Automation, 01-5980-01r2 Functionality…

  • Page 120: Logical Functions And Timers [600]

    CA1 Level LO [6113] Digital Comparator Setup [615] — [618] There are also 4 digital comparators that compare any Fig. 65 Analogue comparator type “Window” available digital signals. Functionality CG Drives & Automation, 01-5980-01r2…

  • Page 121
    CA1 Value AnIn 6112 CA1 Level HI 60% (12 mA/20 mA x 100%) 6113 CA1 Level LO 40% (8 mA/20 mA x 100%) 6114 CA1 Type Hysteresis VIO 1 Dest Run FWD VIO 1 Source CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 122
    The reference signal passes the Level LO Hysteresis/ value from above (negative edge), the window band 40°C comparator CA1 is reset, output is set low. CA1 Level LO CA1 output Hysteresis High Window High Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 123
    The reference signal passes the Level LO value from above (signal outside Window band), the comparator CA1 is reset, output is set low. Set delay Reset delay Fig. 68 Set/reset delay of output signal. CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 124
    “Trip”, and for CD4 [6181] the default is “Ready”. Operation Default: Operation Same selection as in menu Relay 1 Selection: [551], page 112. Input signal for CD1 [6151] Digital comparator 1 Fig. 69 Digital comparator. Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 125: Logic Outputs [620]

    Default: ((1.2).3).4 ((1&1)+1)&0 Default execution order, see which is equal to 0. ((1.2).3).4 explanation below. With the alternative execution order for the L1 Expression Alternative execution order, see (1.2).(3.4) explanation below. this is representing: CG Drives & Automation, 01-5980-01r2 Functionality…

  • Page 126
    Logic output 1 inverted. +=OR Not used for Logic 1. ^=EXOR Logic output 2. Not used for Logic 2. Logic output 2 inverted. Not used for Logic 2. Logic output 3. Not used for Logic 3. Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 127
    The reset of the output signal for the Logic 1 function is delayed with the set value in this menu. Compare to Fig. 68, page 119. 621A L1 Res Dly 0:00:00.0 Default: 0:00:00.0 (hours:minutes:seconds) Range: 0:00:00.0–9:59:59.9 CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 128: Timers [630]

    The function of the “On-time” mode is to extend an Prolongs the activation of the output On-time activated (high) timer output signal in comparison to the signal according to menu [6314]. trigger signal. See Fig. 72. Functionality CG Drives & Automation, 01-5980-01r2…

  • Page 129: Sr Flip-Flops [640]

    RESET This menu shows the actual value of the timer. 6316 Timer1 Val Read-only 0:00:00.0 Fig. 73 Programmable flip-flop modes. Timer 2 — 4 [632] — [634] Refer to the descriptions for Timer 1. CG Drives & Automation, 01-5980-01r2 Functionality…

  • Page 130
    Table 35 Truth table for Edge control without priority 6414 F1 Set Dly 0:00:00.0 RESET Default: 0:00:00.0 (hours:minutes:seconds) — (no change)  Range: 0:00:00.0–9:59:59.9 1 (set)  0 (reset)   No change Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 131: Counters [650]

    Counter 1 is incremented by 1 on every positive edge of the trigger signal. NOTE: Maximum counting frequency is 8 Hz. 6511 C1 Trig Default: Same selections as in menu Relay 1 [551], Selection: page 112. CG Drives & Automation, 01-5980-01r2 Functionality…

  • Page 132: Clock Logic [660]

    Date when the clock output signal (CLK1) is deactivated. Note that if “Clk1DateOff ” is set to an earlier date than “Clk1DateOn”, the result will be that the clock is not deactivated at the set date. Functionality CG Drives & Automation, 01-5980-01r2…

  • Page 133: Operation/Status [700]

    6615 Clk1Weekday — — — — — SS VIO 1 Dest Run FWD 716 Shaft Power Read-only VIO 1 Source Clk1 Clock 2 [662] Unit: Resolution: Refer to the description for Clock 1 [661]. CG Drives & Automation, 01-5980-01r2 Functionality…

  • Page 134
    3. See menu PT100 Inputs [2323], page 78. Used Thermal Capacity [71K] 71B PT100B1 123 This menu displays the used thermal capacity. Read-only Unit: °C 71K Used Th Cap Read-only Resolution: 1°C Unit: Resolution: Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 135: Status [720]

    4 — 2 1=Thyristor driven motor 2=Bypass driven motor Source of Run/Stop command, where: 0=Rem, 1=Keyboard (internal + external), 2=Com, 7 — 5 3=Spare, 4=VIO, 5=Internal keyboard, 6=External keyboard. 15 — 8 Reserved for future use. CG Drives & Automation, 01-5980-01r2 Functionality…

  • Page 136
    Fig. 78 indicates that AnIn is active and has a 65% input Volt Unbal (voltage unbalance) value. NOTE: The shown percentage is an absolute value based on the maximum value of the in- or output; so related to either to 10 V or 20 mA. Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 137
    This menu indicates the active digital comparators (CD1 — CD4). 72B CD1-4 Read-only 0000 Logic function status 1 — 4 [72C] This menu indicates the active logic outputs (L1 — L4). 72C Logic 1-4 Read-only 0000 CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 138: Stored Values [730]

    00: 00: 00–262143: 59: 59 Energy [733] This menu displays the total energy consumption since the last energy reset [7331] took place. 733 Energy Read-only Unit: Wh (shows Wh, kWh, MWh or GWh) Range: 0 Wh–999,999 GWh Functionality CG Drives & Automation, 01-5980-01r2…

  • Page 139: View Trip Log [800]

    Analogue comparator 1 — 4 132 (menu [722]). 812A Digital comparator 1 — 4 812B Logic function status 1-4 812C Timer status 1-4 812D Flip-flop status 1-4 812E Counter status 1-2 812F Time to next start CG Drives & Automation, 01-5980-01r2 Functionality…

  • Page 140: Trip Messages [820] — [890]

    0: V, release version 15–14 1: P, pre-release version β , Beta version α , Alpha version Table 39 Information for Modbus and Profibus number, option version Example Description 7–0 Minor option version 15–8 Major option version Functionality CG Drives & Automation, 01-5980-01r2…

  • Page 141
    12 characters. Press the + / — keys to enter graphic symbols from the same list as for User-defined Unit [323], page 90. See also «Editing parameter values», page 45. 923 Unit Name Default: No characters shown CG Drives & Automation, 01-5980-01r2 Functionality…
  • Page 142
    Functionality CG Drives & Automation, 01-5980-01r2…
  • Page 143: Serial Communication

    The on-board RS232 connection is not galvanically option boards. isolated. Modbus RTU The RS485 and USB option boards from CG Drives & Automation are galvanically isolated. There is an asynchronous unisolated RS232 serial communication interface on top of the Emotron TSA unit.

  • Page 144: Motor Data

    Requires that menu [2151] Run/Stop Control is set to “Com”. Modbus/DeviceNet Function Instance number 42901 Reset Run, active together with either 42902 Run FWD or Run REV to perform start. (1=Run, 0=Stop) 42903 Run FWD (1=Active) 42904 Run REV (1=Active) Serial communication CG Drives & Automation 0-5980-01r2…

  • Page 145: Description Of The Eint Formats

    4-bit signed exponent. Gives a value range: -8..+7 (binary 1000 .. 0111) Where bit 15 indicates that we are using the fixed point m10-m0 11-bit signed mantissa. Gives a format (F=0). value range: -1024..+1023 (binary 10000000000..01111111111) CG Drives & Automation 01-5980-01r2 Serial communication…

  • Page 146
    // make signed Rreturn (*(unsigned short int *)&etmp); //————————————————————————— float eint16_to_float(unsigned short int value) float f; eint16 evalue; evalue=*(eint16 *)&value; if (evalue.f) if (evalue.e>=0) f=(int)evalue.m*pow10(evalue.e); else f=(int)evalue.m/pow10(abs(evalue.e)); else f=value; return f; //————————————————————————— Serial communication CG Drives & Automation 0-5980-01r2…
  • Page 147: Softstarter Theory

    The dashed line indicates the nominal motors’ torque characteristic is added to the diagram. values. Torque Torque Fig. 85 Typical load torque characteristics Fig. 83 Typical torque characteristics for the DOL start CG Drives & Automation 01-5980-01r2 Softstarter theory…

  • Page 148
    This means when the motor current is decreased by a factor of two by means of reducing the supply voltage, the torque delivered by the motor will be decreased by a factor of four (approximately). Softstarter theory CG Drives & Automation 01-5980-01r2…
  • Page 149: Reduced Voltage Starting

    On the other hand for low load applications further savings of starting current are impossible even though a big torque reserve is available. Moreover, the resulting abrupt rise of torque first at start and CG Drives & Automation 01-5980-01r2 Softstarter theory…

  • Page 150
    This means, the lowest possible starting current is determined by the combination of motor and load characteristics. Softstarter theory CG Drives & Automation 01-5980-01r2…
  • Page 151: Other Starting Methods

    However, it is always possible to use a frequency inverter instead. The following illustration shows how the torque and current characteristics are affected when the stator frequency is changed. CG Drives & Automation 01-5980-01r2 Softstarter theory…

  • Page 152: Use Of Softstarters With Torque Control

    (linear, square or constant load, need of initial release torque) must be known. In this case a proper torque control method (linear or square) can be chosen and torque boost can be enabled if needed. Softstarter theory CG Drives & Automation 01-5980-01r2…

  • Page 153: Troubleshooting, Diagnoses And Maintenance

    For more information on maintenance, please contact your this instruction manual, it is absolutely necessary to CG Drives & Automation service partner. read and follow the safety instructions in the manual. Precautions to take with a connected motor…

  • Page 154: Troubleshooting List

    Change the Motor I t Current setting in menu [2312]. (Area D: I Soft trip to the prog-rammed I t settings. Check setting of menu [228] Motor Vent, which affects I Warning behaviour. Troubleshooting, Diagnoses and Maintenance CG Drives & Automation 01-5980-01r2…

  • Page 155
    Mains voltage dip due to starting Soft trip limits set in menu group [433]. other major power consuming Warning Use other mains supply lines if dip is caused by other machines on the same line. machinery. CG Drives & Automation 01-5980-01r2 Troubleshooting, Diagnoses and Maintenance…
  • Page 156
    Possible cause Remedy /Menu (and indicator) No action Hard trip Check 3-phase mains supply. Volt unbalance 4311 Mains supply voltage unbalance. Soft trip Check settings in menu [4312] and [4313]. Warning Troubleshooting, Diagnoses and Maintenance CG Drives & Automation 01-5980-01r2…
  • Page 157
    The alarm can only be reset if the The alarm can not alarm condition is removed. be reset. E.g. PTC, PT100 or over temperature alarm can only be reset after the temperature is decreased. CG Drives & Automation 01-5980-01r2 Troubleshooting, Diagnoses and Maintenance…
  • Page 158
    Troubleshooting, Diagnoses and Maintenance CG Drives & Automation 01-5980-01r2…
  • Page 159: Options

    PC for backup and printing. options are described in a separate manual. Recording can be made in oscilloscope mode. Please contact CG Drives & Automation sales for further information. CG Drives & Automation 01-5980-01r2 Options…

  • Page 160
    Options CG Drives & Automation 01-5980-01r2…
  • Page 161: Technical Data

    Heavy duty: Start current = 5 x I , Start time = 15 s (Size 1) or 30 s (Size 2- 4), 10 starts/hour. n_soft Fuse data for Semi-conductor fuses, see Table 48. H1=Height of enclosure, H2= Total height. CG Drives & Automation 01-5980-01r2 Technical data…

  • Page 162
    Heavy duty: Start current = 5 x I , Start time = 15 s (Size 1) or 30 s (Size 2-4), 10 starts/hour. n_soft Fuse data for Semi-conductor fuses, see Table 48. H1=Height of enclosure, H2= Total height. Technical data CG Drives & Automation 01-5980-01r2…
  • Page 163
    Heavy duty: Start current = 5 x I , Start time = 15 s (Size 1) or 30 s (Size 2-4), 10 starts/hour. n_soft Fuse data for Semi-conductor fuses, see Table 48. H1=Height of enclosure, H2= Total height. CG Drives & Automation 01-5980-01r2 Technical data…
  • Page 164: General Electrical Specifications

    42 000 -085 55 000 -100 99 000 -140 160 000 -170 222 000 -200 332 000 -240 433 000 -300 1000 950 000 -360 1200 1 470 000 -450 1400 1 890 000 Technical data CG Drives & Automation 01-5980-01r2…

  • Page 165: Environmental Conditions

    85 A nominal current: 85 A — (20% x 85 A) = 68 A, which is lower than the required 70 A. An even higher rated model is checked, TSA52-100, rated for 100 A nominal current: CG Drives & Automation 01-5980-01r2 Technical data…

  • Page 166: Derating At High Altitude

    56 A — (11% x 56 A) = 49.8 A, which is well above the required 42 A, and therefore TSA52-056 could be selected in this case. Technical data CG Drives & Automation 01-5980-01r2…

  • Page 167: Control Power- And I/O Signal Connectors

    24 VDC or max 250 VAC) must be used for all three output relays (terminals 21-33). Do not mix AC and DC voltage. Make sure to use the same voltage level within this terminal section, otherwise the softstarter may be damaged. CG Drives & Automation 01-5980-01r2 Technical data…

  • Page 168
    Technical data CG Drives & Automation 01-5980-01r2…
  • Page 169: Index

    LOC/REM key ……. 46 Emergency ………1 Clock settings ……..134 Local control ……..71 EN60204-1 ……..6 Coast ……….94 Logic ……..116, 121 EN61800-3 ……..6 Com Type ……..86 Status ……..133 EN61800-5-1 ……..6 Comparator Low Voltage Directive ……. 6 CG Drives & Automation 01-5980-01r2…

  • Page 170
    Phase compensation capacitor ….1 Status ……….131 Phase loss ………79 Status indications ……43 Phase reversal ………105 Step-up transformer for high Phase sequence …….105, 130 voltage motor ……..36 Planer ……….34 Stop command …….108 Power- and signal connectors ..163 CG Drives & Automation 01-5980-01r2…
  • Page 171: Appendix 1: Menu List

    Appendix 1: Menu List This is a list of the Emotron TSA menu parameters and their factory settings, along with communication settings for the most important bus formats. Complete lists with communication data and parameter set information could be downloaded from www. cgglobal.com or www.emotron.com. Customer settings Modbus Inst.

  • Page 172
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format Motor Power [Motor] W 43043 Long, 1=1W EInt Motor Curr [Motor] A 43044 Long, 1=0.1A EInt Motor Speed [Motor] rpm 43045 UInt, 1=1rpm UInt Motor Poles [Motor] 43046 Long, 1=1…
  • Page 173
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format Copy Set A>B 43021 UInt UInt Default>Set 43023 UInt UInt Copy to CP No Copy 43024 UInt UInt Load from CP No Copy 43025 UInt UInt Autoreset page 83…
  • Page 174
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format 2563 OverVolt 43077 Long, 1=1s EInt 2564 Undervolt 43088 Long, 1=1s EInt Serial Com page 86 Com Type RS232 43031 UInt UInt Modbus RTU 2621 Baudrate 9600 43032 UInt…
  • Page 175
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format 2653 Subnet Mask 0.0.0.0 42711 UInt, 1=1 UInt 0.0.0.0 42712 UInt, 1=1 UInt 0.0.0.0 42713 UInt, 1=1 UInt 0.0.0.0 42714 UInt, 1=1 UInt 2654 Gateway 0.0.0.0 42715 UInt, 1=1…
  • Page 176
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format FB Status page 89 2691 Board Type 31081 UInt, 1=1 UInt 2692 SUP-bit 31082 UInt, 1=1 UInt 2693 State FB 31083 UInt, 1=1 UInt 2694 Serial Nbr 31084 UInt, 1=1 UInt…
  • Page 177
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format StartSetting page 91 Start Method Lin Torq Ctr 43701 UInt, 1=1 UInt Init Torque 43702 UInt, 1=1% UInt EndTorqueSt 150% 43703 UInt, 1=1% UInt Init Volt 43704 UInt, 1=1% UInt…
  • Page 178
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format 4111 MaxAlarmAct No action 43775 UInt UInt 4112 MaxAlarmLev 116% 43776 Long, 1=1% EInt 4113 MaxAlarmDel 0,5s 43330 Long, 1=0.1s EInt MaxPreAlarm page 99 4121 MaxPreAlAct No action 43777 UInt…
  • Page 179
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format 4221 LockRot AA No action 43362 UInt UInt 4222 LockRotTime 5,0s 43757 UInt, 1=0.1s UInt 4223 LockRotCurr 480% 43759 UInt, 1=1% UInt Mains Prot page 104 Volt Unbal 4311 VoltUnbalAA No action…
  • Page 180
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format AnIn Advan 5131 AnIn Min 43203 Long, 1=0.01 EInt 5132 AnIn Max 20mA 43204 Long, 1=0.01 EInt 5134 AnIn FcMin 43206 UInt UInt Long, 1= see 1=0.001, 1rpm, 1%, 1°C, 0.001 5135 AnIn VaMin 43541…
  • Page 181
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format 5334 AnOutFcMin 43256 UInt UInt Long, 1= see 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1% 5335 AnOutVaMin 43545 EInt Notes or 0.001 as set in [322] 5336 AnOutFcMax 43257 UInt…
  • Page 182
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format VIO 2 Dest 43283 UInt UInt VIO 2 Source 43284 UInt UInt VIO 3 Dest 43285 UInt UInt VIO 3 Source 43286 UInt UInt VIO 4 Dest 43287 UInt UInt…
  • Page 183
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format 6117 CA1 Res Dly 00:00:00 43408 UInt, 1=1h UInt 43409 UInt, 1=1m UInt 43410 UInt, 1=0.1s UInt 6118 CA1 Tmr Val 00:00:00 42600 UInt, 1=1h UInt 42601 UInt, 1=1m…
  • Page 184
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format 1W, 0.1Hz, 0.1A, 0.1V, 1rpm, 1%, Long, 1= see 6133 CA3 LevelLO 43424 EInt 0.1°C, 1kWh, 1h or 0.001 as set Notes in [322] 6134 CA3 Type Hysteresis 43425 UInt…
  • Page 185
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format 42611 UInt, 1=0.1s UInt CD1 Setup page 120 6151 CD1 Operation 43444 UInt UInt 6152 CD1 Set Dly 00:00:00 43445 UInt, 1=1h UInt 43446 UInt, 1=1m UInt 43447 UInt, 1=0.1s…
  • Page 186
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format 6173 CD3 Res Dly 00:00:00 43462 UInt, 1=1h UInt 43463 UInt, 1=1m UInt 43464 UInt, 1=0.1s UInt 6174 CD3 Tmr Val 00:00:00 42618 UInt, 1=1h UInt 42619 UInt, 1=1m…
  • Page 187
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format 6219 L1 Set Dly 00:00:00 43480 UInt, 1=1h UInt 00:00:00 43481 UInt, 1=1m UInt 00:00:00 43482 UInt, 1=0.1s UInt 621A L1 Res Dly 43483 UInt, 1=1h UInt 43484 UInt, 1=1m…
  • Page 188
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format Logic 3 page 124 6231 L3 Expr ((1.2).3).4 43780 UInt UInt 6232 L3 Input 1 43781 UInt UInt 6233 L3 Op 1 & 43782 UInt UInt 6234 L3 Input 2 43783…
  • Page 189
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format 6249 L4 Set Dly 00:00:00 43802 UInt, 1=1h UInt 43803 UInt, 1=1m UInt 43804 UInt, 1=0.1s UInt 624A L4 Res Dly 00:00:00 43805 UInt, 1=1h UInt 43806 UInt, 1=1m…
  • Page 190
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format 6323 Timer2 Dly 00:00:00 43821 UInt, 1=1h UInt 43822 UInt, 1=1m UInt 43823 UInt, 1=0.1s UInt 6324 Timer2 T1 00:00:00 43824 UInt, 1=1h UInt 43825 UInt, 1=1m UInt 43826…
  • Page 191
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format Timer4 page 125 6341 Timer4 Trig 43841 UInt UInt 6342 Timer4 Mode Delay 43842 UInt UInt 6343 Timer4 Dly 00:00:00 43843 UInt, 1=1h UInt 43844 UInt, 1=1m UInt 43845…
  • Page 192
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format 6416 F1 Tmr Val 00:00:00 42648 UInt, 1=1h UInt 42649 UInt, 1=1m UInt 42650 UInt, 1=0.1s UInt Flip flop 2 page 127 6421 F2 mode Reset 43861 UInt…
  • Page 193
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format 6436 F3 Tmr Val 00:00:00 42654 UInt, 1=1h UInt 42655 UInt, 1=1m UInt 42656 UInt, 1=0.1s UInt Flip flop 4 page 127 6441 F4 mode Edge 43879 UInt…
  • Page 194
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format Clock logic page 128 Clock 1 6611 Clk1TimeON 00:00:00 43600 Long, 1=1h EInt 43601 Long, 1=1m EInt 43602 Long, 1=1s EInt 6612 Clk1TimeOff 00:00:00 43603 Long, 1=1h EInt 43604…
  • Page 195
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format Shaft Power 31006 UInt, 1=1% UInt El Power 31007 Long, 1=1W EInt RMS Current 31008 Long, 1=0.1A EInt L main volt 31009 Long, 1=0.1V EInt Heatsnk Tmp 31010 Long, 1=0.1°C EInt…
  • Page 196
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format CA1-4 31050 UInt, 1=1 UInt CD1-4 31051 UInt, 1=1 UInt Logic 1-4 31052 UInt, 1=1 UInt Timer 1-4 31053 UInt, 1=1 UInt FlipFlop1-4 31072 UInt, 1=1 UInt Counter 1-2 31073…
  • Page 197
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format Long, 1= see 1rpm, 1%, 1°C, 0.001 as set in 8111 Process Val 31102 EInt Notes [322] 8113 Torque 31104 Long, 1=0.1Nm EInt 8114 Torque 31105 Long, 1=1% EInt…
  • Page 198
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format 8124 AnalogueIn 31129 Long, 1=1% EInt 8125 AnalogueOut 31130 Long, 1=1% EInt 8126 IO StatusB1 31131 UInt, 1=1 UInt 8127 IO StatusB2 31132 UInt, 1=1 UInt 8129 CA1-4 31134…
  • Page 199
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format (Trip log list 2) page 136 (Trip log list 3) (Trip log list 4) Same parameters as for menu group 810 (Trip (Trip log list 5) log list 1).
  • Page 200
    Customer settings Modbus Inst. Fieldbus Modbus Menu Parameters Default settings Notes DeviceNet no. format format 42307 UInt UInt 42308 UInt UInt 42309 UInt UInt 42310 UInt UInt 42311 UInt UInt 42312 UInt UInt…
  • Page 201: Appendix 2: Trip Message Communication Data

    Appendix 2: Trip message communication data Trip log list 31101-31154 31201-31254 31301-31354 Modbus Instance no/ 31401-31454 DeviceNet no: 31501-31554 31601-31654 31701-31754 31801-31854 31901-31954 Trip log list 121/245-122/43 122/90-122/143 122/190-122/243 123/35-123/88 Profibus slot/index 123/135—123/188 123/235-124/33 124/80-124/133 124/180-124/233 125/25-125/78 Trip log list 1101-1154 1201-1254 1301-1354…

  • Page 204
    CG Drives & Automation Sweden AB Mörsaregatan 12 Box 222 25 SE-250 24 Helsingborg Sweden T +46 42 16 99 00 F +46 42 16 99 49 www.emotron.com/www.cgglobal.com…

  • Ремонт частотных преобразователей Emotron
  • Ремонт частотных преобразователей Emotron в сервисном центре
  • Настройка частотного преобразователя Emotron, программирование
  • Коды ошибок частотного преобразователя Emotron VFX
  • Сброс ошибок частотных преобразователей Emotron
  • Частотный преобразователь Emotron, скачать инструкции по эксплуатации
  • Схемы подключения частотного преобразователя Emotron
  • Оставить заявку на ремонт частотных преобразователей Emotron

Ремонт частотных преобразователей Emotron

Ремонт частотных преобразователей EmotronРемонт частотного преобразователя Emotron, впрочем, как и ремонт частотников других производителей имеет ряд особенностей в силу своего конструктива. Частотные преобразователи, точнее их начинка делятся на две части:

  • Аппаратная часть,
  • Программная часть.

Частотники данного производителя не являются исключением из правил, именно поэтому ремонт частотного преобразователя Emotron имеет точно такой же ряд особенностей, как и у других преобразователей.

Диагностировать ту или иную неисправность помогают коды ошибок частотного преобразователя, которые отображаются на небольшом дисплее, расположенном на лицевой панели привода. Коды ошибок частотного преобразователя Emotron в зависимости от серии описаны в инструкции пользователя которые можно скачать с нашего сайта.

Ремонт частотных преобразователей Emotron, как и любых других преобразователей, выпущенных под другими брендами, всегда начинается с аппаратной части, после успешного ремонта аппаратной части наступает очередь программной.

Настройка частотного преобразователя Emotron также прописана в инструкции завода производителя, для каждой серии частотных преобразователей настройка будет индивидуальной, так как каждая линейка преобразователей решает свои собственные задачи, этим обусловливается широкая номенклатура данного промышленного оборудования.

Ремонт частотных преобразователей Emotron в сервисном центре

Ремонт частотных преобразователей EmotronКомпания «Кернел» производит ремонт частотных преобразователей Emotron с 2002 года. За время существования компании наши сотрудники накопили колоссальный опыт в ремонте преобразователей частоты такого известного производителя как Emotron. Ремонт подобного промышленного оборудования ответственное и сложное занятие, требующие максимальной отдачи, профессионализма и максимально полной материальной базе.

Специалисты нашего сервисного центра максимальное внимание уделяют качеству исполнения ремонта, программирования и настройке промышленных преобразователей частоты, не зависимо от производителя данного промышленного оборудования. Именно поэтому мы смело даем гарантию на все выполненные работы шесть месяцев.

Ремонт частотных преобразователей Emotron производится исключительно с использованием оригинальных запасных частей, на компонентном уровне с применением высокотехнологичного диагностического оборудования, квалифицированным персоналом с инженерным образованием.

В случае выхода из строя преобразователя частоты на вашем производстве либо появились проблемы с приводом, которые вы не можете решить самостоятельно, мы всегда рады вам помочь. Специалисты нашего сервисного центра в минимальные сроки проведут глубокую диагностику с последующим ремонтом частотного преобразователя Emotron.

Инженеры сервисного центра выполняют качественный ремонт частотных преобразователей Emotron всех серий, когда-либо выпускаемых компанией.

&Emotron VFX

vfx48-025-20ce, vfx48-025-20ceb, vfx48-030-20ce, vfx48-030-20ceb, vfx48-036-20ce, vfx48-036-20ceb, vfx48-045-20ce, vfx48-045-20ceb, vfx48-060-20ce, vfx48-060-20ceb, vfx48-072-20ce, vfx48-074-20ceb, vfx48-088-20ce, vfx48-088-20ceb, vfx48-106-20ce, vfx48-106-20ceb, vfx48-142-20ce, vfx48-142-20ceb, vfx48-171-20ce, vfx48-171-20ceb, vfx48y205-20ce, vfx48y205-20ceb, vfx48-244-20ce, vfx48-244-20ceb, vfx48-003-54ceb, vfx48-004-54ceb, vfx48-006-54ceb, vfx48-008-54ceb, vfx48-010-54ceb, vfx48-013-54ceb, vfx48-018-54ceb, vfx48-026-54ceb, vfx48-031-54ceb, vfx48-037-54ceb, vfx48-046-54ceb, vfx48-061-54ce, vfx48-061-54ceb, vfx48-074-54ce, vfx48-074-54ceb, vfx48-090-54ce, vfx48-090-54ceb, vfx48-109-54ce, vfx48-109-54ceb, vfx48-146-54ce, vfx48-146-54ceb, vfx48-175-54ce, vfx48-175-54ceb, vfx48-210-54ce, vfx48-210-54ceb, vfx48-250-54ce, vfx48-250-54ceb

Emotron FDU

fdu48-003-54ce, fdu48-003-54ceb, fdu48-004-54ce, fdu48-004-54ceb, fdu48-006-54ce, fdu48-006-54ceb, fdu48-008-54ce, fdu48-008-54ceb, fdu48-010-54ce, fdu48-010-54ceb, fdu48-013-54ce, fdu48-013-54ceb, fdu48-018-54ce, fdu48-018-54ceb, fdu48-026-54ce, fdu48-026-54ceb, fdu48-031-54ce, fdu48-031-54ceb, fdu48-037-54ce, fdu48-037-54ceb, fdu48-046-54ce, fdu48-046-54ceb, fdu48-061-54ce, fdu48-061-54ceb, fdu48-074-54ce, fdu48-074-54ceb, fdu48-090-54ce, fdu48-090-54ceb, fdu48-109-54ce, fdu48-109-54ceb, fdu48-146-54ce, fdu48-146-54ceb, fdu48-175-54ce, fdu48-175-54ceb, fdu48-210-54c, fdu48-210-54ceb, fdu48-250-54ce, fdu48-250-54ceb, fdu48-025-20ce, fdu48-030-20ce,  fdu48036y20ce, fdu48y045y20ce, fdu48y060y20ce, fdu48y072y20ce, fdu48y088y20ce, fdu48y106y20ce, fdu48y142y20ce, fdu48y171y20ce, fdu48y205y20ce, fdu48y244y20ce, fdu48-300-20ce, fdu48-300-20ceв, fdu48-375-20ce, fdu48-375-20ceв, fdu48-430-20ce, fdu48-430-20ceв, fdu48-500-20ce, fdu48-500-20ceв, fdu48-600-20ce, fdu48-600-20ceв, fdu48-650-20ce, fdu48-650-20ceв, fdu48-750-20ce, fdu48-750-20ceв, fdu48-860-20ce, fdu48-860-20ceв, fdu48-1000-20ce, fdu48-1000-20ceв

Emotron VSA

vsa23-01, vsa23-03, vsa23-04, vsa23-07, vsa23-10, vsa48-002, vsa48-004, vsa48-005

Emotron VSS

sс48-009, vsс48-013, vsс48-018

Emotron PFD

pfd55-402, pfd55-404, pfd55-405, pfd50-409, pfd50-413, pfd50-418, pfd50-424

Emotron TSA

tsa-016, tsa-022, tsa-030, tsa-036, tsa-042, tsa-056, tsa-070, tsa-085, tsa-100, tsa-140, tsa-170, tsa-200, tsa-240, tsa-300, tsa-360, tsa-450

Emotron MSF 2.0

msf-017, msf-030, msf-045, msf-060, msf-075, msf-085, msf-110, msf-145, msf-170, msf-210, msf-250, msf-310, msf-370, msf-450, msf-570, msf-710, msf-835,  msf-1000, msf-1400

Emotron MSF

msf-017, msf-030, msf-045, msf-060, msf-072, msf-085, msf-110, msf-145, msf-170, msf-210, msf-250, msf-310, msf-370, msf-450, msf-570

В данной таблице присутствуют далеко не все частотники Emotron ремонт которых предлагает наш сервисный центр.

Настройка частотного преобразователя Emotron, программирование

Программирование частотных преобразователей EmotronНастройка частотных преобразователей Emotron (программирование) происходит в рамках установленных производителем правил, существует общий алгоритм по программированию (настройке частотных преобразователей), относящийся ко всем производителям данного промышленного оборудования. Ниже представлена пошаговая инструкция по настройке частотных преобразователей Emotron.

  • Выбор режима управления приводом Emotron (управление по показанию датчиков, дистанционное управление, дистанционное управление).
  • В случае использования отдельного (выносного) монитора, настраивается вывод на него технической информации.
  • Далее определяем конфигурацию подключения серводвигателя. На данной стадии задаются такие параметры как- возможность применения обратной связи либо без ее применения, а в память блока заносятся данные по: величине крутящего момента, мощности потребителей, номинальное значения частоты, напряжение, ток и скорости вращения ротора.
  • Программируется минимально допустимая величина напряжения и частоты, а также время ускорения ротора от ноля до номинального значения.
  • И в завершении, в программу управления частотным преобразователем Emotron вносятся функциональные данные со значениями отдельных клемм и особенностями сигналов. Отмечаются действия оборудования, выполняющиеся автоматически при отсутствии информации поступающей в оперативном режиме с датчика.

В некоторых частотниках существует пункт наличия/отсутствия фильтра в цепи питания двигателя. Этот пункт отвечает за подключение различных видов нагрузок, в том случае, когда возможно выбрать нормальное или инверсное изменение частоты при повышении уровня сигнала обратной связи.

Все настройки частотных преобразователей Emotron приведены в технической документации ниже в удобном формате (PDF) который можно скачать на свой компьютер, распечатать или просто открыть на нашем сайте.

Коды ошибок частотного преобразователя Emotron VFX

Ошибки частотных преобразователей EmotronВ процессе работы выходит из строя даже самое надежное промышленное оборудование. В данной статье мы приведем ошибки частотного преобразователя Emotron, а точнее Emotron VFX. Частотники в наше время нашли широкое применения в абсолютно всех сферах промышленности управляя как мини моторами в оргтехнике, так и гигантскими двигателями в горнодобывающей промышленности.

Для простоты общения со столь сложной электроникой все частотные преобразователи оснащены небольшими дисплеями с помощью которых выводятся информационные сообщения с кодами ошибок, расшифровав которые можно сразу же узнать причину ее возникновения. Если учесть распространенность данной промышленной электроники, то появляется острая нужда в расшифровке кодов ошибок частотных преобразователей. В этой статье мы рассмотрим одного из самых известных производителей промышленной электроники имеющему уважение во всем мире, Emotron.

Существует несколько видов ошибок, некоторые из них можно устранить автоматически, а некоторые возможно исправить только, обратившись в специализированный сервисный центр. В таблицах ниже приведены коды ошибок частотного преобразователя Emotron и их расшифровка.

Индикация- статусная панель, устранение неисправностей с помощью статусной панели.

Коды ошибок и предупреждений

Варианты выбора

Авария (обычная/ мягкая)

Индикато ры предупре ждений (поле C)

Дв-ль I2t

Авария/Выкл/ Ограничение

Обычная/ мягкая

I2t

PTC

Авария/Выкл

Обычная/ мягкая

Датчик двига- теля PTC

Вкл

Обычная

PT100

Авария/Выкл

Обычная/ мягкая

Потеря дв-ля

Авария/Выкл

Обычная

Блок ротора

Авария/Выкл

Обычная

Внеш ошибка

Через ЦфВх

Обычная/ мягкая

Bнш пepeг дв

Через ЦфВх

Обычная/ мягкая

Перегрузка

Авария/Выкл/ Внимание

Обычная/ мягкая

Недогрузка

Авария/Выкл/ Внимание

Обычная/ мягкая

Ошибка связи

Авария/Выкл/ Внимание

Обычная/ мягкая

Отклонение

Через опцию

Обычная

Энкодер

Авария/Выкл

Обычная

Насос управл

Через опцию

Обычная

Перегрев ПЧ

Вкл

Обычная

ПР

Прев тока Б

Вкл

Обычная

Перенапр Т

Вкл

Обычная

Перенапр Г

Вкл

Обычная

Перенапр

Вкл

Обычная

Превыш скор

Вкл

Обычная

Пониж напряж

Вкл

Обычная

НН

ЖдOxл Уpв

Авария/Выкл/ Внимание через ЦифBx

Обычная/ мягкая

LCL

Десат ### *

Вкл

Обычная

Авария ЦПТ

Вкл

Обычная

Выход авария

BA #### *

Вкл

Обычная

Сеть ПЧ Выкл

Вкл

Обычная

Перенапряжен

Предупрежде- ние

НО

Останов мягк

Предупрежде- ние

МСТ

Тормоз

Авария/Выкл/ Внимание

Обычная

Опция

Вкл

Обычная

Преобразователь частоты разработан таким образом, что он пытается избежать аварийных отключений путем ограничения момента, перенапряжения и т.п. Появление сбоев при вводе в эксплуатацию или вскоре после него обычно свидетельствует о неверной настройке или неправильном подключении. Возникновение неисправностей или проблем после

длительного режима бесперебойной работы обычно происходит по причине изменений в системе или ее окружении (например, в результате износа).

Ошибка

Возможная причина

Устранение

Дв-ль I2t “I2t”

  • Превышено допустимое значение I2t.
  • Перегрузка двигателя превысила заданное значение I2t.
  • Проверьте механическую нагрузку двигателя или механизма (подшипники, редукторы, цепи, ремни и т.д.).
  • Измените значение «Ток защ I2t», в группе меню [230]

TC

Перегрев двигателя (PTC) максимальный уровень.

ПРИМЕЧАНИЕ. Действительно только для платы расширений

  • Проверьте механическую нагрузку двигателя или механизма (подшипники, редукторы, цепи, ремни и т.д.).
  • Проверьте систему охлаждения двигателя.
  • Двигатель с самоохлаждением на низкой скоро- сти при большой нагрузке.
  • Настройте PTC, меню [234] в OFF (Выкл).

Датчик двига- теля PTC

Температура термистора двигателя (PTC)

превышает максимальный уровень.

ПРИМЕЧАНИЕ. Действительно только при задействованном [237].

  • Проверьте механическую нагрузку двигателя или механизма (подшипники, редукторы, цепи, ремни и т.д.).
  • Проверьте систему охлаждения двигателя.
  • Двигатель с самоохлаждением на низкой скоро- сти при большой нагрузке.
  • Настройте PTC, меню [237] в OFF (Выкл).

Температура элемента PT100 превышает допустимый уровень.

ПРИМЕЧАНИЕ. Действительно только при использовании платы расширений PTC/PT100.

  • Проверьте механическую нагрузку двигателя или механизма (подшипники, редукторы, цепи, ремни и т.д.).
  • Проверьте систему охлаждения двигателя.
  • Двигатель с самоохлаждением на низкой скоро- сти при большой нагрузке.
  • Настройте PT100 в OFF (Выкл), меню [234]

Потеря дв-ля

Обрыв фазы или слишком большой дисба- ланс фаз двигателя

  • Проверьте напряжение на всех фазах двигателя.
  • Проверьте качество подключения кабеля двига- теля.
  • Если все соединения в норме, свяжитесь с поставщиком.
  • Отключите сигнал потери двигателя.

Блок ротора

Ограничение момента при заклиненном роторе.

  • Механическая блокировка ротора.
  • Устраните механические проблемы в двигателе или подключенном к нему механизме.
  • Отключите сигнал блока ротора.

Внеш ошибка

Активен внешний сигнал аварии на одном из входов ЦфВх 1-8.

  • Низкий уровень сигнала на входе.
  • Проверьте оборудование, от которого поступил внешний сигнал.
  • Проверьте установки для цифровых входов ЦфВх 1-8.

Bнш пepeг дв

Активен внешний сигнал аварии на одном из входов ЦфВх 1-8.

  • Низкий уровень сигнала на входе.
  • Проверьте оборудование, от которого поступил внешний сигнал.
  • Проверьте установки для цифровых входов ЦфВх 1-8.

Перегрузка

Достигнут уровень основного сигнала перегрузки.

  • Проверьте условия нагрузки механизма.
  • Проверьте установку монитора, см. раздел 11.4.1, страница 130.

Недогрузка

Достигнут уровень основного сигнала недогрузки.

  • Проверьте условия нагрузки механизма.
  • Проверьте установку монитора, см. раздел 11.4.1, страница 130.

Ошибка связи

Ошибка последовательной связи (дополнительное устройство)

  • Проверьте кабель связи и его подключение.
  • Проверьте все установки, касающиеся последовательной связи.
  • Перезапустите оборудование, включая ПЧ

Полный список всех возможных ошибок частотных преобразователей Emotron можно посмотреть и скачать в файлах ниже.

Сброс ошибок частотных преобразователей Emotron

Ремонт частотных преобразователей EmotronКомпания «Кернел» производит ремонт частотных преобразователей Emotron в Фарапе с 2002 года. За это время мы накопили колоссальный опыт в том числе опыт в ремонте частотных преобразователей Emotron. Ремонт подобной промышленной электроники ответственное и сложное занятие, требующие максимальной отдачи, профессионализма и максимально полной материальной базе.

Специалисты нашего сервисного центра уделяют максимальное внимание к качеству исполнения ремонта, программирования и настройке промышленного преобразователя частоты, не зависимо от производителя данного промышленного оборудования. Именно поэтому мы смело даем гарантию на ремонт частотных преобразователей Emotron шесть месяцев.

Ремонт частотных преобразователей Emotron в Фарапе производится исключительно с использованием оригинальных запасных частей, на компонентном уровне с применением высокотехнологичного оборудования, квалифицированным персоналом с инженерным образованием.

Если на вашем производстве появились проблемы с частотным преобразователем, которые вы не можете решить самостоятельно, мы всегда рады вам помочь. Обращайтесь в сервисный центр «Кернел». Специалисты нашей компании в минимальные сроки проведут глубокую диагностику и последующий ремонт частотного преобразователя Emotron. Оставьте заказ на ремонт оборудования используя форму на сайте, либо свяжетесь с нашими менеджерами, сделать это очень просто.

Частотный преобразователь Emotron, скачать инструкции по эксплуатации

Ниже вы можете скачать руководства по эксплуатации частотных преобразователей Emotron

Частотный преобразователь Emotron VS10 и VS30 инструкция

скачать руководство пользователя Скачать PDF

Частотный преобразователь Emotron VFX инструкция

скачать руководство пользователя Скачать PDF

Частотный преобразователь Emotron VSA инструкция

скачать руководство пользователя Скачать PDF

Частотный преобразователь Emotron VSX, VSM, VSR, VSE, VSS инструкция

скачать руководство пользователя Скачать PDF

Частотный преобразователь Emotron FDU инструкция

скачать руководство пользователя Скачать PDF

Частотный преобразователь Emotron AFE инструкция

скачать руководство пользователя Скачать PDF

Частотный преобразователь Emotron CDU инструкция

скачать руководство пользователя Скачать PDF

Частотный преобразователь Emotron CDX инструкция

скачать руководство пользователя Скачать PDF

Частотный преобразователь Emotron DSV-15, DSV-35 инструкция

скачать руководство пользователя Скачать PDF

Схемы подключения частотного преобразователя Emotron

Схемы подключений частотных преобразователей Emotron могут отличатся друг от друга даже если эти преобразователи относятся ко одной линейке. Схема подключения преобразователя зависит от многих факторов таких как потребляемая частотным преобразователем нагрузка или питающая сеть к которой подключается частотник 200V – 380V и конечно же зависит от CPU в паре, с которым предполагается работа преобразователя.

Ниже приведены схемы подключения частотных преобразователей Emotron:

Схема подключения частотного преобразователя Emotron VFX

Схема подключения частотного преобразователя Emotron VSA

Схема подключения частотного преобразователя Emotron VFX

Схема подключения частотного преобразователя Emotron VSA

Схема подключения частотного преобразователя Emotron FDU

Схема подключения частотного преобразователя Emotron CDU

Схема подключения частотного преобразователя Emotron FDU

Схема подключения частотного преобразователя Emotron CDU

Схема подключения частотного преобразователя Emotron DSV

Схема подключения частотного преобразователя Emotron VSX, VSM, VSR, VSE, VSS

Схема подключения частотного преобразователя Emotron DSV

Схема подключения частотного преобразователя Emotron VSX, VSM, VSR, VSE, VSS

Оставьте заявку на ремонт промышленного оборудования используя форму на сайте, либо свяжетесь с нашими менеджерами, сделать это очень просто.

Оставить заявку на ремонт частотных преобразователей Emotron

У вас вышел из строя частотник? Вам необходим срочный ремонт частотных преобразователей Emotron в Фарапе? Оставьте заявку на ремонт нажав на одноименную кнопку в верхней правой части экрана либо свяжитесь с нашими менеджерами. Связаться с ними можно несколькими способами:

Наши контакты

  • Заказав обратный звонок (кнопка в правом нижнем углу сайта)
  • Посредством чата (кнопка расположена с левой стороны сайта)
  • Позвонив по номеру телефона:
    • +7(8482) 79-78-54;
    • +7(8482) 55-96-39;
    • +7(917) 121-53-01
  • Написав на электронную почту: 89171215301@mail.ru

Далеко не полный список производителей промышленной электроники и оборудования, ремонтируемой в нашей компании.

Преобразователи частоты руководства, инструкции, брошюры

 

Инструкции FRECON

Инструкции Frecon

Frecon FR100 Инструкция

Размер файла: 1.07 мб

Руководство пользователя Frecon FR 100

Скачать

Frecon FR200 инструкция

Размер файла: 1.38 мб

Руководство пользователя Frecon FR200

Скачать

Инструкции INSTART

Инструкции instart

Instart FCI ИНСТРУКЦИЯ

Размер файла: 11.41 мб

Руководство по эксплуатации INSTART FCI

Скачать

 

Инструкции WEG 

Instart MCI ИНСТРУКЦИЯ

Размер файла: 6.34 мб

Руководство пользователя INSTART MCI

Скачать

Инструкции WEG

WEG cfw08 инструкция

Размер файла: 5.70 мб

Руководство пользователя WEG CFW 08

Скачать

WEG cfw 09 инструкция

Размер файла: 19.34 мб

Руководство пользователя WEG CFW 09 англ.

Скачать

 

Инструкции HITACHI 

WEG cfw10 инструкция

Размер файла: 3.75 мб

Руководство пользователя WEG cfw 10 англ.

Скачать

WEG mvw 01 Инструкция

Размер файла: 24.99 мб

Руководство пользователя WEG MVW 01 англ.

Скачать

Инструкции hitachi

hitachi SJ 300 ИНСТРУКЦИЯ

Размер файла: 2.15 мб

Руководство пользователя Hitachi SJ 300

Скачать

Hitachi L100 инструкция

Размер файла: 1.02 мб

Руководство пользователя Hitachi l100

Скачать

Hitachi L200 инструкция

Размер файла: 6.50 мб

Руководство пользователя Hitachi L 200

Скачать

Hitachi SJ200 инструкция

Размер файла: 6.40 мб

Руководство пользователя Hitachi SJ 200

Скачать

Hitachi X200 инструкция

Размер файла: 2.62 мб

Руководство пользователя Hitachi X 200

Скачать

Hitachi J300 инструкция

Размер файла: 1.39 мб

Руководство пользователя Hitachi j300

Скачать

HITACHI SJ700 инструкция

Размер файла: 6.70 мб

Руководство пользователя Hitachi SJ 700

Скачать

Инструкции NORD 

Инструкции NORD

Nord NORDAC sk700 инструкция

Размер файла: 3.19 мб

Руководство пользователя NORD NORDAC SK 700E

Скачать

Nord nordac SK 750 ИНСТРУКЦИЯ

Размер файла: 2.48 мб

Руководство пользователя NORD NORDAC SK 750E англ.

Скачать

NORD NORDAC SK200 инструкция

Размер файла: 5.53 мб

Руководство пользователя NORD NORDAC SK 200E

Скачать

 

Инструкции INVT

NORD NORDAC SK 300 ИНСТРУКЦИЯ

Размер файла: 4.24 мб

Руководство пользователя NORD NORDAC TRIO SK 300 англ.

Скачать

nord nordac SK 500E инструкция

Размер файла: 2.39 мб

Руководство пользователя NORD NORDAC SK 500E

Скачать

Nord nordac sk 400 инструкция

Размер файла: 374.33 кб

Руководство пользователя NORD NORDAC SK 400

Скачать

Инструкции INVT

INVT CHF100A ИНСТРУКЦИЯ

Размер файла: 2.85 мб

Руководство пользователя INVT CHF 100 A

Скачать

INVT GD 100 ИНСТРУКЦИЯ

Размер файла: 3.51 мб

Руководство пользователя INVT GD 100

Скачать

 

Инструкции Fuji Electric

INVT GD 200 ИНСТРУКЦИЯ

Размер файла: 3.51 мб

Руководство пользователя INVT GD 200

Скачать

INVT GD 300 ИНСТРУКЦИЯ

Размер файла: 7.99 мб

Руководство пользователя INVT GD 300

Скачать

Инструкции INVT

FUJI FRENIC 5000 ИНСТРУКЦИЯ

Размер файла: 2.91 мб

Руководство пользователя Fuji frenic 5000

Скачать

Fuji Frenic Mini инструкция

Размер файла: 4.20 мб

Руководство пользователя Fuji frenic mini

Скачать

Fuji Frenic Eco инструкция

Размер файла: 9.83 мб

Руководство пользователя Fuji Frenic Eco

Скачать

Fuji frenic mega инструкция

Размер файла: 14.30 мб

Руководство пользователя Fuji Frenic mega

Скачать

 

Инструкции Emotron 

Fuji FRENIC Lift инструкция

Размер файла: 1.28 мб

Руководство пользователя Fuji FRENIC Lift

Скачать

Fuji Frenic Multi инструкция

Размер файла: 8.54 мб

Руководство пользователя Fuji Frenic Multi

Скачать

Инструкции Emotron

Emotron FDU 2-0 инструкция

Размер файла: 22.61 мб

Руководство пользователя Emotron

Скачать

emotron tsa инструкция

Размер файла: 16.17 мб

Руководство пользователя emotron tsa

Скачать

Emotron VFX-FDU ИНСТРУКЦИЯ

Размер файла: 2.84 мб

Дополнение к руководству пользователя Emotron VFX-FDU

Скачать

EMOTRON MSF 2-0 ИНСТРУКЦИЯ

Размер файла: 3.88 мб

Руководство пользователя Emotron MSF 2-0

Скачать

Emotron VFX 2-0 инструкция

Размер файла: 12.37 мб

Руководство пользователя Emotron VFX 2-0

Скачать

 

Инструкции LG

Инструкции Emotron

lg LS iG5 инструкция

Размер файла: 16.39 мб

Руководство пользователя LG LS IG5

Скачать

LG LS iS7 ИНСТРУКЦИЯ

Размер файла: 6.43 мб

Руководство пользователя LG LS IS7

Скачать

LG LS IS5 ИНСТРУКЦИЯ

Размер файла: 4.00 мб

Руководство пользователя LG LS IS5

Скачать

LG LS S100 ИНСТРУКЦИЯ

Размер файла: 6.10 мб

Руководство пользователя LG LS S100

Скачать

LG LS iG5A ИНСТРУКЦИЯ

Размер файла: 4.94 мб

Руководство пользователя LG LS IG5A

Скачать

LG LS iE5 ИНСТРУКЦИЯ

Размер файла: 4.31 мб

Руководство пользователя LG LS IE5

Скачать

LG LS iC5 ИНСТРУКЦИЯ

Размер файла: 5.83 мб

Руководство пользователя LG LS IC5

Скачать

LG LS V5 ИНСТРУКЦИЯ

Размер файла: 5.65 мб

Руководство пользователя LG LS V5

Скачать

 

Инструкции Allen Bradley

Инструкции Emotron

ALLEN BRADLIEY PF40 ИНСТРУКЦИЯ

Размер файла: 4.34 мб

Руководство пользователя Allen bradliey PF 40

Скачать

PowerFlex 525 инструкция

Размер файла: 5.73 мб

Руководство пользователя PowerFlex 525 англ.

Скачать

allen bradley power flex

Размер файла: 6.43 мб

Руководство по выбору низковольтных
преобразователей частоты PowerFlex

Скачать

Понравилась статья? Поделить с друзьями:
  • Построение выкройки юбки карандаш для начинающих пошаговая инструкция
  • Монурал инструкция по применению цена отзывы порошок отзывы от чего
  • Медицинский дезинфектор должностная инструкция по профстандарту
  • Норфлоксацин 400 мг инструкция цена аналоги
  • Сироп солодки инструкция для детей от кашля с какого возраста