GESTRA Steam Systems

GESTRA

NRGT 261

NRGT 261S

Installation Instructions 81021304

Level electrode
NRGT 26-, NRGT 26- S

Advertising

This manual is related to the following products:

NRGT26-1S

Factory setting NRGT 26-1

The level transmitter features the following factory set default values:

Measuring range1300 mm:

Measuring range 1400 mm to 1700 mm:

Measuring range 1800 mm to 1500 mm:

Measuring range 1600 mm to 2000 mm:

Factory setting NRGT 26-1S

The level transmitter features the following factory set default values:

Measuring range1275 mm:

Measuring range 1375 mm to 1675 mm:

Measuring range 1775 mm to 1475 mm:

Measuring range 1575 mm to 1975 mm:

Establishing active measuring range (control range)

Within the measuring range of the transmitter you can establish the active control range.

Use switch r to establish the length of the active measuring range. Switch r see Fig. 11.

X Selected (active) measuring range [mm]

2 4 Measuring range [mm] = xxx % see Fig. 2 and 3

E Lower end of measuring range, adjustable

F Upper end of measuring range, adjustable

5 Water, conductivity ≥ 20 µS/cm

6 Water, conductivity ≥ 25 µS/cm

7 Fuel oil EL, dielectric constant ε

r

Fig. 13

Attention

If X is clearly smaller than 2 4 set switch r one step back.

2,3

r

F

2

4

X

Lower measuring point

E

Switch r position 4, water ≥ 20 µS/cm

Switch r position 4, water ≥ 20 µS/cm

Switch r position 4, water ≥ 20 µS/cm

Switch r position 5, water ≥ 20 µS/cm

Switch r position 4, water ≥ 20 µS/cm

Switch r position 4, water ≥ 20 µS/cm

Switch r position 4, water ≥ 20 µS/cm

Switch r position 5, water ≥ 20 µS/cm

1000

1100

1200

1300

1400

1500

1600

1700

1800

1900

2000

X

5

6

100

4

3

200

4

3

300

4

3

400

4

4

500

4

4

600

4

4

700

4

4

800

4

4

900

4

5

4

5

4

5

4

5

4

5

4

5

4

5

5

5

5

6

5

6

5

6

5

6

7

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

3

4

4

4

17

Loading…

GESTRA

GESTRA Steam Systems

NRGT 26 1

NRGT 26 1S

Installation Instructions 810213-04

Level electrode

NRGT 26-1, NRGT 26-1 S

Contents

Page

Important Notes

Usage for the intended purpose

…………………………………………………………………………………………………4

Safety note…………………………………………………………………………………………………………………………….

4

Danger………………………………………………………………………………………………………………………………….

4

Attention……………………………………………………………………………………………………………………………….

4

ATEX (Atmosphère Explosible)……………………………………………………………………………………………………

4

Explanatory Notes

Scope of supply………………………………………………………………………………………………………………………

5

System description………………………………………………………………………………………………………………….

5

Function………………………………………………………………………………………………………………………………..

5

Designs…………………………………………………………………………………………………………………………………

5

Technical Data

NRGT 26 1, NRGT 26 1S………………………………………………………………………………………………………

6, 7

Corrosion resistance………………………………………………………………………………………………………………..

7

Sizing……………………………………………………………………………………………………………………………………

7

Name plate / marking………………………………………………………………………………………………………………

8

Dimensions.…………………………………………………………………………………………………………………………..

9

Design

NRGT 26 1, NRGT 26 1S………………………………………………………………………………………………………..

10

Key……………………………………………………………………………………………………………………………………..

12

Functional Elements

NRGT 26 1, NRGT 26 1S………………………………………………………………………………………………………..

11

Key……………………………………………………………………………………………………………………………………..

12

Installation

NRGT 26 1…………………………………………………………………………………………………………………………..

13

NRGT 26 1S…………………………………………………………………………………………………………………………

13

Attention……………………………………………………………………………………………………………………………..

13

Note……………………………………………………………………………………………………………………………………

13

Tools.………………………………………………………………………………………………………………………………….

13

Examples of installation………………………………………………………………………………………………………….

14

Key……………………………………………………………………………………………………………………………………..

15

Contents – continued –

Page

Wiring

NRGT 26 1, NRGT 26 1S………………………………………………………………………………………………………..

16

Wiring diagram……………………………………………………………………………………………………………………..

16

Attention……………………………………………………………………………………………………………………………..

16

Tools.………………………………………………………………………………………………………………………………….

16

Basic Setting

Factory setting NRGT 26 1.…………………………………………………………………………………………………….

17

Factory setting NRGT 26 1S.…………………………………………………………………………………………………..

17

Establish active measuring range (control range)………………………………………………………………………..

17

Attention……………………………………………………………………………………………………………………………..

17

Commissioning

Danger………………………………………………………………………………………………………………………………..

18

Check wiring………………………………………………………………………………………………………………………..

18

Apply mains voltage………………………………………………………………………………………………………………

18

Adjust lower measuring range…………………………………………………………………………………………………

18

Adjust upper measuring range…………………………………………………………………………………………………

18

Note……………………………………………………………………………………………………………………………………

18

Operation

NRGT 26 1, NRGT 26 1S………………………………………………………………………………………………………..

19

Note……………………………………………………………………………………………………………………………………

19

Operational Malfunctions

Fault finding list for troubleshooting………………………………………………………………………………………….

20

Decommissioning

Danger………………………………………………………………………………………………………………………………..

21

Disposal………………………………………………………………………………………………………………………………

21

Annex

Declaration of conformity……………………………………………………………………………………………………….

22

Important Notes

Usage for the intended purpose

Use level electrodes NRGT 26-1 and NRGT 26-1S only for indicating liquid levels.

Safety note

The equipment must only be installed and commissioned by qualified and competent staff. Retrofitting and maintenance work must only be performed by qualified staff who – through adequate training – have achieved a recognised level of competence.

Danger

When loosening the electrode steam or hot water might escape. This presents the danger of severe scalds to the whole body.

It is essential not to mount or dismantle the electrode unless the boiler pressure is verified to be 0 bar. The electrode becomes hot during operation. Touching the hot equipment presents the risk of severe burns to hands and arms. All installation and maintenance work must only be performed when the equipment is cold.

The terminal strip of the NRGT 26-1 / NRGT 26-1S is live during operation. This presents the danger of electric shock.

Cut off power supply before fixing or removing the housing cover.

Attention

The name plate specifies the technical features of the equipment. Note that any piece of equipment without its specific name plate must neither be commissioned nor operated.

ATEX (Atmosphère Explosible)

According to the European Directive 94/9/EC the equipment must not be used in potentially explosive areas.

Explanatory Notes

Scope of supply

NRGT 26-1

1 Compact system type NRGT 26-1

with joint ring (of stainless steel 1.4301) D 27 x 32 to DIN 7603, bright annealed 1 Installation manual

NRGT 26-1S (for marine applications)

1 Compact system type NRGT 26-1S with flange DN 50 (2″), PN 40 to DIN 2635 1 Installation manual

System description

The compact system NRGT 26-1 works according to the capacitance measurement principle. The NRGT 26-1 is used for signalling different levels in electrically conductive and non-conductive liquids:

Level maintained within the control band defined by two preset limits

The NRGT 26-1 has a level transmitter integrated in the electrode body which produces a standard signal of 4 -20 mA. External switchgear is not required.

Function

The principle of capacitance measurement is applied to determine the level. The electrode rod and the vessel wall form a capacitor. If the level of the dielectric located between the two capacitor plates changes, the current which flows through the plates changes proportionally to the level. A dielectric is defined as an insulating substance, which excludes many liquids such as water. In order to receive a useful measuring result the measuring rod, which is submerged to varying depths in the liquid, must be completely insulated. After the calibration of the zero point/measuring range (0 %/100 %) the level can be read off from a remote display unit. The level measuring range can be changed during operation.

Designs

NRGT 26 1:

Screwed design ¾» BSP, DIN ISO 228-1. Fig. 2

NRGT 26 1S:

Flanged design for marine application DN 50, PN 40, DIN 2635. Fig. 3

Technical Data

NRGT 26 1, NRGT 26 1S

Type Approval N°

NRGT 26 1:

TÜV · WRS · 02 391

NRGT 26 1S:

LR 98/20075

RINA ELE/30298/2

GL 99249 96HH

BV 10617/AO BV

NKK A 556

DNV A 8394

KR HMB 06190 MS002

Max. service pressure

32 bar g at 238 °C

Connections

NRGT 26 1:

Screwed ¾» BSP, DIN ISO 228 1

NRGT 26 1S:

Flanged DN 50, PN 40, DIN 2635

Materials

Case:

Die cast aluminium 3.2161 (G AlSi8Cu3)

Stem:

S. S. 1.4571 CrNiMoTi17 12 2

Flange:

Forged steel 1.0460 P250GH

Measuring electrodes:

S. S. 1.4571 CrNiMoTi17 12 2

Electrode insulation:

PTFE

Spacer disc:

PTFE (design for marine applications)

Mains supply

230 V +/ 10 %, 50/60 Hz

115 V +/ 10 %, 50/60 Hz (option)

224 V +/ 10 %, 50/60 Hz (option)

24 V DC

Length supplied / measuring range

NRGT 26 1

NRGT 26 1 S

1 Max. installation length at 238 °C

3 Max. installation length at 238 °C

2 Measuring range

4 Measuring range

1

2

3

4

373

300

316

275

477

400

420

375

583

500

526

475

688

600

631

575

794

700

737

675

899

800

842

775

1004

900

947

875

1110

1000

1053

975

1214

1100

1157

1075

1319

1200

1262

1175

1423

1300

1366

1275

1528

1400

1471

1375

1636

1500

1579

1475

2156

2000

See Fig. 2

2099

1975

See Fig. 3

Technical Data – continued –

NRGT 26 1, NRGT 26 1S – continued –

Power consumption

5 VA, 3 VA at 24 V DC

Fuse

Thermal fuse Tmax = 102 °C

Sensitivity

Range 1: Water ≥ 0,5 µS/cm

Range 2: Water ≥ 20 µS/cm Range 3: Fuel oil EL εr 2,3

Output

4 – 20 mA level-proportional; electrically insulated, max. load 500 Ω

Indicators and adjustors

2 red LEDs for “level 0 %” or “level 100 %” within the measuring range, 1 green LED for “level between 0 % and 100 %” of measuring range,

1 code switch for selecting the measuring range,

2 trimmer potentiometers for small-percentage adjustment of the measuring range, 2 terminal lugs for voltage measurement.

Cable entry

Cable gland with integral cable clamp 2 x M20 x 1.5

Protection

IP 65 nach DIN EN 60529

Max. admissible ambient temperature

70 °C (158 °F)

Weight

NRGT 26 1: approx. 1.8 kg NRGT 26 1S: approx. 8.0 kg

Corrosion resistance

Provided that the equipment is used for its intended purpose, its safety is not impaired by corrosion.

Sizing

The body must not be subjected to sharp increases in pressure. Welds and flanges of the electrode are designed to withstand dynamic loading (bending and alternating stress). The dimensional allowances for corrosion reflect the latest state of technology.

Flowserve NRGT26-1 User Manual

Technical Data

– continued –

Name plate / marking

Vor Öffnen des Deckels

Gerät freischalten!

Betriebsanleitung

beachten

Before removing cover

isolate from power supplies

See installation instructions

Avant d’ouvrir le couvercle

dèconnecter complètement

l’appareil

Voir instructions de

montage

NRGT 26-1

PN 40

NRGT 26-1S PN 40

G ¾

1.4571

DN 50

1.4571/1.0460

Pmax

32 bar (464psi)

Tmax

238°C (453°F)

Tmax

70°C

IP 65

(133°F)

24 V

115 V

230 V

50 / 60 Hz

5VA

H= _ _ _ _ _ _ _ _ _ _ mm

4 — 20 mA / 500

250 V ~ T 2,5 A

TÜV . WRS. 02-391

GL 99249-96 HH

GB Reg. Design 2 053 113

US Pat. 5 719 342, Design 383 403

GESTRA AG, D-28215 Bremen

Fig. 1

Vor Öffnen des Deckels Gerät freischalten! Betriebsanleitung beachten

Before removing cover isolate from power supplies See installation instructions

Avant d’ouvrir le couvercle dèconnecter complètement l’appareil

Voir instructions de montage

NRGT 26-1

PN 40

G ¾

1.4571

Pmax

32 bar (464psi)

Tmax

238°C (460°F)

Tmax

IP 65

70°C

(158°F)

24 VDC 3VA

H= _ _ _ _ _ _ _ _ _ _ mm

4 — 20 mA / 500

250 V ~ T 2,5 A

GL 99249-96 HH

TÜV . WRS.

02-391

0525

GESTRA AG

Münchener Str. 77

D-28215 Bremen

Vers.XX Ser.-Nr.: 316141

Specifications:

1431/1431891-nrgt_261s.pdf file (30 Mar 2023)

Accompanying Data:

GESTRA NRGT 26-1S Kitchen Appliances, Transmitter PDF Installation Instructions Manual (Updated: Thursday 30th of March 2023 06:54:12 PM)

Rating: 4.2 (rated by 74 users)

Compatible devices: NRG 16-60, NRG 26-60, NRG 26-61, NRGT 26-2, NRG 17-50, NRG 16-50S, BA 46, NRG 16-11.

Recommended Documentation:

GESTRA NRGT 26-1S: Text of Installation Instructions Manual

(Ocr-Read Version Summary of Contents, UPD: 30 March 2023)

  • 17, 17 Basic Setting Factory setting NRGT 261 The compact system is delivered with the following factory set default values: ■ Measuring range 1300 mm: Switch K position 4, water ≥ 20 µS/cm ■ Measuring range 1400 mm up to 1700 mm: Switch K position 4, water ≥ 20 µS/cm ■ Measuring range 1800 mm up to 1500 mm: Switch K position 4, water ≥ 20 µS/cm ■ Me…

  • 9, 9 42 Flansch PN 40, DN 50 62 ~ 338 140 173 GESTRA Steam System s GESTRA NRGT 26-1S G 3/4 ISO 228-1 173 140 26 37 1 Tiefe: 70 mm 42 GESTRA St eam System s GESTRA NRGT 26-1 ~ 338 337,5 339 173 140 173 62 140 3 4 b = 70 b = 70 ∅ 42 ¾» BSP 37 1 2 26 Flange DN 50, PN 40 ∅ 42 Technical Data – continued – Dimensions Fig. 3Fig. 2 2, 4 constant length (no elo…

  • 24, 24 Agencies all over the world: www.gestra.de 810213-04/1205cm · © 1997 GESTRA AG · Bremen · Printed in Germany GESTRA Great Britain Flowserve Flow Control (UK) Ltd. Burrel Road, Haywards Heath West Sussex RH 16 1TL Tel. 00 44 14 44 / 31 44 00 Fax 00 44 14 44 / 31 45 57 E-mail: [email protected]flowserve.com Italia Flowserve S.p.A. Flow Control Divis…

  • 18, 18 1. Fill boiler or vessel with liquid until the lower measuring point is reached. 2. Wait until boiler or vessel has reached its service pressure. 3. Turn potentiometer L to the left until the red LED M lights up. 4. Turn potentiometer L to the right until only the green LED N lights up. You have now established the lower measuring point. Adjust lower measuring range Commissioning Dang…

  • 19, 19 Operation Operation in steam and (pressurised) hot water plants in accordance with TRD 401, TRD 602, TRD 604, EN 12952, EN 12953 or other national regulations or according to the guidelines of classification societies. NRGT 261, NRGT 261S Note ■ Should malfunctions occur during the commissioning procedure refer to chapter “Operational Malfunctions” on…

  • 5, 5 Explanatory Notes System description The compact system NRGT 26-1 works according to the capacitance measurement principle. The NRGT 26-1 is used for signalling different levels in electrically conductive and non-conductive liquids: ■ Level maintained within the control band defined by two preset limits The NRGT 26-1 has a level transmitter integrated in the electrode body which p…

  • 1,  GESTRA Steam Systems GESTRA NRGT 261 NRGT 261S Installation Instructions 81021304 Level electrode NRGT 26-1, NRGT 26-1 S

  • 10, 10 GESTRA S team Sys tems GESTRA NRGT 26-1S GESTRA Steam Sy stems GESTRA NRGT 26-1 Design Fig. 4 Fig. 6 N 1 N 10 0.5 ∅ 33 ¾» BSP DIN 228 NRGT 261, NRGT 261S A.F. A C B G F E D A Fig. 5

  • 12, 12 A Thermal insulation provided on site, d = 20 mm (without thermal insulation of steam boiler) B Seating surface C Joint ring (of stainless steel 1.4301) D 27 x 32 to DIN 7603 D Electrode thread ¾» BSP, DIN ISO 228-1 E Flange DN 50 (2″), PN 40 to DIN 2635 F Protection tube G Spacer disc H Housing screws M4 I Cable entry M20 x 1.5 J Housing cover …

  • 2, 2 Contents Usage for the intended purpose ………………………………………………………………………………………………..4 Safety note ……………………………………………………………………………………………………………………………4 Danger …………………………………………..…

  • 13, 13 Attention ■ The seating surfaces of the threads or flange provided on the vessel or boiler standpipe must be accurately machined. Fig. 6 ■ Do not bend electrode rod when mounting. ■ Do not lag electrode body. ■ Do not insulate electrode thread with hemp or PTFE tape. Installation NRGT 261 1. Check seating surfaces of threads or �…

  • 8, 8 Technical Data – continued – Name plate / marking Fig. 1 PN 40PN 40 PN 40PN 40 IP 65IP 65 PmaxPmax TmaxTmax NRGT 26-1 NRGT 26-1S TÜV . WRS. 02-391 G ¾ 1.4571 DN 50 1.4571/1.0460DN 50 1.4571/1.0460 250 V ~ T 2,5 A250 V ~ T 2,5 A Before removing cover isolate from power supplies See installation instructions Before removing cover isolate from power supplies See inst…

  • 21, 21 Disposal Decommissioning Remove the level electrode and separate the waste materials in accordance with the material specification. Electronic components (boards) must be disposed of separately. For the disposal of the level electrode observe the pertinent legal regulations concerning waste disposal. Danger Risk of severe burns and scalds to the whole body! B…

GESTRA NRGT 26-1S: Recommended Instructions

i3TOUCH V-11, G700, CL 112, High Efficiency Softener-Cleer 9″

  • 1Bestimmungsgemäße VerwendungSensoren der Sensorfamilie BMF415 dienen zum Erfassen von Kolbenpositionen pneumatischer und hydraulischer Zylinder in Schweißfeld-Applikationen. Die einwandfreie Funktion gemäß den Angaben in den technischen Daten wird nur mit original Balluff Zubehör zugesichert, die Ver-wendung anderer Komponenten bewirkt Haftungsaus-schluss.Eine nichtbesti …

    BMF 415KW-HA W-5 Series 4

  • Issue 1 29/6/2017 1 3 Bowl Steamer Model No. XJ-10102A0 / Cat. No. 7072880 Care & Instruction Manual For household and indoor use only Please read these instructions before use and retain for future reference …

    XJ-10102A0 13

  • Lea este manual antes de usar el artefacto y guárdelo para referenciaREAD THE MANUAL BEFORE USE AND SAVE FOR FUTURE REFERENCEUSER MANUALMANUAL DE USUARIOTriple Food Server/ Bufetera TripleMODEL/MODELO: HH-09001014 …

    HH-09001014 32

  • BedienungsanleitungDruckschalter Typ PEV-1/4A-SW27Winkeldose Typ PEV-1/4A-WDOperating instructionsPressure switch Type PEV-1/4A-SW27Angle socket Type PEV-1/4A-WDEinbau und Inbetriebnahme nur von autorisiertem Fachpersonal, gemäß Bedienungsanleitung.Fitting and commissioning to be carried out by qualified personnel only in accordance with the operating instructions. Es be …

    PEV-1/4A Series 12

  • FR ES ITPTELPLTraduction de la version originale du mode d’emploi / Traducción de las Instrucciones originales / Tradução das Instruções Originais /Traduzione delle istruzioni originali /Μετάφραση τωνπρωτότυπωνοδηγιών / Tłumaczenie instrukcji oryginalnej /KANOEAN CODE :3276007191684327600719182032760071918993276007191783Original InstructionsTra …

    Kano 40

  • Référence : 80834153ALLEGRE PUERICULTURE41 rue Edouard Martel42 000 SAINT ETIENNE — FRANCE Important : Conserver ces instructions pour consultation ultérieure.AVERTISSEMENT ! Ne jamais laisser votre enfant sans surveillance.S’assurer que tous les dispositifs de verrouillage sont enclenchés avant utilisation.Pour éviter toute blessure, maintenir votr …

    80834153 2

  •  !»#$!»#%&»'()*(+,-) …

    Instrumented Buoys 4

  • REV 031308ATTENTIONIf any components of this unit are broken,do not operate properly, or for product returns,please contact Pragotrade Inc. at1-800-814-4895Outside the U.S. call 440-638-3131.For the online catalog, log onto www.westonsupply.com.Exclusively imported by Pragotrade Inc. Strongsville, Ohiowww.pragotrade.comvegiKILN Food Dehydrating System …

    vegiKILN 75-0301-W 8

  • INSTALLATION INSTRUCTIONSInstrucciones de instalaciónInstallationsanleitungInstruções de InstalaçãoIstruzioni di installazioneInstallatie-instructiesInstructions d´installationSFP WALL TRACK ACCESSORYSpanish Product DescriptionGerman Product Description Portuguese Product Description Italian Product DescriptionDutch Product DescriptionFrench Product Descr …

    KSA-1022 16

Additional Information:

Popular Right Now:
Operating Impressions, Questions and Answers:

Понравилась статья? Поделить с друзьями:
  • Антоциан форте инструкция по применению цена отзывы аналоги
  • Должностная инструкция менеджера по работе с ключевыми клиентами образец
  • Как пользоваться паркоматом в тюмени инструкция по применению
  • Руководство по выращиванию зелени
  • Dvp12se11r руководство по эксплуатации