Instruction Manual

IM-106-880, Rev 1.0

January 2007

OCX 8800

Oxygen/Combustibles Transmitter

Hazardous Area OCX 8800 Oxygen/Combustibles Transmitter

with Integral Electronics and Local Operator Interface

http://www.raihome.com

loading

Related Manuals for Emerson OCX 8800

Summary of Contents for Emerson OCX 8800

  • Page 1
    Instruction Manual IM-106-880, Rev 1.0 January 2007 OCX 8800 Oxygen/Combustibles Transmitter Hazardous Area OCX 8800 Oxygen/Combustibles Transmitter with Integral Electronics and Local Operator Interface http://www.raihome.com…
  • Page 3
    HIGHLIGHTS OF CHANGES Effective January, 2007 Rev 1.0 Page Summary Page 2-19 Revised Figure 2-11. Page 3-2 Revised the text for SW1 and SW2 to read internally powered. Page 3-3 Revised Figure 3-1. Updated the paragraph Initial Power Up. Page A-2 thru A-23 Added note 11 to the safety data section.
  • Page 5: Table Of Contents

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Table of Contents Essential Instructions……..i Preface .

  • Page 6
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 SECTION 7 Overview ……….7-1 Maintenance and Service OCX 8800 Removal and Installation.
  • Page 7: Essential Instructions

    If a Model 275/375 Universal HART Communicator is used with this unit, the software within the Model 275/375 may require modification. If a software modification is required, please contact your local Emerson Process Management Service Group or National Response Center at 1-800-654-7768. http://www.raihome.com…

  • Page 8: Preface

    The remaining sections contain detailed procedures and information necessary to install and service the transmitter. Before contacting Emerson Process Management concerning any questions, first consult this manual. It describes most situations encountered in your equipment’s operation and details necessary action.

  • Page 9: Component Checklist

    Use this complete model number for any correspondence with Emerson Process Management. A list of accessories for use with the OCX 8800 is provided in Table 1-2.

  • Page 10
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 1-1. Typical System Package MAN 4275A00 English October 1994 HART Communicator FISHER-ROSEMOUNT 1. Instruction Manual ® 2. HART Communicator Package (optional) 3. Adapter Plate with Mounting Hardware and Gasket 4. Reference Air and Calibration Set 5.
  • Page 11
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 The equipment measures oxygen percentage by reading the voltage developed across a heated electrochemical cell, which consists of a small yttria-stabilized, zirconia disc. Both sides of the disc are coated with porous metal electrodes.
  • Page 12
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 The catalyst is specifically designed to detect carbon monoxide (CO), but the sensor responds to other combustible gases. The sensor is calibrated using CO, thus the output should be expressed in terms of CO. However, since the sensor detects other combustible gases, the output cannot just be labeled CO.
  • Page 13: Sensor Housing

    OCX 8800. The DD software will be supplied with many Model 275/375 units, but can also be programmed into existing units at most Emerson Process Management service offices. Refer to Section 5, Using HART Communications, for additional information.

  • Page 14: System Considerations

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 1-2. System Operation Diagram SENSOR ELECTRONICS HOUSING HOUSING Low O Test Gas Combustibles Sensor HART Board High O Test Gas Power Supply Optional Test Gas Probe Test Gas Sensor Solenoids Eductor Instrument Air Instrument…

  • Page 15
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 After verifying that you have all the components, select mounting locations and determine how each component will be placed in terms of available line voltage, ambient temperatures, environmental considerations, convenience, and serviceability. Figure 1-3 shows a typical system wiring. Simplified installations for the OCX 8800 are shown in Figure 1-4.
  • Page 16
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 1-4. Typical System Installation Adapter OCX 8800 with Gases Plate INTEGRAL ELECTRONICS Duct Stack 4-20 mA Outputs (2 Twisted Pairs) Test Gas Flow Meter Line Voltage Instrument Air Pressure Supply Regulator (Reference Gas) Dilution…
  • Page 17: Specifications

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 SPECIFICATIONS Hazardous Area OCX Specifications Net O Range 0-1% to 0-40% O , fully field selectable Combustibles 0-1000 ppm to 0-5%, fully field selectable Accuracy Oxygen ± 0.75% of reading or 0.05% O (whichever is greater) Combustibles ±…

  • Page 18
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Specifications Sensors Housing NEMA 4, IP66 with fitting and pipe on reference exhaust port to clean, dry atmosphere, two 3/4-14 NPT conduit ports Electronics Housing NEMA 4, IP66 with fitting and pipe on reference exhaust port to clean, dry atmosphere, two 3/4-14 NPT conduit ports Electrical Noise EN 61326-1, Class A…
  • Page 19
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Table 1-1. Product Matrix — Hazardous Area OCX 8800 OCX88C /Combustibles Transmitter — Flameproof Code Probe Length and Material No Probe or Exhaust Tube 18 in. (457 mm) 316 SST up to 1300°F (704°C) 18 in.
  • Page 20
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Table 1-2. Accessories PART NUMBER DESCRIPTION 1A99119H01 Oxygen test gas bottle; 0.4% O , balance N 1A99119H02 Oxygen test gas bottle; 8.0% O , balance N 1A 99119H07 CO test gas bottle; 1000 ppm CO, balance air 1A99120H02 Regulator for Oxygen (may need 2) 1A99120H03…
  • Page 21: Installation

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Section 2 Installation Mechanical Installation ……page 2-2 Electrical Installation .

  • Page 22
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 MECHANICAL Selecting Location INSTALLATION 1. The location of the OCX 8800 in the stack or flue is most important for maximum accuracy in the oxygen analyzing process. The probe must be positioned so the gas it measures is representative of the process. Best results are normally obtained if the transmitter is positioned near the center of the duct (40-60% insertion).
  • Page 23
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 4. Ensure the conduits drop vertically from the OCX 8800 and the conduit is routed below the level of the conduit ports on the housing to form a drip loop. Drip loops minimize the possibility that moisture will damage the electronics (Figure 2-3).
  • Page 24
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 2-1. Installation, OCX 8800 NOTE All dimensions are in inches with millimeters in parentheses. Insulate if exposed to adverse weather or extreme temperature changes, 0.06 In. Thick Gasket install a protective housing and/or insulation around the unit. 3535B18H02 ANSI 3535B45H01…
  • Page 25
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 2-2. Adapter Plate Installation…
  • Page 26
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 2-3. Installation with Drip Loops Duct Wall Conduit Drip Loops Conduit Drip Loop Conduit Drip Loop Duct Wall…
  • Page 27: Electrical Installation

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 ELECTRICAL All wiring must conform to local and national codes. For reference, factory wired solenoid power connections are shown in Figure 2-4. INSTALLATION Disconnect and lock out power before connecting the unit to the power supply. Failure to lock out power could result in serious injury or death.

  • Page 28
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 NOTE To maintain proper earth grounding, ensure a positive connection exists between the sensor housing, the electronics housing, and earth. The connecting ground wire must be 14 AWG minimum. Refer to Figure 2-4. NOTE Line voltage, signal, and relay wiring must be rated for at least 105ºC (221ºF).
  • Page 29
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 2-4. Line Voltage, Earth, and 4-20 mA Connections Alarm Output Relay Terminal Block 4-20 mA Signal Output Terminal Block AOUT2+ COe Signal AOUT2 — AOUT1 — O Signal AOUT1+ Signal Port 3/4 NPT Power Port Terminal…
  • Page 30: Pneumatic Installation

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 PNEUMATIC Pneumatic system connections depend on whether reference air set, calibration solenoids, and/or blowback equipment options are equipped on INSTALLATION your transmitter. Refer to the following paragraphs and select the option that applies to your transmitter configuration.

  • Page 31
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 2-5. Pneumatic Installation, OCX with Reference Sensor Air Set (without Autocalibration) Housing CAL Gas In CAL Gas Reference Air In Flow Meter Eductor 7 scfh, 20-30 psig Air In Recommended Dilution Air In Dilution Air 2-Stage…
  • Page 32
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 2-6. Pneumatic Installation, OCX with Reference Air Set and Solenoids (with Sensor Autocalibration) Housing CAL Gas Flow Meter CAL Gas In 7 scfh, 20-30 psig Recommended Reference Air In Eductor Air In Dilution Air In…
  • Page 33
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 4. Connect the CO high gas to the CAL GAS HI COe inlet fitting. Install a shutoff valve and pressure regulator with gage in the CO high supply line. 5. Connect the CAL GAS outlet fitting of the electronics housing to the inlet port of the CAL GAS flow meter.
  • Page 34
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 2-7. Piping Arrangement, Blowback with Autocalibration Cal Gas Flow Meter Tee — (3 x 1/4 in. 7 scfh, 20-30 psig Tube Unions) Recommended CAUTION Check Pressure regulator with 1/8” inlet port is factory Valve set for 35 or 45 psig.
  • Page 35
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 2-8. Piping Arrangement, Blowback without Autocalibration CAUTION Pressure regulator with 1/8” inlet port is factory set for 35 or 45 psig. Regulator with 1/4” inlet port Check Valve is factory set for 55 psig. If regulators are not installed in correct locations, the OCX 8800 will not work.
  • Page 36: Initial Startup

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 8. Install an air line between the instrument air outlet fitting on the electronics housing and the control air inlet fitting on the air-operated solenoid valve. 9. There are three settings that need to be specified to set up the blowback option.

  • Page 37: Verify Installation

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Section 3 Configuration and Startup Verify Installation ……. . page 3-1 Initial Power Up .

  • Page 38
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Verify Configuration There are three switches on the microprocessor board which are user configurable for the OCX 8800 (Figure 3-1). SW1 determines if the O 4-20 mA signal is internally or externally powered. SW2 determines if the COe 4-20 mA signal is internally or externally powered.
  • Page 39: Initial Power Up

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 3-1. OCX 8800 Defaults Open 21.1 mA Switch Default Postions Shown 3.5 mA Closed O 21.1 mA/3.5 mA: O 4-20 mA Signal Open Rail Limits: Open High — 21.1 mA Closed Low — 3.5 mA Closed…

  • Page 40: Set Test Gas Values

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 SET TEST GAS VALUES Use HART/AMS or the optional LOI to set test gas values for calibration. Refer to Section 4, Using the LOI or Section 5, Using HART Communications for more information. Setting Test Gas Values with HART 1.

  • Page 41: Overview

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Section 4 Using the LOI Overview ……..page 4-1 Display Orientation .

  • Page 42: Loi Controls

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 LOI CONTROLS Overview The LOI, shown in Figure 4-2, utilizes a bright blue gas-fluorescent display. Intensity is adjustable. There is an Infrared LED source and a detector for each key. The detectors can detect a finger placed above the button through the glass window.

  • Page 43: Loi Status Codes

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Lockout The LOI has a lockout feature that prevents nuisance actuation by someone brushing against the glass window, raindrops, dirt, insects, etc. This lockout mode is automatically established when no buttons are pushed for 30 seconds (default).

  • Page 44: Loi Menu Tree

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 LOI MENU TREE This section consists of a menu tree for the LOI on the OCX 8800, Figure 4-4. This menu is specific to the OCX 8800. First Column Submenus From the operating display (O % and COe ppm), the left-pointing Enter key is the only option to move into the first column submenus of the LOI menu tree.

  • Page 45
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 4-4. LOI Menu Tree (Sheet 2 of 4) (CONTINUED FROM Apply Lo O2 Gas Abort Cal SHEET 1) Hit E when ready Flow O2 Lo _____s ______% _____mV Start Cal Read O2 Lo _____s CALIBRATION…
  • Page 46
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 4-4. LOI Menu Tree (Sheet 3 of 4) (CONTINUED FROM SHEET 2) O2 High Gas O2 Low Gas Calib Setup SYSTEM O2 Reset Vals Yes/No O2 Out Tracks Yes/No O2 Cal Interval O2 Next Cal COe Test Gas COe Reset Vals…
  • Page 47
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 4-4. LOI Menu Tree (Sheet 4 of 4) (CONTINUED FROM SHEET 3) O2 Slope ___ mV/D O2 Constant ___ mV O2 T90 Time ___ seconds Parameters SYSTEM COe Slope ___ ppm/ohm COe Constant ___ ohm COe T90 Time ___ seconds Lockout Time ___ seconds…
  • Page 48: D/A Trim Procedures

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 D/A TRIM PROCEDURES D/A trim procedure using the LOI Use the following procedure to perform the O D/A trim procedure at the LOI. Refer to the LOI menu tree in Figure 4-4. To avoid a potentially dangerous operating condition, the OCX 8800 must be removed from the automatic combustion control loop before you start the D/A trim procedure.

  • Page 49
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 COe D/A trim procedure using the LOI Use the following procedure to perform the COe D/A trim procedure at the LOI. Refer to the LOI menu tree in Figure 4-4. To avoid a potentially dangerous operating condition, the OCX 8800 must be removed from the automatic combustion control loop before you start the D/A trim procedure.
  • Page 50
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 4-10…
  • Page 51: Overview

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Section 5 Using HART Communications Overview ……..page 5-1 HART Communicator Signal Connections .

  • Page 52
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 5-1. Signal Line Connections, ≥ 250 Ohms Load Resistance 4-20 mA Terminal Block in Electronics Housing ≥ 250Ω O 4-20 mA Signal Line A OUT 1 + A OUT 1 — Analog Output Device Loop Connectors…
  • Page 53
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Method 2, for Load Resistance < 250 Ohms Refer to Figure 5-2 and the following steps to connect the HART communicator to a signal line with less than 250 ohms load resistance. Do not make connections to the HART communicator’s serial port, 4-20 mA signal lines, or NiCad recharger jack in an explosive atmosphere.
  • Page 54: Hart Communicator Pc Connections

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 HART COMMUNICATOR There is an option to interface the HART communicator with a personal computer. Load the designated AMS software into the PC. Then link the PC CONNECTIONS HART communicator to the PC using the interface PC adapter that connects to the serial port (on the communicator rear panel).

  • Page 55: Hart Menu Tree

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 HART MENU TREE This section consists of a menu tree for the HART communicator. This menu is specific to OCX 8800 applications. Figure 5-3. HART Menu Tree (Sheet 1 of 4) O2 Temp VIEW DEV VARS COe Temp…

  • Page 56
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 5-3. HART Menu Tree (Sheet 2 of 4) (CONTINUED FROM Status group 1 Operate Mode SHEET 1 ) O2 T/C Open Status group 1 O2 T/C Shorted Status group 2 O2 T/C Reversed Status group 3 ADC Failure…
  • Page 57
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 5-3. HART Menu Tree (Sheet 3 of 4) (CONTINUED FROM Date SHEET 2) Descriptor DEVICE Message INFORMATION Final asmbly num O2 Sensor s/n COe Sensor s/n BASIC SETUP Poll addr HART Dev id INFORMATION…
  • Page 58
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 5-3. HART Menu Tree (Sheet 4 of 4) (CONTINUED FROM SHEET 3) Manufacturer DEVICE REVIEW Model INFORMATION Date Descriptor Message Final asmbly num O2 Sensor s/n COe Sensor s/n Hardware rev Software rev HART INFORMATION…
  • Page 59: D/A Trim Procedures

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 D/A TRIM PROCEDURES D/A trim procedure using HART/AMS Use the following procedure to perform the O D/A trim procedure using the HART communicator or AMS. Refer to the HART menu tree, Figure 5-3. NOTE To select a menu item, either use the up and down arrow keys to scroll to the menu item and press the right arrow key or use the number keypad to select…

  • Page 60
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 COe D/A trim procedure using HART/AMS Use the following procedure to perform the COe D/A trim procedure using the HART communicator or AMS. Refer to the HART menu tree, Figure 5-3. NOTE To select a menu item, either use the up and down arrow keys to scroll to the menu item and press the right arrow key or use the number keypad to select…
  • Page 61: Overview

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Section 6 Calibration Overview ……..page 6-1 Fully Automatic Calibration .

  • Page 62
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 4. Scroll down to the last item Use Solenoids. If the unit is equipped with calibration solenoids and timed automatic calibration is desired, select Yes. 5. Use the up-pointing key to select the item O2 Out Tracks. Select Yes or No to determine if updates to the O lock value will take place.
  • Page 63
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 4. Select O2 CalIntrvl (O calibration interval) and enter the desired time in hours between automatic O calibrations. Select COE Callintrvl and enter the desired time between automatic COe calibrations. To disable automatic calibration for O and COe, enter 0 for both CalIntrvl parameters.
  • Page 64: Operator — Initiated Autocalibration

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 OPERATOR — INITIATED An operator can initiate an automatic calibration at any time provided that the unit is equipped with calibration solenoids. AUTOCALIBRATION Autocalibration using the LOI To initiate a calibration using the LOI, perform the following steps on the LOI menu tree.

  • Page 65
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 7. Press the right-pointing key when the low O reading is stable. Turn off the low O test gas and turn on the high O test gas as prompted by the Flow High Gas message.
  • Page 66
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 5. From the SELECT ACTION screen, select START/NEXT CALSTEP to continue calibration, select ABORT CAL to abort calibration or EXIT CAL to exit calibration. Select one item from the list and press ENTER. OCX: TAG NAME SELECT ACTION 1.
  • Page 67
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Manual COe Calibration using HART To perform a manual COe calibration using the HART communicator or AMS, use the following procedure. If necessary, refer to Section 5, Using HART Communications, for the HART menu tree. NOTE To select a menu item, either use the up and down arrow keys to scroll to the menu item and press the right arrow key or use the number keypad to select…
  • Page 68
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 9. The Calibration Status should be automatically changed to FlowCOeHi and then ReadCOeHi for a period of time. During this period, if an attempt is made to go the next calibration step by pressing OK and selecting Start/Next Cal Step, you will be prompted with Operator step command is not accepted at this time.
  • Page 69
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 5. From the SELECT ACTION screen, select START/NEXT CALSTEP to continue calibration, select ABORT CAL to abort calibration or EXIT CAL to exit calibration. Select one from the list and press ENTER. OCX: TAG NAME SELECT ACTION 1.
  • Page 70
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 6-10…
  • Page 71: Overview

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Section 7 Maintenance and Service Overview ……..page 7-1 OCX 8800 Removal and Installation .

  • Page 72: Ocx With

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 OCX with Remove OCX 8800 Integral Electronics 1. Turn off power to the system. 2. Shut off the test gases at the cylinders and shut off the instrument air. 3. Disconnect the test gas and instrument air lines from the electronics housing, Figure 7-1.

  • Page 73
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 7-2. Electronics Housing Terminal Blocks Alarm Output Relay Terminal Block 4-20 mA Signal Output Terminal Block AOUT2+ COe Signal AOUT2 — AOUT1 — O Signal AOUT1+ Signal Port 3/4 NPT Power Port Terminal 3/4 NPT…
  • Page 74
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Install OCX 8800 Observe the following cautions when installing the OCX 8800 in a hot process stack. If the process is shut down and cooled, the transmitter can be installed in the stack prior to connecting the pneumatics and wiring. Before installing the OCX 8800 into a hot stack or ductwork, make sure that the OCX 8800 is turned on and at normal operating temperature.
  • Page 75: Repair Sensor Housing

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 REPAIR SENSOR Use the following procedures to remove damaged components from the OCX 8800 sensor housing and to install new replacement parts. Disassemble the HOUSING unit only as needed to replace damaged components. Use the assembly procedures that apply to install replacement parts and reassemble the unit.

  • Page 76
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 7-3. Removal of O Cell and Heater Strut Assembly 1. Screw 2. Locking Clip 3. Cover 4. O-ring 5. Marking Plate 6. Terminal Insulator 7. Reference Air Tube 8. Sensor Housing 9.
  • Page 77
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 7-4. O Cell, Thermocouple, and O Cell Wires Heater Connections O Heater Wires Thermocouple Wires T/C O2 T/C CO O Cell and Heater Strut Assembly T/C SB Sample Block Sample Block Thermo- Heater Rods couple…
  • Page 78
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 2. Loosen screws (11, Figure 7-3) and rotate heater clamps (12) to release heater rods (13). One heater clamp secures each heater rod. 3. Slide sample block heater rods (13) out of housing (8). 4.
  • Page 79
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 NOTE For easier access, you may remove two screws from base of terminal block mounting (13) and move terminal block assembly out of the way. 3. Remove tubes (2, 3, and 4) from COe sensor assembly (5), eductor fittings (12 and 15), and sensor housing (7).
  • Page 80
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 6. See Figure 7-7. Using straightedge on the sensor holder flat, as shown, matchmark upper flange of sensor housing to show correct alignment of sensor holder. 7. With one wrench holding eductor elbow (12, Figure 7-6), and one wrench on flats of sensor holder (11), unthread and remove COe sensor assembly (5).
  • Page 81
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Remove Eductor The O cell and heater strut assembly (9, Figure 7-3) and the COe sensor assembly (5, Figure 7-6) must be removed before you start this procedure. 1. Use straightedge to matchmark alignment of eductor flat and elbow, as shown in Figure 7-8.
  • Page 82
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 7-9. Removal of Sample Remove Sample and Exhaust Tubes and Exhaust Tubes Use heat resistant gloves when removing the probe tube or exhaust tube. The tubes are bonded with a thread sealing compound. The compound softens at 450°F (232°C). The heated parts can cause severe burns.
  • Page 83
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 7-10. O Cell, Heater, and Thermocouple, Exploded View Do not remove the O cell unless you are certain it needs to be replaced. Removal may damage the cell and platinum pad. Remove the O cell for cell replacement only.
  • Page 84
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Disassemble COe Sensor Assembly 1. Carefully remove screws (1, Figure 7-11), lockwashers (2), and COe sensor (3) from sensor holder (4). Remove and discard gasket (5). 2. If damaged, use the following procedure to remove thermocouple adaptor (6) from sensor holder (4): a.
  • Page 85: Sensor Housing Assembly

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Always remove the stainless steel balls (approximately 200) from sensor holder before removing or installing pre-heater. Turning pre-heater in the sensor holder with the stainless steel balls in place will cause permanent damage to the pre-heater. 3.

  • Page 86
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 7-12. COe Sensor and Pre-Heater Alignment SENSOR ASSEMBLY THERMOCOUPLE TOP VIEW COe Sensor Flat Sensor Holder Pre-Heater Sensor Flat Holder Flat Sensor Holder Flat 2 to 2-1/4 in. (51 to 57 mm) 7.
  • Page 87
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Install Eductor If installed, the O cell and heater strut assembly (9, Figure 7-3) must be removed from sensor housing (8), before you install the eductor. 1. Apply pipe thread sealant (Loctite #567) to the external pipe threads of eductor (6, Figure 7-13).
  • Page 88
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 2. Install and tighten eductor (6) in eductor holder (14). 3. Install and tighten elbow (12) on eductor (6). Male port of elbow must point up and be in line with long axis of eductor. 4.
  • Page 89
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Install COe Sensor Assembly Figure 7-15. Band Heater Height 1. Apply pipe thread sealant (Loctite #567) to the exposed pipe threads of eductor elbow (12, Figure 7-13). Do not apply sealant to the first turn of the pipe threads.
  • Page 90
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 7-16. COe Sensor Holder Alignment Matchmark Straightedge Sensor Holder Flat Matchmark 7-20…
  • Page 91
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 10. Reconnect the COe sensor, thermocouple, and heater wires at the sensor housing terminal blocks. Refer to Figure 7-17. 11. Install and fasten the COe insulator (1, Figure 7-13) around COe sensor assembly (5).
  • Page 92
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 7-18. Installation of O Cell and Heater Strut Assembly 1. Screw 2. Locking Clip 3. Cover 4. O-ring 5. Marking Plate 6. Terminal Insulator 7. Reference Air Tube 8. Sensor Housing 9.
  • Page 93
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 7-19. O Cell, Thermocouple, and O Cell Wires Heater Connections O Heater Wires Thermocouple Wires T/C O2 T/C CO O Cell and Heater Strut Assembly T/C SB Sample Block Sample Block Thermo- Heater Rods couple…
  • Page 94
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Install O Cell and Heater Strut Assembly 1. Rub a small amount of anti-seize compound on both sides of new gasket (10, Figure 7-18). 2. Apply anti-seize compound to threads of O cell and heater strut assembly (9) and sensor housing (8).
  • Page 95: Repair Electronics Housing

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 REPAIR ELECTRONICS Use the following procedures to remove damaged components from the OCX 8800 electronics housing and to install new replacement parts. Disassemble HOUSING the unit only as needed to replace damaged components. Use the assembly procedures that apply to install replacement parts and reassemble the unit.

  • Page 96
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 7-20. Removal/Installation of Electronics Housing Components 1. Screw 2. Locking Clip 3. Cover 4. O-ring 5. Electronics Stack 6. Flash PROM 7. Screw 8. LOI Module 9. LOI Board 10. LOI Connector 11.
  • Page 97
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Remove Solenoid Valves 1. Disconnect solenoid leads from mating terminal connector. 2. Remove top nut of solenoid valve (15 or 16, Figure 7-20). 3. Remove the solenoid coil assembly and washer. 4.
  • Page 98: Electronics Housing Assembly

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Electronics Housing Install EMI Filter and Terminal Block Assembly 1. Install replacement EMI filter (1, Figure 7-21) and/or terminal block (3) on electronic stack. 2. Refer to wiring details in Figure 7-21. Connect EMI filter wiring and ground wire (2) at terminal block (3).

  • Page 99
    O2 CELL+ O2 CELL- CO REF+ CO REF- CJC+ O2 Cell CJC- & Thermocouple EXC- Connector (J5) To Ground ELECTRONICS HOUSING SHLD Screw Signal Cable NOTE: Wire colors shown are for cables supplied Heater by Emerson Process Management. Power Cable 7-29…
  • Page 100
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 7-24. Solenoid Power Terminals SOL 4 CO Test Gas SOL 3 High O Test Gas TOP VIEW SOL 3 Low O Test Gas SOL 2 Instrument Air SOL 1 Install Cover 1.
  • Page 101: Replace Tube Fittings

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 REPLACE TUBE The OCX transmitter housings have special tube fittings that, if clogged or damaged, must be replaced with the same type of fitting. The special tube FITTINGS fittings have alpha or numeric codes etched on the fitting. Unetched tube fittings are standard 1/4 inch, stainless steel fittings.

  • Page 102: Install Tube Fittings

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 7-25. Removal of Tube Fittings 1. Sensor Housing 2. Electronics Housing 3. Tube Fitting . Tube Fitting (Type R) . Tube Fitting (Type 13) 6. Tube Fitting (Type F) Install Tube Fittings 1.

  • Page 103: Overview

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Section 8 Troubleshooting Overview ……..page 8-1 Diagnostic Alarms .

  • Page 104: Total Power Loss

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Total Power Loss In the event that the OCX 8800 will not power up at all, check the incoming power supply to make sure power is being delivered to the OCX 8800. If the incoming power supply is good, then check fuses F1 and F6 in the electronics housing.

  • Page 105: Fault Isolation

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 FAULT ISOLATION Faults in the OCX 8800 Transmitter are indicated by messages displayed on the HART communicator or LOI. Fault indications that can appear are listed in Table 8-1, Troubleshooting. If a fault is indicated on the HART communicator or LOI, locate the fault indication in Table 8-1.

  • Page 106
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 SB Temp Hi (Sample block heater temperature high, > 190ºC) Probable Cause Recommended Corrective Action High noise in OCX power supply Check power supply for line noise or voltage fluctuations. Install power line filter kit (PN 6A00171G01) or high quality line filter for input power.
  • Page 107
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 SB TC Open (Sample block heater thermocouple open) Probable Cause Recommended Corrective Action Sample block thermocouple or thermocouple Check sample block thermocouple and circuit wires for breaks or loose connections per circuit open Figure 8-3 and Figure 7-4.
  • Page 108
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 ADC Failure (Voltage to digital conversion could not complete) ADC Ref Error (Voltage to digital conversion not accurate) Probable Cause Recommended Corrective Action Incorrect wiring between electronics and sensor Check all wiring between the electronics and sensor housings per Figure 8-3. Correct housings wiring faults.
  • Page 109
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Cal Warning (Calibration warning) Cal Failed (Calibration failed) Probable Cause Recommended Corrective Action Calibration gas supply low or gas connection Check calibration gas supplies and connections. Adjust gas pressure and flow. leaking Replenish low calibration gas supplies and tighten or repair loose or leaking connections.
  • Page 110
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Board Temp Hi (Electronics temperature maximum exceeded, > 85ºC) Probable Cause Recommended Corrective Action Electronics housing exposed to high ambient Insulate housing from source of high temperature and/or install cooling fan to remove temperature heat from housing.
  • Page 111
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Line Voltage High (AC power line voltage above maximum, > 278 VAC) Probable Cause Recommended Corrective Action High noise or voltage fluctuations in power Check power supply for line noise or voltage fluctuations. Install power line filter kit supply (PN 6A00171G01) or high quality line filter for input power.
  • Page 112
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 8-3. Electrical Connections Between Electronics and Sensor Housing 2HTR CO 1HTR CO 2HTR O 1HTR O 2HTR SB ground 1HTR SB screw Heater Power Connector (J3) T/C CO+ T/C CO- T/C SB+ T/C SB- T/C O2+…
  • Page 113: Alarm Relay Events

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 ALARM RELAY EVENTS The OCX 8800 contains an alarm relay that can be configured to activate on one of twelve different groups of events. These event groups, and the conditions that trigger them, are listed in Table 8-2, Alarm Relay Event Groups.

  • Page 114
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 8-12…
  • Page 115
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Section 9 Replacement Parts Sensor Housing ……..page 9-2 Electronics Housing .
  • Page 116: Sensor Housing

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 SENSOR HOUSING Figure 9-1. Sensor Housing Components (Requires item 13 for assembly)

  • Page 117
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Index No. Part Number Description 5R10190G02 Cell and Heater Assembly 6P00177H01 Heater Insulator, Mica 4851B46G03 Combustibles Sensor Replacement Kit 1A99786H01 Heater Leads Insulator, 11 inches long 6P00163H01 COe Insulator 1A99746H02 Band Heater 1A99749H01 Thermocouple 1A99747H01…
  • Page 118
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 9-2. Sensor Housing Components…
  • Page 119
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Index No. Part Number Description 1A99089H02 Cover Gasket (O-ring) 5R10246H02 Blowback Filter 1A98448H02 O-ring 5R10247H01 Adaptor 5R10183H02 Tube, Sample, 18 in. (457 mm) 316 Stainless steel 5R10183H06 Tube, Sample, 18 in. (457 mm) Inconel 600 5R10227G01 Tube, Sample, 18 in.
  • Page 120: Electronics Housing

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 ELECTRONICS HOUSING Figure 9-3. Electronics Housing Components…

  • Page 121
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Index No. Part Number Description 1A97902H01 Hose 1A97905H02 Solenoid Valve, 3-Way 1A97905H01 Solenoid Valve, Test Gas 6A00132G01 Electronics Stack, HART Special Order Flash PROM, Programmed 1A97913H06 Fuse (F1 and F6), 10 Amp, 250 VAC 1A99766H01 Fuse (F3), 4 Amp, 250 VAC 1A99766H02…
  • Page 122
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure 9-4. EMI Filter and Terminal Block Blue Brown Blue Brown Green Green Green Index No. Part Number Description 1A98467H01 Filter, EMI 5R10238G01 Ground Wire 1A99714H01 Terminal Block…
  • Page 123: O2 Cell And Heater Strut Assembly

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 CELL AND HEATER STRUT ASSEMBLY Figure 9-5. O Cell and Heater Strut Assembly Index No. Part Number Description 4851B44G01 Contact and Thermocouple Assembly 5R10211G02 Heater Strut Assembly 5R10188G01 Heater Tube Gasket (part of O Cell Replacement Kit, item 7) Cell (part of O Cell Replacement Kit, item 7)

  • Page 124
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 9-10…
  • Page 125
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Appendix A Safety Data Safety Instructions ……..page A-2 Safety Data Sheet for Ceramic Fiber Products .
  • Page 126: Safety Instructions

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 IMPORTANT SAFETY INSTRUCTIONS SAFETY INSTRUCTIONS FOR THE WIRING AND INSTALLATION OF THIS APPARATUS The following safety instructions apply specifically to all EU member states. They should be strictly adhered to in order to assure compliance with the Low Voltage Directive.

  • Page 127
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 DŮLEŽITÉ Bezpečnostní pokyny pro zapojení a instalaci zařízení Následující bezpečnostní pokyny se speciálně vztahují na všechny členské státy EU. Pokyny by měly být přísně dodržovány, aby se zajistilo splnění Směrnice o nízkém napětí. Pokud nejsou pokyny nahrazeny místními či národními normami, měly by je dodržovat i nečlenské…
  • Page 128
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 VIGTIGT Sikkerhedsinstruktion for tilslutning og installering af dette udstyr. Følgende sikkerhedsinstruktioner gælder specifikt i alle EU-medlemslande. Instruktionerne skal nøje følges for overholdelse af Lavsspændingsdirektivet og bør også følges i ikke EU-lande medmindre andet er specificeret af lokale eller nationale standarder.
  • Page 129
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 BELANGRIJK Veiligheidsvoorschriften voor de aansluiting en installatie van dit toestel. De hierna volgende veiligheidsvoorschriften zijn vooral bedoeld voor de EU lidstaten. Hier moet aan gehouden worden om de onderworpenheid aan de Laag Spannings Richtlijn (Low Voltage Directive) te verzekeren. Niet EU staten zouden deze richtlijnen moeten volgen tenzij zij reeds achterhaald zouden zijn door plaatselijke of nationale voorschriften.
  • Page 130
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 BELANGRIJK Veiligheidsinstructies voor de bedrading en installatie van dit apparaat. Voor alle EU lidstaten zijn de volgende veiligheidsinstructies van toepassing. Om aan de geldende richtlijnen voor laagspanning te voldoen dient men zich hieraan strikt te houden. Ook niet EU lidstaten dienen zich aan het volgende te houden, tenzij de lokale wetgeving anders voorschrijft.
  • Page 131
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 WICHTIG Sicherheitshinweise für den Anschluß und die Installation dieser Geräte. Die folgenden Sicherheitshinweise sind in allen Mitgliederstaaten der europäischen Gemeinschaft gültig. Sie müssen strickt eingehalten werden, um der Niederspannungsrichtlinie zu genügen. Nichtmitgliedsstaaten der europäischen Gemeinschaft sollten die national gültigen Normen und Richtlinien einhalten.
  • Page 132
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 ΣΗΜΑΝΤΙΚΟ Οδηγιεσ ασφαλειασ για την καλωδιωση και εγκατασταση τησ συσκευησ Οι ακόλουθες οδηγίες ασφαλείας εφαρµόζονται ειδικά για όλες τις χώρες µέλη της Ευρωπαϊκής Κοινότητας. Θα πρέπει να ακολουθούνται αυστηρά ώστε να εξασφαλιστεί η συµβατότητα µε τις οδηγίες για τη Χαµηλή Τάση. Χώρες…
  • Page 133
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 OLULINE TEAVE Juhtmestiku ja seadme paigaldamisega seotud ohutusjuhised Alljärgnevad ohutusjuhised rakenduvad eriti kõigi Euroopa Liidu liikmesriikide suhtes. Antud juhiseid tuleb täpselt järgida, et kindlustada vastavus madalpinge direktiiviga. Euroopa Liitu mittekuuluvad riigid peavad samuti alljärgnevaid juhiseid järgima, va juhul, kui on olemas vastavad kohalikud riiklikud standardid.
  • Page 134
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 TÄRKEÄÄ Turvallisuusohje, jota on noudatettava tämän laitteen asentamisessa ja kaapeloinnissa. Seuraavat ohjeet pätevät erityisesti EU:n jäsenvaltioissa. Niitä täytyy ehdottomasti noudattaa jotta täytettäisiin EU:n matalajännitedirektiivin (Low Voltage Directive) yhteensopivuus. Myös EU:hun kuulumattomien valtioiden tulee nou-dattaa tätä…
  • Page 135
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 IMPORTANT Consignes de sécurité concernant le raccordement et l’installation de cet appareil. Les consignes de sécurité ci-dessous s’adressent particulièrement à tous les états membres de la communauté européenne. Elles doivent être strictement appliquées afin de satisfaire aux directives concernant la basse tension.
  • Page 136
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 FONTOS Biztonsági előírások a készülék vezetékeléséhez és üzembeállításához A következő biztonsági előírások kifejezetten vonatkoznak az összes EU-tagállamra. Ezeket szigorúan be kell tartani a Kisfeszültségű irányelvnek való megfelelés biztosításához. A nem EU-tagállamok szintén tartsák be a következőket, kivéve ha a helyi és nemzeti szabványok azt másként nem írják elő.
  • Page 137
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 IMPORTANTE Norme di sicurezza per il cablaggio e l’installazione dello strumento. Le seguenti norme di sicurezza si applicano specificatamente agli stati membri dell’Unione Europea, la cui stretta osservanza è richiesta per garantire conformità…
  • Page 138
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 SVARBU š io prietaiso laidų prijungimo ir instaliacijos saugos instrukcijos Toliau išvardinti saugumo reikalavimai taikomi konkrečiai visoms ES šalims narėms. Jų turi būti griežtai paisoma, kad būtų užtikrintai laikomasi Žemos įtampos direktyvos. Ne ES narės taip pat turi laikytis toliau pateikiamų…
  • Page 139
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 SVARĪGI Droš ības norādījumi š īs iekārtas pievienoš anai un uzstādīš anai Turpmākie drošības norādījumi attiecas uz visām ES dalībvalstīm. Tie ir stingri jāievēro, lai nodrošinātu atbilstību Zemsprieguma direktīvai. Turpmāk norādītais jāievēro arī valstīs, kas nav ES dalībvalstis, ja vien šos norādījumus neaizstāj vietējie vai valsts standarti.
  • Page 140
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 IMPORTANTI STRUZZJONIJIET TAS-SIGURTÀ GĦALL-WIRING U L-INSTALLAZZJONI TAT-TAGĦMIR L-istruzzjonijiet tas-sigurtà japplikaw speċifikament għall-Istati Membri ta’ l-UE. Dawn għandhom jiġu osservati b’mod strett biex tkun żgurata l- konformità mad-Direttiva dwar il-Vultaġġ Baxx. Stati li mhumiex membri ta’ l-UE għandhom ukoll ikunu konformi ma’ dan li ġej ħlief jekk dawn ikunu sostituti mill-Istandards lokali jew Nazzjonali.
  • Page 141
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 VIKTIG Sikkerhetsinstruks for tilkobling og installasjon av dette utstyret. Følgende sikkerhetsinstruksjoner gjelder spesifikt alle EU medlemsland og land med i EØS-avtalen. Instruksjonene skal følges nøye slik at installasjonen blir i henhold til lavspenningsdirektivet. Den bør også følges i andre land, med mindre annet er spesifisert av lokale- eller nasjonale standarder.
  • Page 142
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 WAŻNE! Zalecenia dotyczące bezpieczeństwa w zakresie podłączania i instalacji tego urządzenia Następujące zalecenia dotyczą zwłaszcza stosowania urządzenia we wszystkich krajach Unii Europejskiej. Należy się ściśle do nich stosować w celu zapewnienia zgodności z dyrektywą niskonapięciową. W przypadku instalacji urządzenia w krajach nienależących do Unii Europejskiej należy również…
  • Page 143
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 IMPORTANTE Instruções de segurança para ligação e instalação deste aparelho. As seguintes instruções de segurança aplicam-se especificamente a todos os estados membros da UE. Devem ser observadas rigidamente por forma a garantir o cumprimento da Directiva sobre Baixa Tensão. Relativamente aos estados que não pertençam à…
  • Page 144
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 DÔLEŽITÉ Bezpečnostné pokyny pre zapojenie káblov a inš taláciu tohto prístroja Nasledovné bezpečnostné pokyny sa vzt’ahujú konkrétne na všetky členské štáty EÚ. Musia byt’ striktne dodržané, aby sa zaistila zhoda so Smernicou o nízkom napätí.
  • Page 145
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 POMEMBNO Varnostna navodila za povezavo in vgradnjo naprave Naslednja varnostna navodila veljajo za vse države članice EU. Zaradi zagotovitve skladnosti z nizkonapetostno direktivo morate navodila strogo upoštevati. V državah, ki niso članice EU, je treba upoštevati tudi naslednje smernice, razen če jih ne zamenjujejo lokalni ali nacionalnimi standardi.
  • Page 146
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 IMPORTANTE Instrucciones de seguridad para el montaje y cableado de este aparato. Las siguientes instrucciones de seguridad, son de aplicacion especifica a todos los miembros de la UE y se adjuntaran para cumplir la normativa europea de baja tension.
  • Page 147
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 VIKTIGT Säkerhetsföreskrifter för kablage och installation av denna apparat. Följande säkerhetsföreskrifter är tillämpliga för samtliga EU-medlemsländer. De skall följas i varje avseende för att överensstämma med Lågspännings direktivet. Icke EU medlemsländer skall också…
  • Page 148: Safety Data Sheet For Ceramic Fiber Products

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 SAFETY DATA SHEET JULY 1, 1996 FOR CERAMIC FIBER SECTION I. IDENTIFICATION PRODUCTS PRODUCT NAME Ceramic Fiber Heaters, Molded Insulation Modules and Ceramic Fiber Radiant Heater Panels. CHEMICAL FAMILY Vitreous Aluminosilicate Fibers with Silicon Dioxide. CHEMICAL NAME N.A.

  • Page 149
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 SECTION III. HAZARDOUS INGREDIENTS MATERIAL, QUANTITY, AND THRESHOLD/EXPOSURE LIMIT VALUES Aluminosilicate (vitreous) 99+ % 1 fiber/cc TWA CAS. No. 142844-00-0610 fibers/cc CL Zirconium Silicate0-10% 5 mg/cubic meter (TLV) Black Surface Coating**0 — 1% 5 mg/cubic meter (TLV) Armorphous Silica/Silicon Dioxide0-10% 20 mppcf (6 mg/cubic meter) PEL (OSHA 1978) 3 gm cubic meter (Respirable dust): 10 mg/cubic meter,…
  • Page 150
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 EXPOSURE TO USED CERAMIC FIBER PRODUCT Product which has been in service at elevated temperatures (greater than 1800ºF/982ºC) may undergo partial conversion to cristobalite, a form of crystalline silica which can cause severe respiratory disease (Pneumoconiosis).
  • Page 151
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 The International Agency for Research on Cancer (IARC) reviewed the carcinogenicity data on man-made vitreous fibers (including ceramic fiber, glasswool, rockwool, and slagwool) in 1987. IARC classified ceramic fiber, fibrous glasswool and mineral wool (rockwool and slagwool) as possible human carcinogens (Group 2B).
  • Page 152
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 SECTION VIII. SPECIAL PROTECTION INFORMATION RESPIRATORY PROTECTION Use NIOSH or MSHA approved equipment when airborne exposure limits may be exceeded. NIOSH/MSHA approved breathing equipment may be required for non-routine and emergency use. (See Section IX for suitable equipment).
  • Page 153: High Pressure Gas Cylinders

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 IARC has recently reviewed the animal, human, and other relevant experimental data on silica in order to critically evaluate and classify the cancer causing potential. Based on its review, IARC classified crystalline silica as a group 2A carcinogen (probable human carcinogen).

  • Page 154
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 2. Cylinders may be stored in the open, but in such cases, should be protected against extremes of weather and, to prevent rusting, from the dampness of the ground. Cylinders should be stored in the shade when located in areas where extreme temperatures are prevalent.
  • Page 155: Atex Clarification

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 ATEX CLARIFICATION ATEX COMPLIANT GAS ANALYSIS PERFORMED WITHIN A FLAMEPROOF ENCLOSURE Special conditions apply to using a flameproof enclosure analyzer under the scope of the “European Directive for Equipment used in Explosive Atmosphere”…

  • Page 156
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 A-32…
  • Page 157: Overview

    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Appendix B SPA with HART Alarm Overview ……..page B-1 Description .

  • Page 158: Installation

    Jumper and Switch Settings SPA jumper and switch settings are shown in Figure B-3. If the SPA with HART was factory-configured by Emerson Process Management for operation with your OCX 8800, jumper and switch setting adjustments are not required. However, you may use the following procedure to verify that the jumper and switch settings are correct.

  • Page 159
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure B-3. SPA Jumper and Dip Switch Settings NOTICE REMOVE THIS PANEL FOR SERVICE ACCESS. Access Cover STATIC SENSITIVE. USE CAUTION WHEN CHANGING JUMPERS SPA — Bottom View Password Jumper Pins Password Password Source Current Dip Switches…
  • Page 160
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 NOTE The O signal connection is not required for SPA configuration or calibration. The OCX interface will allow you to observe the O signal level when the SPA configuration procedure is completed. 4.
  • Page 161
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 5. Figure B-6 shows the SPA menu, submenus, and parameter values that must be selected to configure the SPA for use with the OCX 8800. Use the following instructions and selections shown to properly configure the SPA.
  • Page 162
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Figure B-6. SPA Configuration Menu for OCX 8800 Communication Ü SET MSTR Ü ô PRIM SCLE INPT Ü SET FUCT Ü ô NRML HART Ü NUM VARS Ü ô 02 Ü PV DSPL Ü…
  • Page 163: Returning Material

    If failure was due to conditions listed in the standard Rosemount Analytical warranty, the defective unit will be repaired or replaced at Emerson Process Management’s option, and an operating unit will be returned to the customer in accordance with shipping instructions furnished in the cover letter.

  • Page 164
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007…
  • Page 165
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 Index Symbols Electrostatic Discharge ..8-1 Essential Instructions ..i «Z» pattern ….4-3 Manual Calibration, HART 6-5, 6-7, 6-8 Manual Calibration, LOI .
  • Page 166
    Instruction Manual IM-106-880, Rev 1.0 OCX 8800 January 2007 RTD ….. . 1-3 Sample and Exhaust Tubes 7-12, 7-16 Sample Block Heater Rods 7-7, 7-22 Selected Distributed Control Systems Sensor Housing Components 9-2, 9-4 Sensor Housing Disassembly .
  • Page 167
    WARRANTY Rosemount Analytical warrants that the equipment manufactured and sold by it will, upon shipment, be free of defects in workmanship or material. Should any failure to conform to this warranty become apparent during a period of one year after the date of shipment, Rosemount Analytical shall, upon prompt written notice from the purchaser, correct such nonconformity by repair or replacement, F.O.B.
  • Page 168
    Republic of Singapore England T 713 467 6000 T 65 6 777 8211 T 44 1243 863121 F 713 827 3329 F 65 6 777 0947 F 44 1243 845354 E analytical@ ap.emersonprocess.com http://www.raihome.com © 2007 Emerson Process Management. All rights reserved.

This manual is also suitable for:

Rosemount ocx 8800

Как пользоваться?

Наша цель — обеспечить Вам самый быстрый доступ к руководству по эксплуатации устройства Emerson ROSEMOUNT OCX 8800. Пользуясь просмотром онлайн Вы можете быстро просмотреть содержание и перейти на страницу, на которой найдете решение своей проблемы с Emerson ROSEMOUNT OCX 8800.

Для Вашего удобства

Если просмотр руководства Emerson ROSEMOUNT OCX 8800 непосредственно на этой странице для Вас неудобен, Вы можете воспользоваться двумя возможными решениями:

  • Полноэкранный просмотр -, Чтобы удобно просматривать инструкцию (без скачивания на компьютер) Вы можете использовать режим полноэкранного просмотра. Чтобы запустить просмотр инструкции Emerson ROSEMOUNT OCX 8800 на полном экране, используйте кнопку Полный экран.
  • Скачивание на компьютер — Вы можете также скачать инструкцию Emerson ROSEMOUNT OCX 8800 на свой компьютер и сохранить ее в своем архиве. Если ты все же не хотите занимать место на своем устройстве, Вы всегда можете скачать ее из ManualsBase.

Руководство по эксплуатации Emerson ROSEMOUNT OCX 8800

Печатная версия

Многие предпочитают читать документы не на экране, а в печатной версии. Опция распечатки инструкции также предусмотрена и Вы можете воспользоваться ею нажав на ссылку, находящуюся выше — Печатать инструкцию. Вам не обязательно печатать всю инструкцию Emerson ROSEMOUNT OCX 8800 а только некоторые страницы. Берегите бумагу.

Резюме

Ниже Вы найдете заявки которые находятся на очередных страницах инструкции для Emerson ROSEMOUNT OCX 8800. Если Вы хотите быстро просмотреть содержимое страниц, которые находятся на очередных страницах инструкции, Вы воспользоваться ими.

Назначение
Описание
Программное обеспечение
Знак утверждения типа
Поверка
Сведения о методах измерений
Рекомендации к применению

Назначение

Газоанализаторы OCX 8800, 5081 FG (далее — газоанализаторы) предназначены для непрерывного измерения содержания кислорода и продуктов неполного сгорания в дымовых газах, образующихся при сжигании топлива в котельных, теплоэлектростанциях, в печах для сжигания мусора, установках для отжига.

Описание

Принцип действия газоанализаторов основан на электрохимическом определении содержания кислорода (OCX 8800, 5081 FG) и термокаталитическом определении содержания продуктов сгорания в пересчете на оксид углерода. (OCX 8800).

Конструктивно газоанализаторы 5081 FG представляет собой керамическую трубку, на одном конце которой внутри расположен сенсор из оксида циркония, на другой -устройство для подачи градуировочного газа и электронный блок. Внешняя защитная трубка изготавливается в зависимости от температуры анализируемой среды из алюминия, муллита или других сплавов.

Газоанализаторы OCX 8800 состоят из двух блоков: аналитического и электронного. Каждый блок помещен в собственный корпус. Конструкция газоанализаторов OCX 8800 позволяет легко заменить при неисправностях сенсоры и электронику в полевых условиях. Электронный блок газоанализаторов OCX 8800 может монтироваться непосредственно на аналитическом блоке или отдельно на расстоянии до 45 м. Отбор пробы производится при помощи воздушного аспиратора.

Для измерения содержания кислорода в газоанализаторах OCX 8800, 5081 FG использованы сенсоры из оксида циркония, принцип действия которых основан на уравнении Нернста. Необходимая для реализации этого метода температура измерительной ячейки в моделях OCX 8800 обеспечивается нагревателем. В газоанализаторе 5081 FG для нагрева измерительной ячейки до необходимой температуры используется измеряемый газ.

Термокаталитический сенсор включает два терморезисторных элемента, один из которых покрыт инертным материалом и является сравнительным, другой покрыт катализатором и является активным элементом.

При прохождении через сенсор продукты сгоревшие неполностью в результате технологического процесса окисляются на поверхности катализатора, что сопровождается выделением тепла, повышением температуры активного элемента и изменением его сопротивления. Разность сопротивлений между двумя элементами пропорциональна суммарному содержанию продуктов неполного сгорания в анализируемом газе. Термокаталитический сенсор градуируют по оксиду углерода и, соответственно, результаты измерений содержания продуктов неполного сгорания выражаются в объемной доле оксида углерода.

Газоанализаторы устанавливают непосредственно в дымовой трубе. Измерения выполняют при высоких температурах, соответствующих условиям протекания технологического процесса.

Программное обеспечение

Идентификационные данные программного обеспечения приведены в таблице 1. Таблица 1

Наименование

программного

обеспечения

Идентифика

ционное

наименование

программного

обеспечения

Номер версии (идентификационный номер) программного обеспечения

Цифровой идентификатор программного обеспечения (контрольная сумма исполняемого кода)

Алгоритм

вычисления

цифрового

идентификатора

программного

обеспечения

Flash,

Programmed, OCX 8800 CPU

Flash,

Programmed, OCX 8800 CPU ver.# 6.02.006

ver.# 6.02.006

0027B727

MD5

Prom,

Programmed, 5081FG HART CPU

Prom,

Programmed, 5081FG HART CPU

ver.# 2.10.0

ver.# 2.10.0

02E85A00

MD5

Уровень защиты ПО от непреднамеренных и преднамеренных изменений по МИ 2955-2010 соответствует уровню:

— «А» — не требуется специальных средств защиты, исключающих возможность несанкционированной модификации, обновления (загрузки), удаления и иных преднамеренных изменений метрологически значимой встроенной части ПО СИ и измеренных данных.

Программное обеспечение не влияет на метрологические характеристики газоанализаторов.

Основные метрологические и технические характеристики приборов приведены в таблице 2.

Таблица 2

ОСХ 8800

5081 FG

Диапазон измерений:

—    объемной доли кислорода, %

—    объемной доли продуктов

сгорания в пересчете на оксид

углерода,

-1

млн

%

0 — 1 0 — 40

0 — 1000 0 — 5

0 — 25

Пределы допускаемых значений абсолютной погрешности измерений объемной доли кислорода, %

± 0,1

(в диапазонах 0 — 1, 0 — 2,5)

± 0,1

(в диапазоне 0 — 2,5)

Пределы допускаемых значений относительной погрешности измерений объемной доли кислорода, %

± 4

(в диапазоне св. 2,5 — 40)

± 1,5

(в диапазоне св. 2,5 — 25)

Пределы допускаемых значений приведенных к верхнему пределу диапазона погрешности измерений объемной доли продуктов сгорания в пересчете на оксид углерода, %

± 3

Время установления показаний, To,9, с

—    по каналу кислорода, %

—    по каналу продуктов сгорания

10

25

10

Параметры питания

110 В / 240 В, 48 — 62 Гц

от 12 В до 30 В пост. тока

Потребляемая мощность, Вт, не более

800

0,9

Длина зонда, м

от 0,46 до 2,74

от 0,46 до 1,22

Масса, кг, не более

22

4,5

Условия применения:

—    температура анализируемого газа, оС

—    температура окружающей среды, оС

аналитический блок электронный блок

от 0 до 1427

от минус 40 до 100 от минус 40 до 65

от 550 до 1400

от минус 40 до 149 от минус 20 до 65

Знак утверждения типа

наносится на газоанализаторы способом наклейки и титульный лист руководства по эксплуатации типографским способом.

Комплектность поставки газоанализаторов приведена в таблице 3: Таблица 3

Наименование

Количество

1. Газоанализатор OCX 8800 или 5081 FG

1 экземпляр

2. Комплект ЗИП

1 комплект

3. Эксплуатационная документация

1 комплект

4. Инструкция по поверке

1 экземпляр

Поверка

осуществляется в соответствии с документом «Инструкция. Газоанализаторы OCX 8800, 5081 FG. Методика поверки», утвержденным ГЦИ СИ ФГУП «ВНИИМС» в 2012 г. Основные средства поверки:

— ГСО 3854-87, ГСО 9125-08 на CO и ГСО 3712-87, ГСО 3716-87, ГСО 3717-87, ГСО 3728-87, O2 по ТУ 6-16-2956-01.

Сведения о методах измерений

Руководства по эксплуатации на газоанализаторы OCX 8800 и 5081 FG.

Нормативные документы, устанавливающие требования к газоанализаторам

1.    ГОСТ 8.578-2008 Государственная поверочная схема для средств измерений содержания компонентов в газовых средах.

2.    ГОСТ 13320-81 Газоанализаторы промышленные автоматические. Общие технические условия

3.    Техническая документация фирмы-изготовителя.

Рекомендации к применению

Осуществление деятельности в области охраны окружающей среды; осуществление производственного контроля за соблюдением установленных законодательством Российской Федерации требований промышленной безопасности к эксплуатации опасного производственного объекта; выполнение работ по оценке соответствия промышленной продукции и продукции других видов, а также иных объектов установленным законодательством Российской Федерации обязательным требованиям.

На этой странице вы можете совершенно бесплатно скачать Инструкция по эксплуатации Emerson ROSEMOUNT OCX 8800.
У документа PDF Инструкция по эксплуатации 168 страниц, а его размер составляет 4.2 Mb.
Читать онлайн Кислородное оборудование Emerson ROSEMOUNT OCX 8800 Инструкция по эксплуатации

Читать онлайн Кислородное оборудование Emerson ROSEMOUNT OCX 8800 Инструкция по эксплуатации

Скачать файл PDF «Emerson ROSEMOUNT OCX 8800 Инструкция по эксплуатации» (4.2 Mb)

Популярность:

1309 просмотры

Подсчет страниц:

168 страницы

Тип файла:

PDF

Размер файла:

4.2 Mb

Прочие инструкции Emerson Кислородное оборудование

  • Кислородное оборудование Emerson ROSEMOUNT NGA2000 TO2 Инструкция по эксплуатации

  • Кислородное оборудование Emerson DO-04 Мануал

    Emerson DO-04 Мануал

    Популярность:

    833 просмотры

    Подсчет страниц:

    70 страницы

    Тип файла:

    PDF

    Размер файла:

    837 Kb

  • Кислородное оборудование Emerson ib-106-340cdr Инструкция по эксплуатации

  • Кислородное оборудование Emerson DO-03 Мануал

    Emerson DO-03 Мануал

    Популярность:

    871 просмотры

    Подсчет страниц:

    70 страницы

    Тип файла:

    PDF

    Размер файла:

    837 Kb

  • Кислородное оборудование Emerson 755A Инструкция по эксплуатации

  • Кислородное оборудование Emerson OXYBALANCE IM-106-4050 Инструкция по эксплуатации

  • Кислородное оборудование Emerson 7003M Инструкция по эксплуатации

  • Кислородное оборудование Emerson 5081FG Инструкция по эксплуатации

  • Кислородное оборудование Emerson ROSEMOUNT 3000 Инструкция по эксплуатации

  • Кислородное оборудование Emerson OXYMITTER 4000 Инструкция по эксплуатации

Прочие инструкции Emerson

  • IP-телефоны Emerson Liebert iCOM Инструкция по эксплуатации

  • Блоки питания Emerson 7000 Series Инструкция по эксплуатации

  • Блоки питания Emerson Liebert NX UPS 40-200kVA, 480V, 60Hz Инструкция по эксплуатации

  • Блоки питания Emerson SERIES 600T Инструкция по эксплуатации

  • Тепловые насосы Emerson 1F95-1280 Инструкция по эксплуатации

  • Термостаты Emerson 1F80-0471 Инструкция по эксплуатации

  • Морозильные камеры Emerson E2 Инструкция по эксплуатации

  • Часы Emerson EE542-1Z Инструкция по эксплуатации

  • Автомобильная система спутникового ТВ Emerson 1HDEZ-1521 Инструкция по эксплуатации

  • Линейные сооружения Emerson NetReach CoolPed 3.0 Руководство по монтажу

Принцип действия газоанализаторов основан на определении объёмной доли кислорода путём измерения напряжения, возникающего на нагретом электрохимическом элементе на основе оксида циркония и суммарного содержания продуктов неполного сгорания (горючих газов), путем определения разницы термосопротивлений на эталонном и активном элементах термокаталитического датчика. Термокаталитический датчик градуируют по монооксиду углерода и, соответственно, результаты измерений содержания продуктов неполного сгорания выражаются в объемной доле монооксида углерода. Оба датчика термостабилизированы.

Конструктивно газоанализаторы состоят из двух блоков: аналитического и электронного. Каждый блок помещен в собственный корпус.

Аналитический блок имеет прямоугольное основание из алюминиевого сплава, на котором снаружи установлено пробоотборное устройство (зонд) — трубка из нержавеющей стали, или сплава Инконель 600, или керамики. Внутри блока расположены эжектор, датчики (чувствительные элементы) кислорода и горючих газов, элементы газовой системы. Блок закрывается резьбовой крышкой с защитой от произвольного раскручивания. Корпус аналитического блока термоизолирован.

Электронный блок имеет аналогичную конструкцию. В нем установлены блок питания, платы электроники, клеммные и заземляющие зажимы, соленоидные клапаны управления пневмосистемой. Корпус электронного блока термоизолирован. Опционально электронный блок может быть оснащен:

  • — мембранной клавиатурой под крышкой со смотровым окном или без него,

  • — вакуумно-люминесцентным или жидкокристаллическим цифровым дисплеем — Local Operator Interface (далее — LOI) с ИК-клавиатурой.

В основании имеются резьбовые отверстия для подсоединения фитингов газовой системы и кабельных вводов, а также наружные заземляющие зажимы. Конструкция газоанализаторов позволяет заменить при неисправностях датчики и электронику в полевых условиях.

В зависимости от условий применения измерительный зонд может быть оснащён фильтром различных модификаций. Влияние внешней температуры учтено при нормировании метрологических характеристик газоанализаторов.

Отбор пробы производится при помощи воздушного аспиратора (эжектора).

По типу исполнения газоанализаторы бывают со встроенным или выносным блоком электроники.

В исполнении со встроенным блоком электроники измерительный зонд и блок электроники представляют собой единую конструкцию.

В исполнении с выносным блоком электроники измерительный зонд и блок электроники устанавливаются раздельно, соединение между измерительным зондом и блоком электроники осуществляется посредством кабельных связей и пневматических линий.

В зависимости от типа и свойств внешнего корпуса, газоанализаторы OCX 8800 выпускаются в следующих модификациях:

  • — OCX88A, OCX 8800 без маркировки Ex — невзрывозащищённые;

  • — OCX88C, OCX 8800 с маркировкой Ex — взрывозащищённые.

Результаты измерений и вычислений газоанализаторов в зависимости от исполнения выводятся:

  • — на дисплей локального интерфейса оператора LOI;

  • — в виде аналогового выходного сигнала 4-20 мА (2х/4х проводный);

  • — в виде цифрового сигнала с протоколами HART, Foundation Fieldbus;

  • — в виде цифрового сигнала с протоколом Wireless HART с использованием модуля Rosemount 775 (ТНиМ™-адаптер).

Общий вид газоанализаторов, варианты исполнений представлены на рисунках 1-5.

Схема пломбировки от несанкционированного доступа, обозначение места нанесения знака поверки представлены на рисунке 6.

Внешний вид. Газоанализаторы (Rosemount OCX 8800), http://oei-analitika.ru

Рисунок 1 — Общий вид газоанализаторов раздельного монтажа без локального интерфейса оператора LOI

Внешний вид. Газоанализаторы (Rosemount OCX 8800), http://oei-analitika.ru

Рисунок 2 — Общий вид газоанализаторов интегрального монтажа без локального интерфейса оператора LOI

Внешний вид. Газоанализаторы (Rosemount OCX 8800), http://oei-analitika.ru

Рисунок 3 — Общий вид газоанализаторов раздельного монтажа c локальным интерфейсом оператора LOI

Внешний вид. Газоанализаторы (Rosemount OCX 8800), http://oei-analitika.ru

Рисунок 4 — Общий вид газоанализаторов интегрального монтажа c локальным интерфейсом оператора LOI

Внешний вид. Газоанализаторы (Rosemount OCX 8800), http://oei-analitika.ru

Рисунок 5 — Общий вид газоанализаторов с беспроводным модулем радиосвязи

Rosemount 775 (THUM — адаптер)

Место пломбирования корпуса

Внешний вид. Газоанализаторы (Rosemount OCX 8800), http://oei-analitika.ru

Место нанесения знака поверки

электронный блок

аналитический блок

Рисунок 6 — Схема пломбировки от несанкционированного доступа, обозначение места нанесения знака поверки

Фотографическое изображение - Газоанализаторы Rosemount OCX 8800

Газоанализатор — это измерительный прибор для определения качественного и количественного состава смесей газов.

Газоанализаторы Rosemount OCX 8800 (далее — газоанализаторы) предназначены для непрерывного измерения содержания объёмной доли кислорода и продуктов неполного сгорания в дымовых и других технологических газах, с целью контроля и оптимизации процессов горения в энергетических и отопительных котлах, в печах для отжига, обжига, для сжигания мусора и отходов, в печах нефтеперерабатывающих и нефтехимических, металлургических и прочих производств.

Данная стаття носит исключительно информационно-ознакомительный характер и не несет никакого рекламного или коммерческого подтекста.

Понравилась статья? Поделить с друзьями:
  • Кто осуществляет руководство деятельностью уполномоченных по охране труда профессионального союза
  • Стиральная машина бош wft 2830 инструкция на русском языке
  • Гель гектор от тараканов инструкция по применению
  • All in 1 hdd docking инструкция на русском
  • Беродуал для ингаляций инструкция это гормональный препарат или нет