    ® Relion 670 series Line differential protection RED670 ANSI Customized Product Guide…
  • Page 2: Table Of Contents

    22. Ordering……………..99 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. © Copyright 2012 ABB.

  • Page 3: Application

    1. Application High set instantaneous phase and ground overcurrent, four RED670 is used for the protection, control and monitoring of step directional or non-directional delayed phase and ground overhead lines and cables in all types of networks. The IED can overcurrent, thermal overload and two step under- and be used from distribution up to the highest voltage levels.

  • Page 4: Available Functions

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 2. Available functions Main protection functions = number of basic instances = option quantities IEC 61850 ANSI Function description Line Differential RED670 Differential protection HZPDIF 1Ph high impedance differential protection…

  • Page 5
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Back-up protection functions IEC 61850 ANSI Function description Line Differential RED670 Current protection PHPIOC Instantaneous phase overcurrent protection OC4PTOC 51_67 Four step phase overcurrent protection EFPIOC Instantaneous residual overcurrent protection…
  • Page 6
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Control and monitoring functions IEC 61850 ANSI Function description Line Differential RED670 Control SESRSYN Synchrocheck, energizing check and synchronizing SMBRREC Autorecloser APC15 Apparatus control for single bay, max 15 apparatuses (2CBs) incl. interlocking…
  • Page 7
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 IEC 61850 ANSI Function description Line Differential RED670 SP16GGIO IEC61850 generic communication I/O functions 16 inputs MVGGIO IEC61850 generic communication I/O functions BSStatReport Logical signal status report RANGE_XP Measured value expander block…
  • Page 8
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Designed to communicate IEC 61850 ANSI Function description Line Differential RED670 Station communication SPA communication protocol LON communication protocol IEC60870-5-103 communication protocol 20/1 Operation selection between SPA and IEC60870-5-103 for SLM DNP3.0 for TCP/IP and EIA-485 communication protocol…
  • Page 9: Differential Protection

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Basic IED functions IEC 61850 Function description Basic functions included in all products IntErrorSig Self supervision with internal event list TIME Time and synchronization error TimeSynch Time synchronization ActiveGroup…

  • Page 10
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 current differential protection with high sensitivity and provides Line differential protection, 3 or 6 CT sets L3CPDIF, L6CPDIF phase selection information for single-pole tripping. (87L) Line differential protection applies the Kirchhoff’s law and…
  • Page 11
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Protected zone Communication Channel Communication Channel Communication Channel ANSI05000040_2_en.vsd ANSI05000040 V2 EN Figure 2. Example of application on a three-terminal line with breaker-and-a-half breaker arrangements The current differential algorithm provides high sensitivity for…
  • Page 12
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 protection zone. Both two- and three-winding transformers are Line differential protection 3 or 6 CT sets, with in-zone correctly represented with phase shift compensations made in transformers LT3CPDIF, LT6CPDIF (87LT) the algorithm.
  • Page 13
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Protected zone Communication Channel ANSI05000043_2_en.vsd ANSI05000043 V2 EN Figure 4. Five terminal lines with master-master system…
  • Page 14
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Protected zone Communication Channels en05000044_ansi.vsd ANSI05000044 V1 EN Figure 5. Five terminal line with master-slave system Current samples from IEDs located geographically apart from The communication link is continuously monitored, and an…
  • Page 15: Impedance Protection

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 The differential function can be allowed to trip as no load is fed • Startup element is sensitive enough to detect the abnormal through the line and protection is not working correctly.

  • Page 16
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 achieve. Therefore, FDPSPDIS (21) has a built-in algorithm for load encroachment, which gives the possibility to enlarge the resistive setting of both the phase selection and the measuring zones without interfering with the load.
  • Page 17
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Faulty phase identification with load encroachment FMPSPDIS (21) The operation of transmission networks today is in many cases close to the stability limit. Due to environmental considerations Operation area…
  • Page 18
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 achieve. Therefore, the function has a built in algorithm for load encroachment, which gives the possibility to enlarge the resistive setting of both the phase selection and the measuring zones without interfering with the load.
  • Page 19: Current Protection

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 5. Current protection Directional operation can be combined together with corresponding communication logic in permissive or blocking Instantaneous phase overcurrent protection PHPIOC (50) teleprotection scheme. Current reversal and weak-end infeed The instantaneous three phase overcurrent function has a low functionality are available as well.

  • Page 20: Voltage Protection

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Thermal overload protection, one time constant LPTTR Pole discordance protection CCRPLD (52PD) The increasing utilizing of the power system closer to the An open phase can cause negative and zero sequence currents…

  • Page 21: Frequency Protection

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Two step overvoltage protection (OV2PTOV, 59) function can Underfrequency protection SAPTUF (81) is used for load be used to detect open line ends, normally then combined with shedding systems, remedial action schemes, gas turbine a directional reactive over-power function to supervise the startup and so on.

  • Page 22: Secondary System Supervision

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 CVGAPC can also be used to improve phase selection for high For better adaptation to system requirements, an operation resistive ground faults, outside the distance protection reach, mode setting has been introduced which makes it possible to for the transmission line.

  • Page 23
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 close first and the second will only close if the fault proved to function handles interlocking of one bay. The interlocking be transient. function is distributed to each IED and is not dependent on any central function.
  • Page 24: Scheme Communication

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 • fast clearance of faults is also achieved at the line end for AutomationBits, command function for DNP3.0 AUTOBITS which the faults are on the part of the line not covered by AutomationBits function for DNP3 (AUTOBITS) is used within its underreaching zone.

  • Page 25
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 The logic can be controlled either by the autorecloser (zone IED. To overcome these conditions, weak-end infeed (WEI) extension) or by the loss-of-load current (loss-of-load echo logic is used.
  • Page 26: Logic

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Features: length, as well as all functionality necessary for correct co- operation with autoreclosing functions. • Carrier redundancy to ensure security in DTT scheme • Blocking function output on CR Channel Error The trip function block also includes a settable latch •…

  • Page 27: Monitoring

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 an IED, either for forcing the unused inputs in other function • Trip value recorder blocks to a certain level/value, or for creating certain logic. • Disturbance recorder • Fault locator 13.

  • Page 28
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 The event recorder logs all selected binary input signals the Event function (EVENT). The event function block is used for connected to the Disturbance report function. Each recording remote communication.
  • Page 29: Metering

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 35-40 degrees apart the accuracy can be still maintained with the advanced compensation included in fault locator. 14. Metering Pulse counter logic PCGGIO Pulse counter (PCGGIO) function counts externally generated binary pulses, for instance pulses coming from an external energy meter, for calculation of energy consumption values.

  • Page 30: Remote Communication

    An IED can communicate with up to 4 remote IEDs. SPA communication protocol A single glass or plastic port is provided for the ABB SPA Binary signal transfer to remote end, 192 signals protocol. This allows extensions of simple substation…

  • Page 31
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 enables extensive monitoring and evaluation of operation of the leased telephone lines. The module supports 64 kbit/s data IED and for all associated electrical circuits. communication between IEDs. Binary output module BOM…
  • Page 32
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 xx05000003.vsd IEC05000003 V1 EN Figure 11. 1/2 x 19” case with rear cover xx05000004.vsd IEC05000004 V1 EN Figure 12. Side-by-side mounting Case size 6U, 1/2 x 19” 10.47 8.81 7.92…
  • Page 33
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 • Wall mounting kit See ordering for details about available mounting alternatives.
  • Page 34: Connection Diagrams

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 20. Connection diagrams Table 1. Designations for 1/2 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM, IOM or X31 and X32 etc. to X51…

  • Page 35
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 2. Designations for 3/4 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM, IOM or X31 and X32 etc. to X101 and X102 X301:A, B, C, D…
  • Page 36
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 3. Designations for 3/4 x 19” casing with 2 TRM slot Module Rear Positions BIM, BOM, SOM, IOM or X31 and X32 etc. to X71 and X301:A, B, C, D…
  • Page 37
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 4. Designations for 1/1 x 19” casing with 1 TRM slot Module Rear Positions BIM, BOM, SOM, X31 and X32 etc. to X161 IOM or MIM and X162…
  • Page 38
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 5. Designations for 1/1 x 19” casing with 2 TRM slots Module Rear Positions BIM, BOM, SOM, X31 and X32 etc. to X131 IOM or MIM and X132…
  • Page 39
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 6. CT/VT-input designation AI01 AI02 AI03 AI04 AI05 AI06 AI07 AI08 AI09 AI10 AI11 AI12 12I, 1A 12I, 5A 9I+3V, 1A 110-220V 110-220V 110-220V 9I+3V, 5A 110-220V 110-220V…
  • Page 40
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 1MRK002802-AB-11-670-1.2-PG-ANSI V1 EN Figure 15. Binary input module (BIM). Input contacts named XA corresponds to rear position X31, X41, etc. and input contacts named XB to rear position X32, X42, etc.
  • Page 41
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 1MRK002802-AB-8-670-1.2-PG-ANSI V1 EN Figure 20. IED with basic functionality communication interfaces…
  • Page 42: Technical Data

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 21. Technical data General Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified…

  • Page 43
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 8. TRM — Energizing quantities, rated values and limits for measuring transformer modules Quantity Rated value Nominal range Current = 1 or 5 A (0-1.8) × I at I = 1 A (0-1.6) ×…
  • Page 44
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Auxiliary DC voltage Table 11. PSM — Power supply module Quantity Rated value Nominal range Auxiliary dc voltage, EL (input) EL = (24 — 60) V EL ± 20% EL = (90 — 250) V EL ±…
  • Page 45
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 13. BIM — Binary input module with enhanced pulse counting capabilities Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ± 20% 48/60 V RL ±…
  • Page 46
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 15. IOM — Binary input/output module contact data (reference standard: IEC 61810-2) Function or quantity Trip and signal relays Fast signal relays (parallel reed relay) Binary outputs Max system voltage…
  • Page 47
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 16. IOM with MOV and IOM 220/250 V, 110mA — contact data (reference standard: IEC 61810-2) Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)
  • Page 48
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 17. SOM — Static Output Module (reference standard: IEC 61810-2): Static binary outputs Function of quantity Static binary output trip Rated voltage 48 — 60 VDC 110 — 250 VDC…
  • Page 49
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 19. BOM — Binary output module contact data (reference standard: IEC 61810-2) Function or quantity Trip and Signal relays Binary outputs Max system voltage 250 V AC, DC…
  • Page 50
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 22. Frequency influence (reference standard: IEC 60255–1) Dependence on Within nominal range Influence Frequency dependence, operate value ± 2.5 Hz for 50 Hz ± 1.0% / Hz ± 3.0 Hz for 60 Hz Frequency dependence for distance protection operate value ±…
  • Page 51
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 24. Insulation Test Type test values Reference standard Dielectric test 2.0 kV AC, 1 min. ANSI C37.90 Impulse voltage test 5 kV, 1.2/50 ms, 0.5 J Insulation resistance >100 MW at 500 VDC…
  • Page 52
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Differential protection Table 28. 1Ph High impedance differential protection HZPDIF (87) Function Range or value Accuracy Operate voltage (20-400) V ± 1.0% of I I=V/R Reset ratio >95% Maximum continuous power V>Pickup…
  • Page 53
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 30. Additional security logic for differential protection STSGGIO (11) Function Range or value Accuracy Operate current, zero sequence (1-100)% of lBase ±1,0% of I Operate current, low operation (1-100)% of lBase ±1,0% of I…
  • Page 54
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Impedance protection Table 31. Distance measuring zone, Quad ZMQPDIS (21) Function Range or value Accuracy Number of zones 5 with selectable direction Minimum operate residual (5-1000)% of IBase current, zone 1…
  • Page 55
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 32. Distance measuring zone, quadrilateral characteristic for series compensated lines ZMCPDIS, ZMCAPDIS (21) Function Range or value Accuracy Number of zones 5 with selectable direction IBase Minimum operate residual…
  • Page 56
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 34. Full-scheme distance protection, Mho characteristic ZMHPDIS (21) Function Range or value Accuracy Number of zones with selectable 5 with selectable direction directions Minimum operate current (10–30)% of I…
  • Page 57
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 36. Distance measuring zone, quadrilateral characteristic, separate settings ZMRPDIS, ZMRAPDIS (21) Function Range or value Accuracy Number of zones 5 with selectable direction Minimum operate residual (5-1000)% of IBase…
  • Page 58
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 37. Phase selection with load encroachment, quadrilateral characteristic FRPSPDIS (21) Function Range or value Accuracy Minimum operate current (5-500)% of IBase Reactive reach, positive (0.50–3000.00) Ω/phase ± 2.0% static accuracy sequence ±…
  • Page 59
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 40. Phase preference logic PPLPHIZ Function Range or value Accuracy Operate value, phase-to-phase (10.0 — 100.0)% of VBase ± 0,5% of V and phase-to-neutral undervoltage Reset ratio, undervoltage <…
  • Page 60
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Current protection Table 42. Instantaneous phase overcurrent protection PHPIOC (50) Function Range or value Accuracy Operate current (1-2500)% of lBase ± 1.0% of I at I £ I ± 1.0% of I at I > I Reset ratio >…
  • Page 61
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 44. Instantaneous residual overcurrent protection EFPIOC (50N) Function Range or value Accuracy Operate current (1-2500)% of lBase ± 1.0% of I at I £ I ± 1.0% of I at I > I Reset ratio >…
  • Page 62
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 46. Four step negative sequence overcurrent protection NS4PTOC (46I2) Function Range or value Accuracy lBase Operate value, negative (1-2500)% of ± 1.0% of I at I £ I sequence current, step 1-4 ±…
  • Page 63
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 47. Sensitive directional residual overcurrent and power protection SDEPSDE (67N) Function Range or value Accuracy lBase Operate level for 3I ·cosj (0.25-200.00)% of ± 1.0% of I at I £ I directional residual ±…
  • Page 64
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 47. Sensitive directional residual overcurrent and power protection SDEPSDE (67N) , continued Function Range or value Accuracy Operate time, non-directional 60 ms typically at 0 to 2 x I…
  • Page 65
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 49. Breaker failure protection CCRBRF (50BF) Function Range or value Accuracy lBase Operate phase current (5-200)% of ± 1.0% of I at I £ I ± 1.0% of I at I > I Reset ratio, phase current >…
  • Page 66
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 52. Directional underpower protection GUPPDUP (37) Function Range or value Accuracy SBase Power level (0.0–500.0)% of ± 1.0% of S at S < S ± 1.0% of S at S > S At low setting: (0.5-2.0)% of…
  • Page 67
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Voltage protection Table 55. Two step undervoltage protection UV2PTUV (27) Function Range or value Accuracy Operate voltage, low and high step (1–100)% of VBase ± 0.5% of V Absolute hysteresis (0–100)% of…
  • Page 68
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 57. Two step residual overvoltage protection ROV2PTOV (59N) Function Range or value Accuracy VBase Operate voltage, step 1 and step 2 (1-200)% of ± 0.5% of V at V < V ±…
  • Page 69
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 60. Loss of voltage check LOVPTUV (27) Function Range or value Accuracy Operate voltage (0–100)% of VBase ± 0.5% of V Pulse timer (0.050–60.000) s ± 0.5% ± 10 ms Timers (0.000–60.000) s…
  • Page 70
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Frequency protection Table 61. Underfrequency protection SAPTUF (81) Function Range or value Accuracy Operate value, pickup function (35.00-75.00) Hz ± 2.0 mHz Operate time, pickup function 100 ms typically…
  • Page 71
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 63. Rate-of-change frequency protection SAPFRC (81) Function Range or value Accuracy Operate value, pickup function (-10.00-10.00) Hz/s ± 10.0 mHz/s Operate value, internal blocking level (0-100)% of VBase ±…
  • Page 72
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Multipurpose protection Table 64. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input Phase A, Phase B, Phase C, PosSeq, NegSeq, 3*ZeroSeq, MaxPh, MinPh,…
  • Page 73
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 64. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Reset time pickup undervoltage 25 ms typically at 0 to 2 x V High and low voltage limit, voltage dependent operation (1.0 — 200.0)% of VBase…
  • Page 74
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Secondary system supervision Table 65. Current circuit supervision CCSRDIF (87) Function Range or value Accuracy Operate current (5-200)% of I ± 10.0% of I at I £ I ± 10.0% of I at I > I…
  • Page 75
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Control Table 67. Synchronizing, synchronism check and energizing check SESRSYN (25) Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage ratio, V 0.500 — 2.000…
  • Page 76
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 68. Autorecloser SMBRREC (79) Function Range or value Accuracy Number of autoreclosing shots 1 — 5 Autoreclosing open time: shot 1 — t1 1Ph (0.000-60.000) s ± 0.5% ± 10 ms…
  • Page 77
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Scheme communication Table 69. Scheme communication logic for distance or overcurrent protection ZCPSCH (85) Function Range or value Accuracy Scheme type Intertrip Permissive Underreach Permissive Overreach Blocking Co-ordination time for blocking (0.000-60.000) s…
  • Page 78
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 72. Current reversal and weak-end infeed logic for phase segregated communication ZC1WPSCH Function Range or value Accuracy Detection pickup phase to (10-90)% of VBase ± 0.5% of V…
  • Page 79
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Direct transfer trip Table 75. Low active power and power factor protection LAPPGAPC (37_55) Function Range or value Accuracy Operate value, low active power (2.0-100.0)% of SBase ± 1,0% of S Reset ratio, low active power <105%…
  • Page 80
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 79. Negative sequence overvoltage protection LCNSPTOV (47) Function Range or value Accuracy Operate value, negative sequence overvoltage (1-200)% of VBase ± 0.5% of V at V<V ± 0.5% of V at V>V Reset ratio, negative sequence overvoltage >95%…
  • Page 81
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 82. Zero sequence overcurrent protection LCZSPTOC (51N) Function Range or value Accuracy Operate value, zero sequence overcurrent (1-2500)% of IBase ± 1.0% of I at I<I ± 1.0% of I at I>I Reset ratio, zero sequence overcurrent >95%…
  • Page 82
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Logic Table 85. Tripping logic SMPPTRC (94) Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Minimum trip pulse length (0.000-60.000) s ± 0.5% ± 10 ms Timers (0.000-60.000) s…
  • Page 83
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Monitoring Table 87. Measurements CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) × f ± 2.0 mHz Voltage (0.1-1.5) ×V ± 0.5% of V at V£V ± 0.5% of V at V > V Connected current (0.2-4.0) ×…
  • Page 84
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 91. Current sequence component measurement CMSQI Function Range or value Accuracy Current positive sequence, I1 (0.1–4.0) × I ± 0.2% of I at I ≤ 0.5 × I Three phase settings ±…
  • Page 85
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 95. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 100, first in — first out…
  • Page 86
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 98. Indications Function Value Buffer capacity Maximum number of indications presented for single disturbance Maximum number of recorded disturbances Table 99. Event recorder Function Value Buffer capacity Maximum number of events in disturbance report…
  • Page 87
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Metering Table 102. Pulse counter PCGGIO Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value Table 103. Energy metering ETPMMTR…
  • Page 88
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Station communication Table 104. IEC 61850-8-1 communication protocol Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 608–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0…
  • Page 89
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 109. SLM – SPA/IEC 60870-5-103/DNP3 port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in Fiber, optical budget Glass fiber: 11 dB (3000ft/1000 m typically *)
  • Page 90
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Remote communication Table 113. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR) Long range (LR) Type of fiber Graded-index Singlemode 9/125 µm Singlemode 9/125 µm…
  • Page 91
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Hardware Table 114. Case Material Steel sheet Front plate Steel sheet profile with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) Table 115. Water and dust protection level according to IEC 60529…
  • Page 92
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Basic IED functions Table 119. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out Table 120. Time synchronization, time tagging…
  • Page 93
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 123. IRIG-B Quantity Rated value Number of channels IRIG-B Number of channels PPS Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –…
  • Page 94
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Inverse characteristic Table 124. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: td = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷…
  • Page 95
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 125. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: td = (0.05-999) in steps of 0.01 æ ö ç ÷ × ç ÷ è ø…
  • Page 96
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 126. RI and RD type inverse time characteristics Function Range or value Accuracy RI type inverse characteristic td = (0.05-999) in steps of 0.01 IEC 60255-151, 5% + 40 ×…
  • Page 97
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 128. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in steps of 0.01 5% +40 ms æ ö VPickup V ç…
  • Page 98
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Table 129. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: td = (0.05-1.10) in steps 5% +40 ms of 0.01 æ ö…
  • Page 99: Ordering

    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 22. Ordering Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functions can only be ordered in combination with other functions and that some functions require specific hardware selections.

  • Page 100
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Optional functions Differential protection 1Ph High impedance differential protection (HZPDIF, 87) Qty: 1MRK 002 901-HB Additional security logic for differential protection (STSGGIO, 11REL) Qty: 1MRK 002 903-PA…
  • Page 101
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Impedance protection Rule: One and only one of the alternatives (Alt. 1-4) can be ordered Alternative 1: Rule: Distance protection and Directional impedance must be ordered together Note: Phase selection FDPSPDIS always included in this package)
  • Page 102
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Phase selection, quadrilateral characteristic with settable angle (FRPSPDIS, 21) Qty: 1MRK 002 925-XA Directional impedance quadrilateral (ZDRDIR, 21D) Qty: 1MRK 002 904-YB Note: Optional with alternative 1 Directional impedance element for mho characteristic (ZDMRDIR, 21D)
  • Page 103
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Current protection Instantaneous phase overcurrent protection (PHPIOC, 50) Qty: 1MRK 002 906-AC Four step phase overcurrent protection (OC4PTOC, 51/67) Qty: 1MRK 002 906-BD Instantaneous residual overcurrent protection (EFPIOC, 50N)
  • Page 104
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Frequency protection Underfrequency protection (SAPTUF, 81) Qty: 1MRK 002 908-NC Overfrequency protection (SAPTOF, 81) Qty: 1MRK 002 908-RC Rate-of-change frequency protection (SAPFRC, 81) Qty: 1MRK 002 908-SB Multipurpose protection…
  • Page 105
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Direct transfer trip Direct transfer trip (DTT) Qty: 1MRK 002 927-XA Station communication Note: Require 2-channel OEM IEC 62439-3 Edition 1 parallel redundancy protocol 1MRK 002 924-YR IEC 62439-3 Edition 2 parallel redundancy protocol…
  • Page 106
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Analog system Rule: One Transformer input module must be ordered Note: The same type of connection terminals has to be ordered for both TRMs Transformer input module, compression terminals…
  • Page 107
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Transformer input module, compression terminals 6I, 5A, 50/60 Hz Qty: 1MRK 002 247-DH Transformer input module, ring lug terminals 12I, 1A, 50/60 Hz Qty: 1MRK 002 247-CC Transformer input module, ring lug terminals…
  • Page 108
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Transformer input module, ring lug terminals 6I, 1A, 50/60 Hz Qty: 1MRK 002 247-DC Transformer input module, ring lug terminals 6I, 5A, 50/60 Hz Qty: 1MRK 002 247-DD Note: One Analog digital conversion module, with time synchronization is always delivered with each Transformer input module.
  • Page 109
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Binary input/output modules Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability is further increased.
  • Page 110
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Binary input module (BIM) with enhanced pulse counting capabilities, 16 inputs RL 24-30 VDC Qty: 1MRK 000 508-HA 10 11 12 13 RL 48-60 VDC Qty: 1MRK 000 508-EA…
  • Page 111
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Make IOM with 50 mA inrush current the primary choice. IOM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability is further increased.
  • Page 112
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Station communication ports Note: Optical ethernet module, 2 glass interfaces is not allowed together with SLM. Optical ethernet module, 1 channel glass 1MRK 002 266-AA Optical ethernet module, 2 channel glass 1MRK 002 266-BA Serial and LON communication module, supports SPA/IEC 60870-5-103, LON and DNP 3.0…
  • Page 113
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Flush mounting kit for terminal Quantity: 1MRK 000 020-Y Flush mounting kit + IP54 sealing (factory mounted). Cannot be ordered separately thus must be Quantity: 1MRK 002 420-EA specified when ordering a terminal.
  • Page 114
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Protection cover Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-AC Protective cover for rear side of terminal, 6U, 3/4 x 19”…
  • Page 115
    Line differential protection RED670 ANSI 1MRK505226-BUS D Customized Product version: 1.2 Rule: Specify additional quantity of IED Connect CD requested . Quantity: 1MRK 002 290-AB Rule: Specify the number of printed manuals requested Operator’s manual ANSI Quantity: 1MRK 505 223-UUS…
  • Page 116
    670 series SPA and signal list 1MRK 500 092-WUS IEC 61850 Data objects list for 670 series 1MRK 500 091-WUS Engineering manual 670 series 1MRK 511 240-UUS Communication set-up for Relion 670 series 1MRK 505 260-UEN More information can be found on www.abb.com/substationautomation.
  • Page 118
    ABB Inc. 3450 Harvester Road Burlington, ON L7N 3W5, Canada Phone Toll Free: 1-800-HELP-365, menu option #8 ABB Mexico S.A. de C.V. Paseo de las Americas No. 31 Lomas Verdes 3a secc. 53125, Naucalpan, Estado De Mexico, MEXICO Phone (+1) 440-585-7804, menu…

This manual is also suitable for:

Rel670

ABB Relion 670 Series Product Manual

  • Contents

  • Table of Contents

  • Bookmarks

Quick Links

®

Relion

670 SERIES

Line differential protection RED670

Version 2.2

Product guide

loading

Related Manuals for ABB Relion 670 Series

Summary of Contents for ABB Relion 670 Series

  • Page 1
    ® Relion 670 SERIES Line differential protection RED670 Version 2.2 Product guide…
  • Page 2: Table Of Contents

    The information in this document is subject to change without notice and should not be construed as a commitment by Hitachi Power Grids. Hitachi Power Grids assumes no responsibility for any errors that may appear in this document. Drawings and diagrams are not binding. ABB is a registered trademark of ABB Asea Brown Boveri Ltd.

  • Page 3: Document Revision History

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Issued: September 2020 Revision: N 1. Document revision history GUID-34B323E4-1319-4D42-80CE-29B0F2D36E2C v4 Table 1. Document revision history Document Date Product revision History revision 2017-07 2.2.0 First release for product version 2.2 2017-10 2.2.1 Ethernet ports with RJ45 connector added.

  • Page 4: Application

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Disturbance recording and fault locator are available to allow independent post-fault analysis after primary 2. Application disturbances. The Disturbance recorder will also show M13635-3 v9 The Intelligent Electronic Device (IED) is used for the remote station currents, as received to this IED, time protection, control and monitoring of overhead lines compensated with measure communication time.

  • Page 5
    On request, ABB is available to support the re-configuration The basic delivery includes one binary input module and work, either directly or to do the design checking.
  • Page 6
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Description of configuration A42 GUID-A3E1E81D-9278-4AC1-8AAA-AD0D56DABE23 v2 RED670 A42 – Single breaker with single or three phase tripping 12AI (6I+6U) WA2_VT VN MMXU WA1_VT Control Control Control S SCBR S SCBR S XCBR VN MMXU 1→0…
  • Page 7
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Description of configuration B33 GUID-1231CFD6-8CEF-464E-8124-E9F7EFD0FF62 v2 RED670 B33 – Multi breaker with single or three phase tripping 12AI (6I+6U) WA1_VT WA1_CT Control Control Control 50BF 3I>BF 52PD S SCBR S SCBR S SCBR CC PDSC VN MMXU…
  • Page 8
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Description of configuration B42 GUID-D1058782-6EAD-4E94-8513-1D3647E67250 v2 RED670 B42 – Multi breaker with single or three phase tripping 12AI (6I+6U) WA1_VT WA1_CT Control Control 52PD Control 50BF 3I>BF S SCBR S SCBR S SCBR CC PDSC VN MMXU…
  • Page 9
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Description of configuration C42 GUID-C82DE474-FDC4-49CF-AF12-445716D9C6B6 v2 RED670 C42 – Single breaker with single or three phase tripping and back-up distance protection 12AI (6I+6U) 21FL DFR/SER DR DRP RDRE LMB RFLO WA2_VT VN MMXU WA1_VT…
  • Page 10: Available Functions

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 3. Available functions GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1 The following tables list all the functions available in the IED. Those functions that are not exposed to the user or do not need to be configured are not described in this manual.

  • Page 11: Differential Protection

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) Differential protection HZPDIF High impedance differential protection, single 3-A02 3-A02 3-A02 3-A02 phase REFPDIF Restricted earth fault protection, low impedance 0–2 L3CPDIF Line differential protection for 3 CT sets, 2-3 line…

  • Page 12
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) ZMRPDIS, Distance measuring zone, quad characteristic ZMRAPDIS separate Ph-Ph and Ph-E settings FRPSPDIS Phase selection, quadrilateral characteristic with settable angle ZMFPDIS High speed distance protection, quad and mho…
  • Page 13: Current Protection

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Back-up protection functions GUID-A8D0852F-807F-4442-8730-E44808E194F0 v16 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) Current protection PHPIOC Instantaneous phase overcurrent protection OC4PTOC Directional phase overcurrent 51_67 protection, four steps EFPIOC Instantaneous residual overcurrent protection…

  • Page 14: Frequency Protection

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) VDCPTOV Voltage differential protection LOVPTUV Loss of voltage check PAPGAPC Radial feeder protection Frequency protection SAPTUF Underfrequency protection 3-E04 3-E04 3-E04…

  • Page 15: Control

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Control and monitoring functions GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v20 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) Control SESRSYN Synchrocheck, energizing check and synchronizing SMBRREC Autorecloser 2-H05 1-H04 2-H05 1-H04 APC10 Control functionality for a…

  • Page 16: Logic

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) I103POSCMD IED commands with position and select for IEC 60870-5-103 I103POSCMDV IED direct commands with position for IEC 60870-5-103 I103IEDCMD IED commands for IEC…

  • Page 17
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) ANDQT, Configurable logic blocks Q/T INDCOMBSPQT, (see Table 6) INDEXTSPQT, INVALIDQT, INVERTERQT, ORQT, PULSETIMERQT, RSMEMORYQT, SRMEMORYQT, TIMERSETQT, XORQT AND, GATE, INV, Extension logic package (see LLD, OR,…
  • Page 18: Monitoring

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) Monitoring CVMMXN Power system measurement CMMXU Current measurement VMMXU Voltage measurement phase-phase CMSQI Current sequence measurement VMSQI Voltage sequence measurement VNMMXU Voltage measurement…

  • Page 19: Metering

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) I103AR Function status auto- recloser for IEC 60870-5-103 I103EF Function status earth-fault for IEC 60870-5-103 I103FLTPROT Function status fault protection for IEC 60870-5-103 I103IED…

  • Page 20
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 3. Total number of instances for basic configurable logic blocks Basic configurable logic block Total number of instances GATE PULSETIMER RSMEMORY SRMEMORY TIMERSET Table 4. Number of function instances in APC10 Function name Function description Total number of instances…
  • Page 21
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 5. Number of function instances in APC15 Function name Function description Total number of instances SCILO Interlocking BB_ES A1A2_BS A1A2_DC ABC_BC BH_CONN BH_LINE_A BH_LINE_B DB_BUS_A DB_BUS_B DB_LINE ABC_LINE AB_TRAFO SCSWI Switch controller SXSWI…
  • Page 22
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 7. Total number of instances for extended logic package Extended configurable logic block Total number of instances GATE PULSETIMER RSMEMORY SLGAPC SRMEMORY TIMERSET VSGAPC Hitachi Power Grids © Copyright 2017 Hitachi Power Grids. All rights reserved…
  • Page 23
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Communication GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v18 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) Station communication LONSPA, SPA SPA communication protocol LON communication protocol HORZCOMM Network variables via LON PROTOCOL Operation selection between SPA and IEC60870-5-103 for SLM…
  • Page 24
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) OPTICAL103 IEC 60870-5-103 Optical serial communication RS485103 IEC 60870-5-103 serial communication for RS485 AGSAL Generic security application component LD0LLN0 IEC 61850 LD0 LLN0 SYSLLN0…
  • Page 25
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) QUALEXP IEC 61850 quality expander Remote communication BinSignRec1_1 Binary signal transfer, receive 3/3/6 3/3/6 3/3/6 3/3/6 3/3/6 BinSignRec1_2 BinSignReceive2 BinSignTrans1_1 Binary signal transfer, transmit…
  • Page 26
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) ZC1WPSCH Current reversal and weak-end infeed 1-B05 1-B05 1-B05 1-B05 logic for phase segregated communication ZCLCPSCH Local acceleration logic 1-B35 1-B35 1-B35…
  • Page 27: Basic Ied Functions

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Basic IED functions GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v14 Table 9. Basic IED functions IEC 61850 or function Description name INTERRSIG Self supervision with internal event list SELFSUPEVLST TIMESYNCHGEN Time synchronization module BININPUT, SYNCHCAN, Time synchronization SYNCHGPS, SYNCHCMPPS,…

  • Page 28
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 9. Basic IED functions, continued IEC 61850 or function Description name ALTMS Time master supervision ALTIM Time management CAMCONFIG Central account management configuration CAMSTATUS Central account management status TOOLINF Tools information COMSTATUS Protocol diagnostic…
  • Page 29
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 measured by one and sometimes by two three-phase current transformer (CT) groups. The voltages at all YNdx ends are also measured if the exact method is selected for charging current compensation. The protected zone is determined by the positions of the CTs at all ends of Autotransformer the protected circuit.
  • Page 30
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Protected zone Comm. Channel Comm. Channel Comm. Channel IEC05000040_2_en.vsd IEC05000040 V2 EN-US Figure 7. Example of application on a three-terminal line with 1½ breaker arrangements The current differential algorithm provides high differential protection can be time-delayed for low sensitivity for internal faults and it has excellent differential currents to achieve coordination with…
  • Page 31
    In this versions than 670 1.2.3 must be verified system, a 64 kbits/s or 2 Mbit/s communication channel with ABB. is only needed between the master and each one of the slave IEDs. The Master-Slave condition for the…
  • Page 32
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 protection logic to always release operation for all faults Distance measuring zone, quadrilateral characteristic detected by the differential function. LDRGFC consists (ZMQPDIS) together with Phase selection with load of four sub functions: encroachment (FDPSPDIS) has functionality for load encroachment, which increases the possibility to detect •…
  • Page 33
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Quadrilateral characteristic is available. this matter. Phase selection, quadrilateral characteristic with fixed angle (FDPSPDIS) is designed to accurately Distance measuring zone, quadrilateral characteristic select the proper fault loop in the distance function for series compensated lines (ZMCPDIS) function has dependent on the fault type.
  • Page 34
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Forward operation Operation area Operation area Operation area Reverse No operation area No operation area operation IEC07000117-2-en.vsd IEC07000117 V2 EN-US Figure 13. Load encroachment influence on the offset mho characteristic en05000034.vsd IEC05000034 V1 EN-US Figure 14.
  • Page 35
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Faulty phase identification with load encroachment FMPSPDIS SEMOD153825-5 v7 The ability to accurately and reliably classify different Forward types of fault so that single phase tripping and operation autoreclosing can be used plays an important roll in today’s power systems.
  • Page 36
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 the possibility to enlarge the resistive setting of both High speed distance protection ZMFCPDIS is the phase selection and the measuring zones without fundamentally the same function as ZMFPDIS but interfering with the load.
  • Page 37
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 fault type and thereby, reliable fault clearance can be Two current channels I3P1 and I3P2 are available in achieved for faults during power swing. OOSPPAM function to allow the direct connection of two groups of three-phase currents;…
  • Page 38
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Synchrophasor data can be reported to up to 8 clients Automatic switch onto fault logic, voltage and over TCP and/or 6 UDP group clients for multicast or current based ZCVPSOF unicast transmission of phasor data from the IED.
  • Page 39
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 protection being out of service due to communication or directional zero sequence current can be used. Current voltage transformer circuit failure. reversal and weak-end infeed functionality are available. Sensitive directional residual overcurrent and power EF4PTOC has an inverse or definite time delay protection SDEPSDE independent for each step.
  • Page 40
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 CCRBRF provides three different options to select how flow in the power system. There are a number of t1 and t2 timers are run: applications where such functionality is needed. Some 1.
  • Page 41
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 selective tripping of a faulty line. Alternatively, the Overexcitation protection OEXPVPH function can be used solely for signaling of the earth- M13319-3 v9 When the laminated core of a power transformer or fault location to the SCADA system when the power generator is subjected to a magnetic flux density network is allowed to operate for a longer time with an…
  • Page 42
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 phase(s) in which the phase selection function has shedding and remedial action schemes. SAPFRC can operated. discriminate between a positive or negative change of frequency. A definite time delay is provided for operate. For delayed tripping, single pole and three pole delays are separately and independently settable.
  • Page 43
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 and islanding in grid networks. Voltage based delta Fuse failure supervision FUFSPVC supervision (DELVSPVC) is needed at the grid SEMOD113820-4 v13 The aim of the fuse failure supervision function interconnection point. (FUFSPVC) is to block voltage measuring functions at failures in the secondary circuits between the voltage Current based delta supervision DELISPVC…
  • Page 44
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 asynchronous systems are in phase and can be evaluated with an additional supervision of the status connected. The synchronizing feature evaluates voltage value of the control object. The command sequence with difference, phase angle difference, slip frequency and enhanced security is always terminated by a frequency rate of change before issuing a controlled…
  • Page 45
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Hardware switches are however sources for Reservation function QCRSV maintenance issues, lower system reliability and an M13506-3 v5 The purpose of the reservation (QCRSV) function is extended purchase portfolio. The selector switch primarily to transfer interlocking information between function eliminates all these problems.
  • Page 46
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 types of communication schemes for permissive On verification of a weak end infeed condition, the weak underreaching, permissive overreaching, blocking, delta end infeed logic provides an output for sending the based blocking, unblocking and intertrip are available.
  • Page 47
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 logic for weak-end infeed and current reversal, included • Low active power trip with 2 selection modes ‘1 out of in Current reversal and weak-end infeed logic for 3’ and ‘2 out of 3’ residual overcurrent protection (ECRWPSCH) function.
  • Page 48
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Zero sequence overcurrent protection LCZSPTOC Trip matrix logic TMAGAPC GUID-F0C38DA1-2F39-46DE-AFFE-F919E6CF4A57 v2 Zero sequence components are present in all abnormal M15321-3 v14 The trip matrix logic (TMAGAPC) function is used to conditions involving earth.
  • Page 49
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 • PULSETIMER function block can be used, for example, inputs signal are copied to the corresponding quality for pulse extensions or limiting of operation of output. outputs, settable pulse time. •…
  • Page 50
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 certain logic. Boolean, integer, floating point, string be used for monitoring, supervision, interlocking and types of signals are available. other logics. One FXDSIGN function block is included in all IEDs. 16.
  • Page 51
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 The Disturbance report function is characterized by The event recorder information is available for the great flexibility regarding configuration, starting disturbances locally in the IED. conditions, recording times, and large storage capacity. The event recording information is an integrated part of A disturbance is defined as an activation of an input to the disturbance record (Comtrade file).
  • Page 52
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Analog, integer and double indication values are also Circuit breaker condition monitoring SSCBR transferred through the EVENT function. GUID-E1FD74C3-B9B6-4E11-AA1B-7E7F822FB4DD v14 The circuit breaker condition monitoring function Generic communication function for Single Point (SSCBR) is used to monitor different parameters of the indication SPGAPC breaker condition.
  • Page 53
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 • Applicable to very long time accumulation (≤ 99999.9 Voltage harmonic monitoring VHMMHAI hours) GUID-868ED1BB-A921-45DE-94C4-0CF23ECD9ADA v1 Voltage harmonic monitoring function VHMMHAI is used • Supervision of limit transgression conditions and to monitor the voltage part of the power quality of a rollover/overflow system.
  • Page 54: Ethernet

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 reverse directions. These energy values are available as The LHMI is used for setting, monitoring and controlling. output signals and also as pulse outputs. Integration of energy values can be controlled by inputs (STARTACC 19.

  • Page 55: Station Communication

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 communication. SCHLCCH is used for communication Substation Automation (SA) bus or Substation over the rear Ethernet ports, RCHLCCH is used for Monitoring (SM) bus. redundant communications over the rear Ethernet ports Available communication protocols are: and FRONTSTATUS is used for communication over the front port.

  • Page 56
    SPA communication protocol Supervison status for IEC 60870-5-103 I103SUPERV SEMOD120134-5 v1 A single glass or plastic port is provided for the ABB SPA I103SUPERV is a function block with defined functions protocol. This allows extensions of simple substation for supervision indications in monitor direction. This automation systems but the main use is for Substation FunctionType parameter;…
  • Page 57: Remote Communication

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 as interface for horizontal peer-to-peer communication IED commands for IEC 60870-5-103 I103IEDCMD (over LON only). I103IEDCMD is a command block in control direction with defined IED functions. All outputs are pulsed and 22.

  • Page 58: Hardware Description

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 designed for 64 kbit/s resp 2Mbit/s operation. The transducers. The module has six independent, converter is delivered with 19” rack mounting galvanically separated channels. accessories. Optical Ethernet module M16073-3 v9 The optical Ethernet module (OEM) provides two 23.

  • Page 59
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Transformer input module TRM M14875-3 v10 The transformer input module is used to galvanically separate and adapt the secondary currents and voltages generated by the measuring transformers. The module has twelve inputs in different combinations of currents and voltage inputs.
  • Page 60
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 11. Case dimensions, continued Case size (mm)/ (inches) The G and H dimensions are defined by the 19” rack mounting kit. Mounting alternatives M16079-3 v14 • 19” rack mounting kit •…
  • Page 61: Connection Diagrams

    1446-18 IEC 61850 Ed2 level A1 10175313-INC 20-2185rev1 certificate issued by DNV GL IEC 61850 Ed1 level B1 1KHL050130 certificate issued by ABB Power Grids Switzerland Ltd, System Verification and Validation Center, SVC Baden IEC 60870-5-103 certificate 10021419-OPE/INC 16-2490 issued by DNV GL DNP 3.0 certificate issued by…

  • Page 62: Technical Data

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 26. Technical data General M10993-1 v4 IP11376-1 v3 Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified requirements Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to…

  • Page 63
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Energizing quantities, rated values and limits Analog inputs M16988-1 v11 IP15842-1 v1 Table 12. TRM — Energizing quantities, rated values and limits for protection transformer Description Value Frequency Rated frequency f 50/60 Hz Operating range ±…
  • Page 64
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 13. TRM — Energizing quantities, rated values and limits for measuring transformer Description Value Frequency Rated frequency f 50/60 Hz Operating range ± 10% Current inputs Rated current I Operating range (0-1.8) ×…
  • Page 65
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Binary inputs and outputs M12576-1 v13 IP15844-1 v1 Table 16. BIM — Binary input module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V RL ±20%…
  • Page 66
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 18. IOM — Binary input/output module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V RL ±20% 220/250 V RL ±20% Power consumption 24/30 V, 50 mA…
  • Page 67
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12318-1 v11 Table 19. IOM — Binary input/output module contact data (reference standard: IEC 61810-1) Function or quantity Trip and signal relays Fast signal relays (parallel reed relay) Binary outputs Max system voltage 250 V AC/DC 250 V DC…
  • Page 68
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12584-1 v11 Table 20. IOM with MOV and IOM 220/250 V, 110mA — contact data (reference standard: IEC 61810-1) Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay) Binary outputs IOM: 10 IOM: 2…
  • Page 69
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 SEMOD175395-2 v11 Table 21. SOM — Static Output Module data (reference standard: IEC 61810-1): Heavy duty static binary outputs Function of quantity Static binary output trip Max system voltage 250 V DC Number of outputs Impedance open state High impedance…
  • Page 70
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 22. SOM — Static Output module data (reference standard: IEC 61810-1): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage 250 V AC/DC Min load voltage 24 V DC Number of outputs Test voltage across open contact, 1 min…
  • Page 71
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12441-1 v11 Table 23. BOM — Binary output module contact data (reference standard: IEC 61810-1) Function or quantity Trip and Signal relays Binary outputs Max system voltage 250 V AC/DC Min load voltage 24V DC Test voltage across open contact, 1 min…
  • Page 72
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 25. Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal Influence range Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01%/% Operative range Full wave rectified…
  • Page 73
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Type tests according to standards M16706-1 v15 IP15778-1 v1 Table 27. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Level 3 Ring wave immunity test, 100 kHz…
  • Page 74
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 29. Environmental conditions Description Value Operating temperature range -25°C to +55°C (continuous) Short-time service temperature range -40°C to +70°C (<16h) Note: Degradation in MTBF and HMI performance outside the temperature range of -25°C to +55°C Relative humidity <93%, non-condensing…
  • Page 75
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Differential protection M13062-1 v22 Table 33. Restricted earth-fault protection, low impedance REFPDIF Function Range or value Accuracy Operating characteristic Adaptable ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >…
  • Page 76
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M16023-1 v12 Table 35. Line differential protection L3CPDIF, L6CPDIF, LT3CPDIF , LT6CPDIF single IED without communication Function Range or value Accuracy IBase Minimum operate current (20-200)% of ±1.0% of I at I ≤…
  • Page 77
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 35. Line differential protection L3CPDIF, L6CPDIF, LT3CPDIF , LT6CPDIF single IED without communication , continued Function Range or value Accuracy **Operate time, unrestrained negative Min. = 10 ms sequence function Max.
  • Page 78
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 36. Line differential protection L3CPDIF, L6CPDIF, LT3CPDIF , LT6CPDIF with 64 Kbit/s communication Function Range or value Accuracy IBase Minimum operate current (20-200)% of ±4.0% of I at I ≤ I ±4.0% of I at I >…
  • Page 79
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 36. Line differential protection L3CPDIF, L6CPDIF, LT3CPDIF , LT6CPDIF with 64 Kbit/s communication , continued Function Range or value Accuracy **Operate time, unrestrained negative Min. = 15 ms sequence function Max.
  • Page 80
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 37. Line differential protection L3CPDIF, L6CPDIF, LT3CPDIF , LT6CPDIF with 2 Mbits/s communication Function Range or value Accuracy IBase Minimum operate current (20-200)% of ±1.0% of I at I ≤ I ±1.0% of I at I >…
  • Page 81
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 37. Line differential protection L3CPDIF, L6CPDIF, LT3CPDIF , LT6CPDIF with 2 Mbits/s communication , continued Function Range or value Accuracy **Operate time, unrestrained negative Min. = 10 ms sequence function Max.
  • Page 82
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-6746298E-4C29-44C6-AB59-41EBF408A5E4 v4 Table 38. High speed line differential protection for 4 CT sets, 2-3 line ends L4CPDIF with 2 Mbit/s communication Function Range or value Accuracy Minimum operate current (20-200)% of IBase ±1.0% of I at I ≤…
  • Page 83
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-0BD8D3C9-620A-426C-BDB5-DAA0E4F8247F v4 Table 39. Additional security logic for differential protection LDRGFC Function Range or value Accuracy Operate current, zero sequence current (1-100)% of lBase ±1.0% of I Operate current, low current operation (1-100)% of lBase ±1.0% of I Operate voltage, phase to neutral…
  • Page 84
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Impedance protection M13842-1 v15 Table 40. Distance measuring zone, Quad ZMQPDIS Function Range or value Accuracy Number of zones Max 5 with selectable direction Minimum operate residual (5-1000)% of IBase current, zone 1 Minimum operate current, (10-1000)% of IBase…
  • Page 85
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 SEMOD173239-2 v10 Table 41. Distance measuring zone, quadrilateral characteristic for series compensated lines ZMCPDIS, ZMCAPDIS Function Range or value Accuracy Number of zones Max 5 with selectable direction IBase Minimum operate residual (5-1000)% of current, zone 1 IBase…
  • Page 86
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 SEMOD173242-2 v14 Table 43. Full-scheme distance protection, Mho characteristic ZMHPDIS Function Range or value Accuracy Number of zones, Ph-E Max 5 with selectable direction Minimum operate current (10–30)% of IBase Positive sequence impedance, (0.005–3000.000) W/phase ±2.0% static accuracy…
  • Page 87
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 SEMOD153649-2 v8 Table 45. Faulty phase identification with load encroachment FMPSPDIS Function Range or value Accuracy Load encroachment criteria: ±2.0% static accuracy (1.00–3000.00) W/ Load resistance, forward and phase Conditions: reverse Voltage range: (0.1–1.1) x U (5–70) degrees…
  • Page 88
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-9E13C38A-3B6D-402B-98A6-6CDA20632CE7 v5 Table 47. Phase selection, quadrilateral characteristic with settable angle FRPSPDIS Function Range or value Accuracy Minimum operate current (5-500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I >…
  • Page 89
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-6C2EF52A-8166-4A23-9861-38931682AA7D v8 Table 48. High speed distance protection ZMFPDIS, ZMFCPDIS Function Range or value Accuracy Number of zones 5 selectable directions, 2 fixed directions Minimum operate current, Ph- (5-6000)% of IBase ±1.0% of I Ph and Ph-E Positive sequence reactance…
  • Page 90
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-E65CE996-C0CE-4620-8E01-A96896E62802 v1 Table 49. Power swing detection, blocking and unblocking ZMBURPSB Function Range or value Accuracy Reactive reach ±2.0% static accuracy (0.10-3000.00) W/phase Conditions: Voltage range: (0.1-1.1) x U Current range: (0.5-30) x I Angle: at 0 degrees and 85 degrees Resistive reach (0.10–1000.00) W/loop…
  • Page 91
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-BACA37F7-E945-40BC-BF9D-A65BFC96CA91 v9 Table 53. Phase preference logic PPLPHIZ Function Range or value Accuracy Operate value, phase-to-phase and (10 — 90)% of UBase ±0.5% of U UPN< phase-to-neutral undervoltage, UPP< Reset ratio, undervoltage <…
  • Page 92
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-42119BFF-1756-431C-A5A1-0AB637213E96 v2 Table 54. Phase preference logic PPL2PHIZ Function Range or value Accuracy Operate value, phase-to-phase and (10 — 90)% of UBase ±0.5% of U UPN< phase-to-neutral undervoltage, UPP< Reset ratio, undervoltage <…
  • Page 93
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Wide area measurement system GUID-F0BAEBD8-E361-4D50-9737-7DF8B043D66A v5 Table 56. Protocol reporting via IEEE 1344 and IEC/IEEE 60255-118 (C37.118) PMUREPORT Influencing quantity Range Accuracy Signal frequency ± 0.1 x f ≤ 1.0% TVE Signal magnitude: Voltage phasor (0.1–1.2) x U…
  • Page 94
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Current protection M12336-1 v14 Table 57. Instantaneous phase overcurrent protection PHPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >…
  • Page 95
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12342-1 v22 Table 58. Directional phase overcurrent protection, four steps OC4PTOC Function Range or value Accuracy lBase Operate current, step 1-4 (5-2500)% of ±1.0% of I at I ≤ I ±1.0% of I at I >…
  • Page 96
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12340-2 v9 Table 59. Instantaneous residual overcurrent protection EFPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >…
  • Page 97
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M15223-1 v18 Table 60. Directional residual overcurrent protection, four steps EF4PTOC Function Range or value Accuracy Operate current, step 1-4 (1-2500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I >…
  • Page 98
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v6 Table 61. Four step directional negative phase sequence overcurrent protection NS4PTOC Function Range or value Accuracy lBase Operate current, step 1 — 4 (1-2500)% of ±1.0% of I at I £…
  • Page 99
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 SEMOD173350-2 v16 Table 62. Sensitive directional residual overcurrent and power protection SDEPSDE Function Range or value Accuracy (0.25-200.00)% of IBase Operate level for 3I ·cosj directional ±1.0% of I at I £ I residual overcurrent ±1.0% of I at I >…
  • Page 100
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12352-1 v15 Table 63. Thermal overload protection, one time constant LCPTTR/LFPTTR Function Range or value Accuracy Reference current (2-400)% of IBase ±1.0% of I Reference temperature (0-300)°C, (0 — 600)°F ±1.0°C, ±2.0°F Operate time: IEC 60255-149, ±5.0% or ±200 ms whichever is greater…
  • Page 101
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12353-1 v15 Table 64. Breaker failure protection CCRBRF Function Range or value Accuracy lBase Operate phase current (5-200)% of ±1.0% of I at I £ I ±1.0% of I at I > I Reset ratio, phase current >…
  • Page 102
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 SEMOD175152-2 v11 Table 67. Directional underpower protection GUPPDUP Function Range or value Accuracy SBase Power level (0.0–500.0)% of ±1.0% of S at S ≤ S for Step 1 and Step 2 ±1.0% of S at S >…
  • Page 103
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-7EA9731A-8D56-4689-9072-D72D9CDFD795 v8 Table 70. Voltage-restrained time overcurrent protection VRPVOC Function Range or value Accuracy Start overcurrent (2.0 — 5000.0)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio, overcurrent >…
  • Page 104
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-BCCA5F2D-9FF7-4188-9B5D-DA05E8E80CC0 v1 Table 71. Average Power Transient Earth Fault Protection APPTEF Function Range or value Accuracy Minimum operate level for residual (5-80)% of UBase ±0.5% of Ur overvoltage 3Uo> start condition «UN>» Reset ratio for residual overvoltage 3Uo>…
  • Page 105
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Voltage protection M13290-1 v15 Table 72. Two step undervoltage protection UV2PTUV Function Range or value Accuracy UBase Operate voltage, low and high step (1.0–100.0)% of ±0.5% of U UBase Absolute hysteresis (0.0–50.0)% of ±0.5% of U UBase…
  • Page 106
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M13304-1 v15 Table 73. Two step overvoltage protection OV2PTOV Function Range or value Accuracy UBase Operate voltage, step 1 and 2 (1.0-200.0)% of ±0.5% of U at U ≤ U ±0.5% of U at U >…
  • Page 107
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M13317-2 v15 Table 74. Residual overvoltage protection, two steps ROV2PTOV Function Range or value Accuracy UBase Operate voltage, step 1 — step 2 (1.0-200.0)% of ± 0.5% of U at U ≤ U ±…
  • Page 108
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 SEMOD166919-2 v7 Table 76. Voltage differential protection VDCPTOV Function Range or value Accuracy UBase Voltage difference for alarm and trip (2.0–100.0) % of ±0.5% of U Under voltage level (1.0–100.0) % of UBase ±0.5% of U Independent time delay for voltage…
  • Page 109
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Frequency protection M13360-1 v16 Table 79. Underfrequency protection SAPTUF Function Range or Value Accuracy Operate value, start function, at (35.00 — 75.00) Hz ±2.0 mHz symmetrical three phase voltage, StartFrequency Reset hysteresis 10.0 mHz fixed ±2.0 mHz…
  • Page 110
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M14964-1 v13 Table 80. Underfrequency protection SAPTOF Function Range or Value Accuracy Operate value, start function, (35.00 — 90.00) Hz ±2.0 mHz at symmetrical three phase voltage, StartFrequency 10.0 mHz fixed ±2.0 mHz Reset hysteresis Start time measurement with…
  • Page 111
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Multipurpose protection M13095-2 v11 Table 82. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, — NegSeq, -3*ZeroSeq, MaxPh, MinPh, UnbalancePh, phase1- phase2, phase2-phase3, phase3- phase1, MaxPh-Ph, MinPh-Ph, UnbalancePh-Ph…
  • Page 112
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 82. General current and voltage protection CVGAPC, continued Function Range or value Accuracy Start undervoltage, step 1 — 2 (2.0 — 150.0)% of UBase ±0.5% of U at U ≤ U ±0.5% of U at U >…
  • Page 113
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 82. General current and voltage protection CVGAPC, continued Function Range or value Accuracy Impulse margin time 15 ms typically Undervoltage: Critical impulse time 10 ms typically at 1.2 x U to 0.8 x Impulse margin time 15 ms typically…
  • Page 114
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Secondary system supervision M12358-1 v10 Table 83. Current circuit supervision CCSSPVC Function Range or value Accuracy Operate current (10-200)% of IBase ±10.0% of I at I ≤ I ±10.0% of I at I > I Reset ratio, Operate current >90% Block current…
  • Page 115
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-E2EA8017-BB4B-48B0-BEDA-E71FEE353774 v5 Table 85. Fuse failure supervision VDSPVC Function Range or value Accuracy Operate value, block of main fuse failure (10.0-80.0)% of UBase ±0.5% of Ur Reset ratio <110% Operate time, block of main fuse failure at 1 x U Min.
  • Page 116
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Control M12359-1 v15 Table 88. Synchronizing, synchrocheck and energizing check SESRSYN Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase ±0.5% of U at U ≤…
  • Page 117
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12379-1 v13 Table 89. Autorecloser SMBRREC Function Range or value Accuracy Dead time: shot 1 “t1 1Ph” (0.000-120.000) s ±0.2% or ±35 ms shot 1 “t1 2Ph” whichever is greater shot 1 “t1 3Ph “…
  • Page 118
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Scheme communication M16038-1 v14 Table 90. Scheme communication logic with delta based blocking scheme signal transmit ZCPSCH Function Range or value Accuracy Scheme type Intertrip Permissive UR Permissive OR Blocking DeltaBlocking Operate voltage, Delta U (0–100)% of UBase…
  • Page 119
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M16039-1 v16 Table 92. Current reversal and weak-end infeed logic for distance protection ZCRWPSCH Function Range or value Accuracy Detection level phase-to- (10-90)% of UBase ±0.5% of U neutral voltage Detection level phase-to-phase (10-90)% of UBase ±0.5% of U…
  • Page 120
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M16051-2 v11 Table 96. Current reversal and weak-end infeed logic for residual overcurrent protection ECRWPSCH Function Range or value Accuracy Operate mode of WEI logic Echo Echo & Trip Operate voltage 3U0 for WEI (5-70)% of UBase ±0.5% of U trip…
  • Page 121
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Direct transfer trip GUID-B5714FAE-A87D-4C2D-A167-6CB3522CE1D5 v5 Table 97. Low active power and power factor protection LAPPGAPC Function Range or value Accuracy Operate value, low active power (2.0-100.0)% of SBase ±1.0% of S Reset ratio, low active power <105% Operate value, low power factor…
  • Page 122
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-C99E063D-B377-40D5-8481-9F46D4166AED v3 Table 100. Carrier receive logic LCCRPTRC Function Range or value Accuracy Operation mode 1 Out Of 2 2 Out Of 2 Independent time delay (0.000-60.000) s ±0.2% or ±35 ms whichever is greater GUID-122A206E-27D2-4D15-AD5A-86B68F1ED559 v6 Table 101.
  • Page 123
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-0E964441-43DE-43B6-B454-485FBBF66B5C v5 Table 103. Negative sequence overcurrent protection LCNSPTOC Function Range or value Accuracy Operate value, negative sequence (3 — 2500)% of IBase ±1.0% of Ir at I ≤ I overcurrent ±1.0% of I at I >…
  • Page 124
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-C4ACE306-2A54-483D-B247-A479D48CBF5F v5 Table 105. Three phase overcurrent LCP3PTOC Function Range or value Accuracy Operate value, overcurrent (5-2500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio, overcurrent >…
  • Page 125
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Logic M12380-1 v15 Table 107. Tripping logic common 3-phase output SMPPTRC Function Range or value Accuracy Program Trip action, 3 phase, 1ph/2ph, 1ph/2ph/3ph Minimum trip pulse (0.000-60.000) s ±0.2% or ±15 ms whichever is greater length , tTripMin tWaitForPHS…
  • Page 126
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v2 Table 113. Number of INDCALH instances Function Quantity with cycle time 3 ms 8 ms 100 ms INDCALH GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v3 Table 114. Number of AND instances Logic block Quantity with cycle time 3 ms 8 ms…
  • Page 127
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-BE6FD540-E96E-4F15-B2A2-12FFAE6C51DB v2 Table 120. Number of RSMEMORY instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms RSMEMORY GUID-7A0F4327-CA83-4FB0-AB28-7C5F17AE6354 v2 Table 121. Number of SRMEMORY instances Logic block Quantity with cycle time 3 ms 8 ms…
  • Page 128
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-77FEBE9B-0882-4E85-8B1A-7671807BFC02 v2 Table 127. Number of INVALIDQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms INVALIDQT GUID-F25B94C6-9CC9-48A0-A7A3-47627D2B56E2 v1 Table 128. Number of INVERTERQT instances Logic block Quantity with cycle time 3 ms 8 ms…
  • Page 129
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-1C381E02-6B9E-44DC-828F-8B3EA7EDAA54 v1 Table 134. Number of XORQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms XORQT GUID-19810098-1820-4765-8F0B-7D585FFC0C78 v8 Table 135. Number of instances in the extension logic package Logic block Quantity with cycle time 3 ms…
  • Page 130
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v2 Table 139. Number of ITBGAPC instances Function Quantity with cycle time 3 ms 8 ms 100 ms ITBGAPC GUID-B258726E-1129-47C9-94F9-BE634A2085FA v4 Table 140. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC Function Cycle time (ms) Range or value…
  • Page 131
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Monitoring M12386-1 v16 Table 144. Power system measurement CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) x f ±2.0 mHz Voltage (10 to 300) V ±0.3% of U at U ≤ 50 V ±0.2% of U at U >…
  • Page 132
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6 Table 147. Voltage measurement phase-earth VNMMXU Function Range or value Accuracy Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V ±0.2% of U at U > 50 V Phase angle (5 to 175) V ±0.5 degrees at U ≤…
  • Page 133
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12760-1 v12 Table 151. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 200, first in — first out Time tagging resolution 1 ms See table…
  • Page 134
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v9 Table 153. Insulation supervision for liquid medium function SSIML Function Range or value Accuracy Oil alarm level 1.00-100.00 ±10.0% of set value or 0.2 whichever is greater Oil lockout level 1.00-100.00 ±10.0% of set value or 0.2 whichever is greater Temperature alarm level…
  • Page 135
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12700-1 v5 Table 156. Event list Function Value Buffer capacity Maximum number of events in the list 5000 Resolution 1 ms Accuracy Depending on time synchronizing M13765-1 v6 Table 157. Indications Function Value Buffer capacity…
  • Page 136
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v3 Relion® 670 series can store up to 10240 security events. Table 161. Event counter with limit supervision L4UFCNT Function Range or value Accuracy Counter value 0-65535 Hitachi Power Grids ©…
  • Page 137
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 161. Event counter with limit supervision L4UFCNT , continued Function Range or value Accuracy Max. count up speed 30 pulses/s (50% duty cycle) GUID-F5E124E3-0B85-41AC-9830-A2362FD289F2 v1 Table 162. Running hour-meter TEILGAPC Function Range or value Accuracy…
  • Page 138
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-2068BBA0-9026-48D0-9DEB-301BCB3C600C v2 Table 165. Voltage harmonic monitoring VHMMHAI (50/60 Hz) Function Range or value Accuracy Fundamental Harmonic Frequency (0.95 — 1.05) X f 2nd order to 5th order (0.1 — 0.5) X U ±…
  • Page 139
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Metering M13404-2 v5 Table 166. Pulse-counter logic PCFCNT Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of (1–3600) s counter value SEMOD153707-2 v5 Table 167.
  • Page 140
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Station communication M15031-1 v9 Table 168. Communication protocols Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 60870–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0 Communication speed for the IEDs…
  • Page 141
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12589-1 v5 Table 173. SLM – LON port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in Fiber, optical budget Glass fiber: 11 dB (1000m/3000 ft typically *) Plastic fiber: 7 dB (10m/35 ft typically *) Fiber diameter Glass fiber: 62.5/125 mm…
  • Page 142
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 177. SFP — Galvanic RJ45 Quantity Rated value Number of channels Up to 6 single or 3 redundant or a combination of single and redundant links for communication using any protocol Standard IEEE 802.3u 100BASE-TX Type of cable…
  • Page 143
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Remote communication M12756-1 v13 Table 179. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR) Long range (LR) Type of fiber Multi-mode fiber Single-mode fiber Single-mode fiber glass 62.5/125 µm…
  • Page 144
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Hardware M11778-1 v7 SEMOD53385-1 v1 Table 181. Case Material Steel sheet Front plate Stainless steel with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) M12327-1 v5 Table 182.
  • Page 145
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v3 Because of limitations of space, when ring lug terminal is ordered for Binary I/O connections, one blank slot is necessary between two adjacent I/O modules. Please refer to the ordering particulars for details.
  • Page 146
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Basic IED functions M11963-1 v5 Table 189. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out M12331-1 v9 Table 190. Time synchronization, time tagging Function Value Time tagging accuracy of the synchrophasor data…
  • Page 147
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 SEMOD141136-2 v10 Table 194. IRIG-B Quantity Rated value Number of channels IRIG-B Number of optical channels Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –…
  • Page 148
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Inverse characteristic M12388-1 v23 Table 195. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 ANSI/IEEE C37.112 , 1.5 x I ≤ I ≤ 20 x I ±2.0% or ±40 ms whichever is greater æ…
  • Page 149
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 197. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 IEC 60255-151, ±2.0% 1.5 x I ≤ I ≤ 20 x I or ±40 ms whichever is greater æ…
  • Page 150
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 198. IEC Inverse time characteristics for Line differential protection Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 1.10 IEC 60255-151, ±5.0% or ±40 ms whichever is greater æ…
  • Page 151
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 200. RI and RD type inverse time characteristics for Line differential protection Function Range or value Accuracy RI type inverse characteristic 0.05 ≤ k ≤ 1.10 IEC 60255-151, ±5.0% or ±40 ms whichever is greater ×…
  • Page 152
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 202. IEC Inverse time characteristics for Line Differential protection Function Range or value Accuracy Operating characteristic: k = (0.05-2.00) in steps of 0.01 IEC 60255-151, ± 5.0% or ± 40 ms whichever is greater æ…
  • Page 153
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-19F8E187-4ED0-48C3-92F6-0D9EAA2B39BB v4 Table 204. ANSI Inverse time characteristics for Sensitive directional residual overcurrent and power protection Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 2.00 ANSI/IEEE C37.112 , 1.5 x I ≤…
  • Page 154
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 205. IEC Inverse time characteristics for Sensitive directional residual overcurrent and power protection Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 2.00 IEC 60255-151, ±5.0% 1.5 x I ≤…
  • Page 155
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-2AE8C92E-5DA8-487F-927D-8E553EE29240 v2 Table 207. ANSI Inverse time characteristics for Voltage restrained time overcurrent protection Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 ANSI/IEEE C37.112 , ± 5.0% or ±40 ms whichever is greater æ…
  • Page 156
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 SEMOD116978-2 v10 Table 209. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ…
  • Page 157
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 210. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ…
  • Page 158
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 211. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps ±5.0% or ±45 ms whichever is greater of 0.01 æ…
  • Page 159: Ordering For Customized Ied

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 27. Ordering for customized IED GUID-79B6B8D2-5EE1-4456-A767-5820B9FA61D7 v13 Table 212. General guidelines Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.

  • Page 160
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 216. Differential protection Position Table 217. Differential functions Function Function Ordering no Position Available Selected Notes and identification rules High impedance differential protection, single phase HZPDIF 1MRK005904-HB 00-03 Restricted earth fault protection, low impedance REFPDIF 1MRK005904-LD Line differential protection for 3 CT sets, 2-3 line ends…
  • Page 161
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 219. Impedance functions, alternatives Function Function Ordering no Position Available Selected Notes and identification rules Note: One and only one alternative can be selected. Selected qty is 0 for other functions in an unselected alternative. Alternative 1 Distance protection, quadrilateral Distance protection zone, quadrilateral characteristic ZMQPDIS,…
  • Page 162
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 220. Current protection Position Table 221. Current functions Function Function Ordering no Position Available Selected Notes and identification rules Instantaneous phase overcurrent protection PHPIOC 1MRK005910-AD Directional phase overcurrent protection, four steps OC4PTOC 1MRK005910-BC Instantaneous residual overcurrent protection…
  • Page 163
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 227. Multipurpose protection Position Table 228. Multipurpose functions Function Function Ordering no Position Available Selected Notes and rules identification General current and voltage protection CVGAPC 1MRK005915-AA Table 229. General calculation Position Table 230.
  • Page 164
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 236. Scheme communication functions Function Function Ordering no Position Available Selected Notes and identification rules Scheme communication logic with delta based blocking ZCPSCH 1MRK005920-AA scheme signal transmit Phase segregated scheme communication logic for distance ZC1PPSCH 1MRK005920-BA protection…
  • Page 165
    Additional local HMI user dialogue language No additional HMI language HMI language, English US 1MRK002920-UB Selected Additional 2nd languages are continuously being added. Please get in touch with local ABB sales contact. Table 244. Casing selection Casing Ordering no Selection Notes and rules 1/2 x 19″…
  • Page 166
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 248. Analog system selection Analog system Ordering no Selection Notes and rules When more than one TRM is selected, the connector type on both TRMs must be the same (A compression or B ring lug). Slot position (front view/rear view) No Transformer input module included TRM 12I 1A, 50/60Hz, compression terminals…
  • Page 167
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 249. Maximum quantity of I/O modules, with compression terminals When ordering I/O modules, observe the maximum quantities according to the tables below. Note: Standard order of location for I/O modules is BIM-BOM-SOM-IOM-MIM from left to right as seen from the rear side of the IED, but can also be freely placed.
  • Page 168
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 251. Binary input/output module selection Binary input/ Ordering no Selection Notes and rules output modules Slot position (front view/rear view) 1/2 case with 1 █ █ █ 3/4 case with 1 █…
  • Page 169
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 251. Binary input/output module selection, continued Binary input/ Ordering no Selection Notes and rules output modules IOM 8 inputs, RL 1MRK000173-BE 110-125 VDC, 50mA, 10+2 output relays IOM 8 inputs, RL 1MRK000173-CE 220-250 VDC, 50mA, 10+2…
  • Page 170
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 252. Station communication, remote end serial communication and time synchronization selection Station communication, remote end Ordering no Selection Notes and rules serial communication and time synchronization Slot position (front view/rear view) Available slots in 1/2, 3/4 and 1/1 █…
  • Page 171: Ordering For Pre-Configured Ied

    Line differential protection, Multi breaker, 1/3 phase tripping, 2-3 line ends 1MRK004810-HG Line differential protection, Single breaker, 1/3 phase tripping, with distance 1MRK004810-KG protection ACT configuration ABB standard configuration Selection for position #2 Hitachi Power Grids © Copyright 2017 Hitachi Power Grids. All rights reserved…

  • Page 172
    No additional HMI language HMI language, English US 1MRK002920-UB Selection for position #4 Additional 2nd languages are continuously being added. Please get in touch with local ABB sales contact. Hitachi Power Grids © Copyright 2017 Hitachi Power Grids. All rights reserved…
  • Page 173
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Casing Ordering no Notes and rules 1/2 x 19″ rack casing, 1 TRM 1MRK000151-VA 3/4 x 19″ rack casing, 1 TRM 1MRK000151-VB 3/4 x 19″ rack casing, 2 TRM 1MRK000151-VE 1/1 x 19″…
  • Page 174
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Analog system Ordering no Notes and rules When more than one TRM is selected, the connector type on both TRMs must be the same (A compression or B ring lug). Slot position (front view/rear view) No Transformer input module included TRM 9I 1A + 3U 110/220V, 50/60Hz, compression terminals…
  • Page 175
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Binary input/ Ordering no Notes and rules output modules For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used. Note: 1 BIM required in position P3 and 1 BOM required in position P4. Slot position (front view/rear view)
  • Page 176
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Binary input/ Ordering no Notes and rules output modules For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used. Note: 1 BIM required in position P3 and 1 BOM required in position P4. IOM 8 inputs, RL 1MRK000173-CE 220-250 VDC,…
  • Page 177
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Station communication, remote end serial Ordering no Notes and rules communication and time synchronization Slot position (front view/rear view) Available slots in 1/2, 3/4 and 1/1 case with 1 █ █…
  • Page 178: Ordering For Accessories

    (ordering number RK926 315- IEDs is described in 1MRK 512 001-BEN and 1MRK BE). 001024-CA. Please refer to the website: Multi-breaker/Single or Three Phase trip with external www.abb.com/protection-control for detailed neutral on current circuit (ordering number RK926 315- information. BV).

  • Page 179
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Protection cover M15040-3 v8 Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-AC Protective cover for rear side of terminal, 6U, 3/4 x 19”…
  • Page 180
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Specify additional quantity of IED Connect USB flash drive requested . Quantity: 1MRK 002 290-AE Hitachi Power Grids © Copyright 2017 Hitachi Power Grids. All rights reserved…
  • Page 181
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 User documentation Specify the number of printed manuals requested Application manual Quantity: 1MRK 505 376-UEN ANSI Quantity: 1MRK 505 376-UUS Technical manual Quantity: 1MRK 505 377-UEN ANSI Quantity: 1MRK 505 377-UUS Commissioning manual Quantity: 1MRK 505 378-UEN…
  • Page 182
    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 ANSI Quantity: 1MRK 511 398-UUS Cyber security deployment guideline Quantity: 1MRK 511 399-UEN Application guide, Communication set-up Quantity: 1MRK 505 382-UEN Reference information M2175-3 v4 For our reference and statistics we would be pleased to be provided with the following application data: Country: End user: Station name:…
  • Page 184
    ABB Power Grids Sweden AB Grid Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 10 738 00 00 Scan this QR code to visit our website https://www.abb.com/protection-control © Copyright 2017 Hitachi Power Grids. All rights reserved.

This manual is also suitable for:

Red670

ABB RED670 Relion 670 series: Available Instructions

Note for Owners:

Guidesimo.com webproject is not a service center of ABB trademark and does not carries out works for diagnosis and repair of faulty ABB RED670 Relion 670 series equipment. For quality services, please contact an official service center of ABB company. On our website you can read and download documentation for your ABB RED670 Relion 670 series device for free and familiarize yourself with the technical specifications of device.

  • sprecher + schuh CT7N-43 Series

    CT7N-43…IEC/EN 60947-1,-4-1,-5-1UL 508CSA C22.2 No. 14Installation instructionAttention: To prevent electrical shock, disconnect from power source before installing or servicing. Install in suitable enclosure. Keep free from contaminants.MontageanleitungAchtung: Vor Installations- oder Servicearbeiten Stromversorgung unterbrechen, um Unfälle zu vermeiden. Die Geräte müssen in einem passenden …

    CT7N-43 Series Relays, 2

  • Siemens 3VA9978-0BB Series

    A5E03472775061-05 Last Update: 07 October 20163ZW1012-1VA00-8AA0sUndervoltage Release, UVR / Universal release, UNIUnterspannungsauslöser, UVR / Universalauslöser, UNIDéclencheur à minimum de tension, UVR / déclencheur universel, UNIDisparador de mínima tensión, UVR / Disparador universal, UNIBobina di minima tensione, UVR / sganciatore universale, UNIDisparador de subtensão, UVR / dispara …

    3VA9978-0BB Series Relays, 6

  • NIVELCO NITIME JEL-111

    Thank you for choosing a NIVELCO instrument. We are sure that you will be satisfied throughout its use. 1. APPLICATION NITIME time relays are microprocessor controlled units suitable for highly diverse timing tasks. The multiple functions, the universal power supply and (1-module width) the rail mountable construction ensure universal usage (automation, lighting, heating, motor and ventilation con …

    NITIME JEL-111 Relays, 2

  • Littelfuse PGR-8800

    Pub. PGR-8800-M. December 14, 2012 • www.littelfuse.com • © 2012 Littelfuse • • 1/82 Arc-Flash Relay PGR-8800 PGR-8800 ARC-FLASH RELAY DECEMBER 14, 2012 REVISION 2 PGR-8800 SERIESARC-FLASH RELAY …

    PGR-8800 Relays, 82

  • Vantage Hearth RadioLink AccentPoint Relay Station II APREL

    ©Vantage, 8/18/2016 / IS-0615-B RadioLink® AccentPoint Relay Station II — MODEL: APREL(-GU) page 1 of 2 INSTALLATION VANTAGECONTROLS.COM VANTAGE INSTALL GUIDES 2168 West Grove Parkway, Suite 300, Pleasant Grove, UT. 84062 USA Telephone: 801 229-2800 ● Fax: 801 224-0355 RadioLink® AccentPoint Relay Station II — MODEL: APREL(-GU) Overview The Vantage AccentPoint Relay II connects …

    RadioLink AccentPoint Relay Station II APREL Relays, 2

  • Siemens SIRIUS 3RR24

    SIRIUS 3RR24DEÜberwachungsrelais zur 3-phasigen Stromüberwachung für IO-Link zum Anbau an Schütze S00 / S0ESRelés de monitoreo para vigilanciatrifásica de corriente, para IO-Link,montaje en contactores S00 / S0TRIO-Link 3 fazlı akım kontrolü içinS00 / S0 kontaktörlere bağlanabilir kontrol rölesiENMonitoring relays for 3-phase current monitoring for IO-Link for mounting on contactors S …

    SIRIUS 3RR24 Relays, 12

  • Pilz PNOZ e2.1p

    Das ZweihandbediengerätPNOZ e2.1pDas Gerät erfüllt die Anforderung nachEN 574, 11/96 Typ III C.Das Zweihandbediengerät zwingt denBediener einer Presse zur Vermeidung vonHandverletzungen die Hände während dergefahrbringenden Schließbewegungaußerhalb der Gefahrenstelle zu halten.Das Gerät ist zum Einbau in Steuerungenfür Pressen der Metallbearbeitung alsBaustein der Gleichzeitigkeit geeign …

    PNOZ e2.1p Relays, 16

  • Pilz PNOZ X3

    Nr. 19 236BetriebsanleitungTechnical InstructionsBetjeningsvejledning PNOZ X3Safety Regulations• The unit may only be installed andoperated by personnel who are familiarwith both these instructions and thecurrent regulations for safety at work andaccident prevention. Follow VDE and localregulations especially as regardspreventative mea …

    PNOZ X3 Relays, 6

  • ABB C6701

    Unter Berücksichtigung der Umgebungsbedingungen müssen die Geräte in Schaltschränke der Schutzart IP32, IP43 oder IP54 eingebaut werden.Die hier beschriebenen Produkte wurden entwickelt, um als Teil einer Gesamtan-lage oder Maschine sicherheitsgerichtete Funktionen zu übernehmen. Ein komplet-tes sicherheitsgerichtetes System enthält in der Regel Sensoren, Auswerteeinheiten, Meldegeräte und …

    C6701 Relays, 11

  • BRP EVINRUDE ICON Series

    Outboard EnginesPrinted in the United States.© 2009 BRP US Inc. All rights reserved.TM, ® and the BRP logo are registered trademarks of Bombardier Recreational Products Inc. or its affiliates.DSS09392I REV 1 1 of 5EVINRUDE® ICON™ GATEWAY MODULE AND CABLE KIT,P/N 764922APPLICATIONUse this instruction sheet when installing the above gateway module and cable kit on 2008 and newerEvinrude E-TEC� …

    EVINRUDE ICON Series Control Unit, 11

  • Basler BE1-87G

    +05647%6+10/#07#.(148#4+#$.’2’4%’06#)’&+((‘4’06+#.4’.#;$’)2WDNKECVKQP 4GXKUKQP , …

    BE1-87G Power distribution unit, 40

Popular Relays User Guides:

Download Product manual of ABB REL670 Controller, Power distribution unit for Free or View it Online on All-Guides.com.

ABB REL670 Product manual - Page 1

1

ABB REL670 Product manual - Page 2

2

ABB REL670 Product manual - Page 3

3

ABB REL670 Product manual - Page 4

4

ABB REL670 Product manual - Page 5

5

ABB REL670 Product manual - Page 6

6

ABB REL670 Product manual - Page 7

7

ABB REL670 Product manual - Page 8

8

ABB REL670 Product manual - Page 9

9

ABB REL670 Product manual - Page 10

10

ABB REL670 Product manual - Page 11

11

ABB REL670 Product manual - Page 12

12

ABB REL670 Product manual - Page 13

13

ABB REL670 Product manual - Page 14

14

ABB REL670 Product manual - Page 15

15

ABB REL670 Product manual - Page 16

16

ABB REL670 Product manual - Page 17

17

ABB REL670 Product manual - Page 18

18

ABB REL670 Product manual - Page 19

19

ABB REL670 Product manual - Page 20

20

ABB REL670 Product manual - Page 21

21

ABB REL670 Product manual - Page 22

22

ABB REL670 Product manual - Page 23

23

ABB REL670 Product manual - Page 24

24

ABB REL670 Product manual - Page 25

25

ABB REL670 Product manual - Page 26

26

ABB REL670 Product manual - Page 27

27

ABB REL670 Product manual - Page 28

28

ABB REL670 Product manual - Page 29

29

ABB REL670 Product manual - Page 30

30

ABB REL670 Product manual - Page 31

31

ABB REL670 Product manual - Page 32

32

ABB REL670 Product manual - Page 33

33

ABB REL670 Product manual - Page 34

34

ABB REL670 Product manual - Page 35

35

ABB REL670 Product manual - Page 36

36

ABB REL670 Product manual - Page 37

37

ABB REL670 Product manual - Page 38

38

ABB REL670 Product manual - Page 39

39

ABB REL670 Product manual - Page 40

40

ABB REL670 Product manual - Page 41

41

ABB REL670 Product manual - Page 42

42

ABB REL670 Product manual - Page 43

43

ABB REL670 Product manual - Page 44

44

ABB REL670 Product manual - Page 45

45

ABB REL670 Product manual - Page 46

46

ABB REL670 Product manual - Page 47

47

ABB REL670 Product manual - Page 48

48

ABB REL670 Product manual - Page 49

49

ABB REL670 Product manual - Page 50

50

ABB REL670 Product manual - Page 51

51

ABB REL670 Product manual - Page 52

52

ABB REL670 Product manual - Page 53

53

ABB REL670 Product manual - Page 54

54

ABB REL670 Product manual - Page 55

55

ABB REL670 Product manual - Page 56

56

ABB REL670 Product manual - Page 57

57

ABB REL670 Product manual - Page 58

58

ABB REL670 Product manual - Page 59

59

ABB REL670 Product manual - Page 60

60

ABB REL670 Product manual - Page 61

61

ABB REL670 Product manual - Page 62

62

ABB REL670 Product manual - Page 63

63

ABB REL670 Product manual - Page 64

64

ABB REL670 Product manual - Page 65

65

ABB REL670 Product manual - Page 66

66

ABB REL670 Product manual - Page 67

67

ABB REL670 Product manual - Page 68

68

ABB REL670 Product manual - Page 69

69

ABB REL670 Product manual - Page 70

70

ABB REL670 Product manual - Page 71

71

ABB REL670 Product manual - Page 72

72

ABB REL670 Product manual - Page 73

73

ABB REL670 Product manual - Page 74

74

ABB REL670 Product manual - Page 75

75

ABB REL670 Product manual - Page 76

76

ABB REL670 Product manual - Page 77

77

ABB REL670 Product manual - Page 78

78

ABB REL670 Product manual - Page 79

79

ABB REL670 Product manual - Page 80

80

ABB REL670 Product manual - Page 81

81

ABB REL670 Product manual - Page 82

82

ABB REL670 Product manual - Page 83

83

ABB REL670 Product manual - Page 84

84

ABB REL670 Product manual - Page 85

85

ABB REL670 Product manual - Page 86

86

ABB REL670 Product manual - Page 87

87

ABB REL670 Product manual - Page 88

88

ABB REL670 Product manual - Page 89

89

ABB REL670 Product manual - Page 90

90

ABB REL670 Product manual - Page 91

91

ABB REL670 Product manual - Page 92

92

ABB REL670 Product manual - Page 93

93

ABB REL670 Product manual - Page 94

94

ABB REL670 Product manual - Page 95

95

ABB REL670 Product manual - Page 96

96

ABB REL670 Product manual - Page 97

97

ABB REL670 Product manual - Page 98

98

ABB REL670 Product manual - Page 99

99

ABB REL670 Product manual - Page 100

100

ABB REL670 Product manual - Page 101

101

ABB REL670 Product manual - Page 102

102

ABB REL670 Product manual - Page 103

103

ABB REL670 Product manual - Page 104

104

ABB REL670 Product manual - Page 105

105

ABB REL670 Product manual - Page 106

106

ABB REL670 Product manual - Page 107

107

ABB REL670 Product manual - Page 108

108

ABB REL670 Product manual - Page 109

109

ABB REL670 Product manual - Page 110

110

ABB REL670 Product manual - Page 111

111

ABB REL670 Product manual - Page 112

112

ABB REL670 Product manual - Page 113

113

ABB REL670 Product manual - Page 114

114

ABB REL670 Product manual - Page 115

115

ABB REL670 Product manual - Page 116

116

ABB REL670 Product manual - Page 117

117

ABB REL670 Product manual - Page 118

118

Relion

®

670 series

Line differential protection RED670 ANSI

Customized

Product Guide

Понравилась статья? Поделить с друзьями:
  • Информация аудитора руководству аудируемого лица представляет собой тест
  • Сколько хранить инструкции по охране труда после замены новыми
  • Руководство по системы управления двигателем ваз
  • Как настроить гбо 4 поколения диджитроник своими руками пошаговая инструкция
  • Nsx r71 инструкция на русском aiwa скачать бесплатно