Control Equipment for the Vibratory Feeder Industry

MFS 268

Frequency Converter for Vibratory Feeders

UL / CSA — Version

268_UL-CSA_ANL_EN_47-13.DOC

21.11.2013

loading

Related Manuals for Reo Elektronik REOVIB MFS 268

Summary of Contents for Reo Elektronik REOVIB MFS 268

  • Page 1
    REOVIB Control Equipment for the Vibratory Feeder Industry MFS 268 Frequency Converter for Vibratory Feeders UL / CSA — Version 268_UL-CSA_ANL_EN_47-13.DOC 21.11.2013…
  • Page 2: Technical Safety Instructions For The User

    The units described herein are electrical controllers for installation in industrial plant. They are designed for controlling vibratory feeders. For use in NFPA 79 Applications only Adapters providing field wiring means are available from REO ELEKTRONIK AG. Refer to REO ELEKTRONIK AG.

  • Page 3: Table Of Contents

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK Contents Technical safety instructions for the user ………………… 1 1.0 General …………………………3 2.0 Function …………………………3 2.1 Track control ……………………….4 2.2 Operating with two speeds (2 set points for coarse/fine switching) ………… 4 2.3 Control inputs and output ……………………

  • Page 4: General

    ELEKTRONIK 1.0 General The REOVIB MFS 268 range comprises special, adaptable controllers for use with vibratory feeders. The units generate an output frequency, to drive feeders, that is independent of mains frequency and so exact tuning with springs is not necessary. The feeders also run quieter because of the sinusoidal output signal.

  • Page 5: Track Control

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 2.1 Track control output switched ON and OFF Sensor from a track component sensor, using internal, adjustable time delays (ton Feeder and toff). The queue of components rises above and drops below the track sensor…

  • Page 6: Output Status Relay

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 2.3.4 Output status relay Status-Relay contact 250 V/1 A (changeover). Relay closes when the feeder is running – the relay opens when there is no enable signal or a fault displayed. 2.3.5 Time-Out output 24 VDC «time Out»…

  • Page 7: Technical Data

    For use in NFPA 79 Applications only E217179 Adapters providing field wiring means are available from REO ELEKTRONIK AG. Refer to REO ELEKTRONIK AG. 6.0 Declaration of Conformity We declare that these products conform with the following standards: EN 61000-6-4 and EN 61000-6-2 in accordance with the regulations of guidelines 2004/108/EC.

  • Page 8: Settings

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 7.0 Settings After checking the correct operation of the controller in conjunction with the vibratory feed system it is advisable to restrict the user to feeder throughput settings only. Setting the feeder throughput: Press the P key twice and adjust the throughput with the cursor keys (Code C.

  • Page 9: Control Elements

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 8.0 Control elements 8.1 Settings The six buttons and a LED display found in the front panel, are used for operating and setting up the unit. All operating methods and adjustable Display parameters can be set up through this panel.

  • Page 10: Commissioning

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 9.0 Commissioning 9.1 Assembling position Please fasten the devices on a vibration-free underground and take care for sufficient air circulation. 9.2 Preliminary steps • Check that the unit is correct for the local mains supply (rating plate information) and that it is correct- ly rated for the feed system.

  • Page 11: Putting The Equipment Into Operation

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 9.3 Putting the equipment into operation 1. Establish the vibrating frequency. 2. Establish the power of the feed system (maximum permissible current draw). For a new feeder where settings are unknown: (see also comments below) Without connecting the feeder, select parameter FAC in menu C210 (reset factory settings), press the cursor key to reset (SAFE) and press the P key to leave the menu.

  • Page 12: Setting Instructions

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.0 Setting Instructions 10.1 User adjustment of throughput Code C. 000 Feeder amplitude set point 0…100 % Running mode A further set point code can be found under C002 (for use in coarse/fine operation) Feeder amplitude set point 0…100 %…

  • Page 13: Track Control

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.2 Track control Code C. 167, 007 On time delay 0…60 sec. Off time delay 0…60 sec. 0 = No sensor inverting I = Sensor inverting 0 = Sensor time out not active I = Sensor time out active E.

  • Page 14: Pulse Feed

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.5 Pulse feed Code C. 004, 064 HOP. = 0 = continuous duty HOP. = I = pulse feed On time delay [sec.] Off time delay [sec.] Invert hopper sensor (not active) Running mode 10.2.6 Regulation mode…

  • Page 15: Instructions For Using Regulation Mode

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.6.1 Instructions for using regulation mode • An accelerometer e.g. SW 70 must be fitted to the vibratory feeder in order to run in regulation mode. The accelerometer should have a frequency range corresponding to that of the feeder.

  • Page 16
    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK In regulation mode the magnitude of the output signal has a direct affect on the maximum ampli- tude of the feeder. On bowl feeders it is advisable to fit the sensor as near as possible to the outside diameter and in this…
  • Page 17: Relationship Between Acceleration And Amplitude

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.6.3 Relationship between acceleration and amplitude The sensor measures the momentary acceleration of the feeder. It generates a sinusoidal output voltage signal. The acceleration gets higher as the frequency increases. The sensor signal is greater for a higher frequency and lower amplitude than for a low frequency with a higher amplitude.

  • Page 18: Optimisating Controller In Regulation Mode

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.6.6 Optimisating controller in regulation mode Setting the control range 1. In Menu C. 096 set parameter P (Max Limit) to 50 % 2. Set A (Feeder throughput) to 100% 3. Increase limit P from 50% until the required maximum feeder throughput is achieved The full set point adjustment range of 0…100% can now be used…

  • Page 19: Display Actual Current And Frequency

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.7 Display actual current and frequency Code C. 040 Actual current (display only) Actual frequency (display only) Running mode 10.2.8 Save selected parameters Code C. 143 Choose user parameter set Save new parameters Running mode 10.2.9 Recall user or factory settings…

  • Page 20: Error Messages / Error Reset

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 11.0 Error messages / ERROR reset Errors are indicated by an alternating code and ERROR display Overload limit Output level exceeded e.g. incorrect frequency setting, coil air- gap to wide. Short circuit trip Faulty coil, short circuit or defective cable..

  • Page 21: Connections For Enclosed Construction (Ip 54): 6-8 A Units

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 12.0 Connections for enclosed construction (IP 54): 6-8 A Units Internal connections When a potentiometer is connected parameter POT must be set to I in Menu C003. Status- relay 1 2 3 4…

  • Page 22: Connections For Enclosed Construction (Ip 54): 12 A Units

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 12.1 Connections for enclosed construction (IP 54): 12 A Units Internal connections Status relay Time out +24 V Air valve +24 V +24 V Accelerometer SW… INPUT Set point (external) +10V 0(4)…20mA 0…10V…

  • Page 23: Connections For Enclosed Construction (Ip 54): 16 A Units

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 12.2 Connections for enclosed construction (IP 54): 16 A Units Internal connections Status relay Time out +24 V Air valve +24 V +24 V Accelerometer SW… INPUT Set point (external) +10V 0(4)…20mA 0…10V…

  • Page 24: Connections For Panel Mounting Construction (Ip 20): 3 A, 6 A, 8 A

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 13.0 Connections for panel mounting construction (IP 20): 3 A, 6 A, 8 A REOVIB MFS268 Material-Sensor +24V Enable 12…24V, DC Set point 0…10V 0(4)…20mA R=500 OHM black External INPUT orange SW… + 24V…

  • Page 25: Connections For Panel Mounting Construction (Ip 20): 16A

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 13.1 Connections for panel mounting construction (IP 20): 16A line choke Mains L, N, PE / 115V/230V, 50/60HZ Material sensor +24V Enable 12…24V, DC Set point 0(4)…20mA 0…10V SPEED +10V black orange INPUT Accelerometer SW…

  • Page 26: Dimensions For 3 A, 6 A, 8 A Units

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 14.0 Dimensions for 3 A, 6 A, 8 A Units Enclosed construction, (IP 54) Ø5,0 REOVIB MFS 268 SPEED www.reo.de Ø5,0 Panel mounting construction, (IP 20) Ø 5,0 Ø 5,0 REOVIB MFS268 REOVIB MFS268 Ø…

  • Page 27: Dimensions Of Enclosed Construction (Ip 54) 12 A

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 14.1 Dimensions of enclosed construction (IP 54) 12 A Ø5,0 REOVIB MFS 268 SPEED www.reo.de Ø5,0 14.2 Dimensions of enclosed construction (IP 54) 16 A Ø5,0 REOVIB MFS 268 SPEED www.reo.de Ø5,0…

  • Page 28: Dimensions Of Panel Mounting Construction (Ip 20) 16 A

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 14.3 Dimensions of Panel mounting construction (IP 20) 16 A Ø5,0 SPEED +10V Ø5,0…

  • Page 29: A 1.0 Service Appendix

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK A 1.0 Service appendix ATTENTION ! The settings described in this section relating to the service menu are intended for use by skilled persons because the functions and limits of the feed system can be greatly influenced by their…

  • Page 30
    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK Frequency adjustment range The control unit is supplied with a maximum frequency range of 5…150Hz. Using an adjustable under and over frequency limits, the user range (parameter F) can be restricted to a maximum ratio of 1:4.
  • Page 31
    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK Enable Service Mode The actual service menu is accessed by opening the service mode. 0 = Service mode off I = Service mode on Running mode The normal service menu, containing the output current and frequency limit settings, is accessed by opening the service mode.
  • Page 32: A 2.0 Accessories / Spare Parts

    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK A 2.0 Accessories / Spare Parts Reo Order Type: Accessories / Spare Parts: Number: Manufacturer Order Number: Harting: 09 20 003 2711 + 19 20 003 1440 + mains input coupling 19 00 000 5082 + 09 20 000 9918…

  • Page 33
    REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK…
  • Page 34
    Headquarters — Germany REO ELEKTRONIK AG Brühler Straße 100 · D-42657 Solingen Tel.: +49 (0)212 8804 0 · Fax: +49 (0)212 8804 188 REO INDUCTIVE COMPONENTS AG Brühler Straße 100 · D-42657 Solingen Tel.: +49 (0)212 8804 0 · Fax: +49 (0)212 8804 188 E-Mail: info@reo.de…

  • Главная

    Электричество и Электроника

    Система Электрического Управления
Задача: Регулирование
Структура: Разомкнутый Цикл
Математическая модель: Линейная
Сигнал: Непрерывный
функция: Автоматический контроль
Сертификация: RoHS, CCC, ISO: 9001, CE
Просмотреть Больше

Вам Наверное Нравиться

Описание Товара

Информация о Компании

Основная Информация.

Структура

Разомкнутый Цикл

Математическая модель

Линейная

функция

Автоматический контроль

Сертификация

RoHS, CCC, ISO: 9001, CE

Индивидуальные

Номера Индивидуальные

Транспортная Упаковка

Cartoon

Происхождение

Suzhou, China

Производственная Мощность

300 Units/Month

Описание Товара

Frequency Converter Reovib Mfs 168 Vibrating Bowl Feeder Controller

Описание

Преобразователи частоты в REOVIB MFS 158 и REOVIB MFS 168 Series для вибрационный дорожный конвейер техники дает возможность эксплуатации вибрационный дорожный конвейера при оптимальной частоты вибрации в соответствии с материалом — полностью независимо от частоты на входе питающей сети.

Устройств в REOVIB MFS 158 серии выпускаются с максимальный выходной ток 4 A и устройств в REOVIB MFS 168 серии выпускаются с максимальный выходной ток 3 A 6 A и 8 A. Обе серии выпускаются в виде IP20 версии для установки в шкафы управления или в качестве автономных IP54.

IP54 с различных вариантов подключения:
* Кабель ввода/вывода кабеля
* Кабель входного/выходного разъема
* Полное решение для подключения кабеля питания и цепи управления

Преимущества

* Недорогих устройств контроля частоты с жизненно важных функций
* Частота — Устройство управления для управления вибрационный дорожный транспортер независимо от частоты на входе питающей сети
* Частоты транспортера регулируется в пределах 35…140 Гц
* Напряжение электросети компенсации с постоянной амплитудой вибрации
* Все настройки могут быть выполнены с помощью встроенного дисплея
* Синусоидальный ток на выходе
* Можно использовать на 110 В или 240 В сети, автоматическое считывание.
* Пользовательские настройки могут быть сохранены
* С уровня заполнения/контроль переполнения
* Версии доступны в различных классов защиты и различные варианты подключения
* REOVIB MFS 168: автоматическое определение резонансной частоты вибрационный дорожный системы конвейера (с дополнительным вибрации
Амплитуда сигнала датчика) и вариант для регулирования амплитуда вибрации — константа скорости подачи может быть достигнуто независимо от нагрузки или
Изменения в системе mechnical

 

Отправить ваш запрос напрямую данному поставщику

REO Schwingfördertechnik Frequenzumrichter REOVIB MFS 168

Complete catalog

Download our extensive catalog and discover many other REO products.

Data sheet

All data and configurations can be found in our product data sheet.

Certifications

FREQUENCY CONVERTER REOVIB MFS 168

IP 54 or IP 20

Description

Frequency converters in the REOVIB MFS 158 and REOVIB MFS 168 series for vibratory conveyor technology offer the option of operating the vibratory conveyor at an optimal vibration frequency for the material – completely independently of the mains input frequency.

Devices in the REOVIB MFS 158 series are available with a max. output current of 4 A and the Devices in the REOVIB MFS 168 series are available with a max. output current of 3 A, 6 A and 8 A. Both series are available as IP20 versions for installation in control cabinets or as IP54 standalone units.

The IP54 housings are available with various connection options:

  • Input cable/output cable
  • Input cable/output socket
  • Complete cable connection solution for mains, output and control connections

Advantages

  • Inexpensive frequency-control devices with the vital functionality
  • Frequency-control device for controlling a vibratory conveyor independently of the mains input frequency
  • Conveyor frequencies adjustable between 35…140 Hz
  • Mains voltage compensation with constant vibration amplitude
  • All settings can be made using the integrated display
  • Sinusoidal output current
  • Can be used on 110 V or 240 V mains, auto sensing.
  • User settings can be stored
  • With fill level/overflow control
  • Versions available in various protection classes and with various connection options
  • REOVIB MFS 168: Automatic detection of the resonant frequency of the vibratory conveyor system (with additional vibration amplitude sensor) and option to regulate the vibration amplitude – Constant feed rates can be achieved independently of load or changes in the mechnical system

Technical specifications

Suitable for this product

REO Schwingfoerdertechnik Schwingmagnet REOVIB WI 721

AC Magnets

REO Schwingfoerdertechnik Beschleunigungssenssoren SW

Accelerometers

Contact

Contact and product inquiry

We are there for you

Do you have questions, requests or suggestions?
Please don’t hesitate to contact us:

REO AG

Brühler Strasse 100
D-42657 Solingen

Tel.: 0049-(0)2 12-88 04-0
Fax: 0049-(0)2 12-88 04-188

E-Mail: info@reo.de

USt-ID-Nr.: DE 182 486 130
St.-Nr.: 128/5819/5634

Частотный преобразователь REO Reovib MFS 168

Частотный преобразователь REO Reovib MFS 168

Ремонт частотного преобразователя. Ремонт на уровне компонентов.

Вы смотрите:Частотный преобразователь REO Reovib MFS 168

Выполненные ремонты

Блок питания Siemens 6ES7 307-1BA00-0AA0

Электронный регулятор Danfoss ECL Comfort 310

Частотный преобразователь HYUNDAI N700E-015HF

Частотный преобразователь Hyundai N700E-220HF

Частотный преобразователь Parker 890CD-532160B0-000-1B3P0

Контроллер Bentrup TC304

Частотный преобразователь Lenze 8200 Vector E82EV302-4C200

Частотный преобразователь Altron (Arkel) 4B14A

Плата управления лифтовая Arkel AKE ATK V3

Частотный преобразователь ESQ-210-4T-7.5 K

Частотный преобразователь Nordac Vector SK11.000/3CT

Контроллер управления горением AUTOFLAME MM70001

Частотный преобразователь ABB ACS355-03E-15A6-4 (Sibocom L2-07K5-3+S6410)

Блок питания Mitsubishi MDS-DH-CV-300

Блок питания POWERNET ADC 9951

Устройство плавного пуска (софтстартер) WEG EUSSW050085T2246EPZ

Контроллер Bentrup TC507

Частотный преобразователь Baumuller BM4434-SI1-01200-03

Частотный преобразователь Vacon NXS 01055A2H0SSSA1A200B100

Частотный преобразователь Vacon NXS 01055A2H0SSSA1A200B100

Ультразвуковой датчик Fife SE-24

300,00 $ — 800,00 $/ шт. |1 шт./шт.(Мин. заказ)

Время выполнения заказа:

Quantity (шт.) 1 — 20 21 — 100 101 — 500 > 500
Примерное время (в днях) 3 4 5 Подлежит согласованию

Изготовление на заказ:

Эмблема на заказ(Мин. заказ 1 шт.)

Индивидуализированная упаковка(Мин. заказ 1 шт.)

Графические настройки(Мин. заказ 1 шт.)

Сведения о покупке

Защита с помощью

Транспортировка:

Связаться с поставщиком для согласования деталей доставки

Для вас Гарантия своевременной отправки

Платежи:

Шифрование и повышенная безопасность платежей Подробнее

Возврат товаров и возмещение средств

Доступны возврат товаров и возмещение средств Подробнее

Покупайте с уверенностью

Напрямую от проверенных площадкой производителей

Понравилась статья? Поделить с друзьями:
  • Как сменить руководство снт
  • Тактика врача невролога практическое руководство купить
  • Ancel ad310 rus автомобильный сканер инструкция
  • Камерон таблетки инструкция по применению цена
  • Тетроген день ночь инструкция по применению цена отзывы