REOVIB
Control Equipment for the Vibratory Feeder Industry
MFS 268
Frequency Converter for Vibratory Feeders
UL / CSA — Version
268_UL-CSA_ANL_EN_47-13.DOC
21.11.2013
Related Manuals for Reo Elektronik REOVIB MFS 268
Summary of Contents for Reo Elektronik REOVIB MFS 268
-
Page 1
REOVIB Control Equipment for the Vibratory Feeder Industry MFS 268 Frequency Converter for Vibratory Feeders UL / CSA — Version 268_UL-CSA_ANL_EN_47-13.DOC 21.11.2013… -
Page 2: Technical Safety Instructions For The User
The units described herein are electrical controllers for installation in industrial plant. They are designed for controlling vibratory feeders. For use in NFPA 79 Applications only Adapters providing field wiring means are available from REO ELEKTRONIK AG. Refer to REO ELEKTRONIK AG.
-
Page 3: Table Of Contents
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK Contents Technical safety instructions for the user ………………… 1 1.0 General …………………………3 2.0 Function …………………………3 2.1 Track control ……………………….4 2.2 Operating with two speeds (2 set points for coarse/fine switching) ………… 4 2.3 Control inputs and output ……………………
-
Page 4: General
ELEKTRONIK 1.0 General The REOVIB MFS 268 range comprises special, adaptable controllers for use with vibratory feeders. The units generate an output frequency, to drive feeders, that is independent of mains frequency and so exact tuning with springs is not necessary. The feeders also run quieter because of the sinusoidal output signal.
-
Page 5: Track Control
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 2.1 Track control output switched ON and OFF Sensor from a track component sensor, using internal, adjustable time delays (ton Feeder and toff). The queue of components rises above and drops below the track sensor…
-
Page 6: Output Status Relay
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 2.3.4 Output status relay Status-Relay contact 250 V/1 A (changeover). Relay closes when the feeder is running – the relay opens when there is no enable signal or a fault displayed. 2.3.5 Time-Out output 24 VDC «time Out»…
-
Page 7: Technical Data
For use in NFPA 79 Applications only E217179 Adapters providing field wiring means are available from REO ELEKTRONIK AG. Refer to REO ELEKTRONIK AG. 6.0 Declaration of Conformity We declare that these products conform with the following standards: EN 61000-6-4 and EN 61000-6-2 in accordance with the regulations of guidelines 2004/108/EC.
-
Page 8: Settings
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 7.0 Settings After checking the correct operation of the controller in conjunction with the vibratory feed system it is advisable to restrict the user to feeder throughput settings only. Setting the feeder throughput: Press the P key twice and adjust the throughput with the cursor keys (Code C.
-
Page 9: Control Elements
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 8.0 Control elements 8.1 Settings The six buttons and a LED display found in the front panel, are used for operating and setting up the unit. All operating methods and adjustable Display parameters can be set up through this panel.
-
Page 10: Commissioning
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 9.0 Commissioning 9.1 Assembling position Please fasten the devices on a vibration-free underground and take care for sufficient air circulation. 9.2 Preliminary steps • Check that the unit is correct for the local mains supply (rating plate information) and that it is correct- ly rated for the feed system.
-
Page 11: Putting The Equipment Into Operation
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 9.3 Putting the equipment into operation 1. Establish the vibrating frequency. 2. Establish the power of the feed system (maximum permissible current draw). For a new feeder where settings are unknown: (see also comments below) Without connecting the feeder, select parameter FAC in menu C210 (reset factory settings), press the cursor key to reset (SAFE) and press the P key to leave the menu.
-
Page 12: Setting Instructions
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.0 Setting Instructions 10.1 User adjustment of throughput Code C. 000 Feeder amplitude set point 0…100 % Running mode A further set point code can be found under C002 (for use in coarse/fine operation) Feeder amplitude set point 0…100 %…
-
Page 13: Track Control
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.2 Track control Code C. 167, 007 On time delay 0…60 sec. Off time delay 0…60 sec. 0 = No sensor inverting I = Sensor inverting 0 = Sensor time out not active I = Sensor time out active E.
-
Page 14: Pulse Feed
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.5 Pulse feed Code C. 004, 064 HOP. = 0 = continuous duty HOP. = I = pulse feed On time delay [sec.] Off time delay [sec.] Invert hopper sensor (not active) Running mode 10.2.6 Regulation mode…
-
Page 15: Instructions For Using Regulation Mode
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.6.1 Instructions for using regulation mode • An accelerometer e.g. SW 70 must be fitted to the vibratory feeder in order to run in regulation mode. The accelerometer should have a frequency range corresponding to that of the feeder.
-
Page 16
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK In regulation mode the magnitude of the output signal has a direct affect on the maximum ampli- tude of the feeder. On bowl feeders it is advisable to fit the sensor as near as possible to the outside diameter and in this… -
Page 17: Relationship Between Acceleration And Amplitude
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.6.3 Relationship between acceleration and amplitude The sensor measures the momentary acceleration of the feeder. It generates a sinusoidal output voltage signal. The acceleration gets higher as the frequency increases. The sensor signal is greater for a higher frequency and lower amplitude than for a low frequency with a higher amplitude.
-
Page 18: Optimisating Controller In Regulation Mode
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.6.6 Optimisating controller in regulation mode Setting the control range 1. In Menu C. 096 set parameter P (Max Limit) to 50 % 2. Set A (Feeder throughput) to 100% 3. Increase limit P from 50% until the required maximum feeder throughput is achieved The full set point adjustment range of 0…100% can now be used…
-
Page 19: Display Actual Current And Frequency
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 10.2.7 Display actual current and frequency Code C. 040 Actual current (display only) Actual frequency (display only) Running mode 10.2.8 Save selected parameters Code C. 143 Choose user parameter set Save new parameters Running mode 10.2.9 Recall user or factory settings…
-
Page 20: Error Messages / Error Reset
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 11.0 Error messages / ERROR reset Errors are indicated by an alternating code and ERROR display Overload limit Output level exceeded e.g. incorrect frequency setting, coil air- gap to wide. Short circuit trip Faulty coil, short circuit or defective cable..
-
Page 21: Connections For Enclosed Construction (Ip 54): 6-8 A Units
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 12.0 Connections for enclosed construction (IP 54): 6-8 A Units Internal connections When a potentiometer is connected parameter POT must be set to I in Menu C003. Status- relay 1 2 3 4…
-
Page 22: Connections For Enclosed Construction (Ip 54): 12 A Units
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 12.1 Connections for enclosed construction (IP 54): 12 A Units Internal connections Status relay Time out +24 V Air valve +24 V +24 V Accelerometer SW… INPUT Set point (external) +10V 0(4)…20mA 0…10V…
-
Page 23: Connections For Enclosed Construction (Ip 54): 16 A Units
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 12.2 Connections for enclosed construction (IP 54): 16 A Units Internal connections Status relay Time out +24 V Air valve +24 V +24 V Accelerometer SW… INPUT Set point (external) +10V 0(4)…20mA 0…10V…
-
Page 24: Connections For Panel Mounting Construction (Ip 20): 3 A, 6 A, 8 A
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 13.0 Connections for panel mounting construction (IP 20): 3 A, 6 A, 8 A REOVIB MFS268 Material-Sensor +24V Enable 12…24V, DC Set point 0…10V 0(4)…20mA R=500 OHM black External INPUT orange SW… + 24V…
-
Page 25: Connections For Panel Mounting Construction (Ip 20): 16A
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 13.1 Connections for panel mounting construction (IP 20): 16A line choke Mains L, N, PE / 115V/230V, 50/60HZ Material sensor +24V Enable 12…24V, DC Set point 0(4)…20mA 0…10V SPEED +10V black orange INPUT Accelerometer SW…
-
Page 26: Dimensions For 3 A, 6 A, 8 A Units
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 14.0 Dimensions for 3 A, 6 A, 8 A Units Enclosed construction, (IP 54) Ø5,0 REOVIB MFS 268 SPEED www.reo.de Ø5,0 Panel mounting construction, (IP 20) Ø 5,0 Ø 5,0 REOVIB MFS268 REOVIB MFS268 Ø…
-
Page 27: Dimensions Of Enclosed Construction (Ip 54) 12 A
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 14.1 Dimensions of enclosed construction (IP 54) 12 A Ø5,0 REOVIB MFS 268 SPEED www.reo.de Ø5,0 14.2 Dimensions of enclosed construction (IP 54) 16 A Ø5,0 REOVIB MFS 268 SPEED www.reo.de Ø5,0…
-
Page 28: Dimensions Of Panel Mounting Construction (Ip 20) 16 A
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK 14.3 Dimensions of Panel mounting construction (IP 20) 16 A Ø5,0 SPEED +10V Ø5,0…
-
Page 29: A 1.0 Service Appendix
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK A 1.0 Service appendix ATTENTION ! The settings described in this section relating to the service menu are intended for use by skilled persons because the functions and limits of the feed system can be greatly influenced by their…
-
Page 30
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK Frequency adjustment range The control unit is supplied with a maximum frequency range of 5…150Hz. Using an adjustable under and over frequency limits, the user range (parameter F) can be restricted to a maximum ratio of 1:4. -
Page 31
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK Enable Service Mode The actual service menu is accessed by opening the service mode. 0 = Service mode off I = Service mode on Running mode The normal service menu, containing the output current and frequency limit settings, is accessed by opening the service mode. -
Page 32: A 2.0 Accessories / Spare Parts
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK A 2.0 Accessories / Spare Parts Reo Order Type: Accessories / Spare Parts: Number: Manufacturer Order Number: Harting: 09 20 003 2711 + 19 20 003 1440 + mains input coupling 19 00 000 5082 + 09 20 000 9918…
-
Page 33
REOVIB MFS 268 UL/CSA Operating Instructions ELEKTRONIK… -
Page 34
Headquarters — Germany REO ELEKTRONIK AG Brühler Straße 100 · D-42657 Solingen Tel.: +49 (0)212 8804 0 · Fax: +49 (0)212 8804 188 REO INDUCTIVE COMPONENTS AG Brühler Straße 100 · D-42657 Solingen Tel.: +49 (0)212 8804 0 · Fax: +49 (0)212 8804 188 E-Mail: info@reo.de…
-
Главная
Электричество и Электроника
Система Электрического Управления
Задача: | Регулирование |
---|---|
Структура: | Разомкнутый Цикл |
Математическая модель: | Линейная |
Сигнал: | Непрерывный |
функция: | Автоматический контроль |
Сертификация: | RoHS, CCC, ISO: 9001, CE |
Просмотреть Больше |
Вам Наверное Нравиться
Описание Товара
Информация о Компании
Основная Информация.
Структура
Разомкнутый Цикл
Математическая модель
Линейная
функция
Автоматический контроль
Сертификация
RoHS, CCC, ISO: 9001, CE
Индивидуальные
Номера Индивидуальные
Транспортная Упаковка
Cartoon
Происхождение
Suzhou, China
Производственная Мощность
300 Units/Month
Описание Товара
Описание
Преобразователи частоты в REOVIB MFS 158 и REOVIB MFS 168 Series для вибрационный дорожный конвейер техники дает возможность эксплуатации вибрационный дорожный конвейера при оптимальной частоты вибрации в соответствии с материалом — полностью независимо от частоты на входе питающей сети.
Устройств в REOVIB MFS 158 серии выпускаются с максимальный выходной ток 4 A и устройств в REOVIB MFS 168 серии выпускаются с максимальный выходной ток 3 A 6 A и 8 A. Обе серии выпускаются в виде IP20 версии для установки в шкафы управления или в качестве автономных IP54.
IP54 с различных вариантов подключения:
* Кабель ввода/вывода кабеля
* Кабель входного/выходного разъема
* Полное решение для подключения кабеля питания и цепи управления
Преимущества
* Недорогих устройств контроля частоты с жизненно важных функций
* Частота — Устройство управления для управления вибрационный дорожный транспортер независимо от частоты на входе питающей сети
* Частоты транспортера регулируется в пределах 35…140 Гц
* Напряжение электросети компенсации с постоянной амплитудой вибрации
* Все настройки могут быть выполнены с помощью встроенного дисплея
* Синусоидальный ток на выходе
* Можно использовать на 110 В или 240 В сети, автоматическое считывание.
* Пользовательские настройки могут быть сохранены
* С уровня заполнения/контроль переполнения
* Версии доступны в различных классов защиты и различные варианты подключения
* REOVIB MFS 168: автоматическое определение резонансной частоты вибрационный дорожный системы конвейера (с дополнительным вибрации
Амплитуда сигнала датчика) и вариант для регулирования амплитуда вибрации — константа скорости подачи может быть достигнуто независимо от нагрузки или
Изменения в системе mechnical
Отправить ваш запрос напрямую данному поставщику
Complete catalog
Download our extensive catalog and discover many other REO products.
Data sheet
All data and configurations can be found in our product data sheet.
Certifications
FREQUENCY CONVERTER REOVIB MFS 168
IP 54 or IP 20
Description
Frequency converters in the REOVIB MFS 158 and REOVIB MFS 168 series for vibratory conveyor technology offer the option of operating the vibratory conveyor at an optimal vibration frequency for the material – completely independently of the mains input frequency.
Devices in the REOVIB MFS 158 series are available with a max. output current of 4 A and the Devices in the REOVIB MFS 168 series are available with a max. output current of 3 A, 6 A and 8 A. Both series are available as IP20 versions for installation in control cabinets or as IP54 standalone units.
The IP54 housings are available with various connection options:
- Input cable/output cable
- Input cable/output socket
- Complete cable connection solution for mains, output and control connections
Advantages
- Inexpensive frequency-control devices with the vital functionality
- Frequency-control device for controlling a vibratory conveyor independently of the mains input frequency
- Conveyor frequencies adjustable between 35…140 Hz
- Mains voltage compensation with constant vibration amplitude
- All settings can be made using the integrated display
- Sinusoidal output current
- Can be used on 110 V or 240 V mains, auto sensing.
- User settings can be stored
- With fill level/overflow control
- Versions available in various protection classes and with various connection options
- REOVIB MFS 168: Automatic detection of the resonant frequency of the vibratory conveyor system (with additional vibration amplitude sensor) and option to regulate the vibration amplitude – Constant feed rates can be achieved independently of load or changes in the mechnical system
Technical specifications
Suitable for this product
AC Magnets
Accelerometers
Contact
Contact and product inquiry
We are there for you
Do you have questions, requests or suggestions?
Please don’t hesitate to contact us:
REO AG
Brühler Strasse 100
D-42657 Solingen
Tel.: 0049-(0)2 12-88 04-0
Fax: 0049-(0)2 12-88 04-188
E-Mail: info@reo.de
USt-ID-Nr.: DE 182 486 130
St.-Nr.: 128/5819/5634
Ремонт частотного преобразователя. Ремонт на уровне компонентов.
Вы смотрите:Частотный преобразователь REO Reovib MFS 168
Выполненные ремонты
Блок питания Siemens 6ES7 307-1BA00-0AA0
Электронный регулятор Danfoss ECL Comfort 310
Частотный преобразователь HYUNDAI N700E-015HF
Частотный преобразователь Hyundai N700E-220HF
Частотный преобразователь Parker 890CD-532160B0-000-1B3P0
Контроллер Bentrup TC304
Частотный преобразователь Lenze 8200 Vector E82EV302-4C200
Частотный преобразователь Altron (Arkel) 4B14A
Плата управления лифтовая Arkel AKE ATK V3
Частотный преобразователь ESQ-210-4T-7.5 K
Частотный преобразователь Nordac Vector SK11.000/3CT
Контроллер управления горением AUTOFLAME MM70001
Частотный преобразователь ABB ACS355-03E-15A6-4 (Sibocom L2-07K5-3+S6410)
Блок питания Mitsubishi MDS-DH-CV-300
Блок питания POWERNET ADC 9951
Устройство плавного пуска (софтстартер) WEG EUSSW050085T2246EPZ
Контроллер Bentrup TC507
Частотный преобразователь Baumuller BM4434-SI1-01200-03
Частотный преобразователь Vacon NXS 01055A2H0SSSA1A200B100
Ультразвуковой датчик Fife SE-24
300,00 $ — 800,00 $/ шт. |1 шт./шт.(Мин. заказ)
Время выполнения заказа:
Quantity (шт.) | 1 — 20 | 21 — 100 | 101 — 500 | > 500 |
Примерное время (в днях) | 3 | 4 | 5 | Подлежит согласованию |
Изготовление на заказ:
Эмблема на заказ(Мин. заказ 1 шт.)
Индивидуализированная упаковка(Мин. заказ 1 шт.)
Графические настройки(Мин. заказ 1 шт.)
Сведения о покупке
Защита с помощью
Транспортировка:
Связаться с поставщиком для согласования деталей доставки
Для вас Гарантия своевременной отправки
Платежи:
Шифрование и повышенная безопасность платежей Подробнее
Возврат товаров и возмещение средств
Доступны возврат товаров и возмещение средств Подробнее
Покупайте с уверенностью
Напрямую от проверенных площадкой производителей