Operating Instructions
SIMOREG DC-MASTER
Converter Commutation Protector
(SIMOREG CCP)
Edition 04
Order No. 6RX1700-0DD74
Related Manuals for Siemens SIMOREG DC-MASTER
Summary of Contents for Siemens SIMOREG DC-MASTER
-
Page 1
Operating Instructions SIMOREG DC-MASTER Converter Commutation Protector (SIMOREG CCP) Edition 04 Order No. 6RX1700-0DD74… -
Page 2
When using a SIMOREG DC-MASTER as basic converter unit: The SIMOREG DC-MASTER must have software release 2.2 or higher. The software release of the SIMOREG DC-MASTER can be read-out at parameters r060 and r065, the software release of the associated SIMOREG CCP can be read-out at parameter n560. -
Page 3: Table Of Contents
Connecting the Firing Unit Trigger Board …………….36 Fuses ……………………….37 Arrangement of the terminals, connectors and fuses………….37 Terminal assignment, connectors……………….38 Commissioning ……………………….41 Operation via the basic unit (SIMOREG DC-MASTER or SINAMICS DCM) ……42 7.1.1 SIMOREG DC-MASTER parameters ………………42 7.1.2 SINAMICS DCM parameters ………………..48 7.1.3…
-
Page 4
Table of Contents 12.2010 Appendix ………………………….73 11.1 Characteristic diagrams ………………….73 11.2 Relevant standards …………………….91 11.3 Certification ……………………..91 11.4 Abbreviations, terminology………………….91 11.5 Environmental compatibility ………………..92 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 5: Notes
Note the following: WARNING Siemens products are only permitted to be used for the applications listed in the catalog and in the associated technical documentation. If third-party products and components are used, they must be recommended or approved by Siemens. These products can only function correctly and safely if they are transported, stored, set up, mounted, installed, commissioned, operated and maintained correctly.
-
Page 6: Warning Notes
Furthermore, the contents of these operating instructions shall not become a part of or modify any prior or existing agreement, commitment, or legal relationship. The Purchase Agreement contains the complete and exclusive obligations of Siemens, including the warranty provisions. Any statements contained in these operating instructions neither expand nor restrict the scope of these contractual warranty conditions.
-
Page 7
Operating the unit in the immediate vicinity (< 1.5 m) of mobile telephones with a transmitter power of > 1 W may lead to incorrect operation of the unit. Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 8: Electrostatic Sensitive Devices (Esd)
The necessary ESD protective measures are illustrated once again in the following diagram: Seated Standing Seated/standing a conductive floor b ESD table c ESD footwear d ESD overall e ESD wrist strap cabinet ground connection ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 9: Type Spectrum, Ordering Information
Item Order No. (MLFB) Operating instructions for 6RX1700-0AD64 SIMOREG DC-MASTER and SIMOREG CCP and DriveMonitor in all of the available languages on CD-ROM Operating instructions for 6RX1800-0AD64 SINAMICS DCM and SIMOREG CCP in all of the available languages on DVD…
-
Page 10
Item Order No. (MLFB) Patch cable UTP CAT5 acc. to ANSI/EIA/TIA 568 6RY1707-0AA08 Parallel cable for SIMOREG DC-MASTER 6RA70 / SINAMICS DCM and SIMOREG CCP approx. 5 m Connecting cable, pulse turn-off interface to the parallel SIMOREG CCP connection Connecting cable, summed firing pulse interface to the SIMOREG DC-MASTER (CUD2) Connecting cable «fast pulse cancellation interface»… -
Page 11: Selecting A Suitable Simoreg Ccp
12.2010 Type spectrum, ordering information Selecting a suitable SIMOREG CCP The rated unit data (taking into account the relevant limit values) of the SIMOREG DC-MASTER or SINAMICS DCM and SIMOREG CCP components form the basis for the selection table. 2.3.1 Selection table for 4Q basic units Converter Commutation Protector SIMOREG CCP 6RA70…
-
Page 12
For system configurations, with reduced rate values (e.g. DC rating, US rating, voltage derating), under certain circumstances, suitable combinations of units can be found that are not listed in the table. ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 13: Selection Table For 2Q Basic Units
1000 V / 1500 A 6RA7095-4LS22-0 1000 V / 1900 A 6RA7095-4LS22-5 1000 V / 1900 A 6RA7096-4MS22-0 1140 V / 2200 A = suitable = not suitable (see note) Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 14
For system configurations, with reduced rate values (e.g. DC rating, US rating, voltage derating), under certain circumstances, suitable combinations of units can be found that are not listed in the table. ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 15: Rating Plate, Packaging Label
Q6 ..QTY 1 VERSION E-STATUS (Version) (Version) Q ..MADE IN EU (AUSTRIA) Packaging label Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 16: Description, Technical Data
If this is the case, then the following occurs: 1. The firing pulses are immediately disabled in the SIMOREG DC-MASTER or SINAMICS DCM. 2. The basic converter unit sends a turn-off command to the SIMOREG CCP (via the serial interface) 3.
-
Page 17: Technical Data
This is calculated using a software algorithm, and depending on the energy that is dissipated during the quenching operation, is up to approx. 20 min. Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 18: Block Diagram
Description, technical data 12.2010 Block diagram ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 19
Units 6RA70…95-6FC00-0 / …95-6KC00-0 (all 2000 A) K2 G2 G1 K1 K2 G2 G1 K1 K1 G1 G2 K2 K1 G1 G2 K2 X 33 X 31 (1C1) (1D1) Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 20: Transport, Unpacking
The packaging materials consist of a cardboard box and corrugated cardboard, and can be disposed of in accordance with local regulations for cardboard packaging materials. If you identify any damage that has occurred in transit, please inform your shipping agent immediately. ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 21: Installation
UL 508 C. To install the unit, the cabinet must have minimum dimensions of 2200 mm x 600 mm x 600 mm (H x W x D). Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 22: Dimension Drawing
Installation 12.2010 Dimension drawing 600 A / 1000 A / 1200 A — units: ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 23
12.2010 Installation 2000 A — units: Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 24: Sinamics Dcm — Installing The Firing Unit Trigger Board
Unit Trigger Board) (Order No.: 6RY1803-0CP00). See chapter 6.3.2. CAUTION Please observe the information provided on «Electrostatic sensitive devices (ESD)» in Chapter 1. WARNING Always carry out the work with the SINAMICS DCM in a no-voltage condition! ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 25
The BOP holder can be released at the side and swung upwards to route the connecting cable • After connecting the cable (see Chapter 6.3.3) relocate the front cover of the SINAMICS DCM and fasten using all of the screws Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 26: Connecting
Also observe all of the safety instructions in the converter unit operating instructions. Note Please observe the installation instructions for EMC-compliant design of drives in Chapter 6.1 of the operating instructions of the basic SIMOREG DC-MASTER or SINAMICS DCM unit. ENGLISH Siemens AG…
-
Page 27: Cable Lengths
SIMOREG CCP Cable length to connect the AC / SINAMICS DCM connections ..l 1C1 1D1 1C1 1D1 Cable length to connect the DC connections ..l l <1> Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 28
The minimum required cable length l_min is 3 m. Use 3m lengths each for 1U1, 1V1, 1W1, 1C1, 1D1. Or: e.g. use 1m lengths each for 1U1, 1V1, 1W1 and 5 m lengths each for 1C1, 1D1 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 29: Recommended Connection
In addition, it must be carefully observed that the total of the delay times of all of the switching elements in the control circuit must not exceed the time set at parameter P089. Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 30: Connecting A Sinamics Dcm
In addition, it must be carefully observed that the total of the delay times of all of the switching elements in the control circuit must not exceed the time set at parameter P50089. ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 31: Versions To Interconnect The Main Contactor (Circuit Breaker) K1
SINAMICS DCM SINAMICS DCM 6.2.4 Recommended connection when using a Siemens 3WL circuit breaker If circuit breakers from other manufacturers are used, then the recommended connection described here applies accordingly. It should be noted that the circuit breaker is equipped with a ready to close signal contact (S20,…
-
Page 32
Control voltage -X_SCHÜTZ:4 Fault inv. -X171:46 -X_SCHÜTZ:5 -X171:47 e.g. Relais DC 24 V SIMOREG DC-MASTER B0107 SINAMICS DCM r2139.03 -S11 -S20 Siemens U< Circuit breaker 3WL control unit Control voltage ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 33: Connecting Units In Parallel
12.2010 Connecting Connecting units in parallel 6.3.1 Parallel connection of SIMOREG DC-MASTER units A SIMOREG CCP is directly connected in parallel to each of the converter units connected in parallel (SIMOREG DC-MASTER). X30_PAR X29_PAR X172 X300 X165 1D1 (1C1) 1C1 (1D1)
-
Page 34: Parallel Connection Of Sinamics Dcm Units
The firing pulses are disabled via the fast pulse cancellation interface 3.4. CAUTION The parallel interface (X165, X166) at the SINAMICS DCM is not compatible to the parallel interface (X165) at the SIMOREG DC-MASTER CCP. It is not permissible that both connectors are connected. ENGLISH…
-
Page 35
1D1 (1C1) 1C1 (1D1) 1D1 (1C1) 1C1 (1D1) X166 X165 X177 X165_2 X30_PAR X29_PAR X172 X300 X165 1D1 (1C1) 1C1 (1D1) 1D1 (1C1) 1C1 (1D1) X166 X165 X177 X165_2 Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 36: 6.3.3 Connecting The Firing Unit Trigger Board
6.3.3 Connecting the Firing Unit Trigger Board Routing of the connecting cable «fast pulse cancellation interface» to the SINAMICS DCM with shield support: ① Firing Unit Trigger Board ② Connector X165_2 ③ Shield support ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 37: Fuses
12.2010 Connecting Fuses Fuses in the armature circuit and in the motor circuit Recommended Siemens semiconductor fuses (depending on the SIMOREG CCP used): Unit Order No. Rated Rated Fuses Fuses (MLFB) current voltage 1U1, 1V1, 1W1 1C1, 1D1 6RA7085-6FC00-0 600 A…
-
Page 38: Terminal Assignment, Connectors
Connection values the same as for the power unit SIMOREG CCP (see above) Control circuit for Wiring, main contactor/circuit breaker main contactor / (see the recommended connection in Chapter 6.2) circuit breaker ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 39
-7 V/+12 V. Equipotential bonding must be implemented if this cannot be guaranteed. Activating the serial interface by setting the protocol at parameter P790 or p50790. Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 40
Connecting 12.2010 Connecting to a SIMOREG DC-MASTER: X172 X172 MINI-COMBICON MINI-COMBICON Connecting to a SINAMICS DCM: SIMOREG CPP SINAMICS DCM X-172 X-177 MINI COMBICON Connector Board Programming interface for the software update X300 Serial interface RS232 9-pin SUBMIN D socket… -
Page 41: Commissioning
If you encounter specific problems that have not been handled in enough detail for the purposes of the buyer, then please contact your local Siemens office. The use of non-approved parts for carrying out repair work on the unit or handling of the unit by inadequately qualified personnel will result in dangerous conditions with the risk of death, serious physical injury, or extensive damage to equipment.
-
Page 42: Operation Via The Basic Unit (Simoreg Dc-Master Or Sinamics Dcm)
Response of the commutation monitoring U583 Test command for the SIMOREG CCP *) For a description of these parameters, see the operating instructions SIMOREG DC-MASTER Chapter 11 Detailed description of parameters The specified software release refers to the software release of the SIMOREG DC-MASTER…
-
Page 43
Display of the I2t value [from SW 2.1] 0 to 100 Ind: None P052 = 3 (2576) of the voltage limitingchoppers 2 of the SIMOREG CCP Type: O2 Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 44
2500 6RA7093-4LV62-0 2500 6RA7095-4LV62-0 2500 6RA7018-6DS22-0 1300 6RA7025-6DS22-0 1300 6RA7028-6DS22-0 1300 6RA7031-6DS22-0 1300 6RA7075-6DS22-0 1300 6RA7078-6DS22-0 1300 6RA7081-6DS22-0 1300 6RA7085-6DS22-0 1300 6RA7087-6DS22-0 1300 6RA7091-6DS22-0 1300 6RA7093-4DS22-0 1500 6RA7095-4DS22-0 1500 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 45
1100 6RA7090-6KC00-0 1600 6RA7095-6KC00-0 1600 Note: The setting value for U577 according to the table above defines the maximum permissible value of the voltage limit for the particular unit. Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 46
P351 = -20 % of P078i001 (according to the factory setting). The following upper limit applies for a value of P351 that deviates from the factory setting: ⎛ ⎞ ∗ ∗ ⎜ ⎜ ⎟ ⎟ ⎝ ⎠ Upper limit = ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 47
Type: O2 This memory is updated each time that fault message F030 is output. It includes more detailed information about the cause of the commutation fault, which can be evaluated by Siemens experts. Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector… -
Page 48: Sinamics Dcm Parameters
CCP chopper voltage setpoint, upper response threshold p51578 CCP quenching capacitor pre-charging voltage setpoint r51579.0…7 CO/BO: CCP command p51580 Commutation monitoring, control word p51583 CCP test turn-off command ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 49
Description: Sets the bus termination for the peer-to-peer interface and the interface to the SIMOREG CCP. Value: 0: off 1: on Note: CCP: Converter Commutation Protector P2P: Peer-to-peer interface Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 50
Displays the software version for the Converter Communication Protector (CCP). Index: [0] = version release of the CCP software [1] = version release of the software of the CCP boot sector ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 51
CO: CCP I2t value voltage limiting chopper 2 / CCP I2t chopper 2 Description: Displays the I2t value for voltage limiting chopper 2 for the Converter Commutation Protector (CCP). Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 52
1700 6RA8090-6GV62-0AA0 1700 6RA8093-4GV62-0AA0 1700 6RA8095-4GV62-0AA0 1700 6RA8096-4GV62-0AA0 1700 6RA8097-4GV62-0AA0 1700 6RA8086-6KV62-0AA0 2100 6RA8090-6KV62-0AA0 2100 6RA8093-4KV62-0AA0 2100 6RA8095-4KV62-0AA0 2100 6RA8097-4KV62-0AA0 2100 6RA8088-6LV62-0AA0 2500 6RA8093-4LV62-0AA0 2500 6RA8095-4LV62-0AA0 2500 6RA8096-4MV62-0AA0 2900 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 53
The parameter is automatically set for the «Optimization run for CCP» (p50051 = 30). The correct setting for this parameter can be taken from the following reference: SIMOREG CCP operating instructions Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 54
-20 % of p50078[0] (according to the factory setting). The following upper limit applies for a value of p50351 that deviates from the factory setting: ⎛ ⎞ 50351 ⎜ ⎜ ⎟ ⎟ ∗ ∗ 50078 ⎝ ⎠ Upper limit = ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 55
Using this parameter, these can be individually set for test purposes. If several decision-making criteria are to be evaluated, then the sum of the corresponding numbers should be set. Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 56: Simoreg Dc-Master Connectors
(U800 = 0 OR U800 = 1 OR [U800 = 2 AND U806 > 10]) Note: Bits 8 and 9 are always updated. For all other a bits, the following applies: The bits after the first bit with the value zero are invalid! ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 57: Simoreg Dc-Master Faults
Field current actual value (K0265) for a fault situation i006 Pulse number (K0105) for a fault situation A SIMOREG DC-MASTER connected in parallel has detected a commutation fault or an overcurrent condition Test command was entered via U583…
-
Page 58: Sinamics Dcm Faults
= actual CD voltage r50047[2] = actual delay angle r50047[3] = actual firing instant r50047[4] = actual EMF r50047[5] = actual Ia sampling value r50047[6] = torque direction when triggering ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 59
The pre-charging of the chopper capacitors was not able to be completed within the time set in p50089 — or the condition according to fault value 5 is fulfilled. Trigger time: 20 ms. Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 60
Note regarding fault value = 707: r50047[1]: Calculated Vmax r50047[2]: Parameter p51578 maximum possible value Note regarding fault value = 708: r50047[1]: Calculated chopper energy r50047[2]: maximum possible chopper energy for SIMOREG ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 61: Simoreg Dc-Master Alarms
Voltage not available at the connections U, V, W of the SIMOREG CCP • Voltage at C-D at the SIMOREG CCP does not match the voltage C-D at the SIMOREG DC-MASTER • The quenching capacitors of the SIMOREG CCP have not reached the setpoint voltage •…
-
Page 62: Commissioning Steps
Determining the setting value for parameter U577 (factory setting = 1600) Required parameter values: r070…MLFB (characteristic number) of the SIMOREG DC-MASTER n570…MLFB (characteristic number) of the SIMOREG CCP ⇒ Determining the setting value according to the parameter description for U577 Commission the basic converter unit according to the operating instructions SIMOREG DC- MASTER, Chapter 7.
-
Page 63
16.0 1.) Rated DC voltage according to the motor rating plate (the values are typical rated data for Siemens DC motors from the product catalog DA12 2.) The characteristic diagrams are provided in the appendix to these operating instructions If the graphically determined value lies below the limit line W_max, then the energy reduction in the armature circuit is assured using the SIMOREG CCP. -
Page 64: Sinamics Dcm Commissioning Steps
This is the reason that before performing the optimization run, the actual value of p50111 should be noted and only set again after the SIMOREG CCP commissioning has been completed. ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 65
16.0 1.) Rated DC voltage according to the motor rating plate (the values are typical rated data for Siemens DC motors from the product catalog DA12 2.) The characteristic diagrams are provided in the appendix to these operating instructions If the graphically determined value lies below the limit line W_max, then the energy reduction in the armature circuit is assured using the SIMOREG CCP. -
Page 66: Maintenance
12 months. The unit should be cleaned using dry compressed air, max. 1 bar, or using a vacuum cleaner. ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 67: Software Update Of The Simoreg Ccp
Step 4. monitoring LED at the SIMOREG CCP flashes slowly if communication with the basic unit has been established). Check the new software release at 560 or r51560[0]. Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 68: Replacing Components
Replace the module(s) Chopper Unit 460 V: MLFB = 6RY1703-0FC01 690 V: MLFB = 6RY1703-0FC02 Note For units 6RA7085-6FC00-0, 6RA7091-6FC00-0 and 6RA7090-6KC00-0, there is only one chopper unit (Item A) ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 69: Replacing Diode, Thyristor And Igbt Modules
Module design Tightening torque, module: 6 Nm Tightening torque, module: 3,5 Nm Tightening torque of the power connections: 12 Nm Tightening torque of the power connections: 5 Nm Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 70
The sequence when bolting the IGBT modules can be seen in the adjacent diagram and this must be maintained under all circumstances. Tightening torque, IGBT: 5 Nm Tightening torque of the busbars: 5 Nm ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 71: Service, Technical Support
Our technical support service can provide you with technical assistance for products, systems, and solutions. http://www.siemens.de/automation/support-request (German) http://www.siemens.com/automation/support-request (English) Central hotlines for technical support for SIMOREG CCP / SIMOREG DC-MASTER / SINAMICS DCM: Time zone Tel: +49 (0)911 895 7222 8:00 to 17:00 CET Europe and Africa Fax: +49 (0)911 895 7223 mailto:support.automation@siemens.com…
-
Page 72: Spare Parts
Thyristor module 115x52x50 0,75 6SY7010-0AA22 ..95-6FC00-0 V32+33, MCC312-18io1 V35+38, V36+37, V39, V40 F1, F2 Fuses 20×5 0,002 6RY1702-0BA00 ..85-6FC00-0 on the Power- ..91-6FC00-0 Interface printed ..90-6KC00-0 circuit board ..95-6FC00-0 ..95-6KC00-0 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 73: Appendix
Characteristic diagrams to define the voltage setpoint for the pre-charging of the SIMOREG CCP quenching capacitors (parameter U578 for SIMOREG DC-MASTER or p51578 for SINAMICS DCM) using the armature circuit inductance (P111 for SIMOREG DC-MASTER or p50111 for SINAMICS DCM) and the actual unit rated DC armature current (r072i002 for SIMOREG DC- MASTER or r50072[1] for SINAMICS DCM) <…
-
Page 74
6RA7085-6FC00-0 for motors with rated armature voltage 420 V (P101 or p50101) 400A 300A 200A 200A 300A 400A 500A 600A Untergrenze Obergrenze 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Armature circuit inductance in mH (P111 or p50111) ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 75
6RA7085-6FC00-0 for motors with rated armature voltage 470 V (P101 or p50101) 500A 400A 300A 200A 200A 300A 400A 500A 600A Untergrenze Obergrenze 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Armature circuit inductance in mH (P111 or p50111) Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 76
800A 700A 600A 500A 500A 600A 700A 800A 900A 1000A 1100A 1200A Untergrenze Obergrenze 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Armature circuit inductance in mH (P111 or p50111) ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 77
800A 700A 600A 500A 500A 600A 700A 800A 900A 1000A 1100A 1200A Untergrenze Obergrenze 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Armature circuit inductance in mH (P111 or p50111) Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 78
6RA7095-6FC00-0 for motors with rated armature voltage 420 V (P101 or p50101) 1800A 1600A 1400A 1200A 1000A 1000A 1200A 1400A 1600A 1800A 2000A Untergrenze Obergrenze 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Armature circuit inductance in mH (P111 or p50111) ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 79
1000A 1200A 1400A 1600A 2000A 1800A 2000A Untergrenze Obergrenze 1800A 1600A 1400A 1200A 1000A 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Armature circuit inductance in mH (P111 or p50111) Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 80
600A 500A 400A 300A 300A 400A 500A 600A 700A 800A 900A 1000A Untergrenze Obergrenze 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Armature circuit inductance in mH (P111 or p50111) ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 81
600A 500A 400A 300A 300A 400A 500A 600A 700A 800A 900A 1000A Untergrenze Obergrenze 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Armature circuit inductance in mH (P111 or p50111) Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 82
600A 500A 400A 300A 300A 400A 500A 600A 700A 800A 900A 1000A Untergrenze Obergrenze 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Armature circuit inductance in mH (P111 or p50111) ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 83
6RA7095-6KC00-0 for motors with rated armature voltage 600 V (P101 or p50101) 1600A 1400A 1200A 1000A 1000A 1200A 1400A 1600A 1800A 2000A 2200A Untergrenze Obergrenze 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Armature circuit inductance in mH (P111 or p50111) Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 84
6RA7095-6KC00-0 for motors with rated armature voltage 600 V (P101 or p50101) 1600A 1400A 1200A 1000A 1000A 1200A 1400A 1600A 1800A 2000A 2200A Untergrenze Obergrenze 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Armature circuit inductance in mH (P111 or p50111) ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 85
2000A 1800A 1600A 1400A 1200A 1000A 1000A 1200A 1400A 1600A 1800A 2000A Untergrenze Obergrenze 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Armature circuit inductance in mH (P111 or p50111) Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 86
10 mH 8 mH 4 mH 6 mH 8 mH 10 mH 4 mH 2 mH 1000 1100 1200 Actual unit rated DC armature current in A (r072i002 or r50072[1]) ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 87
10 mH 4 mH 8 mH 6 mH 8 mH 10 mH 6 mH 4 mH 2 mH 1000 Actual unit rated DC armature current in A (r072i002 or r50072[1]) Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 88
W_max 2 mH 4 mH 6 mH 8 mH 6 mH 10 mH 4 mH 2 mH 1000 Actual unit rated DC armature current in A (r072i002 or r50072[1]) ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 89
6 mH 8 mH 10 mH 2 mH 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 Actual unit rated DC armature current in A (r072i002 or r50072[1]) Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 90
6 mH 8 mH 10 mH 2 mH 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 Actual unit rated DC armature current in A (r072i002 or r50072[1]) ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions… -
Page 91: Relevant Standards
Abbreviations, terminology Communauté Européenne cULus for ready-to-connect products, tested by UL in accordance with the UL and CSA standards Underwriters Laboratories Converter Commutation Protector IGBT insulated gate bipolar transistor Siemens AG 6RX1700-0DD74 ENGLISH SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 92: Environmental Compatibility
The printed circuit boards may be used in recycling processes involving energy recovery. The proportion of components containing hazardous substances is low. ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions…
-
Page 94
The following versions have appeared so far: Version Internal Part No. C98130-A7046-A1-01-7419 C98130-A7046-A1-02-7419 C98130-A7046-A1-03-7419 C98130-A7046-A1-04-7419 SIMEA © Siemens AG, 2005-2010 Siemens Industrial Manufacturing, Subject to change without notice Engineering and Applications Order No.: 6RX1700-0DD74 Postfach 83, A-1211 Wien Printed in EU (Austria)
- Manuals
- Brands
- Siemens Manuals
- Servo Drives
- SIMOREG DC Master 6RA7025-6GS22
Manuals and User Guides for Siemens SIMOREG DC Master 6RA7025-6GS22. We have 1 Siemens SIMOREG DC Master 6RA7025-6GS22 manual available for free PDF download: Operating Instructions Manual
Siemens SIMOREG DC Master 6RA7025-6GS22 Operating Instructions Manual (616 pages)
Microprocessor-Based Converters from 6kW to 1900kW for Variable-Speed DC Drives 6RA70 Series
Brand: Siemens
|
Category: Servo Drives
|
Size: 10 MB
Table of Contents
-
Table of Contents
3
-
Contents
10
-
1 Safety Information
15
-
Type Spectrum
15
-
Converter Order Number Code
18
-
Ordering Information for Options Using Codes
19
-
Applications
23
-
-
Description
23
-
Design
23
-
Special Features of Devices with 460V Rated Connection Voltage
24
-
Mode of Operation
24
-
Technical Data
25
-
-
Load Types
25
-
Load Cycles for 1Q Applications
26
-
Load Cycles for 4Q Applications
27
-
Converters 3AC 400V, 30A to 125A, 1Q
29
-
Converters 3AC 400V, 210A to 600A, 1Q
30
-
Converters 3AC 400V, 850A to 2000A, 1Q
31
-
Converters 3AC 460V, 30A to 125A, 1Q
32
-
Converters 3AC 460V, 210A to 600A, 1Q
33
-
Converters 3AC 460V, 850A to 1200A, 1Q
34
-
Converters 3AC 575V, 60A to 600A, 1Q
35
-
Converters 3AC 575V, 800A to 2000A, 1Q
36
-
Converters 3AC 690V, 720A to 2000A, 1Q
37
-
Converters 3AC 830V, 900A to 1900A, 1Q
38
-
Converters 3AC 400V, 15A to 125A, 4Q
39
-
Converters 3AC 400V, 210A to 600A, 4Q
40
-
Converters 3AC 400V, 850A to 2000A, 4Q
41
-
Converters 3AC 460V, 30A to 125A, 4Q
42
-
Converters 3AC 460V, 210A to 600A, 4Q
43
-
Converters 3AC 460V, 850A to 1200A, 4Q
44
-
Converters 3AC 575V, 60A to 600A, 4Q
45
-
Converters 3AC 575V, 850A to 2000A, 4Q
46
-
Converters 3AC 690V, 760A to 2000A, 4Q
47
-
Converters 3AC 690V, 950A to 1900A, 4Q
48
-
Applicable Standards
50
-
Abbreviations
50
-
-
-
Shipment, Unpacking
51
-
Remove the Transportation Protection for Devices with 1500A to 2000A Rated DC
51
-
-
Installation
53
-
Converters: 30A, 1Q
55
-
Dimension Diagrams for Standard Devices
55
-
Converters: 60A to 280A, 1Q
56
-
Converters: 400A, 1Q
57
-
Converters: 600A, 1Q
58
-
Converters: 720A to 850A, 1Q
59
-
Converters: 900A to 1200A, 1Q
60
-
Converters: 1500A to 2000A, 1Q
61
-
Converters: 15A to 30A, 4Q
62
-
Converters: 60A to 280A, 4Q
63
-
Converters: 400A to 600A, 4Q
64
-
Converters: 760A to 850A, 4Q
65
-
Converters: 950A to 1200A, 4Q
66
-
Converters: 1500A to 2000A, 4Q
67
-
Dimension Diagrams of the Devices with Additional Cable Connections on the Top of the Device
68
-
-
Converters: 60A to 125A, 1Q
68
-
Converters: 210A to 280A, 1Q
69
-
Converters: 450A to 600A, 1Q
70
-
Converters: 850A, 1Q
71
-
Converters: 60A to 125A, 4Q
72
-
Converters: 210A to 280A, 4Q
73
-
Converters: 450A to 600A, 4Q
74
-
Converters: 850A, 4Q
75
-
Mounting Options
76
-
-
Terminal Expansion Board CUD2
76
-
Local Bus Adapter (LBA) for Mounting Optional Supplementary Boards
77
-
Optional Supplementary Boards
77
-
Mounting of Optional Supplementary Boards
78
-
-
-
Connections
79
-
Installation Instructions for Proper EMC Installation of Drives
80
-
Fundamental Principles of EMC
80
-
Limit Values
80
-
Noise Radiation and Noise Immunity
80
-
What Is EMC
80
-
EMC Planning
81
-
Non-Grounded Supply Systems
81
-
SIMOREG Converters in Industrial Applications
81
-
General
82
-
Proper EMC Installation of Drives (Installation Instructions)
82
-
Rules for Proper EMC Installation
82
-
Information on Line-Side Harmonics Generated by Converters in a
93
-
Fully-Controlled Three-Phase Bridge Circuit Configuration
93
-
Block Diagrams with Recommended Connection
95
-
Parallel Connection of Converters
96
-
-
Circuit Diagram Showing Parallel Connection of SIMOREG Converters
96
-
Parameterization of SIMOREG Converters for Parallel Connection
97
-
Standard Operating Mode
97
-
Operating Mode «N+1 Mode» (Redundancy Mode)
98
-
Power Connections
100
-
-
Converters: 30A, 1Q
100
-
Converters: 60A, 1Q
101
-
Converters: 90A to 280A, 1Q
102
-
Converters: 400A to 600A, 1Q
103
-
Converters: 720A, 1Q
104
-
Converters: 800 to 850A, 1Q
105
-
Converters: 900A to 950A, 1Q
106
-
Converters: 1000 to 1200A, 1Q
107
-
Converters: 1500 to 2000A, 1Q
108
-
Converters: 15 to 30A, 4Q
110
-
Converters: 60A, 4Q
111
-
Converters: 90A to 210A, 4Q
112
-
Converters: 280A, 4Q
113
-
Converters: 400A, 4Q
114
-
Converters: 450A to 600A, 4Q
115
-
Converters: 760A, 4Q
116
-
Converters: 850A, 4Q
117
-
Converters: 950A to 1000A, 4Q
118
-
Converters: 1100 to 1200A, 4Q
119
-
Converters: 1500 to 2000A, 4Q
120
-
Field Supply
122
-
Fuses and Commutating Reactors
125
-
-
Commutating Reactors
125
-
Converters 1Q: 400V, 575V, 690V and 830V
125
-
Fuses
125
-
Fuses for Armature Circuit
125
-
Recommended Fuses for Field Circuit
125
-
Converters 1Q: 460V
126
-
Converters 4Q: 400V, 575V, 690V and 830V
127
-
Converters 4Q: 460V
128
-
F1 and F2 Fuses in the Power Interface
128
-
Terminal Arrangement
129
-
Terminal Assignments
132
-
-
Start-Up
143
-
General Safety Information
143
-
Operator Control Panels
145
-
Simple Operator Control Panel (PMU)
145
-
User-Friendly Operator Control Panel (OP1S)
146
-
Parameterization Procedure
148
-
-
Parameter Types
148
-
Parameteratization on Simple Operator Control Panel
148
-
Reset to Default Value and Adjust Offset
150
-
Start-Up Procedure
151
-
Manual Optimization (if Necessary)
158
-
-
Manual Setting of Armature Resistance R a (P110) and Armature Inductance L a (P111)
159
-
Manual Setting of Field Resistance R F (P112)
160
-
Starting up Optional Supplementary Boards
161
-
-
Procedure for Starting up Technology Boards (T100, T300, T400)
161
-
Sequence of Operations for Starting up PROFIBUS Boards (CB1, CBP, CBP2)
162
-
-
Servicing
164
-
Sequence of Operations for Starting up CAN Bus Boards (CB2, CBC)
169
-
Procedure for Starting up SIMOLINK Boards (SLB)
175
-
Procedure for Staring up Expansion Boards (EB1 and EB2)
178
-
Procedure for Starting up the Pulse Encoder Board (SBP)
179
-
-
Function Diagrams
181
-
-
9 Function Descriptions
293
-
General Explanations of Terms and Functionality
293
-
Computation Cycles, Time Dela
297
-
Switch-On, Shutdown, Enabling
298
-
Switch-On / Shutdown (on / OFF) Terminal 37 — Control Word 1, Bit 0
299
-
Operating Enable (Enable) Terminal 38 — Control Word 1, Bit 3
302
-
Definitions
303
-
Control Signals for Ramp-Function Generator
304
-
Ramp-Up Integrator
305
-
Limitation after Ramp-Function Generator
306
-
Crawling
307
-
Safety Shutdown (E-Stop)
308
-
Activation Command for Holding or Operating Brake (Low Active)
309
-
-
Switch on Auxiliaries
312
-
Speed Controller
313
-
Serial Interfaces
314
-
Serial Interfaces with Peer-To-Peer Protocol
317
-
Dynamic Overload Capability of Power Section
324
-
Configuring for Dynamic Overload Capability
325
-
Characteristics for Determining the Dynamic Overload Capability for Intermittent Overload Operation
327
-
Speed-Dependent Current Limitation
357
-
Setting the Speed-Dependent Current Limitation for Motors with Commutation Transition
358
-
Setting of Speed-Dependent Current Limitation for Motors Without Commutation Transition
359
-
-
Automatic Restart
360
-
Direction of Rotation Reversal Using Field Reversal
361
-
Braking with Field Reversal
362
-
Status Description of some Bits of Status Word ZSW1
364
-
Fault Messages
365
-
List of Fault Messages
366
-
Interface Error
369
-
External Faults
371
-
Fault Messages from Motor Sensors
372
-
External Faults
373
-
Start-Up Faults
376
-
External Faults
381
-
Hardware Faults
382
-
Internal Faults
383
-
Communication Errors with Supplementary Boards
386
-
Faults Messages from Supplementary Boards
387
-
Alarms
388
-
Connector List
541
-
Binector List
562
-
Spare Parts
595
-
Replacement of Components
597
-
Replacement of Pcbs
601
-
Replacement of Fuses and Thyristor Assemblies on Converters of 1500A and above
602
-
Europe
603
-
-
15 Simovis
605
-
Scope of Supply
605
-
Further Information
606
-
Advertisement
Advertisement
Related Products
-
Siemens SIMOREG DC Master 6RA7028-6DS22
-
Siemens SIMOREG DC Master 6RA7025-6DS22
-
Siemens SIMOREG DC Master 6RA7025-6FS22
-
Siemens SIMOREG DC Master 6RA7028-6FS22
-
Siemens SIMOREG DC Master 6RA7075-6DS22
-
Siemens SIMOREG DC Master 6RA7078-6DS22
-
Siemens SIMOREG DC Master 6RA7087-6DS22
-
Siemens SIMOREG DC Master 6RA7095-4DS22
-
Siemens SIMOREG DC Master 6RA7031-6FS22
-
Siemens SIMOREG DC Master 6RA7087-6FS22
Siemens Categories
Controller
Control Unit
Industrial Equipment
Washer
Switch
More Siemens Manuals
s SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions (SIMOREG CCP) Edition 04 Order No. 6RX1700-0DD74 12.2010 Unit software version: When these operating instructions went to print, SIMOREG CCP units were being supplied from the factory with software release 1.2. When using a SIMOREG DC-MASTER as basic converter unit: The SIMOREG DC-MASTER must have software release 2.2 or higher. The software release of the SIMOREG DC-MASTER can be read-out at parameters r060 and r065, the software release of the associated SIMOREG CCP can be read-out at parameter n560. When using a SINAMICS DCM as basic converter unit: The SINAMICS DCM must have software release 1201400 or higher. The software release of the SINAMICS DCM can be read-out at parameter r50060[6], the software release of the associated SIMOREG CCP can be read-out at parameter r51560[0]. The latest software release for the SIMOREG CCP is available on the Internet page http://support.automation.siemens.com/WW/view/de/19847387/133100 Transmission as well as duplication of this document, use and communication of its content is not permitted unless expressly authorized. Failure to observe this rule will lead to damage claims. All rights, including rights created by patent grant or registration of a utility model or design, are reserved. © Siemens AG 2005 - 2010 All rights reserved SIMOREG ® and SINAMICS ® are registered trademarks of Siemens 12.2010 Table of Contents Table of Contents ENGLISH 1 Notes .......................................................................................................................................................5 1.1 Warning notes...........................................................................................................................6 1.2 Electrostatic sensitive devices (ESD) .......................................................................................8 2 Type spectrum, ordering information ..................................................................................................9 2.1 Units - order numbers ...............................................................................................................9 2.2 Ordering information for options and accessories....................................................................9 2.3 Selecting a suitable SIMOREG CCP......................................................................................11 2.3.1 Selection table for 4Q basic units ...........................................................................................11 2.3.2 Selection table for 2Q basic units ...........................................................................................13 2.4 Rating plate, packaging label .................................................................................................15 3 Description, Technical Data ................................................................................................................16 3.1 Description ..............................................................................................................................16 3.2 Technical data ........................................................................................................................17 3.3 Block diagram .........................................................................................................................18 4 Transport, Unpacking ..........................................................................................................................20 5 Installation ............................................................................................................................................21 5.1 Dimension drawing .................................................................................................................22 5.2 SINAMICS DCM - Installing the Firing Unit Trigger Board .....................................................24 6 Connecting............................................................................................................................................26 6.1 Cable lengths ..........................................................................................................................27 6.2 Recommended connection .....................................................................................................29 6.2.1 Connecting a SIMOREG DC-MASTER ..................................................................................29 6.2.2 Connecting a SINAMICS DCM ...............................................................................................30 6.2.3 Versions to interconnect the main contactor (circuit breaker) K1...........................................31 6.2.4 Recommended connection when using a Siemens 3WL circuit breaker ...............................31 6.3 Connecting units in parallel.....................................................................................................33 6.3.1 Parallel connection of SIMOREG DC-MASTER units ............................................................33 6.3.2 Parallel connection of SINAMICS DCM units .........................................................................34 6.3.3 Connecting the Firing Unit Trigger Board ...............................................................................36 6.4 Fuses ......................................................................................................................................37 6.5 Arrangement of the terminals, connectors and fuses.............................................................37 6.6 Terminal assignment, connectors...........................................................................................38 7 Commissioning ....................................................................................................................................41 7.1 Operation via the basic unit (SIMOREG DC-MASTER or SINAMICS DCM) .........................42 7.1.1 SIMOREG DC-MASTER parameters .....................................................................................42 7.1.2 SINAMICS DCM parameters ..................................................................................................48 7.1.3 SIMOREG DC-MASTER connectors......................................................................................56 7.1.4 SIMOREG DC-MASTER faults...............................................................................................57 7.1.5 SINAMICS DCM faults............................................................................................................58 7.1.6 SIMOREG DC-MASTER alarms ............................................................................................61 7.1.7 SINAMICS DCM alarms .........................................................................................................61 7.2 Commissioning steps..............................................................................................................62 7.2.1 SIMOREG DC-MASTER commissioning steps......................................................................62 7.2.2 SINAMICS DCM commissioning steps...................................................................................64 8 Maintenance..........................................................................................................................................66 8.1 Software update of the SIMOREG CCP.................................................................................67 8.2 Replacing components ...........................................................................................................68 8.2.1 Replacing modules .................................................................................................................68 8.2.2 Replacing diode, thyristor and IGBT modules ........................................................................69 9 Service, Technical Support .................................................................................................................71 10 Spare parts............................................................................................................................................72 Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 3 Table of Contents 11 4 12.2010 Appendix ...............................................................................................................................................73 11.1 Characteristic diagrams ..........................................................................................................73 11.2 Relevant standards .................................................................................................................91 11.3 Certification .............................................................................................................................91 11.4 Abbreviations, terminology......................................................................................................91 11.5 Environmental compatibility ....................................................................................................92 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 1 Notes Notes Legal notes Warning concept This manual contains information that you should observe to ensure your own personal safety as well as to avoid material damage. The notes referring to your personal safety are highlighted in the manual by a triangular safety alert symbol; notices referring to property damage only have no safety alert symbol. Depending on the hazard level, warnings are displayed in descending order as follows. DANGER Indicates that death or serious injury will result if the appropriate precautionary measures are not taken. WARNING indicates that death or serious injury can result if the appropriate precautionary measures are not taken. CAUTION with a triangular safety alert symbol indicates that minor personal injury can result if the appropriate precautionary measures are not taken. CAUTION without a triangular safety alert symbol indicates that property damage may result if the appropriate precautionary measures are not taken. NOTICE indicates that an unintended result or situation can occur if the corresponding information is not taken into account. In the event of a number of levels of danger occurring simultaneously, the warning corresponding to the highest level of danger is always used. A warning with a triangular safety alert symbol indicating possible injury to personnel may also include a warning relating to property damage. Qualified personnel The product/system that belongs to this documentation may be operated only by personnel qualified for the associated task while observing the appropriate documentation for the associated task, in particular, the safety and warning notes provided in the documentation. Because of their training and experience, qualified personnel can recognize any risks involved with handling these products/systems and avoid any possible dangers. Correct usage of Siemens products Note the following: WARNING Siemens products are only permitted to be used for the applications listed in the catalog and in the associated technical documentation. If third-party products and components are used, they must be recommended or approved by Siemens. These products can only function correctly and safely if they are transported, stored, set up, mounted, installed, commissioned, operated and maintained correctly. The permissible ambient conditions must be adhered to. Notes in the relevant documentation must be observed. Trademarks All names appearing with the registered trademark sign ® are registered trademarks of Siemens AG. Other product names used in this documentation may be trademarks which, if used by third parties, could infringe the rights of their owners. Disclaimer of liability We have checked that the contents of this publication correspond to the hardware and software described here. However, since deviations cannot be entirely precluded, we cannot guarantee full conformance. The information given in this publication is reviewed at regular intervals and any corrections that might be necessary are made in the subsequent editions. Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 5 Notes 1.1 12.2010 Warning notes Note In the interests of clarity, these operating instructions do not contain full details of all information for all product types and cannot take into account every possible aspect of installation, operation, or maintenance. If you require further information, or problems arise, which these operating instructions do not cover in enough detail, please contact your local Siemens office. Furthermore, the contents of these operating instructions shall not become a part of or modify any prior or existing agreement, commitment, or legal relationship. The Purchase Agreement contains the complete and exclusive obligations of Siemens, including the warranty provisions. Any statements contained in these operating instructions neither expand nor restrict the scope of these contractual warranty conditions. WARNING This unit is at a hazardous voltage level and contains dangerous rotating machine parts (fans). Failure to comply with these operating instructions can lead to death, serious physical injury and material damage. Only qualified personnel who are familiar with all the safety instructions provided in these operating instructions, as well as the assembly, operating, and maintenance instructions, should carry out work on this unit. WARNING Only safety extra-low voltages (DVC A) that comply with EN 60204-1 may be connected to all of the connections and terminals between 0 and 48 V. 6 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Notes DANGER When this unit is operated, it is inevitable that certain components will be subject to dangerous voltage levels. Touching these components may lead to serious physical injury or even death. The following precautions should be taken in order to reduce the risk to life and limb. 1. Only qualified personnel who are familiar with this unit and the information supplied with it should work on the unit involving installation, operation, troubleshooting and fault rectification, or repair. 2. The unit must be installed in compliance with the relevant safety regulations (e.g. EN, DIN, VDE) as well as all of the other relevant national or local regulations. Grounding, conductor dimensioning, and the appropriate short-circuit protection measures must be carried out correctly in order to ensure operational safety. 3. The unit must be operated with all covers supplied. 4. Before carrying out visual inspections and maintenance work, ensure that the unit is disconnected from the supply voltage and locked-out. Before they are shut down, both the converter unit and the motor are at dangerous voltage levels. These hazardous voltages may be present even when the converter unit line contactor is open. 5. If measurements need to be taken while the power supply is switched on, under absolutely no circumstances touch the electrical connection points. Remove all jewelry from wrists and fingers. Make sure that the measuring and test equipment is in good condition and is safe to operate. 6. When working on a unit that is switched on and on an insulated surface, make sure that no grounding has been put in place. 7. Follow these operating instructions precisely and observe all notes concerning hazards, warnings, or areas where caution is required. 8. This list is not exhaustive and as such cannot outline all the measures required in order to operate the unit safely. Should you require further information or encounter specific problems which have not been handled in enough detail for the purposes of the buyer, please contact your local Siemens office. CAUTION Operating the unit in the immediate vicinity (< 1.5 m) of mobile telephones with a transmitter power of > 1 W may lead to incorrect operation of the unit. Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 7 Notes 1.2 12.2010 Electrostatic sensitive devices (ESD) CAUTION The electronic boards contain electrostatic sensitive devices. These components can be easily destroyed if not handled correctly. Observe the following notes if you nevertheless have to work with electronic modules: • You should only touch electronic modules if absolutely necessary. • If you do have to touch modules, your body must be electrically discharged first. • Modules must not be brought into contact with highly insulating materials, e.g. plastic foils, insulated tabletops, or clothing made from synthetic fibers. • Modules may be set down only on conducting work surfaces. • Modules and components should only be stored and transported in conductive packaging (such as metalized plastic boxes or metal containers). • If the packaging material is not conductive, the modules must be wrapped with a conductive packaging material, such as conductive foam rubber or household aluminum foil, prior to placing them in the packaging. The necessary ESD protective measures are illustrated once again in the following diagram: Seated Standing Seated/standing a conductive floor b ESD table c ESD footwear d ESD overall e ESD wrist strap f 8 ENGLISH cabinet ground connection Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Type spectrum, ordering information 2 Type spectrum, ordering information 2.1 Units - order numbers Unit Rated current Rated voltage SIMOREG CCP 600 A / 460 V SIMOREG CCP 1200 A / 460 V SIMOREG CCP 1000 A / 690 V SIMOREG CCP 2000 A / 460 V SIMOREG CCP 2000 A / 690 V 600 A 1200 A 1000 A 2000 A 2000 A 460 V 460 V 690 V 460 V 690 V 2.2 Current range that can be covered to 600 A to 1200 A to 1000 A to 2000 A to 2000 A Order No. (MLFB) 6RA7085-6FC00-0 6RA7091-6FC00-0 6RA7090-6KC00-0 6RA7095-6FC00-0 6RA7095-6KC00-0 Ordering information for options and accessories Ordering options with order codes 6 R A 7 0 . . - 6 . C 0 0 - 0 - Z + Order No. of the SIMOREG CCP with identifier Z Order codes (additional) and/or where necessary, plain text Options: Option Printed operating instructions for Converter Commutation Protector SIMOREG CCP in German/English Order codes D74 Order No. (MLFB) 6RX1700-0DD74 Accessories: Item Operating instructions for SIMOREG DC-MASTER and SIMOREG CCP and DriveMonitor in all of the available languages on CD-ROM Operating instructions for SINAMICS DCM and SIMOREG CCP in all of the available languages on DVD Operating instructions for SINAMICS DCM DC Converters in German English French Italian Russian Spanish List Manual for SINAMICS DCM in German English French Italian Russian Spanish Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Order No. (MLFB) 6RX1700-0AD64 6RX1800-0AD64 6RX1800-0AD00 6RX1800-0AD76 6RX1800-0AD77 6RX1800-0AD72 6RX1800-0AD56 6RX1800-0AD78 6RX1800-0ED00 6RX1800-0ED76 6RX1800-0ED77 6RX1800-0ED72 6RX1800-0ED56 6RX1800-0ED78 ENGLISH Operating Instructions 9 Type spectrum, ordering information 12.2010 Item Patch cable UTP CAT5 acc. to ANSI/EIA/TIA 568 Parallel cable for SIMOREG DC-MASTER 6RA70 / SINAMICS DCM and SIMOREG CCP approx. 5 m Connecting cable, pulse turn-off interface to the parallel SIMOREG CCP connection and Connecting cable, summed firing pulse interface to the SIMOREG DC-MASTER (CUD2) and Connecting cable "fast pulse cancellation interface" to SINAMICS DCM Fast pulse inhibit interface module (Firing Unit Trigger Board) 10 ENGLISH Order No. (MLFB) 6RY1707-0AA08 6RY1803-0CP00 Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 2.3 Type spectrum, ordering information Selecting a suitable SIMOREG CCP The rated unit data (taking into account the relevant limit values) of the SIMOREG DC-MASTER or SINAMICS DCM and SIMOREG CCP components form the basis for the selection table. 2.3.1 Selection table for 4Q basic units SIMOREG DC-MASTER Order No. Rated DC voltage / DC current 6RA7013-6DV62-0 6RA7018-6DV62-0 6RA7025-6DV62-0 6RA7028-6DV62-0 6RA7031-6DV62-0 6RA7075-6DV62-0 6RA7078-6DV62-0 6RA7081-6DV62-0 6RA7085-6DV62-0 6RA7087-6DV62-0 6RA7091-6DV62-0 6RA7093-4DV62-0 6RA7095-4DV62-0 6RA7098-4DV62-0 6RA7018-6FV62-0 6RA7025-6FV62-0 6RA7028-6FV62-0 6RA7031-6FV62-0 6RA7075-6FV62-0 6RA7078-6FV62-0 6RA7082-6FV62-0 6RA7085-6FV62-0 6RA7087-6FV62-0 6RA7091-6FV62-0 6RA7025-6GV62-0 6RA7031-6GV62-0 6RA7075-6GV62-0 6RA7081-6GV62-0 6RA7085-6GV62-0 6RA7087-6GV62-0 6RA7090-6GV62-0 6RA7093-4GV62-0 6RA7095-4GV62-0 6RA7096-4GV62-0 6RA7097-4GV62-0 6RA7086-6KV62-0 6RA7090-6KV62-0 6RA7093-4KV62-0 6RA7095-4KV62-0 6RA7097-4KV62-0 6RA7088-6LV62-0 6RA7093-4LV62-0 6RA7095-4LV62-0 6RA7096-4MV62-0 420 V / 15 A 420 V / 30 A 420 V / 60 A 420 V / 90 A 420 V / 125 A 420 V / 210 A 420 V / 280 A 420 V / 400 A 420 V / 600 A 420 V / 850 A 420 V / 1200 A 420 V / 1600 A 420 V / 2000 A 420 V / 3000 A 480 V / 30 A 480 V / 60 A 480 V / 90 A 480 V / 125 A 480 V / 210 A 480 V / 280 A 480 V / 450 A 480 V / 600 A 480 V / 850 A 480 V / 1200 A 600 V / 60 A 600 V / 125 A 600 V / 210 A 600 V / 400 A 600 V / 600 A 600 V / 850 A 600 V / 1100 A 600 V / 1600 A 600 V / 2000 A 600 V / 2200 A 600 V / 2800 A 725 V / 760 A 725 V / 1000 A 725 V / 1500 A 725 V / 2000 A 725 V / 2600 A 875 V / 950 A 875 V / 1500 A 875 V / 1900 A 1000 V / 2200 A x Converter Commutation Protector SIMOREG CCP 6RA70... ..85-6FC00-0 ..91-6FC00-0 ..90-6KC00-0 ..95-6FC00-0 ..95-6KC00-0 460 V / to 600 A 460 V / to 1200 A 690 V / to 1000 A 460 V / to 2000 A 690 V / to 2000 A x x x x x x = suitable Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector x x x x x x x x x x x x x x x x x x x x = not suitable (see note) ENGLISH Operating Instructions 11 Type spectrum, ordering information Converter Commutation Protector SIMOREG CCP 6RA70... SINAMICS DCM Order No. Rated DC voltage/DC current 6RA8013-6DV62-0AA0 6RA8018-6DV62-0AA0 6RA8025-6DV62-0AA0 6RA8028-6DV62-0AA0 6RA8031-6DV62-0AA0 6RA8075-6DV62-0AA0 6RA8078-6DV62-0AA0 6RA8081-6DV62-0AA0 6RA8085-6DV62-0AA0 6RA8087-6DV62-0AA0 6RA8091-6DV62-0AA0 6RA8093-4DV62-0AA0 6RA8095-4DV62-0AA0 6RA8098-4DV62-0AA0 6RA8013-6FV62-0AA0 6RA8018-6FV62-0AA0 6RA8025-6FV62-0AA0 6RA8028-6FV62-0AA0 6RA8031-6FV62-0AA0 6RA8075-6FV62-0AA0 6RA8078-6FV62-0AA0 6RA8082-6FV62-0AA0 6RA8085-6FV62-0AA0 6RA8087-6FV62-0AA0 6RA8091-6FV62-0AA0 6RA8025-6GV62-0AA0 6RA8031-6GV62-0AA0 6RA8075-6GV62-0AA0 6RA8081-6GV62-0AA0 6RA8085-6GV62-0AA0 6RA8087-6GV62-0AA0 6RA8090-6GV62-0AA0 6RA8093-4GV62-0AA0 6RA8095-4GV62-0AA0 6RA8096-4GV62-0AA0 6RA8097-4GV62-0AA0 6RA8086-6KV62-0AA0 6RA8090-6KV62-0AA0 6RA8093-4KV62-0AA0 6RA8095-4KV62-0AA0 6RA8097-4KV62-0AA0 6RA8088-6LV62-0AA0 6RA8093-4LV62-0AA0 6RA8095-4LV62-0AA0 6RA8096-4MV62-0AA0 420 V / 15 A 420 V / 30 A 420 V / 60 A 420 V / 90 A 420 V / 125 A 420 V / 210 A 420 V / 280 A 420 V / 400 A 420 V / 600 A 420 V / 850 A 420 V / 1200 A 420 V / 1600 A 420 V / 2000 A 420 V / 3000 A 500 V / 15 A 500 V / 30 A 500 V / 60 A 500 V / 90 A 500 V / 125 A 500 V / 210 A 500 V / 280 A 500 V / 450 A 500 V / 600 A 500 V / 850 A 500 V / 1200 A 600 V / 60 A 600 V / 125 A 600 V / 210 A 600 V / 400 A 600 V / 600 A 600 V / 850 A 600 V / 1100 A 600 V / 1600 A 600 V / 2000 A 600 V / 2200 A 600 V / 2800 A 725 V / 760 A 725 V / 1000 A 725 V / 1500 A 725 V / 2000 A 725 V / 2600 A 875 V / 950 A 875 V / 1500 A 875 V / 1900 A 1000 V / 2200 A x 12.2010 = suitable ..85-6FC00-0 ..91-6FC00-0 ..90-6KC00-0 ..95-6FC00-0 ..95-6KC00-0 460 V / to 600 A 460 V / to 1200 A 690 V / to 1000 A 460 V / to 2000 A 690 V / to 2000 A x x x x x x x x x x x x x x x x x x x x x x x x x x = not suitable (see note) Note For system configurations, with reduced rate values (e.g. DC rating, US rating, voltage derating), under certain circumstances, suitable combinations of units can be found that are not listed in the table. 12 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 2.3.2 Type spectrum, ordering information Selection table for 2Q basic units SIMOREG DC-MASTER Order No. Rated DC voltage / DC current 6RA7018-6DS22-0 6RA7025-6DS22-0 6RA7028-6DS22-0 6RA7031-6DS22-0 6RA7075-6DS22-0 6RA7078-6DS22-0 6RA7081-6DS22-0 6RA7085-6DS22-0 6RA7087-6DS22-0 6RA7091-6DS22-0 6RA7093-4DS22-0 6RA7095-4DS22-0 6RA7098-4DS22-0 6RA7018-6FS22-0 6RA7025-6FS22-0 6RA7028-6FS22-0 6RA7031-6FS22-0 6RA7075-6FS22-0 6RA7078-6FS22-0 6RA7082-6FS22-0 6RA7085-6FS22-0 6RA7087-6FS22-0 6RA7091-6FS22-0 6RA7025-6GS22-0 6RA7031-6GS22-0 6RA7075-6GS22-0 6RA7081-6GS22-0 6RA7085-6GS22-0 6RA7087-6GS22-0 6RA7090-6GS22-0 6RA7093-4GS22-0 6RA7095-4GS22-0 6RA7095-4GS22-5 6RA7096-4GS22-0 6RA7096-4GS22-5 6RA7097-4GS22-0 6RA7086-6KS22-0 6RA7088-6KS22-0 6RA7093-4KS22-0 6RA7095-4KS22-0 6RA7095-4KS22-5 6RA7097-4KS22-0 6RA7088-6LS22-0 6RA7093-4LS22-0 6RA7095-4LS22-0 6RA7095-4LS22-5 6RA7096-4MS22-0 485 V / 30 A 485 V / 60 A 485 V / 90 A 485 V / 125 A 485 V / 210 A 485 V / 280 A 485 V / 400 A 485 V / 600 A 485 V / 850 A 485 V / 1200 A 485 V / 1600 A 485 V / 2000 A 485 V / 3000 A 550 V / 30 A 550 V / 60 A 550 V / 90 A 550 V / 125 A 550 V / 210 A 550 V / 280 A 550 V / 450 A 550 V / 600 A 550 V / 850 A 550 V / 1200 A 690 V / 60 A 690 V / 125 A 690 V / 210 A 690 V / 400 A 690 V / 600 A 690 V / 850 A 690 V / 1100 A 690 V / 1600 A 690 V / 2000 A 690 V / 2000 A 690 V / 2200 A 690 V / 2200 A 690 V / 2800 A 830 V / 720 A 830 V / 950 A 830 V / 1500 A 830 V / 2000 A 830 V / 2000 A 830 V / 2600 A 1000 V / 900 A 1000 V / 1500 A 1000 V / 1900 A 1000 V / 1900 A 1140 V / 2200 A x Converter Commutation Protector SIMOREG CCP 6RA70... ..85-6FC00-0 ..91-6FC00-0 ..90-6KC00-0 ..95-6FC00-0 ..95-6KC00-0 460 V / to 600 A 460 V / to 1200 A 690 V / to 1000 A 460 V / to 2000 A 690 V / to 2000 A x x x x x x = suitable Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector x x x x x x x x x x x x x x x x x x x x x x = not suitable (see note) ENGLISH Operating Instructions 13 Type spectrum, ordering information SINAMICS DCM Converter Commutation Protector SIMOREG CCP 6RA70... Order No. Rated DC voltage / DC current 6RA8025-6DS22-0AA0 6RA8028-6DS22-0AA0 6RA8031-6DS22-0AA0 6RA8075-6DS22-0AA0 6RA8078-6DS22-0AA0 6RA8081-6DS22-0AA0 6RA8085-6DS22-0AA0 6RA8087-6DS22-0AA0 6RA8091-6DS22-0AA0 6RA8093-4DS22-0AA0 6RA8095-4DS22-0AA0 6RA8098-4DS22-0AA0 6RA8025-6FS22-0AA0 6RA8028-6FS22-0AA0 6RA8031-6FS22-0AA0 6RA8075-6FS22-0AA0 6RA8078-6FS22-0AA0 6RA8082-6FS22-0AA0 6RA8085-6FS22-0AA0 6RA8087-6FS22-0AA0 6RA8091-6FS22-0AA0 6RA8025-6GS22-0AA0 6RA8031-6GS22-0AA0 6RA8075-6GS22-0AA0 6RA8081-6GS22-0AA0 6RA8085-6GS22-0AA0 6RA8087-6GS22-0AA0 6RA8090-6GS22-0AA0 6RA8093-4GS22-0AA0 6RA8095-4GS22-0AA0 6RA8096-4GS22-0AA0 6RA8097-4GS22-0AA0 6RA8086-6KS22-0AA0 6RA8090-6KS22-0AA0 6RA8093-4KS22-0AA0 6RA8095-4KS22-0AA0 6RA8097-4KS22-0AA0 6RA8088-6LS22-0AA0 6RA8093-4LS22-0AA0 6RA8095-4LS22-0AA0 6RA8096-4MS22-0AA0 485 V / 60 A 485 V / 90 A 485 V / 125 A 485 V / 210 A 485 V / 280 A 485 V / 400 A 485 V / 600 A 485 V / 850 A 485 V / 1200 A 485 V / 1600 A 485 V / 2000 A 485 V / 3000 A 575 V / 60 A 575 V / 90 A 575 V / 125 A 575 V / 210 A 575 V / 280 A 575 V / 450 A 575 V / 600 A 575 V / 850 A 575 V / 1200 A 690 V / 60 A 690 V / 125 A 690 V / 210 A 690 V / 400 A 690 V / 600 A 690 V / 800 A 690 V / 1100 A 690 V / 1600 A 690 V / 2000 A 690 V / 2200 A 690 V / 2800 A 830 V / 720 A 830 V / 1000 A 830 V / 1500 A 830 V / 2000 A 830 V / 2600 A 1000 V / 950 A 1000 V / 1500 A 1000 V / 1900 A 1140 V / 2200 A x 12.2010 = suitable ..85-6FC00-0 ..91-6FC00-0 ..90-6KC00-0 ..95-6FC00-0 ..95-6KC00-0 460 V / to 600 A 460 V / to 1200 A 690 V / to 1000 A 460 V / to 2000 A 690 V / to 2000 A x x x x x x x x x x x x x x x x x x x x x x x x x x = not suitable (see note) Note For system configurations, with reduced rate values (e.g. DC rating, US rating, voltage derating), under certain circumstances, suitable combinations of units can be found that are not listed in the table. 14 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 2.4 Type spectrum, ordering information Rating plate, packaging label SIMOREG DC-MASTER Converter Commutation Protector s ... Barcode for MLFB Bestellnr./Order No 1P 6RA70 . . - 6 . . . . - 0 ... For options, the MLFB is followed by a -Z ... Identifier for options (order-specific) ... Bar code, serial number (order-specific) Fabrik-Nr./Serial No S Q6 . . . . . . . . . . Nennstrom/Rated Current .... A Nennspannung/Rated Voltage ... V Netzfrequenz/Frequency 50 / 60 Hz Erz.-Stand/Prod State A1 Kühlung/Cooling S MADE IN EU (AUSTRIA) Rating plate s SIMOREG DC-MASTER Converter Commutation Protector 6RA70 . . - 6 . . . . - 0 1P S ... For options, after the MLFB is a – Z, followed by its identifier (orderspecific) 6RA70 . . - 6 . . . . - 0 Q6 . . . . . . . . . . QTY 1 SW VERSION (Version) 1.0 Q...... E-STATUS (Version) A1 MADE IN EU (AUSTRIA) Packaging label Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 15 Description, technical data 12.2010 3 Description, Technical Data 3.1 Description Application The SIMOREG DC-MASTER Converter Commutation Protector (SIMOREG CCP) is used to protect the semiconductor fuses of a line-commutated converter when operating in the inverter mode. When an inverter commutation fault occurs, a high current flows in the regenerative feedback direction via the line supply or a cross-current in the converter. SIMOREG CCP limits the current to a non-hazardous value so that the thyristors and the associated super-fast fuses are protected. This therefore eliminates the complex replacement of fuses that takes a considerable amount of time. Although it cannot prevent inverter commutation faults, it can provide protection against its effects. Compatibility The SIMOREG CCP is compatible to line-commutated SIMOREG DC-MASTER converters (from software release 2.2) and SINAMICS DCM (from software release 1.2). It can be used for converters connected in parallel. Note It is not possible to use the SIMOREG CCP for converters connected in series. Mode of operation The line supply voltage, line current and the armature voltage are continually sensed in the basic converter unit. These quantities are used to identify as to whether a commutation fault (inverter commutation fault) has occurred. If this is the case, then the following occurs: 1. The firing pulses are immediately disabled in the SIMOREG DC-MASTER or SINAMICS DCM. 2. The basic converter unit sends a turn-off command to the SIMOREG CCP (via the serial interface) 3. SIMOREG CCP turns-off the thyristors by connecting the pre-charged quenching capacitors anti-parallel to all thyristors. As a consequence, the current commutates from the converter into SIMOREG CCP. The quenching capacitors are initially discharged by the current that has been commutated and then they are charged. The armature current starts to decrease as soon as the voltage of the quenching capacitors has reached the value of the motor EMF. However, the armature voltage continues to increase. As soon as it has reached the limit value, resistors are switched-in, which absorb the energy fed back from the motor during the remaining time of the current reduction phase. 4. A fault message is output in the basic converter unit (Fault F030 or F60030). 5. The SIMOREG CCP re-charges the quenching capacitors with the reverse polarity so that a new turn-off operation is possible. Note After the line supply voltage has been connected and after a quenching operation, wait and recovery times must be maintained, refer to the Technical data. 16 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 3.2 Description, technical data Technical data Order No. 6RA70... ..85-6FC00-0 ..91-6FC00-0 ..90-6KC00-0 ..95-6FC00-0 ..95-6KC00-0 Rated voltage 460 V (+15% / -20%) 460 V (+15% / -20%) 690 V (+10% / -20%) 460 V (+15% / -20%) 690 V (+10% / -20%) Rated current 600 A 1200 A 1000 A 2000 A 2000 A current range that can be covered to 600 A to 1200 A to 1000 A to 2000 A to 2000 A Rated supply voltage Electronics power supply 2 AC 380 V (-20 %) to 460 V (+15 %); In=1 A or 1 AC 190 V (-20 %) to 230 V (+15 %); In=2 A Rated frequency 45 to 65 Hz Power loss 100 W Ambient temperature Operation: storage, transport: Installation altitude above sea level ≤ 2000 m without derating > 2000 m with voltage derating *) Environmental class 3K3 acc. to DIN IEC 60 721-3-3 Pollution degree 2 acc. to EN50178 **) Degree of protection IP00 acc. to DIN EN 60529 Dimensions (W x H x D) 780 x 406 x 500 mm, dimension drawing, see Chapter 5.1 Weight (approx.) 35 kg 0 to 55 °C -25 to +70 °C 35 kg 45 kg 55 kg 75 kg *) Voltage derating as a function of installation altitude: When supplying the electronics with voltages of 460 VAC phase to phase (maximum 300 VAC with respect to ground) operation is permitted up to 4500 m. A maximum of 400 VAC phase to phase (maximum 230 V AC with respect to ground) is permitted up to 5000 m. At higher altitudes or a higher voltage, there is no longer "safe electrical separation" - but only basic insulation. **) Definition, pollution degree 2: Normally, only non-conductive pollution occurs. However, occasionally conductive pollution can be expected for a short period of time if the electronic equipment is not operational. Wait time, recovery time: Each time that the line supply voltage is connected (e.g. via a line contactor): The quenching capacitors in the unit are charged. The wait time until the SIMOREG CCP is ready, is approx. 3 s After one quenching operation: The time until the SIMOREG CCP is ready again depends on the operations during the quenching process and immediately afterwards. The quenching capacitors in the SIMOREG CCP are again recharged to the required value, duration approx. 10 s. The chopper resistors, which convert the energy into heat when the armature current is reduced, require a cooling time. This is calculated using a software algorithm, and depending on the energy that is dissipated during the quenching operation, is up to approx. 20 min. Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 17 1D1 1W1 1V1 1U1 1C1 V44 V41 V46 V43 - + - + C2 V40 V42 V45 V39 C1 V32 V31 X20 V33 V48 V47 V34 X172 ENGLISH C98043A7048 K1 HS-Relais X40 X31 X1 R50.1 V35 V100.1 V36 1U2 1U3 X29_PAR 18 V37 R54 R53 R52 R51 X32 C98043-A7046 X34 V54 V53 V52 V51 C3 V38 R50.2 + XP X33 X39 V100.2 C98043A7048 X1 1C1 1D1 1U1 1V1 1W1 X35 X38 X36 X37 V54 V53 V52 V51 R54 R53 R52 R51 X9_PLUS_GLR X5_M_C2 X6_N_C2 X4_MINUS_GLR X3_M_C1 X2_P_C1 X1_PLUS_GLR X11_WID+ X12_WID- X7_P_C3 C98043-A7047 2 4 6 12 X20 1 3 5 11 A1 1U1-1 1V1-1 1W1-1 3RT10 K1 X2 A2 3.3 X30_PAR Description, technical data 12.2010 Block diagram - Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions X_SCHÜTZ-1 X_SCHÜTZ-2 X_SCHÜTZ-3 X_SCHÜTZ-4 X_SCHÜTZ-5 X8_M_C3 X1 X300 X165 12.2010 Description, technical data Arrangement of the thyristor and diode modules Units 6RA70...85-6FC00-0 / ...91-6FC00-0 / ...90-6KC00-0 (all 1000 A) - A X36 X37 K2 K1 G2 G1 A X35 X38 K2 K1 G2 G1 A V48 V36 V35 K K V37 V38 V47 K K AK AK V33 V34 V32 V31 K X40 K1G1 K2 G2 A K K A V40 X39 A V39 K1G1 AK G1G2 G1 G2 K1 K2 K1 K2 X31 X33 X32 X34 C2+ C2- A K2 G2 K A A A V46 V42 V41 V43 V45 K AK K AK 1U1 AK 1V1 1D1 (1C1) AK C1- C1+ V44 K + AK AK AK AK A 1W1 1C1 (1D1) Units 6RA70...95-6FC00-0 / ...95-6KC00-0 (all 2000 A) X36 - X37 X35 X38 K2 G2 G1 K1 K2 G2 G1 K1 A A A V48 V36 V35 K K K K V37 V38 V47 AK AK A AK C2- + AK C1- AK AK V33 V34 K K V32 V31 A A K2 AK V40 K A K2 G2 G1 K1 X40 K1 G1 G2 K2 C2+ X 33 AK K X34 X 31 G2 X39 G1 K1 C1+ A A V44 V46 V42 K K K V41 V43 V45 AK AK AK 1D1 (1C1) A K1 G1 G2 K2 X32 A 1U1 V39 1V1 1C1 (1D1) Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector 1W1 ENGLISH Operating Instructions 19 Transport, unpacking 4 05.2007 Transport, Unpacking The units are packaged in the manufacturer's factory in accordance with the order specification. A product packaging label is attached to the cardboard box. Avoid heavy vibration and severe shocks during transportation, e.g. when placing down. Follow the instructions on the packaging concerning transportation, storage, and proper handling. The unit can be installed once it has been unpacked, and you have checked that the delivery is complete and the unit is intact and has not been damaged. The packaging materials consist of a cardboard box and corrugated cardboard, and can be disposed of in accordance with local regulations for cardboard packaging materials. If you identify any damage that has occurred in transit, please inform your shipping agent immediately. 20 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 5 Installation Installation CAUTION Failure to lift the unit properly can lead to physical injury or material damage. The unit should only be lifted with suitable equipment (work gloves should be used) and by appropriately qualified personnel. In order to prevent the enclosure from becoming deformed, no horizontal forces may be exerted on the lifting eyes. The user is responsible for installing the converter, the motor, the transformer as well as all of the other devices and units according to the relevant safety regulations (e.g. EN, DIN, VDE) as well as all of the other relevant national or local regulations regarding dimensioning conductors and protection, grounding, disconnectors, overcurrent protection etc. The unit must be installed in compliance with the relevant safety regulations (e.g. EN, DIN, VDE) as well as all of the other relevant national or local regulations. Grounding, conductor dimensioning, and the relevant short-circuit protection measures must be carried out correctly in order to ensure operational safety. Cabinet installation of SIMOREG units in conformance with UL 508 C If this unit is to be installed in a cabinet, the cabinet must be sufficiently ventilated and of "Type 1" in accordance with standard UL 508 C. To install the unit, the cabinet must have minimum dimensions of 2200 mm x 600 mm x 600 mm (H x W x D). Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 21 Installation 5.1 12.2010 Dimension drawing for M10 for M10 Lifting lug 20 M12 for PE conductor connection 600 A / 1000 A / 1200 A - units: 22 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Installation for M10 for M10 Lifting lug 20 M12 for PE conductor connection 2000 A - units: Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 23 Installation 5.2 12.2010 SINAMICS DCM - Installing the Firing Unit Trigger Board When using the SIMOREG CCP with SINAMICS DCM connected in parallel, each SINAMICS DCM must be equipped with a supplementary module "fast pulse cancellation interface" (Firing Unit Trigger Board) (Order No.: 6RY1803-0CP00). See chapter 6.3.2. CAUTION Please observe the information provided on "Electrostatic sensitive devices (ESD)" in Chapter 1. WARNING Always carry out the work with the SINAMICS DCM in a no-voltage condition! 24 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Installation • Remove the front cover of the SINAMICS DCM • ① Break-off the extension of the module A7126 Allocation Board • ② Using the guide slots in the holder for the electronic modules, position the Firing Unit Trigger Board A7103 and by shifting the plug connection (X110), establish a connection to the Allocation Board A7126 • ③ Fasten the Firing Unit Trigger Board A7103 using the screw provided, tightening torque 1 Nm • ④ The BOP holder can be released at the side and swung upwards to route the connecting cable • After connecting the cable (see Chapter 6.3.3) relocate the front cover of the SINAMICS DCM and fasten using all of the screws Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 25 Connecting 6 12.2010 Connecting WARNING The units are operated at high voltage levels. All connection work must be carried out in the no-voltage condition! Only qualified personnel who are familiar with all the safety instructions in these operating instructions, as well as the assembly, installation, operating, and maintenance instructions, should carry out work on these units. Non-observance of these warnings can result in death, serious personal injury, or substantial property damage. Connecting the unit incorrectly can lead to it being damaged or destroyed. The units may be connected to a line supply with a residual current operated circuit breaker if a universal current sensitive device is being used, which in the case of a ground fault, can also detect a DC component in the fault current. It is recommended to use a residual current operated circuit breaker with a response current ≥300 mA, which means that it is not suitable for protecting personnel. If you have additional questions, please contact Technical Support. Even when the motor is stationary, power terminals and control terminals can still be at a certain voltage. Even after being disconnected from the power supply, the snubber capacitors in the converter unit can still be at a dangerous voltage level. For this reason, the unit should not be opened until an adequate period of time has elapsed. When handling the unit while it is open, remember that live parts are exposed. The unit must only be operated with the front covers provided by the factory in place. The user is responsible for ensuring that the SIMOREG CCP, the motor, converter unit and other devices are installed and connected in accordance with the recognized technical rules in the country of installation and applicable regional regulations. Special attention should be paid to cable dimensioning, fuses, grounding, shutdown, disconnection, and overcurrent protection. The units described here control rotating mechanical equipment (drives). Failure to follow these operating instructions may result in death, serious physical injury, or extensive material damage. Perfect, safe and reliable operation of the units is conditional upon them having been professionally transported, stored, mounted, and installed, and having been carefully operated and maintained. Also observe all of the safety instructions in the converter unit operating instructions. Note Please observe the installation instructions for EMC-compliant design of drives in Chapter 6.1 of the operating instructions of the basic SIMOREG DC-MASTER or SINAMICS DCM unit. 26 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 6.1 Connecting Cable lengths Lengths of the connecting cables between connections 1U1, 1V1, 1W1, 1C1, 1D1 of the basic converter unit and the SIMOREG CCP The connecting cables between the basic converter unit and the SIMOREG CCP also serve as commutation inductance for quenching operations and must therefore have a defined length. The cable length is valid for each cable for 1U1, 1V1, 1W1, 1C1, 1D1 and can be taken from the following diagram. The actual cable length used must lie between l_min and l_max (also refer to the example below). Note The correct values for parameters U578 or p51578 must be available before determining the cable length. Length (l) of the connecting cable between the basic unit and SIMOREG CCP 40 35 l_min [m] l_max [m] Cable length (l) in m 30 25 20 15 10 5 0 100 200 300 400 500 600 700 800 900 Charging voltage according to U578 in V l <1> <1> l = cable length 1U1 1V1 1W1 1U1 1V1 1W1 SIMOREG DC-MASTER / SINAMICS DCM SIMOREG CCP 1C1 1D1 1C1 1D1 l <1> Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Cable length to connect the AC connections .... lUVW Cable length to connect the DC connections .... lCD ENGLISH Operating Instructions 27 Connecting 12.2010 The following basic rule applies The sum of the lengths, formed from lUVW and lCD must have twice the value of l (2*l) according to the diagram above (2*l= lUVW + lCD). You can e.g. keep the line-side connecting cables as short as possible or as required (e.g. using busbars) and use motor-side connecting cables with the required length. Example The minimum required cable length l_min is 3 m. Use 3m lengths each for 1U1, 1V1, 1W1, 1C1, 1D1. Or: e.g. use 1m lengths each for 1U1, 1V1, 1W1 and 5 m lengths each for 1C1, 1D1 28 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Connecting 6.2 Recommended connection 6.2.1 Connecting a SIMOREG DC-MASTER 3 AC 400-690 V, 50-60 Hz 3 AC 380-460 V, 50-60 Hz 1 AC 230 V, 50-60 Hz <1> K1 or Field Armature 109 110 XR 1 SIMOREG CCP 5N1 5W1 5U1 5N1 5W1 5U1 2W1 2 3 4 5 X_SCHÜTZ 2 3 1 2 3 XP XP Power supply Power Interface X30_PAR X172 1D1(1C1) 1C1(1D1) 1D1(1C1) 1C1(1D1) 3C 3D X166 X165 C98043-A7006 X29_PAR C98043-A7046 CUD2 X165 X172 C98043-A7001 2V1 1 SIMOREG DC-MASTER 6RA70 CUD1 2U1 1W1 1V1 1U1 1W1 1V1 1U1 3U1 3W1 5U1 Power supply NC X300 Fan 5W1 5N1 L3 L2 L1 see operating instructions SIMOREG DC-MASTER 6RA70 M <1> CAUTION Operation without a main contactor/circuit breaker is not permissible. The control voltage for the main contactor (or the circuit breaker) must always be routed via terminal XR (connections 109 and 110) of the SIMOREG unit and via terminal X_SCHÜTZ (connections 4 and 5) of the SIMOREG CCP. For a parallel connection (see Chapter 6.3.1) all SIMOREG units must be incorporated in this interlock circuit. In applications with SIMOREG CCP, in the case of a fault, the basic converter unit or the SIMOREG CCP must be able to safely and reliably disconnect the arrangement from the line supply. In addition, it must be carefully observed that the total of the delay times of all of the switching elements in the control circuit must not exceed the time set at parameter P089. Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 29 Connecting 6.2.2 12.2010 Connecting a SINAMICS DCM 3 AC 400-690 V, 50-60 Hz 3 AC 380-460 V, 50-60 Hz 1 AC 230 V, 50-60 Hz <1> K1 or 109 110 XR 1 SIMOREG CCP 5N1 5W1 5U1 5N1 5W1 5U1 2W1 2 3 4 5 X_SCHÜTZ 2 3 1 2 3 XP XP Power supply Power Interface X30_PAR X165 1D1(1C1) 1C1(1D1) 1D1(1C1) 1C1(1D1) 3C 3D X166 X29_PAR C98043-A7046 C98043-A7100 X165 X177 2V1 1 SINAMICS DCM C98043-A7125 2U1 1W1 1V1 1U1 1W1 1V1 Armature X172 Field 1U1 3W1 3U1 5U1 5W1 Power supply NC X300 Fan 5N1 L3 L2 L1 see operating instructions SINAMICS DCM M <1> CAUTION Operation without a main contactor/circuit breaker is not permissible. The control voltage for the main contactor (or the circuit breaker) must always be routed via terminal XR1 (connections 109 and 110) of the SINAMICS DCM and via terminal X_SCHÜTZ (connections 4 and 5) of the SIMOREG CCP. For a parallel connection (see Chapter 6.3.2) all SINAMICS DCM units must be incorporated in this interlock circuit. In applications with SIMOREG CCP, in the case of a fault, the basic converter unit or the SIMOREG CCP must be able to safely and reliably disconnect the arrangement from the line supply. In addition, it must be carefully observed that the total of the delay times of all of the switching elements in the control circuit must not exceed the time set at parameter P50089. 30 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 6.2.3 Connecting Versions to interconnect the main contactor (circuit breaker) K1 after the supply transformer before the supply transformer 3 AC 50-60 Hz 3 AC 50-60 Hz 50-60 Hz 230 V K1 50-60 Hz 230 V 400 V-690 V 109 110 4 5 XR X_SCHÜTZ 400 V-690 V SIMOREG DC-MASTER / SINAMICS DCM 6.2.4 SIMOREG CCP 1U1 1V1 1W1 2U1 2V1 2W1 1U1 1V1 1W1 5 4 110 109 X_SCHÜTZ XR SIMOREG DC-MASTER / SINAMICS DCM 3 AC 50-60 Hz 400 V-690 V 2U1 2V1 2W1 K1 SIMOREG CCP Recommended connection when using a Siemens 3WL circuit breaker If circuit breakers from other manufacturers are used, then the recommended connection described here applies accordingly. It should be noted that the circuit breaker is equipped with a ready to close signal contact (S20, order option Z=C22) and undervoltage release (F3 short-time delayed or F4 with the shortest possible delay time, the version is defined using the 15th position of the MLFB of the circuit breaker). Also refer to the operating instructions for the 3WL circuit breaker, Order No.: 3ZX1812-0WL000AN0 Chapter8.4 Auxiliary release/ electrical close inhibit ( http://support.automation.siemens.com/WW/view/en/8912465 ) Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 31 Connecting 12.2010 with undervoltage release F4: -XR:109 Control voltage -XR:110 P24 Fault inv. -X_SCHÜTZ:4 -X171:46 -X_SCHÜTZ:5 -X171:47 M -S11 -X5:12 -X5:13 -X5:14 -X6:7 -X6:6 -X6:5 -X5:2 e.g. Relais DC 24 V SIMOREG DC-MASTER B0107 SINAMICS DCM -S20 -M1 -Y1 -F4 1 SIEMENS Circuit breaker 3WL control unit -X6:8 -X5:11 U< -X5:1 M r2139.03 Control voltage with undervoltage release F3: -XR:110 -XR:109 Control voltage P24 -X_SCHÜTZ:4 Fault inv. -X171:46 -X_SCHÜTZ:5 e.g. Relais DC 24 V -X171:47 M SIMOREG DC-MASTER -X5:12 -X6:7 -X6:6 -X6:5 -X5:2 B0107 SINAMICS DCM r2139.03 -S20 -Y1 -F3 U< Siemens Circuit breaker 3WL control unit -X5:11 -M1 -X5:1 M -X6:8 -S11 1 Control voltage 32 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 3) NC 1U1 3W1 3U1 5N1 5W1 5U1 5N1 5W1 5U1 2W1 2V1 2U1 1W1 1W1 1V1 1U1 3W1 3U1 5N1 5W1 5U1 Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector 1D1 (1C1) 1C1 (1D1) 1V1 1U1 X166 X165 1C1 (1D1) 1D1 (1C1) 1C1 (1D1) X166 3C 5) Parallel connection of SIMOREG DC-MASTER units X165 X300 1D1 (1C1) 1C1 (1D1) 3D X165 X172 X30_PAR X29_PAR 1D1 (1C1) 3D 3C X172 X30_PAR X29_PAR X172 X165 X300 1D1 (1C1) 3D X165 X172 Operating Instructions ENGLISH For further connections for the SIMOREG devices, see operating instructions for the SIMOREG DC-MASTER 6RA70 3.2) SIMOREG CCP (Slave) Power supply 6.3.1 Warning: The triggering of the main contactors is not shown here; please refer to the connection suggestion in Section 6.2. 3.3) 2) NC Connecting units in parallel M 5) 1C1 (1D1) 3.1) 3C 5) 1U1 3.2) 1V1 X166 3.4) 3.3) 1V1 1C1 (1D1) 3.2) 1W1 1D1 (1C1) 2) 1W1 CUD2 1U1 3.1) 2U1 CUD1 1V1 2) 2V1 CUD2 2W1 CUD1 5U1 CUD2 5W1 CUD1 5N1 SIMOREG-converter (Slave) 1W1 SIMOREG CCP (Master) 2U1 SIMOREG-converter (Master) 5U1 Armature 2V1 SIMOREG CCP (Slave) 5W1 Field 1) 2W1 SIMOREG-converter (Slave) 5N1 Power supply 3U1 Power supply 3W1 Armature 1U1 Field NC 1V1 Power supply NC 1W1 Power supply 1) 5U1 Armature NC 4) 5W1 Field NC 4) 5N1 Power supply 1) 4) 6.3 1) The same phase sequence is required between 1U1 /1V1 /1W1. 2) The same phase sequence is required between 1C1 / 1D1. 3) Connecting cables: 3.1) Connection of the SIMOREG devices in parallel 3.2) Serial connection of SIMOREG device -> SIMOREG CCP 3.3) Extinction pulse interface 3.4) Group firing pulse interface 4) These fuses may only be used on converters up to 850A 5) For converters up to 850A in 4Q operation only 3 AC 380-460 V 50-60 Hz 3 AC 400-690 V 50-60 Hz 12.2010 Connecting A SIMOREG CCP is directly connected in parallel to each of the converter units connected in parallel (SIMOREG DC-MASTER). X30_PAR X29_PAR X172 X172 X165 X300 33 Connecting 6.3.2 12.2010 Parallel connection of SINAMICS DCM units The following topologies are possible when connecting SINAMICS DCM in parallel: • 12-pulse parallel connection: Each of the two SINAMICS DCM should be equipped with one SIMOREG CCP. Interconnection and parameterization is just the same as for a single SINAMICS DCM. • 6-pulse parallel connection: Each of the SINAMICS DCM used should be equipped with one SIMOREG CCP. Parameterization is just the same as for a single SINAMICS DCM. Note For series connections it is not permissible to use a SIMOREG CCP. A SIMOREG CCP is directly connected in parallel to each of the converter units connected in parallel (SINAMICS DCM). Each SINAMICS DCM must be equipped with a supplementary module "fast pulse cancellation interface" (Firing Unit Trigger Board) - available as accessory - also refer to Chapter 5.2 (Installation) and 6.3.3 (connection). Ordering data, refer to chapter 2.2 (ordering data for options and accessories) The interconnection must be made according to the following diagram. Mode of operation: • • The inverter commutation fault monitoring is continuously active in the SINAMICS DCM. • The turn-off command is transferred from this SIMOREG CCP to the additional SIMOREG CCP. All SIMOREG CCP units simultaneously execute the turn-off operation. The turn-off command is transferred via the turn-off pulse interface 3.3, with which all SIMOREG CCPs are connected with one another. • At the same time, the firing pulses are immediately disabled in all SINAMICS DCM units from the assigned SIMOREG CCP. This therefore ensures that the SINAMICS DCM, which have (still) not identified an inverter commutation fault, do not prevent the turn-off operation. The firing pulses are disabled via the fast pulse cancellation interface 3.4. If an inverter commutation fault is identified in a SINAMICS DCM then a turn-off command is issued to the associated SIMOREG CCP. The turn-off command is transferred via the serial connection 3.2. CAUTION The parallel interface (X165, X166) at the SINAMICS DCM is not compatible to the parallel interface (X165) at the SIMOREG DC-MASTER CCP. It is not permissible that both connectors are connected. 34 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 1U1 3W1 5N1 3U1 5U1 5W1 5N1 5W1 5U1 2W1 2V1 2U1 1W1 1W1 1V1 1U1 3W1 5N1 3U1 5U1 5W1 Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector 1D1 (1C1) 1C1 (1D1) 1V1 1U1 1D1 (1C1) 1C1 (1D1) 3C 3D 3D X165 X166 X165_2 X177 X30_PAR X29_PAR X172 X300 X165 1D1 (1C1) 1C1 (1D1) X165 X166 X177 X165_2 Operating Instructions SIMOREG CCP (Slave) X165 1D1 (1C1) 1C1 (1D1) X166 X165 X165_2 X177 X30_PAR X29_PAR Warning: The triggering of the main contactors is not shown here; please refer to the connection suggestion in Section 6.2. 5) 2) NC Power supply X300 1D1 (1C1) 1C1 (1D1) ENGLISH for additional connections and settings for the SINAMICS DCM units, refer to the operating instructions of the SINAMICS DCM M 3.4) 3C 3.4) 3.2) 3.3) 3.4) 3C 3.2) 3.3) 3D 5) 1U1 3.1) 1V1 2) A7100 A7125 1C1 (1D1) 5) 1V1 1D1 (1C1) 2) 1W1 SINAMICS DCM (Slave) 1U1 3.2) 1W1 A7103 1V1 3.1) 2U1 SIMOREG CCP (Master) 2V1 A7100 A7125 2W1 SINAMICS DCM (Master) 5U1 A7103 1W1 SIMOREG CCP (Slave) 2U1 A7100 A7125 5W1 Armature 2V1 SINAMICS DCM (Slave) 5N1 Field 1) 2W1 A7103 5U1 Power supply 5W1 Power supply 5N1 Armature 3U1 Field NC 3W1 Power supply NC 1U1 Power supply 1) 1V1 Armature NC 1W1 Field NC 4) 5U1 Power supply 1) 4) 5W1 3) NC 4) 5N1 1) The same phase sequence is required between 1U1/1V1/1W1. 2) The same phase sequence is required between 1C1/1D1 3) Connecting cable: 3.1) Parallel connection of SINAMICS DCM units 3.2) Serial connection between the SINAMICS DCM unit - SIMOREG CCP 3.3) Turn-off pulse interface 3.4) Fast pulse cancellation interface 4) These fuses may only be used with units up to 850 A 5) Only for units up to 850 A 3 AC 380-460 V 50-60 Hz 3 AC 400-690 V 50-60 Hz 12.2010 Connecting X30_PAR X29_PAR X172 X172 X300 X165 35 Connecting 12.2010 6.3.3 Connecting the Firing Unit Trigger Board Routing of the connecting cable "fast pulse cancellation interface" to the SINAMICS DCM with shield support: 36 ① Firing Unit Trigger Board ② Connector X165_2 ③ Shield support ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 6.4 Connecting Fuses Fuses in the armature circuit and in the motor circuit Recommended Siemens semiconductor fuses (depending on the SIMOREG CCP used): Unit Order No. (MLFB) Rated current Rated voltage Fuses 1U1, 1V1, 1W1 Fuses 1C1, 1D1 6RA7085-6FC00-0 600 A 460 V 3NE3335 (560 A / 1000 V) 3NE7431-0C (350 A / 2000 V) 6RA7091-6FC00-0 1200 A 460 V 3NE3335 (560 A / 1000 V) 3NE7431-0C (350 A / 2000 V) 6RA7090-6KC00-0 1000 A 690 V 3NE3335 (560 A / 1000 V) 3NE7431-0C (350 A / 2000 V) 6RA7095-6FC00-0 2000 A 460 V 3NE3338-8 (800 A / 800 V) 3NE7648-1C (525 A / 2000 V) 6RA7095-6KC00-0 2000 A 690 V 3NE3338-8 (800 A / 800 V) 3NE7648-1C (525 A / 2000 V) Note It is no longer recommended to use the fuse types as listed in previous editions of the SIMOREG CCP operating instructions. Fuses for pre-charging 10 A line protection e.g. type Diazed 5SD604 Fuses F1 and F2 in the Power Interface Only UL-listed or UL-recognized fuses may be used in UL-listed units. Wickmann 198 1 A / 250 V 5 x 20 mm time-lag Wickmann 343 1 A / 250 V 6.3 x 32 mm time-lag Schurter FSD 1 A / 250 V 5 x 20 mm time-lag order designation 0034.3987 Schurter FST 1 A / 250 V 5 x 20 mm time-lag order designation 0034.3117 6.5 Arrangement of the terminals, connectors and fuses Module C98043-A7046 Power Interface SIMOREG CCP C98043-A7046 LED H1 F1 X165 S1 X172 X300 F2 X29_PAR X30_PAR 5U1 5W1 5N1 XP 56 57 58 59 60 Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 37 Connecting 6.6 12.2010 Terminal assignment, connectors WARNING If the unit is incorrectly connected, this can result in damage or destruction. The power cable or busbars must be mechanically fixed outside the unit. Power unit Terminal type: 600 A / 1000 A / 1200 A units Through hole for M10 (Cu - busbar 3x25) 2000 A units Through hole for M10 (Cu - busbar 5x40) The units are designed for a permanent line supply connection in accordance with DIN VDE 0160, Section 6.5.2.1. Protective conductor connection: Minimum cross-section 10 mm2. (Connection option, see Chapter 5.1) The connection cross-sections should be determined according to the applicable regulations e.g. DIN VDE 100 Part 523, DIN VDE 0276 Part 1000. The connection lengths should be determined according to the diagram in Chapter 6 – Connecting. Function Terminal Armature power input Connection values/Comments 1U1 1V1 1W1 see Technical data, Chapter 3.2 Protective conductor PE Armature circuit-motor connection 1C1 (1D1) 1D1 (1C1) Pre-charging, main contactor / circuit breaker Terminal strip WAGO 264-105 Conductor cross section AWG max. 2.5 mm2 max. 12 Stripped length 8 - 9 mm Function Connection Terminal X_SCHÜTZ Power connection, pre-charging 1 2 3 2U1 2V1 2W1 Control circuit for main contactor / circuit breaker 4 5 38 ENGLISH Connection values/Comments Cable cross-section 1.5 mm2 Fuse protection 10 A (see Chapter 6.4) Connection values the same as for the power unit SIMOREG CCP (see above) Wiring, main contactor/circuit breaker (see the recommended connection in Chapter 6.2) Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Connecting Electronics power supply Terminal type: plug-in terminal, type 49 maximum conductor cross-section 1.5 mm2 finely stranded Module C98043-A7046 Power Interface SIMOREG CCP Function Connection Infeed 400 V NC Terminal XP Connection values/Comments 1 2 3 5U1 5W1 5N1 2 AC 380 V (–20 %) to 460 V (+15 %); In=1 A internal fuse protection with F1, F2 on the C98043A7046 module (see Chapter 6.4) external fuse protection max. 6A, Characteristic C recommended 1 2 3 5U1 1 AC 190 V(–20 %) to 230 V (+15 %); In=2 A internal fuse protection with F1, F2 on the C98043A7046 module (see Chapter 6.4) external fuse protection max. 6 A, Characteristic C recommended or Infeed 230 V 5W1 5N1 Note For line supply voltages outside the tolerance range specified in Chapter 3.2, the electronic supply voltage must be adapted using transformers in order to comply with the value specified in Chapter 3.2. An isolation transformer is mandatory for rated line supply voltages exceeding 460 V. The rated supply voltage for the armature circuit should be set in parameter P078 (Index 001) or p50078[1]. Serial interface RS 485 Module C98043-A7046 Power Interface SIMOREG CCP Function Terminal X172 Connection values/Comments TX+ 56 RS485, 4-wire send cable, positive differential output TX- 57 RS485, 4-wire send cable, negative differential output RX+ 58 RS485, 4-wire receive cable, positive differential input RX- 59 RS485, 4-wire receive cable, negative differential input M 60 Ground max. cable length 600 m The following points must be noted: DIN 19245 Part 1 It is especially important that the voltage difference between the data reference potential M of all connections does not exceed -7 V/+12 V. Equipotential bonding must be implemented if this cannot be guaranteed. Activating the serial interface by setting the protocol at parameter P790 or p50790. Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 39 Connecting 12.2010 Connecting to a SIMOREG DC-MASTER: 56 57 58 59 60 56 57 58 59 60 X172 MINI-COMBICON X172 MINI-COMBICON Connecting to a SINAMICS DCM: SIMOREG CPP SINAMICS DCM TX+ TXRX+ RXM 37 56 38 57 39 58 40 59 36 60 TX+ TXRX+ RXM X-172 MINI COMBICON X-177 Connector Board Programming interface for the software update X300 Serial interface RS232 9-pin SUBMIN D socket Module C98043-A7046 Power Interface SIMOREG CCP Connector pin X300 Function 2 Receive cable, RS232 standard (V.24) 5 Ground 7 Send cable, RS232 standard (V.24) Cable: 1 1 6 6 2 2 7 7 3 3 8 8 4 4 9 9 5 5 X300 1 2 RxD (RS232) 3 Rx+/Tx+ (RS 485) 4 5 Ground 6 +5V (OP1S) 7 Tx D (RS232) 8 Rx-/ Tx- (RS485) 9 Ground 6RA70 X300 connector PC COMx socket Use a shielded connecting cable. Ground the shield at both ends. Additional connectors Module C98043-A7046 Power Interface SIMOREG CCP Connector Function X165 "Output pulse inhibit": Used when connecting several SINAMICS DCM in parallel X29_PAR Pulse turnoff interface to the parallel connection of SIMOREG CCPs The two connectors are connected in parallel. X30_PAR 40 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 7 Commissioning Commissioning CAUTION The operator must be electrostatically discharged before coming into contact with modules in order to protect electronic components against high voltages caused by electrostatic charge. The easiest way to do this is to touch a conductive, grounded object immediately beforehand (for example, the bare metal part of a control cabinet). It is not permissible that modules come into contact with highly insulating materials (e.g. plastic foils, insulating desktops, articles of clothing manufactured out of man-made fibers). Modules may be set down only on conducting work surfaces. WARNING The unit is at a hazardous voltage. Failure to comply with these operating instructions can lead to death, serious physical injury, and material damage. The units may be connected to a line supply with a residual current operated circuit breaker if a universal current sensitive device is being used, which in the case of a ground fault, can also detect a DC component in the fault current. It is recommended to use a residual current operated circuit breaker with a response current ≥300 mA, which means that it is not suitable for protecting personnel. If you have additional questions, please contact Technical Support. Only qualified personnel who are familiar with all of the safety instructions in this description, as well as the assembly, installation, operating, and maintenance instructions, should carry out work on these units. The successful and safe operation of this equipment is dependent on proper transportation, storage, installation, and assembly, as well as on careful operation and maintenance. The unit is at dangerous voltage levels even when the converter unit line contactor is open. Before commencing any maintenance or service work, disconnect all power sources of the converter infeed and lock them out so that they cannot be accidentally reconnected. These instructions are not exhaustive and, as such, cannot outline all the measures required in order to operate the unit safely. Where necessary, additional information or instructions may be required for special applications. If you encounter specific problems that have not been handled in enough detail for the purposes of the buyer, then please contact your local Siemens office. The use of non-approved parts for carrying out repair work on the unit or handling of the unit by inadequately qualified personnel will result in dangerous conditions with the risk of death, serious physical injury, or extensive damage to equipment. All safety measures listed in these operating instructions, as well as all warning signs attached to the unit, must be followed. Observe all the warning information outlined in Chapter 1 of these operating instructions. Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 41 Commissioning 7.1 12.2010 Operation via the basic unit (SIMOREG DC-MASTER or SINAMICS DCM) The basic converter unit has setting and monitoring parameters for commissioning, operation, monitoring and diagnostics of the SIMOREG CCP. The state of the SIMOREG CCP is signaled via connectors and the triggering of the SIMOREG CCP or erroneous states are signaled using fault and alarm messages. Data is exchanged between the basic converter unit and SIMOREG CCP via the serial interface. 7.1.1 SIMOREG DC-MASTER parameters (see below for a detailed description) P790 *) Protocol selection for the basic converter interface G-SST2 r799 *) Diagnostics information for G-SST2 r812 *) Receive data at G-SST2 n560 Software version of the SIMOREG CCP n569 Serial number of the SIMOREG CCP n570 MLFB (Order No.) of the SIMOREG CCP n571 Rated supply voltage of the SIMOREG CCP n572 Rated current of the SIMOREG CCP n574 State of the SIMOREG CCP n575 Display of the I2t value of the voltage limiting choppers 1 of the SIMOREG CCP n576 Display of the I2t value of the voltage limiting choppers 2 of the SIMOREG CCP U577 Voltage setpoint for the upper response threshold of the SIMOREG CCP chopper U578 Voltage setpoint for the pre-charging of the SIMOREG CCP quenching capacitors U580 Control word for commutation monitoring U581 Diagnostics memory for the commutation monitoring U582 Response of the commutation monitoring U583 Test command for the SIMOREG CCP *) For a description of these parameters, see the operating instructions SIMOREG DC-MASTER Chapter 11 Detailed description of parameters The specified software release refers to the software release of the SIMOREG DC-MASTER PNU Description n560 (2560) Software version of the SIMOREG CCP n569 (2569) Value range [dimension] Graduation [from SW 2.1 and higher] i001: Version release of the SIMOREG CCP software i002: Version release of the SIMOREG CCP software, boot sector Serial number of the SIMOREG CCP [from SW 2.1 and higher] No. of indices Factory setting (FS) Type Ind: 2 Type: O2 See/ change (Access / state) Ind: 16 Type: L2 P052 = 3 250 to 254 1 Ind: None Type: O2 P052 = 3 10 to 830 [V] 1V Ind: None Type: O2 P052 = 3 0.0 to 9.9 0,1 i001: 1. and 2nd position of the serial number i002: 3. and 4th position of the serial number i003: 5. and 6th position of the serial number i004: 7. and 8th position of the serial number i005: 9. and 10th position of the serial number i006: 11. and 12th position of the serial number i007: 13. and 14th position of the serial number i008 to i015: 0 i016: Checksum of the serial number P052 = 3 The ASCII-Code of the serial number can be read from this parameter. n570 (2570) MLFB (Order No.) of the SIMOREG CCP n571 (2571) Rated supply voltage of the SIMOREG CCP 42 [from SW 2.1 and higher] Here, the coding of the corresponding MLFB is displayed. [from SW 2.1 and higher] Rated supply voltage of the SIMOREG CCP stamped on the rating plate ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Commissioning PNU Description Value range [dimension] Graduation n572 (2572) Rated current of the SIMOREG CCP n574 (2574) State of the SIMOREG CCP [from SW 2.1 and higher] Rated current of the SIMOREG CCP stamped on the rating plate 0.0 to 6553.5 [A] 0.1A [from SW 2.2 and higher] Display at the operator panel (PMU): 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 No. of indices Factory setting (FS) Type Ind: None Type: O2 See/ change (Access / state) Ind: None Type: V2 P052 = 3 Ind: None Type: O2 P052 = 3 Ind: None Type: O2 P052 = 3 P052 = 3 Segment lit or bit = 1: significance specified below applies Segment dark or bit = 0: significance specified below does not apply Segment or bit 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Voltage at U, V, W is OK Voltage at C – D greater than +100 V Voltage at C – D less than -100 V The quenching capacitors have reached the setpoint voltage Turn-off operation running Connection between parallel SIMOREG CCP OK Parallel interface connected at CCP I2t value of voltage limiting chopper 1 is too high I2t value of voltage limiting chopper 2 is too high Contents of the memory of the technical data of the SIMOREG CCP (MLFB, rated values, serial number) valid Pre-charging of the chopper capacitors completed - n575 (2575) Note: This parameter has the same bit assignment as connector K0574. Display of the I2t value [from SW 2.1] of the voltage limitingchoppers 1 of the SIMOREG CCP n576 (2576) Display of the I2t value of the voltage limitingchoppers 2 of the SIMOREG CCP Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector [from SW 2.1] 0 to 100 [%] 1% 0 to 100 [%] 1% ENGLISH Operating Instructions 43 Commissioning 12.2010 PNU Description Value range [dimension] Graduation U577 (2577) Voltage setpoint for the upper response threshold of the SIMOREG CCP chopper [from SW 2.2 and higher] 850 to 1600 [V] 1V The set voltage value defines the upper response threshold of the voltage limiter implemented in the SIMOREG CCP. Within the scope of the turn-off operation of the CCP, this limits the counter-voltage that occurs - which is also necessary - when the armature current is reduced to a value that is not dangerous for the basic unit and the associated SIMOREG CCP. The required setting value depends on the blocking voltage strength of the power semiconductors used in the basic converter (SIMOREG DCMASTER) and in the SIMOREG CCP and is therefore dependent on the Unit MLFB. The following table should be used to correctly set this parameter. No. of indices Factory setting (FS) Type Ind: None FS=1600 Type: O2 See/ change (Access / state) P052 = 3 P051 = 40 online As a result of the unit MLFB for the basic converter and SIMOREG CCP, two setting values are obtained from which the lower of the two should be set at U577. Example: Basic converter MLFB: 6RA7085-6DV62-0 (r070=9) ⇒ U577=1300 V SIMOREG CCP MLFB: 6RA7085-6FC00-0 (n570=250) ⇒ U577=1100 V therefore the following setting is obtained: U577=1100 V Table to determine the setting value for U577: MLFB SIMOREG DC-MASTER 6RA7013-6DV62-0 6RA7018-6DV62-0 6RA7025-6DV62-0 6RA7028-6DV62-0 6RA7031-6DV62-0 6RA7075-6DV62-0 6RA7078-6DV62-0 6RA7081-6DV62-0 6RA7085-6DV62-0 6RA7087-6DV62-0 6RA7091-6DV62-0 6RA7093-4DV62-0 6RA7095-4DV62-0 6RA7025-6GV62-0 6RA7031-6GV62-0 6RA7075-6GV62-0 6RA7081-6GV62-0 6RA7085-6GV62-0 6RA7087-6GV62-0 6RA7090-6GV62-0 6RA7093-4GV62-0 6RA7095-4GV62-0 6RA7086-6KV62-0 6RA7090-6KV62-0 6RA7093-4KV62-0 6RA7095-4KV62-0 6RA7088-6LV62-0 6RA7093-4LV62-0 6RA7095-4LV62-0 6RA7018-6DS22-0 6RA7025-6DS22-0 6RA7028-6DS22-0 6RA7031-6DS22-0 6RA7075-6DS22-0 6RA7078-6DS22-0 6RA7081-6DS22-0 6RA7085-6DS22-0 6RA7087-6DS22-0 6RA7091-6DS22-0 6RA7093-4DS22-0 6RA7095-4DS22-0 44 ENGLISH MLFB characteristic number (r070) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 Setting value for U577 [V] 1300 1300 1300 1300 1300 1300 1300 1300 1300 1300 1300 1500 1500 1700 1700 1700 1700 1700 1700 1700 1700 1700 2100 2100 2100 2100 2500 2500 2500 1300 1300 1300 1300 1300 1300 1300 1300 1300 1300 1500 1500 Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 PNU Commissioning Description 6RA7025-6GS22-0 6RA7031-6GS22-0 6RA7075-6GS22-0 6RA7081-6GS22-0 6RA7085-6GS22-0 6RA7087-6GS22-0 6RA7090-6GS22-0 6RA7093-4GS22-0 6RA7095-4GS22-0 6RA7086-6KS22-0 6RA7088-6KS22-0 6RA7093-4KS22-0 6RA7095-4KS22-0 6RA7088-6LS22-0 6RA7093-4LS22-0 6RA7095-4LS22-0 6RA7096-4GV62-0 6RA7096-4GS22-0 6RA7000-0MV62-0 6RA7095-4GS22-5 6RA7095-4KS22-5 6RA7095-4LS22-5 6RA7096-4GS22-5 6RA7018-6FV62-0 6RA7025-6FV62-0 6RA7028-6FV62-0 6RA7031-6FV62-0 6RA7075-6FV62-0 6RA7078-6FV62-0 6RA7082-6FV62-0 6RA7085-6FV62-0 6RA7087-6FV62-0 6RA7091-6FV62-0 6RA7018-6FS22-0 6RA7025-6FS22-0 6RA7028-6FS22-0 6RA7031-6FS22-0 6RA7075-6FS22-0 6RA7078-6FS22-0 6RA7082-6FS22-0 6RA7085-6FS22-0 6RA7087-6FS22-0 6RA7091-6FS22-0 6RA7098-4DV62-0 6RA7097-4GV62-0 6RA7097-4KV62-0 6RA7096-4MV62-0 6RA7098-4DS22-0 6RA7097-4GS22-0 6RA7097-4KS22-0 6RA7096-4MS22-0 6RA7095-4MV62-0 MLFB SIMOREG CCP 6RA7085-6FC00-0 6RA7091-6FC00-0 6RA7095-6FC00-0 6RA7090-6KC00-0 6RA7095-6KC00-0 Value range [dimension] Graduation 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 96 97 98 99 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 MLFB characteristic number (n570) 250 251 252 253 254 No. of indices Factory setting (FS) Type See/ change (Access / state) 1700 1700 1700 1700 1700 1700 1700 1700 1700 2100 2100 2100 2100 2500 2500 2500 1700 1700 2900 1700 2100 2500 1700 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1700 2100 2100 1500 1700 2100 2900 2900 Setting value for U577 [V] 1100 1100 1100 1600 1600 Note: The setting value for U577 according to the table above defines the maximum permissible value of the voltage limit for the particular unit. Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 45 Commissioning 12.2010 PNU Description Value range [dimension] Graduation U578 (2578) Voltage setpoint for the pre-charging of the SIMOREG CCP quenching capacitors [from SW 2.2] 145 to 830 [V] 1V To successfully turn off the thyristors, the set voltage value defines the minimum charge voltage required for the quenching capacitors in the SIMOREG CCP. This value is used as setpoint for the two-level controller, which precharges the quenching capacitors from the line supply. The maximum pre-charging voltage that can be reached is limited by the average rectified value of the line supply voltage that is connected (minimum value according to the lower tolerance limit as defined by P351). No. of indices Factory setting (FS) Type Ind: None FS=145 Type: O2 See/ change (Access / state) P052 = 3 P051 = 40 online The value to be set at the parameter U578 should be determined as follows using the characteristic diagrams provided in the Appendix of these operating instructions. To start, the number of the associated characteristic diagram is selected from the following table for the SIMOREG CCP being used (MLFB according to parameter n570 or according to the rating plate) and for the rated armature voltage of the motor according to parameter P101. MLFB SIMOREG CCP 6RA7085-6FC00-0 MLFB characteristic number (n570) 250 6RA7091-6FC00-0 251 6RA7095-6FC00-0 252 6RA7090-6KC00-0 253 6RA7095-6KC00-0 254 P101 [V] No. of the associated characteristic diagram 420 470 420 470 420 470 520 600 720 520 600 720 1, 1A 2, 2A 3, 3A 4, 4A 5, 5A 6, 6A 7.0, 7.0A 7, 7A 8, 8A 9.0, 9.0A 9, 9A 10, 10A Then, for the specified values of P111 and r072i002, a search is made for the associated voltage value in the characteristic diagram. Below is an example for determining U578 for n570 P101 P111 r072i002 = 6RA7091-6FC00-0 (characteristic number = 251) = 470 V = 0.23 mH = 890,0 A According to n570 and r071 characteristic diagram 4 (4A) should be used. As abscissa value, as an approximation, instead of P111 = 0.23 mH the next lower grid value of 0.22 mH is used. For r072i002 = 890.0 A, a linear interpolation is made in the associated current range 800 A to 900 A. The next higher ordinate grid value for 380 V is used here as an approximation. As a consequence, U578 = 380 V should be set. If the armature circuit inductance according to P111 exceeds the value range shown in the characteristic diagram, then the value should be determined for the maximum value of P111 that is shown. Depending on the values of P111 and r072i002, the voltage value being searched for can lie outside the upper or lower limit shown in the characteristic diagram. The upper limit shown in the characteristic diagram is valid for a value of P351 = -20 % of P078i001 (according to the factory setting). The following upper limit applies for a value of P351 that deviates from the factory setting: ⎛ P351 ⎞ ⎟ 1.35 ∗ P078.001 ∗ ⎜⎜1 + 100 % ⎟⎠ ⎝ Upper limit = 1.073 46 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 PNU Commissioning Description Value range [dimension] Graduation No. of indices Factory setting (FS) Type See/ change (Access / state) 0 to 7 1 Ind: None FS=7 Type: O2 P052 = 3 P051 = 40 online 0 to 65536 1 Ind: 68 Type: O2 P052 = 3 The following situations can occur: Determined voltage value < 145 V (lower limit in the characteristic diagram): U578 = 145 V should be set. The successful turn-off operation by the SIMOREG CCP is assured in all situations, however, the voltage load (or torque increase) of the motor that can briefly occur for a turn-off operation is higher than necessary. Determined voltage value lies between the lower limit (145 V) and the upper limit: The voltage value determined should be set at U578. The successful turn-off operation by the SIMOREG CCP is assured in all situations. Determined voltage value > upper limit: Operation involving the basic converter - SIMOREG CCP combination is not permissible. The successful turn-off operation by the SIMOREG CCP is not assured. This problem may be able to be resolved by contacting the manufacturer. Note: When communications are established between the basic converter and SIMOREG CCP (P790=6), then the setpoint according to U578 in the SIMOREG CCP is set using its operating firmware. If the selected setpoint cannot be reached due to the fact that the actual line supply voltage is too low, for operating states < 4.0, the basic converter outputs Alarm A032 followed by Fault F032 (fault value 3) - to signal that the required charge voltage has not been achieved. If, after commissioning, one of the relevant system parameters changes, then the correct setting of U578 should be checked and, if required, it should be appropriately set again. U580 (2580) Control word for commutation monitoring [from SW 2.1 and higher] Converter commutation is permanently monitored. Fault message F030 is output when a commutation fault is detected and the SIMOREG CCP (if being used) initiates that the thyristors are turned off. Detecting a commutation fault is based on 3 criteria. Using this parameter, these can be individually activated/deactivated for test purposes. 0: 1: 2: 4: None of the 3 decision-making criteria is evaluated Decision-making criterion 1 (adequate voltage-time integral for the commutation) is evaluated Decision-making criterion 2 (curvature of the current cusp) is evaluated Decision-making criterion 3 (magnitude of the current actual value) is evaluated Setting note: Each decision-making criterion is coded using a number. If several decision-making criteria are to be evaluated, then the sum of the corresponding numbers should be set. If U806 ≥ 2 (this means that the basic converter is a slave connected in parallel), then decision-making criterion 1, is not evaluated independent of the setting of U580. U581 (2581) Diagnostics memory for the commutation monitoring [from SW 2.1 and higher] This memory is updated each time that fault message F030 is output. It includes more detailed information about the cause of the commutation fault, which can be evaluated by Siemens experts. Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 47 Commissioning 12.2010 PNU Description Value range [dimension] Graduation U582 (2582) Response of the commutation monitoring [from SW 2.1 and higher] This parameter can be used to define the response of the commutation monitoring. 1 After a commutation fault or an overcurrent condition has been detected, this results in an immediate pulse cancellation and Alarm message A030 is output. The pulses are enabled again after approx. 20 ms and alarm message A030 disappears. 2 After a commutation fault or an overcurrent condition has been detected, this results in an immediate pulse cancellation and fault message F030 is output. 1 to 2 1 No. of indices Factory setting (FS) Type Ind: None FS=2 Type: O2 See/ change (Access / state) P052 = 3 P051 = 40 online Ind: None FS = 0 Type: O2 P052 = 3 P051 = 40 online Notice: The setting U582=1 is not permissible for a selected SIMOREG CCP (P790=6)! U583 (2583) [from SW 2.2 and higher] Test command for the SIMOREG CCP This parameter can be used to issue a turn-off command to the SIMOREG CCP for test purposes. 0 No turn-off command is issued 1 A turn-off command is issued in MI 2 A turn-off command is issued in MII After issuing a single turn-off command to the SIMOREG CCP, this parameter automatically sets itself back to the value 0! 0 to 2 1 Note: If the test command is issued while operational (i.e. in operating states I and II), then the basic converter defines the torque direction required to select the correct test command. In the operating state, torque direction 0 (--) the test command is issued in torque direction I. 7.1.2 SINAMICS DCM parameters (see below for a detailed description) r50047[0..31] r50071 p50790 p50795 p50797 r50799[0..8] r51560[0..1] r51569[0...15] r51570 r51571 r51572 r51574.0...12 r51575 r51576 p51577 p51578 r51579.0...7 p51580 p51583 48 Faults, supplementary information Rated unit supply voltage for armature P2P interface operating mode P2P/CCP bus termination P2P interface telegram monitoring time P2P/CCP diagnostics CCP software version CCP serial number CCP order number CCP rated supply voltage CCP rated current CO/BO: CCP state CO: CCP I2t value voltage limiting chopper 1 CO: CCP I2t value voltage limiting chopper 2 CCP chopper voltage setpoint, upper response threshold CCP quenching capacitor pre-charging voltage setpoint CO/BO: CCP command Commutation monitoring, control word CCP test turn-off command ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Commissioning Detailed description of parameters PNU Description Value range [dimension] Graduation r50047 [0...31] Faults, additional information/fault addit. info 1 1 Description: Display of additional information on faults that have occurred with numbers from 60000 and higher. Access level [Vrms] - Ind: None - 1 0 to 6 1 1 Ind: None FS = 0 2 0 to 1 1 1 Ind: None FS = 0 2 1 [0] = [1] = r50071 fault value additional information on the last fault that occurred (refer to the corresponding fault) ... [30] = additional information on the last fault that occurred (refer to the corresponding fault) [31] = fault number Rated unit supply voltage armature / Unit Va_rated No. of indices Factory setting (FS) Ind: 32 - Description: Displays the unit rated supply voltage for the armature according to the rating plate of the unit. p50790 P2P interface operating mode / P2P operating mode Description: Sets the operating mode for the peer-to-peer interface (P2P interface). Value: 0: No function 5: Peer-to-peer communication 6: Communication with SIMOREG CCP Note: Correct communication is optically displayed using an LED on the Power Interface module C98043-A7046: LED flashes slowly (<1 Hz): Communication with SINAMICS DCM OK LED flashes quickly (~3 Hz): Communication error with SIMOREG CCP p50795 P2P/CCP bus termination / P2P/CCP bus term. Description: Sets the bus termination for the peer-to-peer interface and the interface to the SIMOREG CCP. Value: 0: off 1: on Note: CCP: Converter Commutation Protector P2P: Peer-to-peer interface Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 49 Commissioning 12.2010 PNU Description Value range [dimension] Graduation p50797 P2P interface telegram monitoring time / P2P t_tel_monit 0 to 65 [s] 0.01 s Description: Sets the telegram monitoring time for the peer-to-peer interface (P2P interface). The set time is only effective in the "peer-to-peer interface" operating mode (p50790 = 5). No. of indices Factory setting (FS) Ind: None FS = 0 Access level 0 to 65534 1 1 Ind: 9 - 1 - Ind: 2 - 3 2 p50797 = 0: Monitoring is disabled. p50797 > 0: Monitoring is enabled. Within the set time, after a valid telegram has been received, the next valid telegram must be received. Otherwise, Fault F60012 is output. Dependency: See also: F60012 Note: Telegram monitoring is activated in the following cases: - From the reception of the first error-free telegram. - After the electronics power supply has been switched-on. - From the reception of the first error-free telegram after the telegram monitoring responds (when the telegram monitoring time expires timeout). The telegram monitoring time (p50797) is dependent on the selected baud rate (p50793). For safe, reliable operation, the following minimum setting values are recommended: - 300 Baud → p50797 = 0.520 s (recommended minimum value) - 600 Baud → p50797 = 0.260 s (recommended minimum value) - 1200 Baud → p50797 = 0.140 s (recommended minimum value) - 2400 Baud → p50797 = 0.080 s (recommended minimum value) - 4800 Baud → p50797 = 0.040 s (recommended minimum value) If, for the peer-to-peer communication partner, the "automatic restart" function (p50086 > 0) is selected, then only the parameterization p50797 > p50086 (of the communication partner) makes sense. r50799 [0...8] P2P/CCP diagnostics / P2P/CCP diag Description: Displays the diagnostics information for the peer-to-peer interface and the interface to the SIMOREG CCP. Index: [0] = number of error-free telegrams [1] = number telegrams with error [2] = number of byte frame errors [3] = number of overrun errors [4] = number of parity errors [5] = number of STX errors [6] = number of block check errors [7] = number of break errors [8] = number of timeout errors Note: The error frequency is detected using free-running counters and when 65535 is reached, the particular counter is reset to 0. For communication with SIMOREG CCP (p50790 = 6) the diagnostics information in indices 5, 6 and 8 has no significance. Possible error causes for STX errors: - The start pause before STX was not maintained. - STX error, i.e. not equal to 02. Possible error cause for timeout errors: - The telegram monitoring interval has expired (p50797). r51560 [0...1] CCP software version / CCP SW version Description: Displays the software version for the Converter Communication Protector (CCP). Index: [0] = version release of the CCP software [1] = version release of the software of the CCP boot sector 50 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Commissioning PNU Description Value range [dimension] Graduation r51569 [0...15] CCP serial number / CCP serial No. 0 to 255 1 1 Description: Displays the serial number of the Converter Commutation Protector (CCP). Note: The individual characters of the number are displayed in the ASCII code in the indices. An ASCII table (excerpt) can be found in the Appendix of the List Manual for example. r51570 CCP order number / CCP Order No. Description: Displays the order number (MLFB) of the connected Converter Commutation Protector (CCP). No. of indices Factory setting (FS) Ind: 16 - Access level 0 to 254 1 1 Ind: None - 3 [V] - Ind: None - 3 [A] - Ind: None - 3 1 1 Ind: None - 3 [%] - Ind: None - 3 [%] - Ind: None - 3 3 Value: 0: No CCP connected 250: 6RA7085-6FC00-0 251: 6RA7091-6FC00-0 252: 6RA7095-6FC00-0 253: 6RA7090-6KC00-0 254: 6RA7095-6KC00-0 r51571 CCP rated supply voltage / CCP V_rated Description: Displays the rated supply voltage according to the rating plate of the Converter Communication Protector (CCP). r51572 CCP rated current / CCP I_rated Description: Displays the rated current according to the rating plate of the Converter Communication Protector (CCP). r51574. 0...12 CO/BO: CCP state/ CCP state Description: Displays the connector output for the state of the Converter Communication Protector (CCP). Bit array Bit 00 Bit 01 Bit 02 Bit 03 r51575 Signal name 1 signal Voltage at U, V, W ok. Yes Voltage at C - D higher than +100 V Yes Voltage at C - D less than -100 V Yes Quenching capacitors have reached their Yes setpoint voltage Bit 04 Turn-off operation running Yes Bit 05 Connection between parallel CCP ok. Yes Bit 08 Connector X165_2 (at the DCM) is connected Yes with X165 (at the CCP) Bit 09 I2t value voltage limiting chopper 1 too high Yes Bit 10 I2t value voltage limiting chopper 2 too high Yes Bit 11 Memory for technical data for the CCP ok. Yes Bit 12 Chopper capacitors pre-charging completed Yes CO: CCP I2t value voltage limiting chopper 1 / CCP I2t chopper 1 Description: Displays the I2t value for voltage limiting chopper 1 for the Converter Commutation Protector (CCP). r51576 CO: CCP I2t value voltage limiting chopper 2 / CCP I2t chopper 2 Description: Displays the I2t value for voltage limiting chopper 2 for the Converter Commutation Protector (CCP). Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector 0 signal No No No No No No No No No No No ENGLISH Operating Instructions 51 Commissioning 12.2010 PNU Description Value range [dimension] Graduation p51577 CCP chopper voltage setpoint, upper response threshold / CCP V_set thresh up 850 to 2900 [V] 1V No. of indices Factory setting (FS) Ind: None FS=1600 Access level 3 Description: Sets the upper response threshold of the voltage limiter implemented in the CCP. Within the scope of the turn-off operation of the CCP, this limits the counter-voltage - which is also necessary - that occurs when the armature current is reduced to a value that is not dangerous for the basic converter unit and the associated CCP. Note: CCP: Converter Commutation Protector The parameter is automatically set for the "Optimization run for CCP" (p50051 = 30). The following table should be used to correctly set this parameter. As a result of the unit MLFB for the basic converter unit and SIMOREG CCP, two setting values are obtained from which the lower of the two should be set at p51577. Example: Basic converter unit MLFB: 6RA8085-6DV62-0 p51577=1300 V SIMOREG CCP MLFB: 6RA7085-6FC00-0 p51577=1100 V therefore the following setting is obtained: p51577=1100 V Table to determine the setting value for p51577: MLFB SINAMICS DCM 6RA8013-6DV62-0AA0 6RA8018-6DV62-0AA0 6RA8025-6DV62-0AA0 6RA8028-6DV62-0AA0 6RA8031-6DV62-0AA0 6RA8075-6DV62-0AA0 6RA8078-6DV62-0AA0 6RA8081-6DV62-0AA0 6RA8085-6DV62-0AA0 6RA8087-6DV62-0AA0 6RA8091-6DV62-0AA0 6RA8093-4DV62-0AA0 6RA8095-4DV62-0AA0 6RA8098-4DV62-0AA0 6RA8013-6FV62-0AA0 6RA8018-6FV62-0AA0 6RA8025-6FV62-0AA0 6RA8028-6FV62-0AA0 6RA8031-6FV62-0AA0 6RA8075-6FV62-0AA0 6RA8078-6FV62-0AA0 6RA8082-6FV62-0AA0 6RA8085-6FV62-0AA0 6RA8087-6FV62-0AA0 6RA8091-6FV62-0AA0 6RA8025-6GV62-0AA0 6RA8031-6GV62-0AA0 6RA8075-6GV62-0AA0 6RA8081-6GV62-0AA0 6RA8085-6GV62-0AA0 6RA8087-6GV62-0AA0 6RA8090-6GV62-0AA0 6RA8093-4GV62-0AA0 6RA8095-4GV62-0AA0 6RA8096-4GV62-0AA0 6RA8097-4GV62-0AA0 6RA8086-6KV62-0AA0 6RA8090-6KV62-0AA0 6RA8093-4KV62-0AA0 6RA8095-4KV62-0AA0 6RA8097-4KV62-0AA0 6RA8088-6LV62-0AA0 6RA8093-4LV62-0AA0 6RA8095-4LV62-0AA0 6RA8096-4MV62-0AA0 52 ENGLISH Setting value for p51577 [V] 1300 1300 1300 1300 1300 1300 1300 1300 1300 1300 1300 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 2100 2100 2100 2100 2100 2500 2500 2500 2900 Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 PNU Commissioning Description 6RA8025-6DS22-0AA0 6RA8028-6DS22-0AA0 6RA8031-6DS22-0AA0 6RA8075-6DS22-0AA0 6RA8078-6DS22-0AA0 6RA8081-6DS22-0AA0 6RA8085-6DS22-0AA0 6RA8087-6DS22-0AA0 6RA8091-6DS22-0AA0 6RA8093-4DS22-0AA0 6RA8095-4DS22-0AA0 6RA8098-4DS22-0AA0 6RA8025-6FS22-0AA0 6RA8028-6FS22-0AA0 6RA8031-6FS22-0AA0 6RA8075-6FS22-0AA0 6RA8078-6FS22-0AA0 6RA8082-6FS22-0AA0 6RA8085-6FS22-0AA0 6RA8087-6FS22-0AA0 6RA8091-6FS22-0AA0 6RA8025-6GS22-0AA0 6RA8031-6GS22-0AA0 6RA8075-6GS22-0AA0 6RA8081-6GS22-0AA0 6RA8085-6GS22-0AA0 6RA8087-6GS22-0AA0 6RA8090-6GS22-0AA0 6RA8093-4GS22-0AA0 6RA8095-4GS22-0AA0 6RA8096-4GS22-0AA0 6RA8097-4GS22-0AA0 6RA8086-6KS22-0AA0 6RA8090-6KS22-0AA0 6RA8093-4KS22-0AA0 6RA8095-4KS22-0AA0 6RA8097-4KS22-0AA0 6RA8088-6LS22-0AA0 6RA8093-4LS22-0AA0 6RA8095-4LS22-0AA0 6RA8096-4MS22-0AA0 MLFB SIMOREG CCP Value range [dimension] Graduation No. of indices Factory setting (FS) Access level 145 to 830 [V] 1V Ind: None FS=145 3 1300 1300 1300 1300 1300 1300 1300 1300 1300 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1500 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 1700 2100 2100 2100 2100 2100 2500 2500 2500 2900 Setting value for p51577 [V] 6RA7085-6FC00-0 6RA7091-6FC00-0 6RA7095-6FC00-0 6RA7090-6KC00-0 6RA7095-6KC00-0 1100 1100 1100 1600 1600 Note: The setting value for p51577, according to the table above, defines the maximum permissible value of the voltage limit for the particular unit. p51578 CCP quenching capacitor pre-charging voltage setpoint / C pre-charging V_set Description: Setting of the minimum required charge voltage of the quenching capacitors in the CCP for successful thyristor turn-off. This value is used as setpoint for the two-level controller, which precharges the quenching capacitors from the line supply. The maximum pre-charging voltage that can be reached is limited by the rectified average value of the line supply voltage that is connected. Note: CCP: Converter Commutation Protector The parameter is automatically set for the "Optimization run for CCP" (p50051 = 30). The correct setting for this parameter can be taken from the following reference: SIMOREG CCP operating instructions Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 53 Commissioning PNU 12.2010 Description Value range [dimension] Graduation MLFB SIMOREG CCP p50101 [V] 6RA7085-6FC00-0 420 470 420 470 420 470 520 600 720 520 600 720 6RA7091-6FC00-0 6RA7095-6FC00-0 6RA7090-6KC00-0 6RA7095-6KC00-0 No. of indices Factory setting (FS) Access level No. of the associated characteristic diagram 1, 1A 2, 2A 3, 3A 4, 4A 5, 5A 6, 6A 7.0, 7.0A 7, 7A 8, 8A 9.0, 9.0A 9, 9A 10, 10A Then, for the specified values of p50111 and r50072[1], a search is made for the associated voltage value in the characteristic diagram. Below is an example for determining p51578 for p51570 p50101 p50111 r50072[1] = 6RA7091-6FC00-0 = 470 V = 0.23 mH = 890,0 A According to p51570 and r50071, characteristic diagram 4 (4A) should be used. As abscissa value, the next lower grid value of 0.22 mH is used as an approximation, instead of P50111 = 0.23 mH. For r50072[1] = 890.0 A, a linear interpolation is made in the associated current range 800 A to 900 A. The next higher ordinate grid value for 380 V is used here as an approximation. As a consequence, p51578 = 380 V should be set. If the armature circuit inductance according to p50111 exceeds the value range shown in the characteristic diagram, then the value should be determined for the maximum value of p50111 that is shown. Depending on the values of p50111 and r50072[1], the voltage value being searched for can lie outside the upper or lower limit shown in the characteristic diagram. The upper limit shown in the characteristic diagram is valid for a value of p50351 = -20 % of p50078[0] (according to the factory setting). The following upper limit applies for a value of p50351 that deviates from the factory setting: ⎛ p50351 ⎞ ⎟ 1.35 ∗ p50078[0] ∗ ⎜⎜1 + 100 % ⎟⎠ ⎝ Upper limit = 1.073 54 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 PNU Commissioning Description Value range [dimension] Graduation No. of indices Factory setting (FS) Access level 0 to 255 1 1 Ind: None - 3 0 to 7 1 1 Ind: None FS = 7 3 The following situations can occur: Determined voltage value < 145 V (lower limit in the characteristic diagram): p51578 = 145 V should be set. The successful turn-off operation by the SIMOREG CCP is assured in all situations, however, the voltage load (or torque increase) of the motor that can briefly occur for a turn-off operation is higher than necessary. Determined voltage value lies between the lower limit (145 V) and the upper limit: The voltage value determined should be set at p51578. The successful turn-off operation by the SIMOREG CCP is assured in all situations. Determined voltage value > upper limit: Operation involving the basic converter unit - SIMOREG CCP combination is not permissible. The successful turn-off operation by the SIMOREG CCP is not assured. This problem may be able to be resolved by contacting the manufacturer. Note: When communications are established between the basic converter unit and SIMOREG CCP (p50790=6), then the setpoint according to p51578 in the SIMOREG CCP is set using its operating firmware. If the selected setpoint cannot be reached due to the fact that the actual line supply voltage is too low, for operating states < 4.0, the basic converter outputs Alarm A60321 - followed by Fault F60320 (fault value 3) - to signal that the required charge voltage has not been achieved. If one of the relevant system parameters changes after commissioning, then the correct setting of p51578 should be checked, and if required, it should be appropriately set again. r51579. 0...7 CO/BO: CCP command/ CCP command Description: Display and connector output for the commands from the SINAMICS DCM to the SIMOREG CCP. Bit array Bit 00 Bit 01 Bit 02 Signal name Fire turn-off thyristors Line supply voltage (armature) in the tolerance range CCP connected to the parallel switching master Main contactor CLOSE Torque direction I active Torque direction II active Reserved (always 1) Reserved (always 1) Bit 03 Bit 04 Bit 05 Bit 06 Bit 07 Note: CCP: Converter Commutation Protector p51580 1 signal Yes Yes 0 signal No No Yes No Yes Yes Yes Yes Yes No No No No No Commutation monitoring control word / commut_monit STW Description: Setting of the criterion to detect a commutation fault for the commutation monitoring. Bit array Bit 00 Bit 01 Bit 02 Signal name Use criterion 1 (message from the thyristor blocking voltage) Use criterion 2 (curvature of the current cusp) Use criterion 3 (magnitude of the current actual value) 1 signal Yes 0 signal No Yes Yes No No Note: Converter commutation is permanently monitored. When a commutation fault is detected, Fault F60030 is output and thyristor turn-off is initiated by the CCP (if being used). The detection of a commutation fault is based on 3 decisionmaking criteria. Using this parameter, these can be individually set for test purposes. If several decision-making criteria are to be evaluated, then the sum of the corresponding numbers should be set. Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 55 Commissioning 12.2010 PNU Description Value range [dimension] Graduation p51583 CCP test turn-off command / CCP turn-off command 0 to 2 1 1 Description: Setting to issue a turn-off command to the Converter Commutation Protector (CCP) for test purposes. No. of indices Factory setting (FS) Ind: None FS = 0 Access level 3 Value: 0: No turn-off command 1: Issue in torque direction I 2: Issue in torque direction II Notice: After a turn-off command has been issued to the CCP, this parameter automatically sets itself back to the value 0. Note: If the test command is issued during operation (i.e. in the operating state o0.1 or o0.2), then the turn-off operation of the SIMOREG CCP acts on the thyristor bridge that is presently enabled. This is independent of issuing the turn-off command in torque direction I or II. 7.1.3 SIMOREG DC-MASTER connectors States of the SIMOREG CCP ∧1 1= K0575 State of the SIMOREG CCP Significance of the individual bits: See under parameter n574 I2t value of voltage limiting chopper 1 of the SIMOREG CCP K0576 I2t value of voltage limiting chopper 2 of the SIMOREG CCP ∧ 100% 16384 = K0577 Low byte: Command to the SIMOREG CCP Bit0 = Fire turn-off thyristors Bit1 = Line supply voltage (armature) is in the tolerance range Bit2 = This SIMOREG CCP is connected to the parallel switching master Bit3 = Main contactor CLOSE Bit4 = Torque direction 1 active Bit5 = Torque direction 2 active Bit6 = always 1 Bit 7 = always 1 ∧1 1= K0574 ∧ 100% 16384 = High byte: Diagnostics information about the monitoring of the blocking voltage-time integral The monitoring of the blocking voltage-time integral results in the SIMOREG CCP being triggered (and A030 or F030 with fault value 1), if bit 8 OR bit 9 = 1 AND ALL additional bits = 1 (i.e. the condition is fulfilled) Bit 8 = Torque direction I AND EMF <= +5% (i.e. regenerative feedback) Bit9 = Torque direction II AND EMF >= -5% (i.e. regenerative feedback) Bit 10 = delay angle > 90° (i.e. regenerative feedback) Bit 11 = no return pulse jump Bit12 = Armature current flows (The I = 0 signal has been present for a maximum of 0.6 ms) Bit13 = The blocking voltage-time integral is too low (< 50% of the theoretical value) Bit14 = Decision-making criteria 1 is evaluated (see U580) Bit15 = "No parallel operation" or "Parallel switching master" (U800 = 0 OR U800 = 1 OR [U800 = 2 AND U806 > 10]) Note: Bits 8 and 9 are always updated. For all other a bits, the following applies: The bits after the first bit with the value zero are invalid! 56 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 7.1.4 F030 Commissioning SIMOREG DC-MASTER faults Commutation fault or an overcurrent condition has occurred - or a test command was issued via U583 (active in all operating states) Possible error causes • • F032 Line voltage dip during regenerative operation Current control loop not optimized Fault value: r047 indices 002 to 016: 1 for i001= 1 to 3 and 5, i002 to i006 are valid for i001= 4, i002 to i015 are invalid i002 delay angle (K0100) for a fault situation i003 EMF actual value (K0287) for a fault situation i004 Gating unit diagnostics (K0989) for a fault situation i005 Field current actual value (K0265) for a fault situation i006 Pulse number (K0105) for a fault situation The blocking voltage-time integral for the commutating thyristor pair was too small 2 The current cusp breaks upwards 3 The amplitude of the current cusp was higher than 250% of the actual rated unit current according to r072i002 4 A SIMOREG DC-MASTER connected in parallel has detected a commutation fault or an overcurrent condition 5 Test command was entered via U583 SIMOREG CCP not ready (active for operating states < o4.0) Possible error causes • • • • • • • • Missing connection or interrupted cable at X172 (G-SST2) For a parallel connection, missing connection or interrupted cable at X165 (parallel interface, master) For a parallel connection, missing connection or interrupted cable at X29_PAR or X30_PAR (turn-off pulse interface) Hardware defect in the charge circuit of the quenching capacitors Ruptured fuse in the armature circuit, either line side or motor side Ruptured fuse in the pre-charging circuit for the chopper capacitors presently in the cooling-down phase necessary for the chopper resistors MLFB data of the SIMOREG CCP (n570, n571, n572) invalid or not available Fault value: r047 indices 002 to 016: 1 for i001= 1 to 12, i002 to i006 are valid 2 3 4 5 6 7 11 12 20 Voltage not available at the connections U, V, W of the SIMOREG CCP Voltage at C-D at the SIMOREG CCP does not match the voltage C-D at the SIMOREG DC-MASTER The quenching capacitors of the SIMOREG CCP have not reached the setpoint voltage The parallel interface cable is not connected at the SIMOREG CCP, which is assigned the parallel switching master No connection between the SIMOREG DC-MASTER and SIMOREG CCP via the serial interface G-SST2 (r799.i001 is not incremented) No connection between parallel SIMOREG CCP units for i001= 20, only i002 is valid i002 state of the SIMOREG CCP (K0574) for a fault situation i003 I2t value of chopper 1 (K0575) for a fault situation i004 I2t value of chopper 2 (K0576) for a fault situation i005 armature voltage actual value (r038) for a fault situation in 0.1 V for i005 > 32767 the following applies: VARMATURE[V] = (65536-r047i005)/10 i006 effective time until a fault is initiated in 20 ms Contents of the memory of the technical data of the SIMOREG CCP (MLFB, rated values, serial number) invalid The I2t value (n575) of the voltage limiting chopper 1 is too high (> 100%) The I2t value (n576) of the voltage limiting chopper 2 is too high (> 50%) The pre-charging of the chopper capacitors was not able to be completed within the time set in P089 - or the condition according to fault value 5 is fulfilled Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 57 Commissioning 7.1.5 12.2010 SINAMICS DCM faults F60300 Commutation fault or an overcurrent condition has occurred - or a test command was issued via p51583 (active in all operating states) Possible error causes • • Line voltage dip during regenerative operation Current control loop not optimized Fault value: r50047[0..8]: 1: Commutation was unsuccessful because the commutating thyristor did not assume a blocking voltage (only when parameter p50166 is activated). 2: The current cusp breaks upwards 3: The amplitude of the current cusp was greater than 290 % of the actual rated unit current acc. to r50072[1]. Criterion 1: r50047[0] = decision-making criterion (=1) r50047[1] = fired thyristor pairs r50047[2] = thyristor state (=r53146) r50047[3] = actual delay angle r50047[4] = actual EMF as a % 4: A SINAMICS DCM connected in parallel has detected a commutation fault or an overcurrent condition. 5: Test command was entered via p51583. Criterion 2: r50047[0] = decision-making criterion (=2) Criterion 2.1: r50047[1] = sub-criterion (=1) r50047[2] = delta Ia sampling values when initiating r50047[3] = last Ia sampling value r50047[4] = actual Ia sampling value r50047[5] = actual delay angle r50047[6] = currently valid counter status Criterion 2.2: r50047[1] = sub-criterion (=2) r50047[2] = delta Ia sampling values when initiating r50047[3] = delta minimum r50047[4] = actual Ia sampling value r50047[5] = first delta Ia r50047[6] = actual delay angle r50047[7] = currently valid counter status Criterion 3: r50047[0] = decision-making criterion (=3) r50047[1] = delta counter status when initiating r50047[2] = last CD voltage r50047[3] = actual CD voltage r50047[4] = delta Va r50047[5] = actual delay angle r50047[6] = actual firing instant r50047[7] = actual EMF r50047[8] = actual Ia sampling value Triggering a CCP in a parallel connection: r50047[0] = fault value (=4) Test command: r50047[0] = decision-making criterion (=5) r50047[1] = actual CD voltage r50047[2] = actual delay angle r50047[3] = actual firing instant r50047[4] = actual EMF r50047[5] = actual Ia sampling value r50047[6] = torque direction when triggering 58 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Commissioning F60320 SIMOREG CCP not ready Possible error causes • • • • • • • • Missing connection or interrupted cable at X177 For a parallel connection, missing connection or interrupted cable at X165/X166 (parallel interface, master) For a parallel connection, missing connection or interrupted cable at X29_PAR or X30_PAR (turn-off pulse interface) Hardware defect in the charge circuit of the quenching capacitors Ruptured fuse in the armature circuit, either line side or motor side Ruptured fuse in the pre-charging circuit for the chopper capacitors presently in the cooling-down phase necessary for the chopper resistors MLFB data of the SIMOREG CCP (r51570,r51571,r51572) invalid or not available Fault value: 1 2 3 4 5 6 7 11 12 20 r50047[0..2]: Voltage not available at the connections U, V, W of the r50047[0] = fault value SIMOREG CCP. r50047[1] = CCP state (extended status word + r51574) Trigger time: 5 s. Voltage at C-D at the SIMOREG CCP does not match r50047[2] = armature voltage the voltage C-D at the SINAMICS DCM. Trigger time: 15 s. The quenching capacitors of the SIMOREG CCP have not reached the setpoint voltage. Trigger time: 15 s for 460 V, 7 s for 690 V. The parallel interface cable is not connected at the SIMOREG CCP, which is assigned the parallel switching master. Trigger time: 15 s. No connection between the SINAMICS DCM and SIMOREG CCP via the serial interface. (The dynamic values are not updated) Trigger time: 15 s No connection between parallel SIMOREG CCP units. Trigger time: 15 s Contents of the memory of the technical data of the SIMOREG CCP (MLFB, rated values, serial number) invalid. Trigger time: immediately The I2t value (r51575) of the voltage limiting chopper 1 is too high (> 100 %). Trigger time: immediately The I2t value (r51576) of the voltage limiting chopper 2 is too high (> 50 %). Trigger time: immediately The pre-charging of the chopper capacitors was not able to be completed within the time set in p50089 - or the condition according to fault value 5 is fulfilled. Trigger time: 20 ms. Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 59 Commissioning 12.2010 F60050 Optimization run interrupted by an internal cause. Possible error causes • • • • • • • • Missing connection or interrupted cable at X177 For a parallel connection, missing connection or interrupted cable at X165/X166 (parallel interface, master) For a parallel connection, missing connection or interrupted cable at X29_PAR or X30_PAR (turn-off pulse interface) Hardware defect in the charge circuit of the quenching capacitors Ruptured fuse in the armature circuit, either line side or motor side Ruptured fuse in the pre-charging circuit for the chopper capacitors presently in the cooling-down phase necessary for the chopper resistors MLFB data of the SIMOREG CCP (r51570, r51571, r51572) invalid or not available Fault value: r50047[0..4] 701 Parameter p50790 P2P-interface, operating mode not set to communicate with SIMOREG CCP 702 No communication to the CCP 703 p51570 incorrect order number (MLFB) of the CCP 704 Incorrect supply voltage 705 SINAMICS DCM chopper threshold = 0 706 Armature circuit inductance = 0 707 Vmax > as maximum value that can be set for p51578 708 Calculated chopper energy too high Note regarding fault value = 701: r50047[1]: Parameter value p50790 Note regarding fault value = 704: r50047[1]: Parameter value p50078[0] r50047[2]: Parameter value p51571 r50047[3]: Line supply voltage tolerance SINAMICS DCM r50047[4]: Line supply voltage tolerance SIMOREG CCP Note regarding fault value = 707: r50047[1]: Calculated Vmax r50047[2]: Parameter p51578 maximum possible value Note regarding fault value = 708: r50047[1]: Calculated chopper energy r50047[2]: maximum possible chopper energy for SIMOREG CCP 60 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 7.1.6 A030 Commissioning SIMOREG DC-MASTER alarms Commutation fault or overcurrent condition has occurred (active for operating states – –, I, II) Possible causes • Line voltage dip during regenerative operation • Current control loop not optimized A032 SIMOREG CCP not ready (active for operating states < o4.0) Possible causes • Voltage not available at the connections U, V, W of the SIMOREG CCP • Voltage at C-D at the SIMOREG CCP does not match the voltage C-D at the SIMOREG DC-MASTER • The quenching capacitors of the SIMOREG CCP have not reached the setpoint voltage • The parallel interface cable is not connected at the SIMOREG CCP, which is assigned the parallel switching master • No connection between the SIMOREG DC-MASTER and SIMOREG CCP via the serial interface G-SST2 • No connection between parallel SIMOREG CCP units • Contents of the memory of the technical data of the SIMOREG CCP (MLFB, rated values, serial number) invalid • The I2t value of the voltage limiting chopper 1 in the SIMOREG CCP is too high (> 100 %). • The I2t value of the voltage limiting chopper 2 in the SIMOREG CCP is too high (> 50 %). 7.1.7 A60321 SINAMICS DCM alarms SIMOREG CCP not ready Possible causes: 1. 2. 3. 4. 5. 6. 7. 11. 12. 20. Voltage not available at the connections U, V, W of the SIMOREG CCP. Trigger time: 1 s Voltage at C-D at the SIMOREG CCP does not match the voltage C-D at the SINAMICS DCM. Trigger time: 1 s The quenching capacitors of the SIMOREG CCP have not reached the setpoint voltage. Trigger time: 1 s The parallel interface cable is not connected at the SIMOREG CCP which is assigned to the parallel switching master . Trigger time: 1 s No connection between the SINAMICS DCM and SIMOREG CCP via the serial interface. (The dynamic values are not updated) Trigger time: 1 s No connection between parallel SIMOREG CCP units. Trigger time: 1 s Contents of the memory of the technical data of the SIMOREG CCP (MLFB, rated values, serial number) invalid. Trigger time: immediately The I2t value (r51575) of the voltage limiting chopper 1 is too high (> 100 %). Trigger time: immediately The I2t value (r51576) of the voltage limiting chopper 2 is too high (> 50 %). Trigger time: immediately The pre-charging of the chopper capacitors was not able to be completed within the time set in p50089 - or the condition according to fault value 5 is fulfilled. Trigger time: 20 ms after fault value 5 occurs Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 61 Commissioning 12.2010 7.2 Commissioning steps 7.2.1 SIMOREG DC-MASTER commissioning steps Note The parameter values to be set when commissioning the SIMOREG CCP must be graphically determined using the characteristic diagram (Appendix). Alternatively, an existing commissioning script for the DriveMonitor can be used (script fileccp.ssc and database filesimoreg-ccp-mlfb.xml). If the basic converter unit has a software release from V 3.1 and higher, SIMOREG CCP can be commissioned by selecting P051=30 (automatic setting of the parameters for SIMOREG CCP). This optimization run must be performed after commissioning step 4. In this case, commissioning steps 3, 5 and 6 are not performed. If Fault F050 occurs during the optimization run (optimization run cannot be performed) the fault description of the particular fault value (r047.001) provides information about possible causes. 1. Connect SIMOREG CCP according to the recommended connection in Chapter 6. 2. Set P790=6 (communication with the CCP). Correct communication is optically displayed using an LED on the Power Interface module C98043-A7046: LED flashes slowly (<1 Hz) Communication with SIMOREG CCP OK, LED flashes quickly (approx. 3 Hz) no communication with the SIMOREG CCP 3. Determining the setting value for parameter U577 (factory setting = 1600) Required parameter values: r070...MLFB (characteristic number) of the SIMOREG DC-MASTER n570...MLFB (characteristic number) of the SIMOREG CCP ⇒ Determining the setting value according to the parameter description for U577 4. Commission the basic converter unit according to the operating instructions SIMOREG DCMASTER, Chapter 7. The commissioning must be correctly completed. This also means that the optimization runs according to commissioning step 8 must be performed. The optimization run for the pre-control and current controller for the armature and field (P051=25) is absolutely mandatory, as the armature inductance is determined in this run and the value of P111 is required for the subsequent SIMOREG CCP commissioning. Notice: P351 must not be parameterized more negative than the factory setting. Otherwise, when the line contactor is closed (or the circuit breaker) then a charging current surge occurs in the chopper capacitors. This can destroy the CCP power semiconductors. Comment: The chopper capacitors are charged via an internal pre-charging circuit. When reaching the undervoltage threshold defined by P351, the line contactor (or circuit breaker) is closed, which means that the pre-charging circuit is bypassed. Note: If Fault F030 occurs when commissioning the basic converter unit (especially during the optimization runs), then the commutation monitoring should be deactivated for the commissioning (U580=0). After commissioning has been successfully completed, the commutation monitoring must be reactivated (U580=7). Notice: If an existing drive system was retrofitted with a SIMOREG CCP, then the optimization run for the pre-control and current controller for the armature and field (P051=25) is absolutely necessary. The value of P111 determined in this optimization run is required to commission the SIMOREG CCP. Parameter P111 can be modified through manual optimization. This is the reason that before performing the optimization run with P051=25, the actual value of 62 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Commissioning P111 should be noted and only set again after the SIMOREG CCP commissioning has been completed. 5. Determining the maximum energy in the armature circuit for the turn-off operation Parameter value required: n570 MLFB (Order No.) of the SIMOREG CCP r072i002 Actual rated unit DC current, armature [A] P101 Rated motor armature voltage [V] 1.) P111 Armature circuit inductance [mH] as well as a characteristic diagram according to the following table: MLFB SIMOREG CCP 6RA7085-6FC00-0 MLFB characteristic number 250 6RA7091-6FC00-0 251 6RA7095-6FC00-0 252 6RA7090-6KC00-0 253 P101 [V] 1.) No. of the associated characteristic diagram 2.) 420 470 420 470 420 11 12 11 12 13 520 14.0 600 14 720 15 6RA7095-6KC00-0 254 520 16.0 600 16 720 17 1.) Rated DC voltage according to the motor rating plate (the values are typical rated data for Siemens DC motors from the product catalog DA12 2.) The characteristic diagrams are provided in the appendix to these operating instructions If the graphically determined value lies below the limit line W_max, then the energy reduction in the armature circuit is assured using the SIMOREG CCP. 6. Determining the setting value for parameter U578 (factory setting = 145) Required parameter values: n570 MLFB (Order No.) of the SIMOREG CCP r071 Rated unit supply voltage (armature) [V] r072i002 Actual rated unit DC current, armature [A] P078i001 Actual rated converter input voltage, armature [V] P101 Rated motor armature voltage [V] P111 Armature circuit inductance [mH] P351 Threshold for the undervoltage shutdown [%]. ⇒ Determining the setting value according to the parameter description for U578 The SIMOREG CCP is now ready to run. Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 63 Commissioning 7.2.2 12.2010 SINAMICS DCM commissioning steps Note If the basic converter unit has a software release from V 1.2 and higher, the SIMOREG CCP can be commissioned by selecting p50051=30 (automatic setting of the parameters for SIMOREG CCP). This optimization run must be performed after commissioning step 4. In this case, commissioning steps 3, 5 and 6 are not performed. If Fault F60050 occurs during the optimization run (optimization run interrupted internally) the fault description of the particular fault value (r50047) provides information about possible causes. 1. Connect SIMOREG CCP according to the recommended connection in Chapter 6. 2. Set p50790=6 (communication with the CCP). Correct communication is optically displayed using an LED on the Power Interface module C98043-A7046: LED flashes slowly (<1 Hz) Communication with SIMOREG CCP OK, LED flashes quickly (approx. 3 Hz) no communication with the SIMOREG CCP 3. Determining the setting value for parameter p51577 (factory setting = 1600) Required parameter values: r50070...MLFB (characteristic number) of the SINAMICS DCM r51570...MLFB (characteristic number) of the SIMOREG CCP ⇒ Determining the setting value according to the parameter description for p51577 4. Commission the basic converter unit according to the operating instructions SINAMICS DCM, Chapter 7. The commissioning must be correctly completed. This also means that the optimization runs according to commissioning step 8 must be performed. The optimization run for the pre-control and current controller for the armature and field (p50051=25) is absolutely mandatory, as the armature inductance is determined in this run and the value of p50111 is required for the subsequent SIMOREG CCP commissioning. Notice: p50351 must not be parameterized more negative than the factory setting. Otherwise, when the line contactor is closed (or the circuit breaker) then a charging current surge occurs in the chopper capacitors. This can destroy the CCP power semiconductors. Comment: The chopper capacitors are charged via an internal pre-charging circuit. When reaching the undervoltage threshold defined by p50351, the line contactor (or circuit breaker) is closed, which means that the pre-charging circuit is bypassed. Note: If Fault F60300 occurs when commissioning the basic unit (especially during the optimization runs), then the commutation monitoring must be deactivated for the commissioning (p51580=0). After commissioning has been successfully completed, the commutation monitoring must be reactivated (p51580=7). Notice: If an existing drive system was retrofitted with a SIMOREG CCP, then the optimization run for the pre-control and current controller for the armature (p50051=25) and field (p50051=24) is absolutely necessary. The value of p50111 determined in this optimization run is required to commission the SIMOREG CCP. Parameter p50111 can be modified through manual optimization. This is the reason that before performing the optimization run, the actual value of p50111 should be noted and only set again after the SIMOREG CCP commissioning has been completed. 64 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Commissioning 5. Determining the maximum energy in the armature circuit for the turn-off operation Parameter value required: p51570 MLFB (Order No.) of the SIMOREG CCP r50072[1] actual rated unit DC current, armature [A] r50101 rated motor armature voltage [V] 1.) p50111 Armature circuit inductance [mH] as well as a characteristic diagram according to the following table: MLFB SIMOREG CCP 6RA7085-6FC00-0 MLFB characteristi c number 250 6RA7091-6FC00-0 251 6RA7095-6FC00-0 252 6RA7090-6KC00-0 253 p50101 [V] 1.) No. of the associated characteristic diagram 2.) 420 470 420 470 420 11 12 11 12 13 520 14.0 600 14 720 15 6RA7095-6KC00-0 254 520 16.0 600 16 720 17 1.) Rated DC voltage according to the motor rating plate (the values are typical rated data for Siemens DC motors from the product catalog DA12 2.) The characteristic diagrams are provided in the appendix to these operating instructions If the graphically determined value lies below the limit line W_max, then the energy reduction in the armature circuit is assured using the SIMOREG CCP. 6. Determining the setting value for parameter p51578 (factory setting = 145) Required parameter values: p51570 MLFB (Order No.) of the SIMOREG CCP r50071 Rated unit supply voltage (armature) [V] r50072[1] actual rated unit DC current, armature [A] r50078[0] actual rated converter input voltage, armature [V] r50101 rated motor armature voltage [V] p50111 armature circuit inductance [mH] p50351 Threshold for the undervoltage shutdown [%]. ⇒ Determining the setting value according to the parameter description for p51578 The SIMOREG CCP is now ready to run. Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 65 Maintenance 8 12.2010 Maintenance WARNING When electrical equipment is operated, some of the components will be at hazardous voltage levels. Failure to handle/operate the equipment properly can result in death or severe bodily injury as well as substantial property damage. When performing maintenance on this unit, you should therefore observe all information provided in this chapter as well as any notices attached to the product itself. • Only qualified personnel who are familiar with all the safety instructions in this description, as well as the installation, operating, and maintenance instructions, should carry out maintenance work on this unit. • Before carrying out visual inspections and maintenance work, it must be ensured that the unit is disconnected from the AC power supply, locked out so that the power supply cannot be reconnected, and grounded. Before they are shut down, both the converter unit and the motor are at dangerous voltage levels. A hazardous voltage is present even if the converter unit contactor is open. • Even after being disconnected from the power supply, the snubber capacitors in the basic converter unit can still be at a hazardous voltage. For this reason, the unit should not be opened until an adequate period of time has elapsed. • Before commencing any work, ensure that the unit is in a no-voltage condition (see Chapter 1) Only spare parts approved by the manufacturer may be used. The converter unit must be well protected against pollution in order to prevent voltage flashovers and, therefore, destruction. Dust and foreign bodies, which are drawn in by the cooling-air flow in particular, must be thoroughly removed at specific intervals; this depends on the rate of accumulation of dirt, but should be carried out at least every 12 months. The unit should be cleaned using dry compressed air, max. 1 bar, or using a vacuum cleaner. 66 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 8.1 Maintenance Software update of the SIMOREG CCP 1 Switch-off the electronics power supply of the SIMOREG CCP 2 Connect one COM port of the PC to connector X300 at the SIMOREG CCP. Order number of the cable: 6SX7005-0AB00 (also see Chapter 6.5) 3 Switch-on the electronics power supply AND while doing this press button S1 on the Power Interface module C98043-A7046 Note: From this instant onwards, a timer runs in the SIMOREG CCP for approximately 2 minutes. If, during this time, the update is not started from the PC, then the SIMOREG CCP returns to the normal operating state. To restart the software update, the sequence from step 1 should be repeated. ⇒ the SIMOREG CCP goes into the programming mode (the yellow monitoring LED on the SIMOREG CCP remains dark) 4 At the PC, start the load program LOAD_CCP.exe and using the "Open file" button, select the required data file (7046Axxx.hex). Pressing the "Open" button starts the load operation (this takes about 10 s). Note: In the properties dialog of a link to LOAD_CCP.exe a parameter of form COMx can be transferred - whereby 1 or 2 should be used for x (default: COM1) 5 After the software has been successfully updated, the SIMOREG CCP automatically goes into the normal operating state (the yellow monitoring LED at the SIMOREG CCP flashes slowly if communication with the basic unit has been established). Note: If the electronics power supply is switched-off during the software update, then you must repeat the operation starting from Step 4. 6 Check the new software release at 560 or r51560[0]. 7 END Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 67 Maintenance 12.2010 8.2 Replacing components 8.2.1 Replacing modules WARNING Modules must only be replaced by qualified personnel. Modules must not be inserted or withdrawn under voltage. Non-observance of the warnings can result in death, severe personal injury or significant property damage. CAUTION The modules contain electrostatically sensitive devices. Discharge yourself before touching any electronic modules. The easiest way to do this is to touch a conductive, grounded object immediately beforehand (for example, bare metal parts of control cabinet or the protective ground contact of a socket outlet). Replacing the chopper unit • • • • Remove the Limiter Board C98043-A7047 Release screw (1) Release screw (2) Replace the module(s) B 2 1 2 1 2 1 1 Chopper Unit 460 V: MLFB = 6RY1703-0FC01 690 V: MLFB = 6RY1703-0FC02 1 A 1 1 2 2 1 2 Note For units 6RA7085-6FC00-0, 6RA7091-6FC00-0 and 6RA7090-6KC00-0, there is only one chopper unit (Item A) 68 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Maintenance Replacing printed circuit boards Limiter Board MLFB = 6RY1703-0AC01 Power Interface MLFB = 6RY1703-0DC01 8.2.2 Replacing diode, thyristor and IGBT modules The modules are fixed using self-tapping screws. To mount modules, it is absolutely necessary to use screws with metric thread with the same length as the original screws and locking elements (washer and spring washer). When screwing modules to busbars and other assemblies, screws with metric thread with the same length as the original screws and locking elements (washer and spring washer) must also be used. Module design Tightening torque, module: 3,5 Nm Tightening torque of the power connections: 5 Nm Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Tightening torque, module: 6 Nm Tightening torque of the power connections: 12 Nm ENGLISH Operating Instructions 69 Maintenance 12.2010 IGBT type SKM 500 GA 174 DS 1 2 NOTICE All 4 IGBT modules must always be replaced. It is only permissible to use the original IGBT types. The sequence when bolting the IGBT modules can be seen in the adjacent diagram and this must be maintained under all circumstances. 4 3 Tightening torque, IGBT: 5 Nm Tightening torque of the busbars: 5 Nm 70 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 9 Service, technical support Service, Technical Support Note We would be grateful if you could specify the following unit data when you have any queries: • Unit order number and serial number • Software version • Hardware version of the C98043-A7046 module (Power Interface) (screen printed on the component side) You can find information on our services and regional contact partners under: http://www.siemens.de/automation/csi_de/service Technical support Our technical support service can provide you with technical assistance for products, systems, and solutions. http://www.siemens.de/automation/support-request (German) http://www.siemens.com/automation/support-request (English) Central hotlines for technical support for SIMOREG CCP / SIMOREG DC-MASTER / SINAMICS DCM: Time zone Europe and Africa Tel: +49 (0)911 895 7222 Fax: +49 (0)911 895 7223 mailto:[email protected] 8:00 to 17:00 CET Time zone, Americas 24-hour hotline: +1 800 333 7421 8:00 to 17:00 Eastern Standard Time Time zone Asia / Australia Tel.: +1 423 262 2960 Fax: +1 423 262 2200 mailto:[email protected] m Tel: +86 1064 757575 Fax: +86 1064 747474 mailto:[email protected] 7:30 to 17:30 Local time, Beijing Repairs If you wish to have a part/unit repaired, then please contact your regional contact partner for repairs. Service calls Qualified personnel can perform repair work on your units and offer services that ensure their availability. This work can be carried out with charges that are scaled according to the amount of time and work involved, or at a flat rate as part of a contract. Services whose charges depend on the amount of time and work involved are performed within the normal working hours for the region and with an appropriate response time. You can request service calls through your regional contact partner. Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 71 Spare parts 10 12.2010 Spare parts Equipment identifiers Designation Dimensions LxWxH (mm) Weight (kg) Order No. (MLFB) used in 6RA70.. C98043-A7046 Power-Interface SIMOREG CCP printed circuit board 360x260x42 0,8 6RY1703-0DC01 ..85-6FC00-0 ..91-6FC00-0 ..90-6KC00-0 ..95-6FC00-0 ..95-6KC00-0 C98043-A7047 Limiter Board SIMOREG CCP 375x360x68 1 6RY1703-0AC01 ..85-6FC00-0 ..91-6FC00-0 ..90-6KC00-0 ..95-6FC00-0 ..95-6KC00-0 V100.1 Chopper unit 460 V 310x110x210 3 6RY1703-0FC01 ..85-6FC00-0 ..91-6FC00-0 V100.1, V100.2 Chopper unit 460 V 310x110x210 3 6RY1703-0FC01 ..95-6FC00-0 V100.1 Chopper unit 690 V 310x110x210 3 6RY1703-0FC02 ..90-6KC00-0 V100.1, V100.2 Chopper unit 690 V 310x110x210 3 6RY1703-0FC02 ..95-6KC00-0 V41+V44, V42+V45, V43+V46, V47, V48 Diode module SKKD162/18 94x30x34 0,165 6RY1700-0BA06 ..85-6FC00-0 ..91-6FC00-0 V41+V44, V42+V45, V43+V46, V47, V48 Diode module SKKD162/22 94x30x34 0,165 6RY1700-0BA07 ..90-6KC00-0 V41+V44, V42+V45, V43+V46, V47, V48 Diode module DD261N22 115x52x50 0,8 6RY1700-0BA08 ..95-6FC00-0 ..95-6KC00-0 V31+34, V32+33, V35+38, V36+37, V39, V40 Thyristor module SKKT162/18 94x30x34 0,165 6SY7010-0AA73 ..85-6FC00-0 ..91-6FC00-0 V31+34, V32+33, V35+38, V36+37, V39, V40 Thyristor module MCC161-22io1 94x30x34 0,125 6SY7010-0AA74 ..90-6KC00-0 V31+34, V32+33, V35+38, V36+37, V39, V40 Thyristor module MCC224-22io1 115x52x50 0,75 6SY7010-0AA75 ..95-6KC00-0 V31+34, V32+33, V35+38, V36+37, V39, V40 Thyristor module MCC312-18io1 115x52x50 0,75 6SY7010-0AA22 ..95-6FC00-0 F1, F2 Fuses on the PowerInterface printed circuit board 20x5 0,002 6RY1702-0BA00 ..85-6FC00-0 ..91-6FC00-0 ..90-6KC00-0 ..95-6FC00-0 ..95-6KC00-0 72 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Appendix 11 Appendix 11.1 Characteristic diagrams Characteristic diagrams to define the voltage setpoint for the pre-charging of the SIMOREG CCP quenching capacitors (parameter U578 for SIMOREG DC-MASTER or p51578 for SINAMICS DCM) using the armature circuit inductance (P111 for SIMOREG DC-MASTER or p50111 for SINAMICS DCM) and the actual unit rated DC armature current (r072i002 for SIMOREG DCMASTER or r50072[1] for SINAMICS DCM) < Untergrenze > = lower limit < Obergrenze > = upper limit Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 73 Appendix 1 12.2010 6RA7085-6FC00-0 for motors with rated armature voltage 420 V (P101 or p50101) 200A 400A 500A 600A Untergrenze Voltage setpoint in V (U578 or p51578) Obergrenze 340 600A 290 500A 240 400A 190 300A 200A 140 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 300A 390 1 Armature circuit inductance in mH (P111 or p50111) 1A 390 Voltage setpoint in V (U578 or p51578) 400A 340 300A 290 200A 240 200A 300A 190 400A 500A 600A Untergrenze Obergrenze 140 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 6RA7085-6FC00-0 for motors with rated armature voltage 420 V (P101 or p50101) 0.1 Armature circuit inductance in mH (P111 or p50111) 74 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Appendix 2 6RA7085-6FC00-0 for motors with rated armature voltage 470 V (P101 or p50101) 200A 400A 500A 600A Untergrenze Obergrenze Voltage setpoint in V (U578 or p51578) 390 340 600A 290 500A 240 400A 190 300A 200A Actual unit rated DC armature current in A (r072i002 or r50072[1]) 300A 440 140 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 Armature circuit inductance in mH (P111 or p50111) 2A 500A 440 Voltage setpoint in V (U578 or p51578) 390 400A 340 300A 290 200A 240 200A 300A 400A 190 500A 600A Untergrenze Obergrenze 140 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 6RA7085-6FC00-0 for motors with rated armature voltage 470 V (P101 or p50101) 0.1 Armature circuit inductance in mH (P111 or p50111) Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 75 Appendix 12.2010 3 390 Voltage setpoint in V (U578 or p51578) 1000A 900A 340 800A 290 700A 240 600A 500A 600A 700A 800A 900A 190 500A 1000A 1100A 1200A Untergrenze Obergrenze Actual unit rated DC armature current in A (r072i002 or r50072[1]) 6RA7091-6FC00-0 for motors with rated armature voltage 420 V (P101 or p50101) 140 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 Armature circuit inductance in mH (P111 or p50111) 3A 6RA7091-6FC00-0 for motors with rated armature voltage 420 V (P101 or p50101) Voltage setpoint in V (U578 or p51578) 700A 340 600A 290 500A 240 500A 600A 700A 800A 900A 190 1000A 1100A 1200A Untergrenze Obergrenze 140 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Actual Unit rated DC armature current in A (r072i002 or r50072[1]) 800A 390 0.1 Armature circuit inductance in mH (P111 or p50111) 76 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Appendix 4 6RA7091-6FC00-0 for motors with rated armature voltage 470 V (P101 or p50101) 500A 700A 800A 900A 1100A 1000A 1100A 1200A Voltage setpoint in V (U578 or p51578) 390 Untergrenze 1000A Obergrenze 380 V 900A 340 800A 290 700A 240 600A 500A 190 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 1200A 600A 440 140 0 0.1 0.2 0.22 0.3 0.4 0.5 0.6 0.7 0.8 Armature circuit inductance in mH (P111 or p50111) Note: The values shown refer to the example in the description for parameter U578 4A 6RA7091-6FC00-0 for motors with rated armature voltage 470 V (P101 or p50101) 800A Voltage setpoint in V (U578 or p51578) 390 700A 340 600A 290 240 190 140 0.03 500A 500A 600A 700A 800A 900A 1000A 1100A 1200A Untergrenze Obergrenze 0.04 0.05 0.06 0.07 0.08 0.09 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 900A 440 0.1 Armature circuit inductance in mH (P111 or p50111) Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 77 Appendix 12.2010 5 6RA7095-6FC00-0 for motors with rated armature voltage 420 V (P101 or p50101) 1000A 1400A 1600A 2000A 1800A 2000A Untergrenze Voltage setpoint in V (U578 or p51578) Obergrenze 340 1800A 1600A 290 1400A 240 1200A 1000A 190 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 1200A 390 140 0 0.1 0.2 0.3 0.4 0.5 0.6 Armature circuit inductance in mH (P111 or p50111) 5A 390 Voltage setpoint in V (U578 or p51578) 1800A 1600A 340 1400A 290 1200A 240 1000A 1000A 1200A 190 1400A 1600A 1800A 2000A Untergrenze Obergrenze 140 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 6RA7095-6FC00-0 for motors with rated armature voltage 420 V (P101 or p50101) 0.1 Armature circuit inductance in mH (P111 or p50111) 78 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Appendix 6 6RA7095-6FC00-0 for motors with rated armature voltage 470 V (P101 or p50101) 1000A 1400A 1600A 1800A 2000A Untergrenze Obergrenze Voltage setpoint in V (U578 or p51578) 390 2000A 340 1800A 1600A 290 1400A 240 1200A 1000A 190 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 1200A 440 140 0 0.1 0.2 0.3 0.4 0.5 0.6 Armature circuit inductance in mH (P111 or p50111) 6A 6RA7095-6FC00-0 for motors with rated armature voltage 470 V (P101 or p50101) 1000A 1400A 1600A 2000A 1800A 2000A Untergrenze Obergrenze Voltage setpoint in V (U578 or p51578) 390 1800A 1600A 340 1400A 290 1200A 240 1000A 190 140 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 1200A 440 0.1 Armature circuit inductance in mH (P111 or p50111) Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 79 Appendix 7.0 12.2010 6RA7090-6KC00-0 for motors with rated armature voltage 520 V (P101 or p50101) 400A 1000A 500A 540 600A 700A 800A Voltage setpoint in V (U578 or p51578) 900A 900A 490 1000A Untergrenze Obergrenze 800A 440 390 700A 340 600A 290 500A 240 400A 190 300A Actual unit rated DC armature current in A (r072i002 or r50072[1]) 300A 140 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 Armature circuit inductance in mH (P111 or p50111) 7.0A 540 600A Voltage setpoint in V (U578 or p51578) 490 500A 440 400A 390 340 300A 290 300A 400A 500A 600A 240 700A 800A 900A 1000A 190 Untergrenze Obergrenze 140 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 6RA7090-6KC00-0 for motors with rated armature voltage 520 V (P101 or p50101) 0.1 Armature circuit inductance in mH (P111 or p50111) 80 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Appendix 7 6RA7090-6KC00-0 for motors with rated armature voltage 600 V (P101 or p50101) 400A 1000A 500A 540 600A 700A 800A Voltage setpoint in V (U578 or p51578) 900A 900A 490 1000A Untergrenze Obergrenze 800A 440 390 700A 340 600A 290 500A 240 400A 190 300A Actual unit rated DC armature current in A (r072i002 or r50072[1]) 300A 140 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 Armature circuit inductance in mH (P111 or p50111) 7A 600A 540 Voltage setpoint in V (U578 or p51578) 490 500A 440 400A 390 300A 340 290 300A 400A 500A 600A 240 700A 800A 900A 1000A 190 Untergrenze Obergrenze 140 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 6RA7090-6KC00-0 for motors with rated armature voltage 600 V (P101 or p50101) 0.1 Armature circuit inductance in mH (P111 or p50111) Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 81 Appendix 12.2010 8 6RA7090-6KC00-0 for motors with rated armature voltage 720 V (P101 or p50101) 300A 500A 640 600A 700A 800A 900A Voltage setpoint in V (U578 or p51578) 1000A Untergrenze 1000A 540 Obergrenze 900A 800A 440 700A 600A 340 500A 240 400A 300A Actual unit rated DC armature current in A (r072i002 or r50072[1]) 400A 140 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 Armature circuit inductance in mH (P111 or p50111) 8A 640 700A Voltage setpoint in V (U578 or p51578) 600A 540 500A 400A 440 300A 340 300A 400A 500A 600A 700A 240 800A 900A 1000A Untergrenze Obergrenze 140 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 6RA7090-6KC00-0 for motors with rated armature voltage 720 V (P101 or p50101) 0.1 Armature circuit inductance in mH (P111 or p50111) 82 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Appendix 9.0 2000A Voltage setpoint in V (U578 or p51578) 540 490 1800A 440 1600A 390 1400A 340 1200A 290 1000A 1000A 1200A 1400A 240 1600A 1800A 2000A 190 2200A Untergrenze Obergrenze Actual unit rated DC armature current in A (r072i002 or r50072[1]) 6RA7095-6KC00-0 for motors with rated armature voltage 600 V (P101 or p50101) 140 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 Armature circuit inductance in mH (P111 or p50111) 9.0A 540 1600A Voltage setpoint in V (U578 or p51578) 490 1400A 440 1200A 390 1000A 340 290 1000A 1200A 1400A 240 1600A 1800A 2000A 190 2200A Untergrenze Obergrenze 140 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 6RA7095-6KC00-0 for motors with rated armature voltage 600 V (P101 or p50101) 0.1 Armature circuit inductance in mH (P111 or p50111) Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 83 Appendix 12.2010 9 2000A 540 1800A Voltage setpoint in V (U578 or p51578) 490 440 1600A 390 1400A 340 1200A 290 1000A 1000A 1200A 1400A 240 1600A 1800A 2000A 190 2200A Untergrenze Obergrenze Actual unit rated DC armature current in A (r072i002 or r50072[1]) 6RA7095-6KC00-0 for motors with rated armature voltage 600 V (P101 or p50101) 140 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 Armature circuit inductance in mH (P111 or p50111) 9A 540 1600A Voltage setpoint in V (U578 or p51578) 490 1400A 440 1200A 390 1000A 340 290 1000A 1200A 1400A 240 1600A 1800A 2000A 190 2200A Untergrenze Obergrenze 140 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 6RA7095-6KC00-0 for motors with rated armature voltage 600 V (P101 or p50101) 0.1 Armature circuit inductance in mH (P111 or p50111) 84 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Appendix 10 6RA7095-6KC00-0 for motors with rated armature voltage 720 V (P101 or p50101) 1000A 1400A 640 1600A 1800A 2000A Untergrenze Voltage setpoint in V (U578 or p51578) Obergrenze 2000A 540 1800A 1600A 440 1400A 340 1200A 1000A 240 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 1200A 140 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 Armature circuit inductance in mH (P111 or p50111) 10A 6RA7095-6KC00-0 for motors with rated armature voltage 720 V (P101 or p50101) Voltage setpoint in V (U578 or p51578) 1800A 1600A 540 1400A 440 1200A 1000A 340 1000A 1200A 1400A 240 1600A 1800A 2000A Untergrenze Obergrenze 140 0.03 0.04 0.05 0.06 0.07 0.08 0.09 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 2000A 640 0.1 Armature circuit inductance in mH (P111 or p50111) Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 85 Appendix 12.2010 Characteristic diagrams to determine the maximum energy in the armature circuit using the armature circuit inductance (P111 or p50111) and the actual rated unit armature DC current (r072i002 or r50072[1]) 11 6RA7085-6FC00 and 6RA7091-6FC00 for motors with rated armature voltage 420 V (P101 or p50101) 70 10 mH W_max 2 mH 4 mH 6 mH 50 8 mH 8 mH 10 mH 4 mH W [kJ] 40 30 2 mH 20 10 0 200 300 400 500 600 700 800 900 1000 1100 Armature circuit inductance in mH (P111 or p50111) 6 mH 60 1200 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 12 6RA7085-6FC00 and 6RA7091-6FC00 for motors with rated armature voltage 470 V (P101 or p50101) 70 6 mH W_max 2 mH 10 mH 4 mH 8 mH 6 mH 8 mH 50 10 mH 4 mH W [kJ] 40 30 2 mH 20 10 0 200 300 400 500 600 700 800 900 1000 1100 Armature circuit inductance in mH (P111 or p50111) 60 1200 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 86 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Appendix 13 6RA7095-6FC00 for motors with rated armature voltage 420 V (P101 or p50101) 140 100 10 mH W_max 2 mH 4 mH 6 mH 8 mH 10 mH 6 mH 8 mH 4 mH W [kJ] 80 60 2 mH 40 20 0 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 Armature circuit inductance in mH (P111 or p50111) 120 2000 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 14.0 6RA7090-6KC00 for motors with rated armature voltage 520 V (P101 or p50101) 70 W_max 2 mH 10 mH 4 mH 6 mH 50 8 mH 8 mH 10 mH 6 mH W [kJ] 40 , 30 4 mH 20 2 mH 10 0 400 500 600 700 800 900 Armature circuit inductance in mH (P111 or p50111) 60 1000 Actual unit rated DC armature current in A (r072i002 or r50072[1]) Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 87 Appendix 12.2010 14 6RA7090-6KC00 for motors with rated armature voltage 600 V (P101 or p50101) 60 50 W_max 2 mH 4 mH 6 mH 8 mH 10 mH 10 mH 8 mH 6 mH W [kJ] 40 , 30 4 mH 20 2 mH 10 0 400 500 600 700 800 900 Armature circuit inductance in mH (P111 or p50111) 70 1000 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 15 6RA7090-6KC00 for motors with rated armature voltage 720 V (P101 or p50101) 70 60 10 mH W_max 2 mH 4 mH 6 mH 50 8 mH 6 mH 10 mH W [kJ] 40 4 mH 30 20 2 mH 10 0 400 500 600 700 800 900 Armature circuit inductance in mH (P111 or p50111) 8 mH 1000 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 88 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Appendix 16.0 6RA7095-6KC00 for motors with rated armature voltage 520 V (P101 or p50101) 140 8 mH W_max 2 mH 6 mH 10 mH 4 mH 8 mH 6 mH 4 mH 8 mH 100 10 mH W [kJ] 80 , 60 2 mH 40 20 0 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 Armature circuit inductance in mH (P111 or p50111) 120 2000 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 16 6RA7095-6KC00 for motors with rated armature voltage 600 V (P101 or p50101) 140 100 10 mH W_max 2 mH 4 mH 6 mH 8 mH 10 mH 6 mH 8 mH 4 mH W [kJ] 80 , 60 2 mH 40 20 0 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 Armature circuit inductance in mH (P111 or p50111) 120 2000 Actual unit rated DC armature current in A (r072i002 or r50072[1]) Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 89 Appendix 12.2010 17 6RA7095-6KC00 for motors with rated armature voltage 720 V (P101 or p50101) 140 120 W_max 2 mH 10 mH 6 mH 8 mH 4 mH 6 mH 8 mH 100 10 mH W [kJ] 80 2 mH , 60 40 20 0 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 Armature circuit inductance in mH (P111 or p50111) 4 mH 2000 Actual unit rated DC armature current in A (r072i002 or r50072[1]) 90 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 11.2 Appendix Relevant standards EN 50178 Electronic equipment for use in power installations EN 60068 Part 2 A93 Electrical engineering; basic environmental testing techniques; checks EN 61800 Part 1 Adjustable speed electrical power drive systems: General requirements. Definition for the dimensioning of low-voltage DC drive systems EN 60146 Part 1 Semiconductor converters: General requirements and special requirements for line-commutated converters EN 60204 EN 60529 11.3 Machinery Directive Part 4-2 A12.01 Degrees of protection; protection against contact, foreign objects, and water for electrical equipment (EN 60529: 1991) EN 60721 Electrical engineering; certification of environmental conditions: EN 61140 Protection against electric shock Part1 A08.03 Classification of electrical and electronic equipment EN 61800 Part 3 EMC product standard for adjustable speed drives DIN VDE 0110 Part 1 and 2 A01.89 Insulation coordination for electrical equipment in lowvoltage systems SN36350 Environmentally friendly product design UL 508 C Power Conversion Equipment ISO 14001:2004 Environmental management Certification The products listed in this document are manufactured and sold according to DIN ISO 9001. The SIMOREG CCP complies with all of the requirements of UL 508, however has not been certified. 11.4 Abbreviations, terminology CE cULus UL CCP IGBT Communauté Européenne for ready-to-connect products, tested by UL in accordance with the UL and CSA standards Underwriters Laboratories Converter Commutation Protector insulated gate bipolar transistor Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector ENGLISH Operating Instructions 91 Appendix 11.5 12.2010 Environmental compatibility Environmental aspects during development The use of highly-integrated components has enabled the number of parts to be kept to a minimum, with energy being used as efficiently as possible during production as a result. Particular emphasis has been placed on ensuring that the metal and plastic parts have a low volume and low weight, and that the number of different types is kept to a minimum. Front parts: PC + ABS ABS Cycoloy Novodur GE-Plastics Bayer Plastic parts in the unit: PC PA 6.6 SE1-GFN1 Lexan 141-R Noryl Insulation materials: PC (FR) fl Makrolon or Lexan Rating plate: Polyester film Pollutant-free materials have been used for all significant parts. No flame retardants containing halogen or insulation materials containing silicon have been used. Environmental compatibility was a key criterion in selecting supplier parts. Environmental aspects during production The majority of supplier parts are transported in reusable packaging. The packaging materialitself can be reused, it mainly comprises cardboard. With the exception of the enclosure, no surface coatings have been used. The production processes do not produce any emissions. Environmental aspects for disposal The unit features screw-in and snap-in connections that can be easily released in order to separate it into different mechanical components for recycling purposes. The printed circuit boards may be used in recycling processes involving energy recovery. The proportion of components containing hazardous substances is low. 92 ENGLISH Siemens AG 6RX1700-0DD74 SIMOREG DC-MASTER Converter Commutation Protector Operating Instructions 12.2010 Bisher sind folgende Ausgaben erschienen: The following versions have appeared so far: SIMEA Siemens Industrial Manufacturing, Engineering and Applications Postfach 83, A-1211 Wien Ausgabe Version interne Sachnummer Internal Part No. 01 C98130-A7046-A1-01-7419 02 C98130-A7046-A1-02-7419 03 C98130-A7046-A1-03-7419 04 C98130-A7046-A1-04-7419 © Siemens AG, 2005-2010 Subject to change without notice Order No.: 6RX1700-0DD74 Printed in EU (Austria)