Tcn4s руководство по эксплуатации

DRW170776AA

DUAL INDICATOR TEMPERATURE CONTROLLER

TCN4 SERIES

I N S T R U C T I O N M A N U A L

Thank you for choosing our Autonics product.

Please read the following safety considerations before use.

Safety Considerations

※Please observe all safety considerations for safe and proper product operation to avoid hazards.

※Safety considerations are categorized as follows.

Warning Failure to follow these instructions may result in serious injury or death.

Caution Failure to follow these instructions may result in personal injury or product damage.

※The symbols used on the product and instruction manual represent the following

symbol represents caution due to special circumstances in which hazards may occur.

Warning

1. Fail-safe device must be installed when using the unit with machinery that may cause

serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment,

ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster

prevention devices, etc.)

Failure to follow this instruction may result in fire, personal injury, or economic loss.

2. Install on a device panel to use.

Failure to follow this instruction may result in electric shock or fire.

3. Do not connect, repair, or inspect the unit while connected to a power source.

Failure to follow this instruction may result in electric shock or fire.

4. Check ‘Connections’ before wiring.

Failure to follow this instruction may result in fire.

5. Do not disassemble or modify the unit.

Failure to follow this instruction may result in electric shock or fire.

Caution

1. When connecting the power input and relay output, use AWG 20(0.50mm

2

) cable or over and

tighten the terminal screw with a tightening torque of 0.74~0.90N . m.

When connecting the sensor input and communication cable without dedicated cable, use

AWG 28~16 cable and tighten the terminal screw with a tightening torque of 0.74~0.90N . m.

Failure to follow this instruction may result in fire or malfunction due to contact failure.

2. Use the unit within the rated specifications.

Failure to follow this instruction may result in fire or product damage.

3. Use dry cloth to clean the unit, and do not use water or organic solvent.

Failure to follow this instruction may result in electric shock or fire.

4. Do not use the unit in the place where flammable/explosive/corrosive gas, humidity, direct

sunlight, radiant heat, vibration, impact, or salinity may be present.

Failure to follow this instruction may result in fire or explosion.

5. Keep metal chip, dust, and wire residue from flowing into the unit.

Failure to follow this instruction may result in fire or product damage.

Ordering Information

T

CN

4 S

2 4 R

P

No-mark Bolt wiring method

Wiring method

P

Connector plug connection method

Control output

R

Relay contact + SSR drive output

2

24VAC 50/60Hz, 24-48VDC

Power supply

4

100-240VAC 50/60Hz

Sub output

2

Alarm1 + Alarm2 output

S

DIN W48 × H48mm

M

DIN W72 × H72mm

Size

H

DIN W48 × H96mm

L

DIN W96 × H96mm

Digit

4

9999 (4 digit)

Setting type

CN

Dual display type, set by touch switch

Item

T

Temperature controller

1: Only for TCN4S model.

2: In case of the AC voltage model, SSR drive output method (standard ON/OFF control, cycle

control, phase control) is available to select.

※ The above specifications are subject to change and some models may be discontinued

without notice.

※ Be sure to follow cautions written in the instruction manual and the technical descriptions

(catalog, homepage).

Specification

Series

TCN4S

TCN4M

TCN4H

Power

AC Power

100-240VACᜠ 50/60Hz

supply

AC/DC Power 24VACᜠ 50/60Hz, 24-48VDCᜡ

Allowable voltage range 90 to 110% of rated voltage

AC Power

Max. 5VA(100-240VAC 50/60Hz)

Power

consumption

AC/DC Power Max. 5V(24VAC 50/60Hz), Max. 3W(24-48VDC)

Display method

7 segment (PV: red, SV: green), other display part(green, red) LED method

PV(W×H)

7.0×15.0mm

9.5×20.0mm

7.0×14.6mm

Character

size

SV(W×H)

5.0×9.5mm

7.5×15.0mm

6.0×12.0mm

RTD

DIN Pt100Ω, Cu50Ω (Allowable line resistance max.5Ω per a wire)

Input

type

TC

K(CA), J(IC), L(IC), T(CC), R(PR), S(PR)

Display

RTD

At room temperature(23ºC ± 5ºC): (PV ± 0.5% or ±1ºC, select the higher one) ± 1 digit

accuracy

Out of room temperature range: (PV± 0.5% or ±2ºC, select the higher one)± 1digit

TC

1

For TCN4S- -P, add ±1℃ by accuracy standard.

Control

Relay

250VACᜠ 3A 1a

output

SSR

12VDCᜡ±2V 20mA Max.

Alarm output

AL1, AL2 Relay: 250VACᜠ 1A 1a

Control method

ON/OFF control, P, PI, PD, PID control

1 to 100℃/℉ (0.1 to 50.0℃/℉)

Hysteresis

Proportional band(P)

0.1 to 999.9ºC/℉

Integral time(I)

0 to 9999 sec.

Derivative time(D)

0 to 9999 sec.

Control period(T)

0.5 to 120.0 sec.

Manual reset

0.0 to 100.0%

Sampling period

100ms

AC power

2000VAC 50/60Hz 1min.(between input terminal and power terminal)

Dielectric

strength

AC/DC power 1000VAC 50/60Hz 1min.(between input terminal and power terminal)

Vibration

0.75mm amplitude at frequency of 5 to 55Hz in each X, Y, Z direction for 2 hours

Mechanical OUT: Over 5,000,000 times, AL1/2: Over 5,000,000 times

Relay life

OUT: Over 200,000 times(250VAC 3A resistive load)

cycle

Electrical

AL1/2: Over 300,000 times(250VAC 1A resistive load)

Insulation resistance

Min. 100MΩ(at 500VDC megger)

Noise

Square-wave noise by noise simulator(pulse width 1㎲) ±2KV R-phase and S-phase

Memory retention

Approx. 10 years (when using non-volatile semiconductor memory type)

Ambient temp. -10 to 50ºC, Storage: -20 to 60ºC

Environ

-ment

Ambient humi. 35 to 85%RH, Storage: 35 to 85%RH

Double insulation or reinforced insulation (mark:

Insulation type

the measuring input part and the power part : AC power 2kV, AC/DC power 1kV)

Approval

Approx. 147g

Approx. 203g

Approx. 194g

Weight

2

(approx. 100g)

(approx. 133g)

(approx. 124g)

1:

At room temperature(23ºC±5ºC)

— Below 200ºC of thermocouple R(PR), S(PR) is (PV ±0.5% or ±3ºC, select the higher one) ±1 digit

— Over 200ºC of thermocouple R(PR), S(PR) is (PV ±0.5% or ±2ºC, select the higher one) ±1 digit

— Termocouple L (IC), RTD Cu50Ω is (PV ±0.5% or ±2ºC, select the higher one) ±1 digit

Out of room temperature range

— Below 200ºC of thermocouple R(PR), S(PR) is (PV ±1.0% or ±6ºC, select the higher one) ±1 digit

— Over 200ºC of thermocouple R(PR), S(PR) is (PV ±0.5% or ±5ºC, select the higher one) ±1 digit

— Thermocouple L(IC), RTD Cu50Ω is (PV ±0.5% or ±3ºC, select the higher one) ±1 digit

For TCN4S- -P, add ±1℃ by accuracy standard.

2: The weight includes packaging. The weight in parentheses is for unit only.

Environment resistance is rated at no freezing or condensation.

Unit Description

1. Present temperature (PV) display (Red)

1) RUN mode: Present temperature (PV) display

2) Parameter setting mode: Parameter display

2. Set temperature (SV) display (Green)

1) RUN mode: Set temperature (SV) display

1

2) Parameter setting mode

: Parameter setting value display

3. Control/Alarm output display indicator

8

1) OUT: It turns ON when the control output is ON.

3

During SSR drive output type in CYCLE/

2

PHASE control, this indicator turns ON when

7

MV is over 3.0%.

4

2) AL1/AL2: It turns ON when the alarm output is ON.

5

4. Auto tuning indicator

AT indicator flashes by every 1 sec during operating

auto tuning.

5.

key

6

Used when entering into parameter groups,

returning to RUN mode, moving parameter, and saving

setting values.

6. Adjustment

Used when entering into set value change mode, digit moving and digit up/down.

1

7. Digital input key

2

Press

keys for 3 sec. to operate the set function

(RUN/STOP, alarm output reset, auto tuning) in digital input key [DI-T].

8. Temperature unit (

/℉) indicator

ºC

It shows current temperature unit.

Input Sensor and Temperature Range

Input sensor

Display

Temperature range(

-50 to 1200

KCaH

K(CA)

-50.0 to 999.9

KCaL

JIcH

-30 to 800

J(IC)

JIcL

-30.0 to 800.0

-40 to 800

LIcH

Thermocouple

L(IC)

-40.0 to 800.0

LIcL

TCcH

-50 to 400

T(CC)

TCcL

-50.0 to 400.0

R(PR)

0 to 1700

RPR

S(PR)

0 to 1700

SPR

DPtH

-100 to 400

DPt100Ω

-100.0 to 400.0

DPtL

RTD

-50 to 200

CUsH

Cu50Ω

CUsL

-50.0 to 200.0

Dimensions

TCN4L

TCN4S Series

48

6

64.5

11.0×22.0mm

7.0×14.0mm

TCN4H Series

6

64.5

48

Bracket

TCN4S Series

TCN4M, TCN4H, TCN4L Series

31

48.6

20

5

45

, dielectric strength between

15

21

Approx. 275g

55

(approx. 179g)

56

Connections

1)TCN4S Series

AL1 OUT

SSR

250VAC

OUT

※1

1A 1a

AL2 OUT

250VAC

1A 1a

Relay OUT

B’

250VAC

3A 1a

B

A

RTD

※2

SOURCE

2)TCN4S- -P

SSR

※1

OUT

Relay OUT

250VAC

3A 1a

※2

SOURCE

ºC

) Temperature range(℉)

※ TCN4 Series has selectable control output; Relay output, and

-58 to 2192

SSR drive output. AC/DC voltage type does not have SSRP

-58.0 to 999.9

function.

※1: 12VDC±2V 20mA Max.

-22 to 1472

※2: AC voltage type: 100-240VAC 5VA 50/60Hz

-22.0 to 999.9

AC/DC voltage type: 24VAC 5VA 50/60Hz

-40 to 1472

24-48VDC 3W

(unit: mm)

-40 to 999.9

※Use crimp terminals or teminals of size specified below.

Terminal

a

-58 to 752

a

b

c

number

-58.0 to 752.0

1 to 8

6

Max. 1.7 Max. 3.7

c

b

32 to 3092

9 to 11

6 to 8 Max. 2.1 Max. 4.2

<Crimp terminal>

12 to 14 6 to 8 Max. 1.5 Max. 3.5

32 to 3092

-148 to 752

a b

a b

-148.0 to 752.0

<Round>

<Forked>

-58 to 392

a

Min. 3.0

Min. 3.0

-58.0 to 392.0

b

Max.5.8

Max.5.8

TCN4S- -P

6

56

11.5

48

1.7

TCN4L Series

96

6

64.5

Panel cut-out

A

C

46

Size

A

B

C

D

Series

TCN4S

Min. 65

Min. 65

45

45

0.6

0

TCN4M

Min. 90

Min. 90

68

68

0.7

0

12

TCN4H

Min. 65

Min. 115

45

0.6

92

0

23.9

TCN4L

Min. 115

Min. 115

92

92

0.8

0

Parameter Groups

3)TCN4M Series

1. All Parameter

Please any key among

,

,

,

SV setting

Parameter 1group

AL1 OUT

SSR

250VAC

OUT

※1

1A 1a

AL1 alarm termerature

TC

AL2 OUT

250VAC

1A 1a

AL2 alarm termerature

Relay OUT

B’

250VAC

3A 1a

B

+

TC

A

+

RTD

SOURCE

※2

4)TCN4H/L Series

AL1 OUT

250VAC

1A 1a

AL2 OUT

250VAC

1A 1a

B’

B

TC

A

RTD

AL1 OUT

250VAC

SSR

1A 1a

※1

OUT

AL2 OUT

Press

key over 3 sec in any parameter group, it saves the set value and returns to RUN mode.

250VAC

Relay OUT

1A 1a

(Exception: Press

250VAC

If no key entered for 30 sec., it returns to RUN mode automatically and the set value of parameter

TC

RTD

3A 1a

B’

is not be saved.

Press

key again within 1 sec. after returning to RUN mode, it advances of the first parameter

B

of previous parameter group.

A

Press

key to move next parameter.

Parameter marked in

Set parameter as ‘Parameter 2 group → Parameter 1 group → Setting group of set value’ order

SOURCE

※2

considering parameter relation of each setting group.

1: It is not displayed for AC/DC power model (TCN4 -22R).

(unit: mm)

TCN4M Series

72

6

64.5

Terminal cover(sold separately)

RSA-COVER(48×48mm)

RMA-COVER(72×72mm)

70

3

48.4

9.8

22.5

RHA-COVER(48×96mm)

RLA-COVER(96×96mm )

47.2

4

94

3

0.6

0

0.7

0

0.8

0

0.8

0

Run mode

2sec.

4sec.

Parameter 2group

PAR1

PAR2

Input

Temperature

Input

Input

sensor

unit

correction

digital filter

AL1

IN-T

UNIT

IN-B

MAvF

AL2

Control output

SV high-

SV low-limit

Control type

operation

limit value

value

Auto tunung

C-MD

O-FT

H-SV

L-SV

AT

Proportional band

SSR drive output

Control output

Control

AL1 alarm

method

※1

P

type

cycle

operation mode

OUT

SSrM

T

AL-1

Integral time

I

LBA detection

LBA

Alarm output

AL2 alarm

band

monitoring time

hysteresis

operation mode

Derivative time

LBaT

AHYS

AL-2

LBaB

D

Manual reset

REST

Digital input

Control output MV in case

Parameter

key

of input break error

lock

DI-K

ErMV

LOC

Hysteresis

HYS

3sec.

3sec.

key once in SV setting group, it returns to RUN mode).

might not be displayed depending on other parameter settings.

2. Parameter 2group

key: Moves parameter and saves the set,

or

key: Changes the set

Parameter

Display

Description

Setting range: Refer to ‘ Input Sensor And Temperature Range’.

Input sensor

If changing input sensor, SV, IN-B, H-SV, L-SV, AL1, AL2, LBaT,

IN-T

LBaB, AHYS parameter values are initialized.

?C

?F

Temperature unit UNIT

If changing temperature unit, SV, IN-B, H-SV, L-SV, AL1, AL2,

LBaT, LBaB, AHYS parameter values are initialized.

Setting range

Input correction

● KCaH, JIcH, LIcH, TCcH, RPR, SRP, DPtH, CUsH:-999 to 999℃/℉

IN-B

● KCaL, JIcL, LIcL, TCcL, DPtL, CUsL: -199.9 to 999.9℃/℉

Input digital filter

Setting range: 0.1 to 120.0 sec.

MAvF

Setting range: Within the rated temperature range by input

sensor[

When changing SV lower limit value, if SV

L-SV, SV is initialized as L-SV.

SV low-limit value L-SV

In case of changing input sensor type[IN-T], it changes automatically as min.

value of the changed input sensor.

Setting range: Within the rated temperature range by input sensor[ H-SV

SV high-limit

When changing SV higher limit value, if SV

H-SV, SV is initialized as

H-SV

value

In case of changing input sensor type [IN-T], it changes automatically as

max. value of the changed input sensor.

Control output

HEAT

COOL

O-FT

operation

When changing control output operation, ErMV is initialized.

PID

ONOF

Control type

When changing control type, ErMV is initialized (control output MV is

C-MD

below 100%) and DI-T turns OFF automatically.

Control output type

OUT

RLY

SSR

STND

CYCL

PHAS

SSR drive output

SSrM

It is displayed when selecting control output [OUT] as [SSR].

method

It is not displayed for AC/DC power model (TCN4 -22R).

Setting range: 0.5 to120.0 sec.

In case of Relay drive output [RLY] of control output [OUT], it is set as

Control cycle

T

20.0 sec. In case of SSR drive output [SSR] of that, it is set as 2.0 sec.

T is not displayed when SSR drive output [SSR.M] method is set as CYCL, PHAS.

AL1 alarm

AM)_

AM!A

AM@A

AM^A

SBaA

AL-1

operation mode

SBaB

SBaA

LBaB

AM!A

AM!B

AM!C

AM!D

AM!E

AL2 alarm

AL-2

For more details refer to

Functions 6. Alarm.

operation mode

Black: Flashes, Gray: Fixed

When changing AL1, AL2 alarm operation mode, AL1, AL2 alarm

temperature value are initialized.

Setting range: Refer to

Functions 4. Alarm output hysteresis.

Alarm output

is not displayed when AL1, AL2 alarm operation mode [AL-1,

AHYS

AHYS

hysteresis

AL-2] is set as [AM0._,

,

].

SBa

LBa

Setting range: 0 to 9999 sec.

LBA monitoring

‘0’ is set, loop break alarm function is OFF.

LBaT

time

is displayed when AL1, AL2 alarm operation mode [AL-1,

LBaT

AL-2] is set as

LBa

.

Setting range: 0 to 999(0.0 to 999.9)

, ‘0’ is set, loop break alarm function is OFF.

LBA monitoring

is displayed when AL1, AL2 alarm operation mode [AL-1,

LBaB

LBaB

range

AL-2] is set as

LBa

and

LBaT

is not ‘0’.

STOP

AlRE

AT

OFF

Press

keys for 3 sec. and it executes the set function.

Digital input key

DI-K

For more information, refer to

Functions 5. Digital input key.

When control type [C-MD] is ONOF, AT is not displayed.

Setting range 0.0 to 100.0%

Control output

Only 0.0, 100% are displayed when control type [C-MD] is set as ONOF.

MV in case of

ErMV

When changing PID control to ON/OFF control, if MV is below

input break error

100.0%, it is initialized as 0.0%.

OFF

LOC1

LOC2

LOC3

LOC1: Locks parameter 2 group, LOC2: Locks parameter 1, 2 group

Parameter lock

LOC

LOC3: Locks parameter 1, 2 group and SV setting

Parameter setting values are still possible to check when parameter lock is set.

key: Moves parameter and saves the set,

3. Parameter 1 group

key: Moves digit,

or

key: Changes the set

Parameter

Display

Description

Setting range: Deviation alarm(-F.S to F.S), Absolute value alarm(temperature range)

AL1 alarm temp.

AL1

In case alarm operation mode [AL-1, AL-2] of Parameter 2 group AM)_/

AL2 alarm temp.

AL2

, no parameters is displayed.

SBa

/

LBA

Auto tuning

Front AT indicator flashes during auto tuning operation.

AT

OFF

ON

Proportional band

Setting range: 0.1 to 999.9

P

Integral time

I

Setting range: 0 to 9999 sec. Integral operation is OFF when set value is «0».

Derivative time

D

Setting range: 0 to 9999 sec. Derivative operation is OFF when set value is «0».

Manual reset

Setting range: 0.0 to

100.0%/ It is displayed in P/PD control.

REST

Setting range

● KCaH, JIcH, LIcH, TCcH, RPR, SRP, DPtH, CUsH:

Hysteresis

HYS

● KCaL, JIcL, LIcL, TCcL, DPtL, CUsL:

0.1 to 50.0

It is displayed when control type [C-MD] of parameter 2 group is set ONOF.

4. SV setting

You can set the temperature to control with

keys.

Setting range is within SV lower limit value [L-SV] to SV higher limit value [H-SV].

E.g.) In case of changing set temperature from 210ºC to 250ºC

①RUN mode

Press any key among

,

,

,

once.

②SV setting mode

Change SV

by

,

,

keys

④Check SV

5. Parameter reset

Reset all parameters as factory default. Hold the front

+ +

keys for 5 sec., to enter parameter reset

[INIT] parameter. Select ‘YES’ and all parameters are reset as factory default. Select ‘NO’ and previous

settings are maintained. If setting parameter lock [LOC] or processing auto-tuning, parameter reset is

unavailable.

Functions

key: Moves digit,

1. Auto tuning [AT]

Auto tuning measures the control subject’s thermal characteristics and thermal response rate, and then

determines the necessary PID time constant. (When control type[C-MD] is set as PID, it is displayed.)

Application of the PID time constant realizes fast response and high precision temperature control.

If error [OPEN] occurs during auto tuning, it stops this operation automatically. To stop auto tuning,

change the set as [OFF]. (It maintains P, I, D values of before auto tuning.)

2. Hysteresis [HYS]

In case of ON/OFF control, set between ON and OFF intervals

as hysteresis. (When control type [C-MD] is set as ONOF, it

is displayed.) If hysteresis is too small, it may cause control

output hunting (takeoff, chattering) by external noise, etc.

L-SV

(H-SV-1digit)]

3. SSR drive output selection(SSRP function) [SSrM]

● SSRP function is selectable one of standard ON/OFF control, cycle control, phase control by utilizing

standard SSR drive output.

● Realizing high accuracy and cost effective temperature control as linear output(cycle control and

(L-SV+1digit)]

phase control).

H-SV.

● Select one of standard ON/OFF control [STND], cycle control [CYCL] , phase control [PHAS] at [SSrM]

parameter of parameter 2 group. For cycle control, connect zero cross turn-on SSR or random

turn-on SSR. For phase control, connect random turn-on SSR.

Temperature controller

(TCN4 series)

SSR drive output

(12VDC)

Power

100-240VAC

50/60Hz

When selecting phase or cycle control mode, the power supply for load and temperature

LBaA

controller must be the same.

In case of selecting PID control type and phase [PHAS] / cycle [PHAS] control output modes, control

cycle [T] is not allowed to set.

LBaA

For AC/DC power model (TCN -22R), this parameter is not displayed and it is available only standard

control by relay or SSR.

AM!F

1)Standard ON/OFF control mode [STND]

A mode to control the load in the same way as Relay output type.

(ON: output level 100%, OFF: output level 0%)

AC

OUT

ON

OFF

ON

2)Cycle control mode [CYCL]

A mode to control the load by repeating output ON / OFF according to the rate of output within setting

cycle. Having improved ON / OFF noise feature by Zero Cross type.

AC

OUT

50Cycle

50%

3)Phase control mode [ PHAS]

A mode to control the load by controlling the phase within AC half cycle. Serial control is available.

RANDOM Turn-on type SSR must be used for this mode.

AC

OUT

10%

4. Alarm output hysteresis [AHYS]

It displays alarm output ON and OFF interval and hysteresis is applied to both AL1 OUT and AL2 OUT.

KCaH, JIcH, LIcH, TCcH, RPR, SPR, DPtH, CUsH: 1 to 100

KCaL, JIcL, LIcL, TCcL, DPtL, CUsL: 0.1 to 50.0

E.g.) AL1 alarm operation[AL-1]: AM#A

Temp.

AL1 alarm operation[AL1]: 10ºC

Alarm output hysteresis[AHYS]: 4 210ºC

SV 200ºC

1 to 100

190ºC

ON

AL1 OUT

OFF

210

5. Digital input key ( +

3sec.) [DI-K]

Parameter

Operation

OFF

OFF

It does not use digital input key function.

Pauses control output. Auxiliary output (except loop break alarm, sensor break alarm)

except Control output operates as setting. Hold the digital input keys for 3 sec. to restart.

t

t

t

RUN/STOP

STOP

③ Completes

SV setting

RUN

STOP

RUN

Clears alarm output by force.

(only when alarm option is alarm latch, or alarm latch and standby sequence 1/2

Clear alarm

AlRE

This function is applied when present value is out of alarm operation range but alarm

output is ON.

Alarm operates normally right after clearing alarm.

Starts/Stops auto-tuning. This function is same as auto-tuning[AT] of parameter 1 group.

(You can start auto-tuning [AT] of parameter 1 group and stop it by digital input key.)

Auto-tuning

※ This parameter

AT appears only when

control method

AT

is set as PID. When

control method

[C-MD]

parameter is changed as OFF.

Set both alarm operation and alarm option by combining.

6. Alarm

Alarm outputs are two and each one operates individually.

AM!A

When the current temperature is out of alarm range, alarm clears

Alarm

Alarm

automatically. If alarm option is alarm latch or alarm latch and standby

operation

option

sequence 1/2, press digital input key( +

key[DI-K] of parameter 2 group set as AlRE), or turn OFF the power

1)Alarm operation

and turn ON to clear alarm.

Mode

Name

Alarm operation

AM)_

Heating operation

OFF

H

ON

Deviation

ON

OFF

high-limit

AM!

SV

PV

Hysteresis

alarm

100℃

110℃

High deviation: Set as 10℃

[HYS]

Temperature

ON

H

OFF

Deviation

SV

low-limit

AM@

PV

SV

alarm

90℃

100℃

Lower deviation: Set as 10℃

Deviation

ON

H

high/low-

AM#

limit

PV

90℃

alarm

High/Lower deviation: Set as 10℃

Deviation

OFF

H

high/low-

AM$

limit

PV

SSR Module

reserve

90℃

Load

High/Lower deviation: Set as 10℃

alarm

OFF

H

ON

Absolute

value high

PV

SV

AM%

90℃

100℃

limit alarm

Absolute-value Alarm:

Set as 90℃

ON

H

OFF

Absolute

AM^

value low

PV

SV

90℃

100℃

limit alarm

Absolute-value Alarm:

Set as 90℃

Sensor

SBa

break alarm

Loop break

LBa

alarm

※ H: Alarm output hysteresis[AHYS]

2)Alarm opetion

Option Name

Description

Standard

If it is an alarm condition, alarm output is ON. If it is a clear alarm condition, alarm output

AM .A

alarm

is OFF.

If it is an alarm condition, alarm output is ON and maintains ON status.

AM .B

Alarm latch

(Alarm output HOLD)

OFF

First alarm condition is ignored and from second alarm condition, standard alarm

Standby

AM .C

operates. When power is supplied and it is an alarm condition, this first alarm condition

sequence 1

is ignored and from the second alarm condition, standard alarm operates.

Alarm latch

If it is an alarm condition, it operates both alarm latch and standby sequence. When

and standby

power is supplied and it is an alarm condition, this first alarm condition is ignored and

AM .D

sequence 1

from the second alarm condition, alarm latch operates.

First alarm condition is ignored and from second alarm condition, standard alarm

Standby

operates. When re-applied standby sequence and if it is alarm condition, alarm output

AM .E

sequence 2

does not turn ON. After clearing alarm condition, standard alarm operates.

Basic operation is same as alarm latch and standby sequence1. It operates not only by

Alarm latch

50Cycle

power ON/OFF, but also alarm setting value, or alarm option changing. When re-applied

AM .F

and standby

standby sequence and if it is alarm condition, alarm output does not turn ON. After

80%

sequence 2

clearing alarm condition, alarm latch operates.

Condition of re-applied standby sequence for standby sequence 1, alarm latch and standby sequence 1: Power ON

Condition of re-applied standby sequence for standby sequence 2, alarm latch and standby sequence 2: Power ON,

changing set temperature, alarm temperature (AL1, AL2) or alarm operation (AL-1, AL-2), switching STOP mode

to RUN mode.

3)Sensor break alarm

The function that alarm output will be ON when sensor is not connected or when sensor’s disconnection

is detected during temperature controlling. You can check whether the sensor is connected with buzzer

or other units using alarm output contact. It is selectable between standard alarm [SBaA] or alarm latch

[SBaB].

50%

4)Loop break alarm(LBA)

It checks control loop and outputs alarm by temperature change of the subject. For heating

control(cooling control), when control output MV is 100%(0% for cooling control) and PV is not

increased over than LBA detection band [LBaB] during LBA monitoring time [LBaT], or when control

output MV is 0%(100% for cooling control) and PV is not decreased below than LBA detection band

[LBaB] during LBA monitoring time [LBaT], alarm output turns ON.

AHYS: 4

PV

AHYS: 4

Time

206

190

194

Start control

When control output MV is 100%, PV is increased over than LBA detection band [LBaB] during

to

LBA monitoring time [LBaT].

to

The status of changing control output MV (LBA monitoring time is reset.)

Digital input key

t

(t: over 3 sec.)

When control output MV is 0% and PV is not decreased below than LBA detection band [LBaB]

to

during LBA monitoring time [LBaT], loop break alarm (LBA) turns ON after LBA monitoring time.

STOP

RUN

to

Control output MV is 0% and loop break alarm (LBA) turns and maintains ON.

to

The status of changing control output MV (LBA monitoring time is reset.)

.)

When control output MV is 100% and PV is not increased over than LBA detection band [LBaB]

to

during LBA monitoring time [LBaT], loop break alarm (LBA) turns ON after LBA monitoring time.

When control output MV is 100% and PV is increased over than LBA detection band [LBaB] during

to

LBA monitoring time [LBaT], loop break alarm (LBA) turns OFF after LBA monitoring time.

to

The status of changing control output MV (LBA monitoring time is reset.)

[C-MD]

parameter 2 group

When executing auto-tuning, LBA detection band[LBaB] and LBA monitoring time are automatically set

parameter 2 group

is set as ONOF, this

based on auto tuning value. When alarm operation mode [AL-1, AL-2] is set as loop break alarm(LBA)

[LBa ], LBA detection band [LBaB] and LBA monitoring time [LBaT] parameter is displayed.

7. Manual reset[REST]

When selecting P/PD control mode, certain temperature

difference exists even after PV reaches stable status because

heater’s rising and falling time is inconsistent due to thermal

3 sec., digital input

characteristics of controlled objects, such as heat capacity,

heater capacity. This temperature difference is called offset

and manual reset [REST] function is to set/correct offset.

Description

When PV and SV are equal, reset value is 50.0%. After control

No alarm output

is stable, PV is lower than SV, reset value is over 50.0% or PV

If deviation between PV and SV

OFF

H

ON

is higher than SV, reset value is below 50.0%.

as high-limit is higher than set

8. Input correction[IN-B]

PV

SV

value of deviation temperature,

Controller itself does not have errors but there may be error by external input temperature sensor.

90℃

100℃

the alarm output will be ON.

High deviation: Set as -10℃

This function is for correcting this error.

If deviation between PV and SV

E.g.) If actual temperature is 80ºC but controller displays 78ºC, set input correction value [IN-B] as

ON

H

OFF

‘002’ and controller displays 80ºC.

as low-limit is higher than set

SV

PV

value of deviation temperature,

As the result of input correction, if current temperature value (PV) is over each temperature range

100℃

110℃

the alarm output will be ON.

of input sensor, it displays ‘HHHH’ or ‘LLLL’.

Lower deviation: Set as -10℃

9. Input digital filter[MAvF]

OFF

H

ON

If deviation between PV and SV

If current temperature (PV) is fluctuating repeatedly by rapid change of input signal, it reflects to MV

as high/low-limit is higher than set

and stable control is impossible. Therefore, digital filter function stabilizes current temperature value.

SV

PV

value of deviation temperature,

100℃

110℃

For example, set input digital filter value as 0.4 sec, and it applies digital filter to input values during 0.4

the alarm output will be ON.

sec and displays this values. Current temperature may be different by actual input value.

ON

H

OFF

If deviation between PV and SV

10. Error

as high/low-limit is higher than set

Display

Description

SV

PV

value of deviation temperature,

100℃

110℃

the alarm output will be OFF.

OPEN

Flashes if input sensor is disconnected or sensor is not connected. Check input sensor state.

Flashes if measured sensor input is higher than temperature range. When input is within the rated

HHHH

OFF

H

ON

LLLL

Flashes if mesured sensor input is lower than temperature range

If PV is higher than the absolute

SV

PV

value, the output will be ON.

100℃

110℃

Absolute-value Alarm:

Factory Default

Set as 110℃

1. SV setting

ON

H

OFF

Parameter Default

If PV is lower than the absolute

SV

PV

value, the output will be ON.

100℃

110℃

Absolute-value Alarm:

2. Parameter 1 group

Set as 110℃

It will be ON when it detects

Parameter Default

sensor disconnection.

AL1

1250

It will be ON when it detects loop

AL2

1250

break.

3. Parameter 2 group

Parameter Default

IN-T

KCaH

UNIT

?C

IN-B

0000

MAvF

00)1

L-SV

-050

The AC/DC voltage models do not have SSR drive output method[SSrM]. In case of control output

[ OUT] , if set as SSR, it supports only ON/OFF output.

Installation

TCN4S(48×48mm) Series

Insert product into a panel, fasten bracket by pushing with tools as shown above.

Cautions during Use

1. Follow instructions in ‘Cautions during Use’. Otherwise, It may cause unexpected accidents.

2. Check the polarity of the terminals before wiring the temperature sensor.

For RTD temperature sensor, wire it as 3-wire type, using cables in same thickness and length.

For thermocouple (CT) temperature sensor, use the designated compensation wire for extending wire.

3. Keep away from high voltage lines or power lines to prevent inductive noise.

In case installing power line and input signal line closely, use line filter or varistor at power line and

shielded wire at input signal line.

Do not use near the equipment which generates strong magnetic force or high frequency noise.

4. Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting

the power.

5. Do not use the unit for other purpose (e.g. voltmeter, ammeter), but temperature controller.

6. When changing the input sensor, turn off the power first before changing.

After changing the input sensor, modify the value of the corresponding parameter.

7. 24VAC, 24-48VDC power supply should be insulated and limited voltage/current or Class 2, SELV

power supply device.

8. Make a required space around the unit for radiation of heat.

Time

For accurate temperature measurement, warm up the unit over 20 min after turning on the power.

9. Make sure that power supply voltage reaches to the rated voltage within 2 sec after supplying power.

10. Do not wire to terminals which are not used.

11. This unit may be used in the following environments.

①Indoors (in the environment condition rated in ‘Specifications’)

③Pollution degree 2

Major Products

Photoelectric Sensors

Fiber Optic Sensors

Door Sensors

Door Side Sensors

Area Sensors

Proximity Sensors

Pressure Sensors

Rotary Encoders

Connector/Sockets

Switching Mode Power Supplies

Control Switches/Lamps/Buzzers

I/O Terminal Blocks & Cables

Stepper Motors/Drivers/Motion Controllers

Graphic/Logic Panels

Field Network Devices

Laser Marking System (Fiber, Co₂, Nd: YAG)

Laser Welding/Cutting System

·Manual reset [REST] by control result

Set below 50.0 as reset value

Offset

SV

Offset

Set over 50.0 as reset value

Measured value

Troubleshooting

temperature range, this display

disappears.

0

Parameter Default

Parameter Default

Parameter Default

AT

OFF

I

0000

REST

05)0

P

01)0

D

0000

HYS

002

Parameter Default

Parameter Default

Parameter Default

H-SV

1200

T

02)0

LBaB

0002

O-FT

HEAT

AL-1

AMiA

DI-K

STOP

C-MD

PID

LA-2

Am@A

ErMV

00)0

OUT

RLY

AHYS

001

LOC

OFF

SSrM

STND

LBaT

0000

Other Series

②Altitude max. 2,000m

④Installation category II

Temperature Controllers

Temperature/Humidity Transducers

SSRs/Power Controllers

Counters

Timers

Panel Meters

Tachometer/Pulse (Rate) Meters

Display Units

Sensor Controllers

http://www.autonics.com

HEADQUARTERS:

18, Bansong-ro 513beon-gil, Haeundae-gu, Busan,

South Korea, 48002

TEL: 82-51-519-3232

E-mail: sales@autonics.com

DRW170776AA

TCN4_EN(EP-KE-03-0350) RU

Представленные в документации товары

Наименование Краткое описание Карточка
товара
TCN4S-24R (AUTONICS) Внешний вид TCN4S-24R
TCN4M-24R (AUTONICS)
TCN4M-24R 100-240VAC50/60Hz (AUTONICS)
Внешний вид TCN4M-24R

Скачать документацию: Документация на TCN4S-24R (1.26 Мб)

Понравилась статья? Поделить с друзьями:
  • Danfoss терморегулятор на батарею инструкция по применению
  • Вориконазол инструкция по применению цена отзывы аналоги таблетки
  • Abro epoxy steel 4 minute kwik set инструкция
  • Креон 10000 инструкция по применению взрослым от чего помогает цена
  • Siemens wash dry 2100 инструкция по применению