-
Contents
-
Table of Contents
-
Bookmarks
Quick Links
Installation and Service
Instructions
for use by heating contractor
Vitotronic 300, Type GW5B
Digital boiler control unit
Vitotronic 300-K, Type MW1B
Weather-compensated digital cascade control unit
VITOTRONIC 300, GW5B
VITOTRONIC 300-K, MW1B
Certified as a component
part for Viessmann boilers
5693 973 — 03 07/2014
Vitotronic 300, GW5B
Vitotronic 300-K, MW1B
Product may not be exactly as shown
IMPORTANT
Read and save these instructions
for future reference.
Please file in Service Binder
Summary of Contents for Viessmann VITOTRONIC 300
- Manuals
- Brands
- Viessmann Manuals
- Heating System
- VITOTRONIC 300
Manuals and User Guides for Viessmann VITOTRONIC 300. We have 10 Viessmann VITOTRONIC 300 manuals available for free PDF download: Installation And Service Instructions Manual, Installation Instructions Manual, Operating Instructions Manual, Technical Data Manual
Viessmann VITOTRONIC 300 Installation And Service Instructions Manual (164 pages)
For contractors. Type CM1E, CC1E
Brand: Viessmann
|
Category: Controller
|
Size: 10.04 MB
Table of Contents
-
Table of Contents
6
-
Liability
15
-
Information Disposal of Packaging
16
-
-
Disposal of Packaging
17
-
Product Information
17
-
Installation Sequence Installing the Extension for Heating Circuits 2 and 3
18
-
Adjusting the High Limit Safety Cut-Out (if Required)
19
-
Adjusting the Temperature Controller (if Required)
20
-
Mounting Control Unit Front
21
-
Opening the Control Unit
22
-
Connecting the Extension for Heating Circuits 2 and 3
25
-
Connecting the Network Module
26
-
Outside Temperature Sensor
27
-
Ciency Circulation Pumps
28
-
Pumps in the Underfloor Heating Circuit
30
-
-
Connecting Actuators
31
-
External Functions
32
-
Adding External Boiler as Last in Boiler Sequence
33
-
External Changeover of Multi Stage/Modulating Burners
34
-
External Demand, Common System Flow Temperature
35
-
External Operating Program Changeover (Heating Circuits)
36
-
-
Provisional Burner Operation
37
-
Connecting an AC Burner
38
-
Connecting a Three-Phase Burner
40
-
Safety Chain Not Potential-Free
41
-
Connection Examples
42
-
Control Unit Power Supply
44
-
Commissioning Commissioning the System
46
-
Matching the Control Unit to the Modulating Burner
47
-
Vitotronic 300
48
-
-
Integrating the Control Unit into LON
49
-
Carrying out the LON Subscriber Check
50
-
-
Selecting the Boiler Sequence at the Vitotronic 300
51
-
Adjusting the Set Room Temperature
52
-
Changing the Slope and Level
53
-
Parameter Levels Parameter Levels
56
-
System Scheme
57
-
-
Time Constant for Calculating the Adjusted Outside Temperature
58
-
Fault Message Module 2
59
-
Extension AM1
60
-
-
Extension EA1
61
-
Function, Input DE3 at Extension EA1
62
-
-
Sensor 17B
63
-
Pump
64
-
-
Communication LON
65
-
Automatic Summer/Wintertime Changeover
66
-
Winter Time Starts: Month
67
-
LON Communication Module: Outside Temperature
68
-
-
Boiler, Vitotronic 300
69
-
Maximum Boiler Water Temperature Limit
70
-
C Function Butterfly Valve
71
-
Runtime Servomotor Mod. Burner
72
-
F Flue Gas Temperature Sensor
73
-
Burner Fuel Consumption (Stage 2)
74
-
Cascade, Vitotronic 300
75
-
Permanent Last Boiler
76
-
A Cylinder Priority Control
77
-
ECO Threshold Boiler 1
78
-
ECO Threshold Boiler 6
79
-
Selection of Set DHW Temperature
80
-
Circulation Pump for Cylinder Heating
81
-
C for Solar DHW Heating: DHW Temperature Target
82
-
DHW Circulation Pump for DHW Heating
83
-
-
Solar, Vitotronic 300
84
-
Max. Speed, Solar Circuit Pump
85
-
C Delta T Monitoring
86
-
Minimum Collector Temperature
87
-
Start Temperature for Thermostat Function
88
-
-
Heating Circuit 1, Heating Circuit 2, Heating Circuit 3, Vitotronic 300
89
-
Temperature Limits, Frost Protection Function
90
-
Heating Limit: Economy Function: Outside Temperature
91
-
Pump Idle Time
92
-
E Economy Function: Room Temperature
93
-
Learning Start Optimisation
94
-
System Dynamics Mixer
95
-
Extension EA1: Operating Program Changeover
96
-
Time Limit for Comfort Mode
97
-
Perature
98
-
System Scheme
99
-
Burner Control Unit Connection
100
-
-
Function, Output A2 at Extension AM1
101
-
Connection at Plug 20A1
102
-
Pump
103
-
LON Communication Module: Fault Manager
104
-
Viessmann System Number
105
-
Switching Hysteresis Burner
106
-
Maximum Burner Output in Kw
107
-
D Function Therm Control
108
-
Burner Offset with Start Optimisation
109
-
Interval in Burner Hours until the Next Service
110
-
A Burner Fuel Consumption (Stage 2)
111
-
Change Passwords
113
-
Brief Scan
114
-
-
LON Service PIN
115
-
Deactivating the Wifi Connection
116
-
Acknowledging the Fault Display
117
-
Lead Break, Outside Temperature Sensor
118
-
A LAN Hardware Error
119
-
Short Circuit, Cylinder Temperature Sensor 1
120
-
Short Circuit, Temperature Sensor 17A
121
-
Short Circuit, Sensor 7, Solar Control Module, Type SM1
122
-
Lead Break, Sensor 10, Solar Control Module, Type SM1
123
-
A0 Fault Message Module 2: Safety Equipment 1
124
-
AC Configuration Fault, Return Temperature Control
125
-
B7 Coding Card
126
-
BE Communication Error, Remote Control, Heating Circuit 3
127
-
C8 Fault Message Module 1, Input 1: Water Level Limiter
128
-
CF Communication Error, LON Communication Module
129
-
D6 Fault Message at Digital Input 1, EA1 Extension
130
-
DE Lead Break, Room Temperature Sensor Vitotrol, HC 2
131
-
Outside Temperature Sensor
132
-
-
-
Fault Indicator
117
-
Checking the Fuses
133
-
Brief Description
134
-
-
Cascade Control
135
-
Standalone Control
136
-
Control Strategies
137
-
-
Control of the Heating Circuits
139
-
Control Sequence
142
-
Functions
143
-
Control Sequence
144
-
-
Plug-In Adaptor for External Safety Equipment (Accessories)
145
-
EA1 Extension (Accessories)
146
-
Analogue Input 0 – 10 V
147
-
Functions
148
-
-
-
Boiler Function Description
149
-
Vitotronic 300
150
-
PCB, Low Voltage
152
-
PCB, Extension for Heating Circuits 2 and 3 with Mixer
153
-
-
Vitotronic 100
154
-
PCB, Low Voltage
156
-
-
-
Specification for Vitotronic 300 and Vitotronic 100
158
-
Declaration of Conformity
159
Advertisement
Viessmann VITOTRONIC 300 Installation And Service Instructions Manual (116 pages)
Type GW5B & MW1B, Digital boiler control unit & Weather-compensated digital cascade control unit
Brand: Viessmann
|
Category: Control Unit
|
Size: 2.37 MB
Table of Contents
-
Safety, Installation and Warranty Requirements
2
-
Product Documentation
2
-
Warranty
2
-
Licensed Professional Heating Contractor
2
-
Advice to Owner
2
-
Operating and Service Documentation
2
-
-
Product Information
2
-
Table of Contents
3
-
About These Instructions
6
-
For Your Safety
7
-
Operation
7
-
Flue Gas Smell
7
-
Working on the Equipment
7
-
Maintenance and Cleaning
7
-
Technical Data Manual
7
-
If You Smell Gas
7
-
In Emergencies
7
-
Installation of Additional Components
7
-
Boiler Room Conditions
7
-
-
Designation in the System Example
8
-
Overview of System Example
8
-
System Example
9
-
Overview of Electrical Connections
15
-
External Connection Overview
17
-
Inserting Cables and Applying Strain Relief
18
-
Inserting the Boiler Coding Card
18
-
Inserting the LON Communication Module
19
-
Connecting Sensors
19
-
External Connection
19
-
Connecting Actuators
21
-
Connection the Central Fault Massage Facility
22
-
Connection of Low Water Cut-Off Device
22
-
Connections to Terminal 150
23
-
Connections to Terminal 151
23
-
Blocking Boiler Externally/Adding to the Boiler Sequence
24
-
Connecting a Burner
25
-
Preparing Boilers for Cascade Mode
25
-
Overview of Electrical Connections
26
-
Mounting the Control Unit
28
-
Inserting Cables/Leads and Applying Strain Relief
29
-
Connecting Pumps
30
-
Connecting Sensors
31
-
External Connection
32
-
Connecting Actuators
33
-
Connection Central Fault Massage Facility
34
-
External Demand Via Switching Contact
34
-
External Demand Via 0-10V Input
35
-
External Blocking Via Switching Contact
35
-
External «Mixing Valve Closed»/»Mixing Valve Open
36
-
External Heating Program Changeover
36
-
Making the LON Connection
37
-
Power Supply
38
-
Fitting the Control Unit Front
39
-
Opening the Control Unit
39
-
Changing the Language on the Vitotronic 300-K
40
-
Testing the High Limit Safety Cut-Out
40
-
Setting the Date and Time the Vitotronic 300-K
40
-
Matching the Coding Addresses to the System Version
41
-
Selecting the Boiler Sequence at the Vitotronic 300-K
42
-
Connecting the Control Unit to the LON
43
-
Checking Actuators and Sensors at the Vitotronic 300 GW5B
46
-
Vitotronic 300-K
47
-
Adjusting Heating Curves
48
-
Calling up the Service Menu
50
-
Exiting Service Menu
50
-
Calling up Service Menu
51
-
Scanning Operating Data
51
-
Brief Scan
52
-
Scanning and Resetting Service Display
52
-
Fault Codes
53
-
Fault Display
55
-
Fault Codes
56
-
Boiler Temperature Control of the Vitotronic 300 GW5B
60
-
Cascade Control of the Vitotronic 300-K
62
-
Heating Circuit Control Unit of the Vitotronic 300
65
-
DHW Tank Temperature Control of the Vitotronic 300-K
69
-
Calling up Coding Level 1
71
-
Group 1 «General
71
-
Group 2 «Boiler
72
-
Calling up Coding Level 2
73
-
Group 1 «General
74
-
Group 2 «Boiler
78
-
Calling up Coding Level 1
79
-
General» Group
80
-
Cascade» Group
81
-
DHW» Group
81
-
Solar» Group
82
-
Heating Circuit 1″, «Heating Circuit 2», «Heating Circuit 3» Group
83
-
Calling up Coding Level 2
86
-
General» Group
87
-
Cascade» Group
92
-
DHW» Group
93
-
Solar» Group
95
-
Heating Circuit 1″, «Heating Circuit 2», «Heating Circuit 3» Group
98
-
Connection and Wiring Diagram
103
-
Connection and Wiring Diagram
106
-
Sensors
110
-
Boiler Coding Card
111
-
Mixing Valve Motor Kit
111
-
Extension EA1 Accessory (Optional)
112
-
Parts List Vitotronic 300, GW5B
113
-
Parts List Vitotronic 300-K
114
-
Specification Vitotronic 300, GW5B
115
-
Specification Vitotronic 300-K
115
Viessmann VITOTRONIC 300 Installation Instructions Manual (128 pages)
Weather-compensated boiler and heating circuit control unit in single boiler or multi boiler systems
Brand: Viessmann
|
Category: Control Unit
|
Size: 2.96 MB
Table of Contents
-
Safety, Installation and Warranty Requirements
2
-
Product Information
2
-
Table of Contents
3
-
About These Instructions
5
-
For Your Safety
6
-
Overview of System Example
7
-
Designations in the Example
7
-
System Examples
8
-
Single Boiler System
8
-
Multi Boiler System
12
-
Components
14
-
-
Overview of Electrical Connections
21
-
Boiler Control and Junction Box
26
-
Mounting the Control Unit
26
-
Opening the Control Unit
27
-
Plugging in the Boiler Coding Card
27
-
Inserting Cables and Applying Strain Relief
28
-
Connecting Sensors
28
-
Control Power Supply
29
-
Connecting the Burner
30
-
Connecting Pumps
31
-
Specification
33
-
Connecting a Central Fault Massage Facility
34
-
Connecting Actuators
34
-
Connection of Low Water Cut-Off Device
36
-
Connecting External Safety Equipment
37
-
Connections to Terminal Aba
38
-
Provisional Burner Operation
39
-
Sequence
40
-
External Blocking Via Switching Contact
41
-
External Demand Via Switching Contact
42
-
External «Mixing Valve Closed»/»Mixing Valve Open
43
-
External Demand Via 0 -10V Input
43
-
External Operating Program Changeover
44
-
Components
45
-
Power Supply
45
-
Making the LON Connection
46
-
Commissioning the System
48
-
Adjusting Coding
49
-
Connecting the Control Unit to the LON
50
-
Setting the Boiler Sequence at the Cascade Control Unit
52
-
Carrying out an Actuator Test
53
-
Checking Sensors
54
-
Adjusting the Heating Curve
54
-
Calling up the Service Menu
57
-
Leaving the Service Menu
58
-
Change Passwords
58
-
Resetting All Passwords to Factory Settings
58
-
Scanning Operating Data
59
-
Resetting Operating Data
59
-
Brief Scan
60
-
Maintenance Display
61
-
Fault Display
62
-
Boiler System Fault Codes
63
-
Burner Fault Codes
69
-
Boiler Water Temperature Control
72
-
Cascade Control Unit
72
-
Heating Circuit Control Unit
77
-
DHW Tank Temperature Control
81
-
Calling up Coding Levels
85
-
Resetting Coding to Their Factory Set Condition
85
-
General» Group
86
-
Combustion Controller» Group
88
-
Boiler» Group
88
-
Cascade» Group
89
-
DHW» Group
91
-
Solar» Group
91
-
Heating Circuit
92
-
General» Group
95
-
Combustion Controller» Group
102
-
Boiler» Group
103
-
Cascade» Group
103
-
DHW» Group
106
-
Solar» Group
108
-
Heating Circuit
111
-
Connection and Wiring Diagram
117
-
EA1 Extension
120
-
Sensors
121
-
Extension EA1 Accessory (Optional)
122
-
Parts List — Programming Module
123
-
Parts List — Connection Module
124
-
Specification Vitotronic 300, GW6B
125
Advertisement
Viessmann VITOTRONIC 300 Installation And Service Instructions Manual (146 pages)
Outdoor-reset logic digital boiler and heating circuit control unit
Brand: Viessmann
|
Category: Control Unit
|
Size: 5.8 MB
Table of Contents
-
Start-Up Procedure (Overview)
63
-
General Information
2
-
Table of Contents
63
-
Controls and Indicators
64
-
Check Assignment of Heating Circuits
64
-
Check the Fixed High Limit
65
-
Select the Language (if Required)
65
-
Integrate the Control Unit in the LON BUS System (in Conjunction with Heating Circuits Connected Downstream)
66
-
Carry out Participant Check
67
-
Match the Control Unit to the System Type
68
-
Check Outputs (Actuators) and Sensors
68
-
Match the Coding Addresses
69
-
Adjust the Heating Curves
71
-
Troubleshooting
79
-
Outdoor Sensor
80
-
-
-
Overview
92
-
Technical Data
93
-
Electronics Board
94
-
Line-Voltage Motherboard
94
-
Low-Voltage Motherboard
94
-
Power Supply Unit Board
94
-
System Components
94
-
Optolink/Emissions Test Switch Board
95
-
Programming Unit
95
-
Adjustable High Limit
96
-
Fuses
96
-
TEST Button
96
-
Outdoor Temperature Sensor
99
-
Strap-On Temperature Sensor/Immersion Temperature Sensor
102
-
Flue Gas Temperature Sensor
104
-
Installation Examples
105
-
Room Temperature Sensor
106
-
Remote Control
107
-
-
Vitotrol
106
-
Vitotrol 200
106
-
Input Module 0 to 10V
113
-
Call up Coding Level 1
114
-
Coding 1
114
-
Codings
114
-
Coding 1
115
-
Call up Coding Level 2
116
-
Overview of All Codings
117
-
Reset Codings to Factory Settings
117
-
Wiring Diagram
139
-
Viessmann VITOTRONIC 300 Installation And Service Instructions Manual (88 pages)
Type GW5B, Vitotronic 300, Type GW5B Weather-compensated, digital boiler control unit for boiler model CM2 — 400, 500, 620 and 620 TX
Brand: Viessmann
|
Category: Control Unit
|
Size: 1.88 MB
Table of Contents
-
Safety, Installation and Warranty Requirements
2
-
Product Documentation
2
-
Licensed Professional Heating Contractor
2
-
Advice to Owner
2
-
Warranty
2
-
Operating and Service Documentation
2
-
-
Product Information
2
-
Table of Contents
3
-
Overview of System Example
5
-
Designations in the System Example
5
-
System Example
6
-
Technical Data
7
-
Overview of Electrical Connections
11
-
Inserting Cables and Applying Strain Relief
14
-
Inserting the Boiler Coding Card
14
-
Connecting Sensors
15
-
Connect Sensors
15
-
External Connection
16
-
Connecting the Central Fault Message Facility
18
-
Connecting Actuators
19
-
Connection to Low Water Cut-Off Device
20
-
Connection to Terminal 151
20
-
External Demand Via Switching Contact
21
-
External Demand Via 0-10V Input
21
-
External «Mixer Closed»/»Mixer Open
22
-
External Block Via Switching Contact
22
-
External Heating Program Changeover
23
-
Provisional Burner Operation
24
-
Connecting a Burner
24
-
Power Supply
25
-
Boiler Control and Junction Box
28
-
Mounting the Control Unit
29
-
Opening the Control Unit
29
-
Setting the Language
30
-
Setting the Time and Date
30
-
Testing the High Limit Safety Cut-Out
30
-
Checking Actuators and Sensors
31
-
Adjusting Heating Curves
32
-
Connecting the Control Unit to the LON
34
-
Integrating a Control Unit into the LON
35
-
Entering the Service PIN for LON Participants
35
-
Calling up the Service Menu
36
-
Exiting the Service Menu
36
-
Operating Data
37
-
Brief Scan
38
-
Display
39
-
Fault Codes
40
-
Boiler Water Temperature Control
49
-
Heating Circuit Control Unit
49
-
DHW Tank Temperature Control
53
-
Calling up Coding Level 1
55
-
General» Group
56
-
Boiler» Group
57
-
DHW» Group
58
-
Solar» Group
58
-
Heating Circuit 1″, «Heating Circuit 2», «Heating Circuit 3» Group
59
-
Calling up Coding Level 2
62
-
General» Group
63
-
Boiler» Group
69
-
DHW» Group
69
-
Solar» Group
71
-
Heating Circuit 1″, «Heating Circuit 2», «Heating Circuit 3» Group
74
-
Connection and Wiring Diagram
79
-
Sensors
83
-
Mixing Valve Motor Kit
84
-
Extension EA1 Accessory (Optional)
85
-
Parts List
86
-
Specifications
87
Viessmann VITOTRONIC 300 Operating Instructions Manual (40 pages)
Digital boiler control unit
Brand: Viessmann
|
Category: Control Unit
|
Size: 0.72 MB
Table of Contents
-
Safety, Installation and Warranty Requirements
2
-
Product Documentation
2
-
Licensed Professional Heating Contractor
2
-
Advice to Owner
2
-
Warranty
2
-
-
Safety Terminology
2
-
Table of Contents
3
-
Commissioning
5
-
Your System Is Preset at the Factory
5
-
Controls
6
-
Opening the Control Unit
6
-
Programming Unit
6
-
-
Menu
7
-
Standard Menu
7
-
Selecting the Set Room Temperature
7
-
Setting the Heating Program
7
-
Symbols on Display
7
-
Extended Menu
8
-
-
How to Use the Controls
8
-
Starting the Heating System
10
-
Shutting down the Heating System
11
-
With Frost Protection Monitoring
11
-
For the Heating Circuit Displayed in the Header
11
-
For the Other Heating Circuits
11
-
Ending the Heating Program «Standby Mode
11
-
Without Frost Protection Monitoring (Shutdown)
11
-
Information on a Prolonged Shutdown
11
-
-
Required Settings (Central Heating)
12
-
Selecting a Heating Circuit
12
-
Setting the Room Temperature
13
-
Setting the Room Temperature for Standard Heating Mode
13
-
For the Heating Circuit Displayed in the Header
13
-
For the Other Heating Circuits
13
-
Setting the Room Temperature for Reduced Heating Mode (Night Setback)
13
-
-
Setting the Heating Program for Central Heating
14
-
Setting the Time Program for Central Heating
14
-
Changing the Heating Curve
16
-
Stopping Central Heating
16
-
Select Comfort Function «Party Mode
17
-
Select Comfort Function «Economy Mode
18
-
Select Energy Saving Function «Holiday Program
19
-
Required Settings (DHW Heating)
20
-
Setting the DHW Temperature
20
-
Setting the Heating Program for DHW Heating
20
-
Setting the Time Program for DHW Heating
21
-
Stopping DHW Heating
23
-
Setting the Display Contrast
23
-
Setting the Display Brightness
23
-
Entering the Names for the Heating Circuits
24
-
Changing the Standard Menu
24
-
Setting the Time and Date
25
-
Language Selection
25
-
Setting the Temperature Unit (°C/°F)
25
-
Restoring Factory Settings
25
-
Scanning Information
26
-
Scanning in Conjunction with Solar Thermal Systems
26
-
Resetting Data
26
-
-
Scanning Service Messages
27
-
Display in Standard Menu
27
-
Display in Extended Menu
27
-
Calling up an Acknowledged Fault Message
27
-
-
Scanning Fault Messages
28
-
Display in Standard Menu
28
-
Display in Extended Menu
28
-
Calling up an Acknowledged Fault Message
28
-
-
Burner Fault
29
-
Emissions Test Mode
29
-
Ending Emissions Test Mode
29
-
-
Rooms Are too Cold
30
-
Rooms Are too Hot
31
-
There Is no Hot Water
31
-
Central Control» Is Displayed
32
-
Flashes and «Fault» Is Displayed
32
-
Flashes and «Service» Is Displayed
32
-
Controls Locked Out» Is Displayed
32
-
External Hook-Up» Is Displayed
32
-
External Program» Is Displayed
32
-
The DHW Is too Hot
32
-
Maintenance
33
-
Menu Overview
34
-
Appendix
37
-
Terminology
37
Viessmann VITOTRONIC 300 Operating Instructions Manual (73 pages)
Brand: Viessmann
|
Category: Controller
|
Size: 3.34 MB
Table of Contents
-
Safety Instructions
3
-
Installation Room Requirements
4
-
Introductory Information
9
-
Intended Use
9
-
Operating Principles
12
-
Control Unit Operation
13
-
Special Operating Programs
18
-
Setting the Room Temperature
22
-
Stopping Central Heating
24
-
Setting the «Time Program» for DHW Heating
28
-
Switching off DHW Heating
30
-
Further Adjustments
31
-
Setting the Display Brightness
31
-
Locking the Controls
32
-
Naming Heating Circuits
34
-
Calling up Help Messages
36
-
Calling up Information
36
-
Burner Faults
38
-
Scanning Fault Messages
39
-
Control Unit Controls
41
-
Without Frost Protection Monitoring (Shutdown)
42
-
Rooms Are too Cold
43
-
Rooms Are too Hot
44
-
There Is no Hot Water
45
-
«External Hook-Up» Is Displayed
47
-
«External Program» Is Displayed
47
-
Inspection and Maintenance
48
-
DHW Cylinder (if Installed)
48
-
Potable Water Filter (if Installed)
48
-
Damaged Cables / Lines
49
-
Maintenance
49
-
Fuel Oil Additives
50
-
Combustion Improvers
50
-
Buttons and Icons
51
-
Main Menu Overview
53
-
Heating Circuit Pump
65
-
Information on Disposal
67
-
Your Contact
72
Viessmann VITOTRONIC 300 Operating Instructions Manual (61 pages)
Single boiler system or multi boiler system with weather-compensated control unit.
Brand: Viessmann
|
Category: Controller
|
Size: 1.33 MB
Table of Contents
-
For Your Safety
3
-
Safety Instructions
3
-
Intended Use
7
-
Energy Saving Tips
8
-
Introductory Information
9
-
Tips for Greater Comfort
9
-
Standard Menu
10
-
General Information
13
-
Opening the Control Unit
13
-
Default Display
13
-
Switching on the Heating System
17
-
Shutting down the Heating System
17
-
Operating Program
19
-
Time Program
19
-
Central Heating
21
-
Setting the Time Program Efficiently
21
-
Deleting Time Phases
22
-
Room Temperature
23
-
Setting the Heating Curve
24
-
Stopping Central Heating
25
-
Comfort Function
25
-
DHW Temperature
33
-
DHW Heating
33
-
Setting the Display Backlighting
36
-
Naming Heating Circuits
37
-
Setting the Measuring Units
38
-
Restoring Factory Settings
38
-
Scanning Information
39
-
Resetting Data
40
-
Scanning Service Messages
40
-
Scanning Fault Messages
40
-
Rooms Are too Cold
43
-
Rooms Are too Hot
43
-
There Is no Hot Water
44
-
«Service» Is Displayed
45
-
Inspection and Maintenance
46
-
DHW Cylinder (if Installed)
46
-
Potable Water Filter (if Installed)
46
-
Main Menu Overview
49
-
Your Contact
60
Viessmann VITOTRONIC 300 Operating Instructions Manual (30 pages)
Weather-Compensated, digital boiler and heating circuit control unit
Brand: Viessmann
|
Category: Heating System
|
Size: 0.31 MB
Table of Contents
-
Operating Instructions
1
-
For Your Safety
2
-
Table of Contents
3
-
Ready for Operation the Main Controls
4
-
-
Overview of Controls and Indicators
5
-
Selecting the Heating Program (Winter, Summer)
7
-
Activating the Energy Saving Mode
10
-
Shutting down the Heating System
11
-
Settings Time Programs
12
-
Changing the Domestic Hot Water Temperature
18
-
Resetting the Time and Date
20
-
Changing the Heating Pattern of the Boiler
21
-
Scanning Scanning Temperatures and Operating Status Information
24
-
Troubleshooting Guide
25
-
Remote Control
25
-
Diagnosis and Correction
26
-
Servicing/Cleaning Instructions and Note on Disposal of Unwanted Equipment
29
-
Alphabetical Index
30
Viessmann VITOTRONIC 300 Technical Data Manual (8 pages)
Weather-responsive indoor/outdoor, digital boiler control for heating systems with one or more heating circuits
Brand: Viessmann
|
Category: Control Unit
|
Size: 1.12 MB
Advertisement
Related Products
-
Viessmann Vitotronic 200 Series
-
Viessmann VITOBLOC 200
-
Viessmann VITOLADENS
-
Viessmann VITOPEND
-
Viessmann VITODENS
-
Viessmann VITOSOL300
-
Viessmann VITOTRONIC 200
-
Viessmann VITOTRONIC 100
-
Viessmann VITOTRONIC300
-
Viessmann Vitotronic 300 Series
Viessmann Categories
Boiler
Toy
Control Unit
Heat Pump
Solar panel
More Viessmann Manuals
Installation and Service
Instructions
for use by heating contractor
Vitotronic 300, Type GW5B
Digital boiler control unit
Vitotronic 300-K, Type MW1B
Weather-compensated digital cascade control unit
VITOTRONIC 300, GW5B
VITOTRONIC 300-K, MW1B
Vitotronic 300, GW5B
Certified as a component part for Viessmann boilers
5693 973 — 06 06/2016
Vitotronic 300-K, MW1B
Product may not be exactly as shown
IMPORTANT
Read and save these instructions for future reference.
Please file in Service Binder
2
General
Vitotronic 300, GW5B and MW1B Installation and Service
Safety, Installation and Warranty Requirements
Please ensure that these instructions are read and understood before commencing installation. Failure to comply with the instructions listed below and details printed in this manual can cause product/property damage, severe personal injury, and/or loss of life. Ensure all requirements below are understood and fulfilled (including detailed information found in manual subsections).
Product documentation
Read all applicable documentation before commencing installation. Store documentation near boiler in a
readily accessible location for reference in the future by service personnel.
For a listing of applicable literature,
please see section entitled “Important
Regulatory and Safety Requirements”.
Licensed professional heating contractor
The installation, adjustment, service and maintenance of this equipment must be performed by a licensed
professional heating contractor.
WARNING
Installers must follow local regulations with respect to installation of carbon monoxide detectors. Follow the
Viessmann maintenance schedule of the boiler contained in this manual.
Operating and Service Documentation
It is recommended that all product documentation such as parts lists, operating and service instructions be handed over to the system user for storage.
Documentation is to be stored near boiler in a readily accessible location for reference by service personnel.
Please see section entitled
“Important Regulatory and Installation
Requirements”.
Advice to owner
Once the installation work is complete, the heating contractor must familiarize the system operator/ ultimate owner with all equipment, as well as safety precautions/requirements, shutdown procedure, and the need for professional service annually before the
heating season begin.
Warranty
Information contained in this and related product documentation must be read and followed. Failure to do so renders the warranty null and void.
Product Information
Vitotronic 300, Type GW5B
For installation in or mounting on Viessmann boilers only.
Applicable to the following control units
Order No. 7134555, 7143156, 7511362 from
Serial No. 7143000
Order No. 7134555, 7143156, 7511362 from
Serial No. 7187101
Order No. 7134555, 7143156, 7511362 from
Serial No. 7248248
Vitotronic 300, GW5B and MW1B Installation and Service
General
Safety
Preparing for Installation
Installation, Vitotronic 300, GW5B
Installation, Vitotronic 300-K
Table of Contents
Page
Safety, Installation and Warranty Requirements…………..2
Product documentation………………………………..2
Warranty………………………………………………….2
Licensed
Advice to owner…………………………………………2
Operating and Service Documentation………………2
Product Information…………………………………………….2
About these Instructions………………………………………6
For your Safety………………………………………………….7
Operation…………………………………………………7
Flue gas smell……………………………………………7
Working on the equipment…………………………….7
Maintenance
Technical Data Manual…………………………………7
smell gas…………………………………………7
emergencies…………………………………………..7
Installation of additional components……………….7
Boiler conditions…………………………………7
Safety Terminology……………………………………………..7
Designation in the System Example………………………….8
Overview of System Example…………………………………8
System Example…………………………………………………9
Overview of Electrical Connections………………………..15
120V External Connection Overview….………………..…17
Inserting Cables and Applying Strain Relief………………18
Inserting the Boiler Coding Card……………………………18
Inserting the LON Communication Module……………….19
Connecting Sensors…………………………………………..19
120V External Connection…………………………..………19
Connecting Actuators…………………………………………21
Connection the Central Fault Massage Facility…………..22
Connection of low Water Cut-off Device…………………22
Connections to Terminal 150………………………….……23
Connections to Terminal 151………………………….……23
Blocking Boiler Externally / Adding to the Boiler Sequence…24
Connecting a Burner………………………………………….25
Preparing Boilers for Cascade Mode…………………….…25
Overview of Electrical Connections………………………..26
Mounting the Control Unit…………………………………..28
Inserting Cables/Leads and Applying Strain Relief………29
Connecting Pumps…………………………………………….30
Connecting Sensors…………………………………………..31
120V External Connection……………………………..……32
Connecting Actuators………………………………………..33
Connection Central Fault Massage Facility……………….34
External Demand Via Switching Contact………………….34
External Demand via 0-10V Input………………………….35
External Blocking via Switching Contact………………….35
External “Mixing Valve Closed” / “Mixing Valve Open”……36
External Heating Program Changeover…………………….36
Making the LON Connection…………………………………37
3
4
Table of Contents
Power Supply
Opening and Closing the Control Units
Commissioning
Preparing for Installation
Installation Sequences
Service Scans, Vitotronic 300, GW5B
Service Scans, Vitotronic 300-K
Troubleshooting, Vitotronic 300, GW5B
Troubleshooting, Vitotronic 300-K
Function Description
Vitotronic 300, GW5B and MW1B Installation and Service
Page
Power Supply…………………………………………………..38
Fitting the Control Unit Front………………………………..39
Opening the Control Unit…………………………………….39
Testing the High Limit Safety Cut-out……………………..40
Changing the Language on the Vitotronic 300-K………..40
Setting the Date and Time the Vitotronic 300-K………..40
Matching the Coding Addresses to the System Version….41
Selecting the Boiler Sequence at the Vitotronic 300-K…42
Connecting the Control Unit to the LON………………….43
Checking Actuators and Sensors at the
Vitotronic 300 GW5B………………………………………..46
Checking Actuators and Sensors at the
Vitotronic 300-K………………………………………………47
Adjusting Heating Curves…………………………………….48
Calling up Service Menu……………………………………..50
Exiting Service Menu…………………………………………50
Calling up Service Menu……………………………………..51
Scanning Operating Data…………………………………….51
Brief Scan………………………………………………………52
Scanning and Resetting Service Display…………………..52
Fault Codes…………………………………………………….53
Fault Display……………………………………………………55
Fault Codes……………………………………………………..56
Boiler Temperature Control of the
Vitotronic 300 GW5B………………………………………..60
Cascade Control of the Vitotronic 300-K…………………62
Heating Circuit Control Unit of the Vitotronic 300-…….65
DHW Tank Temperature Control of the
Vitotronic 300-K……………………………………………….69
Vitotronic 300, GW5B and MW1B Installation and Service
Code 1, Vitotronic 300, GW5B
Code 2, Vitotronic 300, GW5B
Code 1, Vitotronic 300-K
Code 2, Vitotronic 300-K
Wiring, Vitotronic 300, GW5B
Wiring, Vitotronic 300-K
Components
Parts Lists
Specification
Table of Contents
Page
Calling up Coding Level 1……………………………………71
Group 1 “General”…………………………………………….71
Group 2 “ Boiler”………………………………………………72
Calling up Coding Level 2……………………………………73
Group 1 “General”…………………………………………….74
Group 2 “ Boiler”………………………………………………78
Calling up Coding Level 1……………………………………79
“General” Group……………………………………………….80
“Cascade” Group……………………………………………..81
“DHW” Group………….………………………………….……81
“Solar” Group………………………………………………….82
“Heating Circuit 1”, “Heating Circuit 2”,
“Heating Circuit 3” Group……………………………………83
Calling up Coding Level 2……………………………………86
“General” Group……………………………………………….87
“Cascade” Group……………………………………………..92
“DHW” Group………………………………………………….93
“Solar” Group…………………………………………………..95
“Heating Circuit 1”, “Heating Circuit 2”,
“Heating Circuit 3” Group……………………………………98
Connection and Wiring Diagram…………………………..103
Connection and Wiring Diagram…………………………..106
Sensors………………………………………………………..110
Boiler Coding Card…………………………………………..111
Mixing Valve Motor Kit……………………………………..111
Extension EA1 Accessory (optional)…………………….112
Parts List Vitotronic 300, GW5B…………………………113
Parts List Vitotronic 300-K………………………………..114
Specification Vitotronic 300, GW5B…………………….115
Specification Vitotronic 300-K……………………………115
5
6
Safety
About these Instructions
Vitotronic 300, GW5B & MW1B Installation and Service
Take note of all symbols and notations intended to draw attention to potential hazards or important product information. These include “WARNING”, “CAUTION”, and “IMPORTANT”. See below.
Warnings draw your attention to the presence of
potential hazards or important product information.
WARNING
Indicates an imminently hazardous situation which, if not avoided, could result in loss of life, serious injury or substantial product/property damage.
CAUTION
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product/ property damage.
Cautions draw your attention to the presence of
potential hazards or important product information.
IMPORTANT
Helpful hints for installation, operation or maintenance
which pertain to the product.
This symbol indicates that additional, pertinent
information is to be found.
This symbol indicates that other instructions must
referenced.
Vitotronic 300, GW5B & MW1B Installation and Service
For your Safety
Safety
CAUTION
Follow these safety instructions closely to avoid the risk of injury and damage to property.
H
Operation
Before operating the boiler, make sure you fully
understand its method of operation. Your heating
contractor should always perform the initial start-up
and explain the system. Any warranty is null and void
if these instructions are not followed.
H
Flue gas smell
— Deactivate heating equipment.
— Open windows and doors.
— Inform your heating contractor.
H
Working on the equipment
All personnel working on the equipment or the heating
system must have the proper qualifications and hold
all necessary licenses. Ensure main power to
equipment, heating system, and all external controls
has been deactivated. Close main gas supply valve.
Take precautions in all instances to avoid accidental
activation of power during service work.
H
Dangerous conditions
— Deactivate main power immediately.
— Close gas supply valve.
H
Maintenance and cleaning
Regular inspection and service by a qualified heating
contractor is important to the performance of the boiler.
Neglected maintenance impacts on warranty; regular
inspection ensures clean, environmentally friendly and
efficient operation. We recommend a maintenance
contract with a qualified heating contractor.
H
Technical Data Manual
— Installation Instruction and Service Instructions
— Operating Instructions and User’s Information Manual
Additional applicable literature:
— Accessory manuals
If you smell gas
H
Don’t smoke! Don’t use naked flames or cause sparks
(e.g. by switching lights or electrical appliances on
H
Open windows and doors
H
Close the gas shut-off valve
H
Inform your heating engineers/service contractors from
outside the building
H
Observe the safety regulations of your gas supply
company (see gas meter) and those of your heating
engineers (see start-up or instruction report).
In emergencies
H
Immediately switch off the power supply, e.g. at the
separate fuse or power supply disconnect switch
(unless there is a smell of gas).
H
Close the shut-off valves in the oil pipes or close the
gas shut-off valve, whichever applicable.
H
Use suitable extinguishers in the event of fire.
Installation of additional components
The installation of additional components which have not been tested together with the boiler can adversely affect the function and performance of the boiler.
Our warranty does not cover and weaccept no liability for damage attributable to the installation of such components.
Boiler room conditions
H
Do not use a room in which the air is polluted by
halogenated hydro-carbons (e.g. as contained in
aerosols, paints, solvents and cleaning agents)
H
Do not use a room subject to high levels of dust
H
Do not use a room subject to permanently high humidity
H
The room should be frost-protected
H
Max. ambient temperature 95° F (35° C).
H
Provide good ventilation and do not close or obstruct
vents (if installed).
This symbol indicates a reference to other instructions which must be observed.
Safety Terminology
Take note of all symbols and notations intended to draw attention to potential hazards or important product information. These include ”WARNING” and ”CAUTION”. See below.
WARNING
Indicates an imminently hazardous situation which, if not avoided, could result in substantial product / property damage, serious injury or loss of life.
CAUTION
Indicates an imminently hazardous situation which, if not avoided, may result in minor injury or product / property damage.
7
Preparing for Installation
Designations in the System Example
Vitotronic 300, GW5B and MW1B Installation and Service
8
Overview of System Example
Boiler
Vitocrossal, 200 CM2
Characteristics
Multi-boiler installation
H
This system example is merely a generic layout and must therefore be checked on site for completeness
and function.
H
Connect three-phase consumers via additional contactors.
H
With the Vitotronic 300-K, the communication module is integrated.
Page
9
Vitotronic 300, GW5B & MW1B Installation and Service
System Example
Multi boiler system: Vitocrossal 200 CM2
Hydraulic installation layout
Preparing for Installation
Note: This layout is a basic example without shut-off devices or safety equipment. This does not replace the need for local engineering.
9
10
Preparing for Installation
System Example
(continued)
Vitotronic 300, GW5B & MW1B Installation and Service
Equipment required
Pos. Description
1
Boiler I (cascade mode)
2
Neutralizing system
3
Boiler water temperature sensor KTS
5
6
Supply temperature sensor, common heating supply VTS as contact temperature sensor (standard delivery for Vitotronic 300-K) or immersion temperature sensor
Outside temperature sensor ATS
7
Vitotronic 300-K
8
Vitotronic 300, GW5B
9
Boiler II (cascade mode) qP
Neutralizing system qQ
Boiler water temperature sensor KTS qE
Vitotronic 300, GW5B qR
DHW tank
qT
DHW tank temperature sensor STS qZ
Circulation pump for DHW tank heating UPSB qU
DHW recirculation pump ZP qI
Heating circuit 2
wP qO wQ qO wQ
Heating circuit pump M2
Extension kit for one heating circuit with mixing valve:
Supply temperature sensor M2 as contact temperature sensor and
Mixing valve motor M2 or
Supply temperature sensor M2 as contact temperature sensor or immersion temperature sensor and
Mixing valve motor for flanged mixing valve M2 wW wR wE wT wE wT wZ wI wU wO
Heating circuit 3
Heating circuit pump M3
Extension kit for one heating circuit with mixing valve:
Supply temperature sensor M3 as contact temperature sensor and
Mixing valve motor M3 or
Supply temperature sensor M3 as contact temperature sensor or immersion temperature sensor and
Mixing valve motor for flanged mixing valve M3
Heating circuit 1 at the Vitotronic 200-H
Heating circuit pump M1
Extension kit for one heating circuit with mixing valve:
Supply temperature sensor M1 as contact temperature sensor and
Mixing valve motor M1 or
Vitotronic 300, GW5B & MW1B Installation and Service
System Example
(continued)
Preparing for Installation zT zZ zU uP rP rI tP zP zQ
Equipment required
Pos. Description
wU wO
Supply temperature sensor M1 as contact temperature sensor or immersion temperature sensor and
Mixing valve motor for flanged mixing valve M1 eP eQ
Vitotronic 200-H and
LON communication module (accessory) and
LON connecting cable (accessory)
Outside temperature sensor ATS
Boiler accessories
eR eT eZ eU eI zR zI zO eE eI
Connection to safety equipment aBÖ (see page 23)
Minimum pressure limiter SDB
Maximum pressure limiter SDB
Low water cutoff
Central fault message system
External hook-ups
— External changeover of stepped/modulating burners
— External boiler blocking
— Start boiler externally as the last one in the boiler sequence
System accessories
Vitotrol 200 A or Vitotrol 300 A
Central fault message system zW zE
ON/OFF switch
Vitocom 100 LAN1
KM BUS distributor, for several KM BUS participants
Extension EA1
1 switching output (floating changeover contact):
— Switching a accessories pump to a substation
— Signalling reduced mode for a heating circuit
1 analogue input (0–10V):
— Specifying the set system supply temperature
3 digital inputs:
External heating program changeover, separately adjustable for heating circuits 1 to 3
External demand
External blocking with fault message
Fault message input
Short term operation of DHW recirculation pump
External hook-ups
— External blocking/mixing valve closed
— External demand
— External heating program changeover/mixing valve open
LON communication module (standard delivery Vitotronic 300-K) for communication with the following components:
Vitotronic boiler and heating circuit control units
11
12
Preparing for Installation
System Example
(continued)
Electrical installation wiring
Vitotronic 300, GW5B & MW1B Installation and Service
Vitotronic 300, GW5B & MW1B Installation and Service
System Example
(continued)
Preparing for Installation
13
Preparing for Installation
System Example
(continued)
Vitotronic 300, GW5B & MW1B Installation and Service
14
Code required at every Vitotronic 300, GW5B
Group Function
01:2 2 “Boiler” Multi boiler system with cascade control via LON
Boiler number at the Vitotronic:
07:2
07:3
07:4
77:2
77:3
77:4
2 “Boiler”
2 “Boiler”
2 “Boiler”
Boiler 2
Boiler 3
Boiler 4
LON participant number at the Vitotronic:
1 “General”
1 “General”
1 “General”
Vitotronic 300-K with two Vitotronic 300, GW5B
Boiler 3
Boiler 4
Code required at the Vitotronic 300-K
Group Function
System scheme without system circuit (heating circuit A1) 00:3,
00:4,
00:7,
00:8
35:1 “Cascade” Vitotronic 300-K with one Vitotronic 300, GW5B
35:2
35:3
35:4
“Cascade”
“Cascade”
“Cascade”
Vitotronic 300-K with two Vitotronic 300, GW5B
Vitotronic 300-K with three Vitotronic 300, GW5B
Vitotronic 300-K with four Vitotronic 300, GW5B
Vitotronic 300, GW5B & MW1B Installation and Service
Overview of Electrical Connections
Installation, Vitotronic 300, GW5B
Note: When connecting plugs aVD and aVH, bundle the individual cores of the cables close to the terminals.
This prevents the cores from shifting into the neighboring voltage area.
Main PCB low voltage
aJ A Return temperature sensor T1
(optional accessory, not used) aJ
B Return temperature sensor T2
(optional accessory, not used) aVD External hook-up aVG
KM BUS participant (accessory) aVH
External hook-up
Main PCB 120V~
sÖ A1 Switching output pump sL
Boiler circuit pump fÖ
Power supply fA Burner (call for heat) gÖ Central fault message gS A1 Isolation valve aBÖ
External connections, e.g. supplementary safety
equipment aBA Safety chain, floating aBH Power supply connection for accessories
Prior to making any connections ensure that the control control and junction box have been installed as per the boiler Installation Instructions.
15
16
Installation, Vitotronic 300, GW5B
Vitotronic 300, GW5B & MW1B Installation and Service
Overview of Electrical Connections
(continued)
Vitotronic 300, GW5B & MW1B Installation and Service
120V External Connection Overview
Installation, Vitotronic 300, GW5B
Legend
A Pumps
B To the control unit
Rated current: 2A~
* Maximum output 6FLA shared between all
120V outputs.
Pumps 120V
Available pump connections
sÖ M1/A1 Switching contact sL pump
17
Installation, Vitotronic 300, GW5B
Vitotronic 300, GW5B & MW1B Installation and Service
Inserting Cables and Applying Strain Relief
H
Control unit fitted on the boiler:
Route cables from below through the front panel of the boiler into the wiring chamber of the control unit.
H
Control unit fitted to the side of the boiler:
Route cables from below out of the cable channel into the control unit.
18
Legend
A
Cables with moulded strain relief
B On-site cables; strip up to 4 in. (100 mm) insulation
Inserting the Boiler Coding Card
Only use the boiler coding card supplied with the boiler
(see table in chapter “Components”).
Insert the boiler coding card into slot “X7”, through the recess in the cover.
Boiler
Vitocrossal 200, CM2
Coding card Part no.
1042 7841113
Vitotronic 300, GW5B & MW1B Installation and Service
Inserting the LON Communication Module
Installation, Vitotronic 300, GW5B
Making the LON connection, see page 37.
Connecting Sensors
Legend
Main PCB low voltage aJ A Return temperature sensor T1 (optional accessory) aJ B Return temperature sensor T2 (optional accessory)
120V External Connection
120V pumps with an amperage draw of <2FLA
A Din rail
B
Pump
19
20
Installation, Vitotronic 300, GW5B
120V External Connection
(continued)
Vitotronic 300, GW5B & MW1B Installation and Service
120V pumps with an amperage draw of >2FLA
Contactor specification 120VAC 1A
A Din rail
B Contactor/relay (field supplied)
C
Pump
D
Power supply w/disconnect and protection
240V pumps
Contactor specification 120VAC 1A
A
Din rail
B Contactor/relay (field supplied)
C Pump
D Power supply w/disconnect and protection
208/460/575V 3 phase pumps
Contactor specification 120VAC 1A
A Din rail
B
Contactor/relay (field supplied)
C
Pump
D Power supply w/disconnect and protection
Vitotronic 300, GW5B & MW1B Installation and Service
Connecting Actuators
Installation, Vitotronic 300, GW5B
Legend
A
24V Mixing Valve Adaptor
B
DIN Rail (in junction box)
C
24V Valve Actuator
D
Valve
Legend
A
120V Mixing Valve Adaptor
B
DIN Rail (in connection enclosure)
C 120V Valve Actuator
D Valve
120V Valve Adaptor
Rated voltage:
Rated current:
24V Valve Adaptor
Rated voltage:
Rated current:
120VAC max. 0.1 FLA
24VAC max. 0.15 FLA
Operating time: 5 to 199 sec. selected via coding
“40”.
Available connections
gS A1 Motor for 3-way mixing valve, primary store system gS M2 For heating circuit 2 gS M3 For heating circuit 3
1. Disconnect power to control.
2. Install 120V or 24V valve adaptor on DIN rail inside enclosure.
3. Insert the plug gS into socket gS on the Vitotronic
control.
4. Fasten cable with tie.
5. Connect black wire of the adaptor to terminals 8,9 or
10 on the Din rail.
6. Connect valve actuator wires to the adaptor terminals
Rated voltage: 120V~
Rated current Max.: 0.1A~
Motor runtime for
3-way mixing valve: 10 to 255 sec, adjustable via
coding the”DHW”group, “C3” in the HC2 group and “C3” in the HC3 group.
21
22
Installation, Vitotronic 300, GW5B
Vitotronic 300, GW5B & MW1B Installation and Service
Connecting the Central Fault Message Facility
Rated voltage
Rated current
120V~ max. 2A~
Connection of Low Water Cut-off Device
1. Remove jumper between terminals 12 and 15.
2. Make connection as shown in diagram.
CAUTION
The diagram shown is only a simplified conceptual drawing of a typical low water cut off (LWCO) device.
Refer to the manual specific to the device for interconnection details.
aBH
Power supply for accessories.
aBÖ
Connection for external equipment.
A Low water cut-off (typical)
Vitotronic 300, GW5B & MW1B Installation and Service
Connections to Safety Equipment
Installation, Vitotronic 300, GW5B
1. Connect the external safety equipment in series.
Connections to Terminal aBA
Legend
A DIN rail
B Low water cutoff
C
Other safety controls
External shut-off
1. Remove jumper between terminals 19 and 20.
2. Connect dry contact. Controlled switch-off takes place
when the contact is opened.
WARNING
The terminals should be used for safety switch-off purposes only (e.g. through a high limit thermostat).
During switch-off, there is no frost protection of the heating system and the boiler is not kept at the minimum boiler water temperature.
23
24
Installation, Vitotronic 300, GW5B
Vitotronic 300, GW5B & MW1B Installation and Service
Blocking Boiler Externally/Adding to the Boiler Sequence
Legend
A
Blocking boiler externally (dry contact)
B
Start boiler externally as the last one in the boiler sequence (dry contact)
Connection at plug aVD.
Note: ‘Live’ contacts lead to short circuits or phase failure. The external connection must be floating.
Contact A:
H
Contact closed:
The boiler is removed from the boiler sequence.
The isolation valve or the 3- way mixing valve are closed for constant return temperature control.
Shunt pump or boiler circuit pump are switched off.
The heat demand has to be met by the other boilers.
Note: If all boilers are blocked or there is no other boiler available for duty, there will be no frost protection for the heating system.
H
Contact open:
The boiler is integrated into the current boiler sequence.
Contact B:
H
Contact closed:
The heat demand of the heating system is met by the other boilers. This boiler is started if the output of these boilers is insufficient.
H
Contact open:
The boiler is integrated into the current boiler sequence.
Vitotronic 300, GW5B & MW1B Installation and Service
Connecting the Burner
Installation, Vitotronic 300, GW5B
The burner cables are included in the standard boiler delivery.
Max. power consumption 3A.
Terminal codes
L Burner control power supply
?
Ground conductor to burner
N Neutral conductor to burner
T1 120V~ from boiler control unit
T2 Base load demand
S3 Connection for burner fault
B4 Connection for hours run meter
Legend
A
To the Vitotronic control
B
To the burner (burner control unit)
C KM BUS cable
Preparing Boilers for Cascade Mode
IMPORTANT
The following procedure must be done to configure each boiler for constant temperature control (cascade control) mode.
1. Turn on the boiler and set the language then press
‘OK’.
2. Set the time and date and press ‘OK’.
Refer to the boiler Installation Instructions.
3. Press and hold OK and until service menu comes
up.
4. Scroll using to the service functions, press OK.
5. Scroll using to the multi-boiler system.
6. Press OK.
7. Scroll using to “Yes”.
8. Press OK.
Note: The boiler will restart in cascade mode.
9. Set the language and press ‘OK’.
Refer to the boiler Installation Instructions.
25
Installation, Vitotronic 300-K
Overview of Electrical Connections
Vitotronic 300, GW5B & MW1B Installation and Service
Note: When connecting plugs aVD, aVH, sA, sK, ?
M2/M3 and sÖ M2/M3, bundle the individual wires of the cables close to the terminals.
This ensures that, should there be an error, for example when detaching a wire, the wires cannot drift into the adjacent voltage area.
26
Extension for heating circuits 2 and 3 with mixing valve
?
M2/M3 Supply temperature sensor sÖ M2/M3 Heating circuit pump gS M2/M3 Mixing valve motor
Main PCB 120V~
sÖ A1 Heating circuit pump
or
Primary pump, primary store system sA
Circulation pump for DHW tank heating
(optional accessory, not used)
Main PCB low voltage
!
Outside temperature sensor
§ /? Supply temperature sensor, common heating flow
%
A DHW tank temperature sensor
%
B DHW tank temperature sensor 2 for primary store aVD aVG system (optional accessory, not used) aJ B Return temperature sensor T2 (optional accessory,
not
or
Temperature sensor primary store system
(optional accessory, not used)
External hook-up
KM BUS participant (optional accessory, not used) aVH
External hook-up
LON LON BUS, connecting cable for data exchange with the Vitotronic 300, GW5B, 200-H, Vitocom and
Vitogate sK DHW recirculation pump (on site) sL Shunt pump or distribution pump (on site) fÖ
Power supply gÖ
Central fault message gS A1 Motor for 3-way mixing valve, primary store system
or
Motor for 3-way mixing valve, return temperature
control aBH
Power supply connection for mixing valve module circuit M2 and M3
Note: When inserting cables and applying strain relief see page 29.
Vitotronic 300, GW5B & MW1B Installation and Service
Installation, Vitotronic 300-K
Overview of Electrical Connections, Vitotronic 300-K
(continued)
Legend
A Vitotronic 300-K
B Din rail
27
28
Installation, Vitotronic 300-K
Mounting the Control Unit
Vitotronic 300, GW5B & MW1B Installation and Service
1. Fasten metal backplate onto mounting surface with fasteners.
2. Position midplate between backplate and connection
enclosure.
3. Install midplate and connection enclosure onto
backplate.
4. Fasten connection enclosure and midplate onto backplate with two fasteners.
5. Install control rear section onto connection enclosure housing. Hook control onto backplate tabs and pivot
downwards.
6. Fasten control rear section onto connection enclosure with two fasteners.
Vitotronic 300, GW5B & MW1B Installation and Service
Inserting Cables/Leads and Applying Strain Relief
Installation, Vitotronic 300-K
Run the cables from the connection enclosure into the control unit.
Apply strain relief to cables.
Cables with moulded strain relief clamp:
Connect cable and strain relief clamp.
OR
Fasten cable to the cable lead with cable tie.
Legend
A Cables with moulded strain relief
B On-site cables; strip up to 4 in. (100 mm) insulation.
29
Installation, Vitotronic 300-K
Connecting Pumps
Vitotronic 300, GW5B & MW1B Installation and Service
*
*
30
Legend
A 120V outputs
B To the control unit
Rated current: 2 A~
* Maximum pump output 6FLA shared between all
120V outputs.
Pumps 120V
Available pump connections
sÖ
M1/A1 High temperature circuit pump/ primary store pump sÖ M2 sÖ M3
Heating circuit 2 pump
Heating circuit 3 pump sA DHW sK sL
DHW recirculation pump pump
Vitotronic 300, GW5B & MW1B Installation and Service
Connecting Sensors
Installation, Vitotronic 300-K
Installation point for outside temperature sensor
H
North or north-western wall, 6.6 to 8.2 ft. (2 to 2.5 m) above ground level; in multi storey buildings, in the upper half of the second floor
H
Not above windows, doors or ventilation outlets
H
Not immediately below balconies or gutters
H
Never render over
Outside temperature sensor connection
Two wire communication cable 18 AWG
Legend
!
Outside temperature sensor
§ /? Common supply temperature sensor
% A DHW tank temperature sensor 1
%
B DHW tank temperature sensor 2 for primary store system (optional accessory, not used) aJ B Return temperature sensor T2
or
Temperature sensor primary store system
(optional accessory, not used)
31
32
Installation, Vitotronic 300-K
120V External Connection
Vitotronic 300, GW5B & MW1B Installation and Service
120V pumps with an amperage draw of <2FLA
A
Din rail
B Pump
120V pumps with an amperage draw of >2FLA
Contactor specification 120VAC 1A
A Din rail
B
Contactor/relay (field supplied)
C
Pump
D Power supply w/disconnect and protection
240V pumps
Contactor specification 120VAC 1A
A Din rail
B
Contactor/relay (field supplied)
C
Pump
D Power supply w/disconnect and protection
208/460/575V 3 phase pumps
Contactor specification 120VAC 1A
A Din rail
B
Contactor/relay (field supplied)
C
Pump
D Power supply w/disconnect and protection
Vitotronic 300, GW5B & MW1B Installation and Service
Connecting Actuators
Installation, Vitotronic 300-K
Legend
A
B
C
D
24V Mixing Valve Adaptor
DIN Rail (in junction box)
24V Valve Actuator
Valve
Legend
A 120V Mixing Valve Adaptor
B
DIN Rail (in junction box)
C 24V Valve Actuator
D Valve
120V Valve Adaptor
Rated voltage:
Rated current:
120 VAC max. 0.1 FLA
Recommended connection wire size: AWG 14
24V Valve Adaptor
Rated voltage:
Rated current:
24 VAC max. 0.15 FLA
Recommended connection wire size: AWG 14
Operating time: 5 to 199 sec. selected via coding
“40”.
Available connections
gS A1 Motor for 3-way mixing valve, primary store system gS M2 For heating circuit 2 gS
M3 For heating circuit 3
1. Disconnect power to control.
2. Install 120V or 24V valve adaptor on DIN rail inside enclosure.
3. Insert the plug gS into socket gS on the control.
4. Fasten cable with tie.
5. Connect black wire of the adaptor to terminals 8,9 or
10 on the Din rail.
6. Connect valve actuator wires to the adaptor terminals
Refer to the mixing valve adaptor Installation
Instructions for additional information.
Rated voltage: 120V~
Rated current Max.: 0.1A~
Motor runtime for
3-way mixing valve: 10 to 255 sec, adjustable via
coding the”DHW”group, “C3” in the HC2 group and “C3” in the HC3 group.
33
Installation, Vitotronic 300-K
Vitotronic 300, GW5B & MW1B Installation and Service
Connecting the Central Fault Message Facility
Rated voltage
Rated current
120V~ max. 2 A~
External Demand Via Switching Contact
Connection
Note: ‘Live’ contacts lead to short circuits or phase failure. The external connection must be floating.
Connection options:
H
Plug aVH
H
Extension EA1 (accessory, see page 113)
Legend
A
Floating contact
B Plug aVH of the control unit
With the contact closed, the boiler burners are started subject to load. They heat to the set supply temperature selected in coding address “9B” in the “General” group.
The temperature is limited by this set value and the electronic maximum supply temperature limit (coding address “37” in the “Cascade” group).
34
Legend
A Floating contact
B Extension EA1
Codes
Plug aVD
No code required.
Extension EA1
Set “5D”, “5E” or “5F” in the “General” group to 2.
Vitotronic 300, GW5B & MW1B Installation and Service
External Demand via 0–10V Input
Installation, Vitotronic 300-K
Connection at input 0 – 10V at extension EA1
(see page 113).
0 — 1V no default set supply temperature
1V
10V
set value 50° F (10° C)
set value 212° F (100° C)
Observe coding address “1E” in the “General” group.
External Blocking via Switching Contact
Legend
A Floating contact
B Plug aVD of the control unit
Connection options:
H
Plug aVD
H
Extension EA1 (accessory, see page 113)
Connection
Note: ‘Live’ contacts lead to short circuits or phase failure. The external connection must be floating.
With the contact closed, the burners of all boilers will be subject to a control shutdown.
Any connected shunt or distribution pump is stopped.
Shut-off devices are closed.
Note: The heating system has no frost protection during blocking. The boilers are not held at the lower boiler water temperature.
Legend
A
Floating contact
B
Extension EA1
Codes
Plug aVD
Set coding address “99” in the “General” group, which the input should influence.
Extension EA1
Set “5D”, “5E” or “5F” in the “General” group to 3 or 4.
35
Installation, Vitotronic 300-K
Vitotronic 300, GW5B & MW1B Installation and Service
External “Mixing Valve Closed”/”Mixing Valve Open”
Connection at plug aVD.
Note: ‘Live’ contacts lead to short circuits or phase failure.
The external connection must be floating.
Codes
External “Mixing valve open”
Via coding address “9A” in the “General” group, this function is assigned to the heating circuits.
External “Mixing valve closed”
Via coding address “99” in the “General” group, this function is assigned to the heating circuits.
Legend
A External “Mixing valve open” (floating contact)
B External “Mixing valve closed” (floating contact)
External Heating Program Changeover
Legend
A Floating contact
B Plug aVD of the control unit
Connection
Note: ‘Live’ contacts lead to short circuits or phase failure. The external connection must be floating.
Connection options:
H
Plug aVD
H
Extension EA1 (accessory, see page 112)
Codes
Plug aVD
This function is assigned to the heating circuits via coding address “91” in the
“General” group.
Extension EA1
Set “5D”, “5E” or “5F” in the “General” group to 1.
This function can be assigned to the heating circuits via coding address
“D8” in the “Heating circuit…” group.
Legend
A
Floating contact
B Extension EA1
36 or w or w
Preselected heating program
(Contact open)
9
Central heating OFF/
DHW OFF
Coding
D5:0
(factory set condition)
D5:1
Changed heating program
(Contact closed)
Permanent operation with reduced room temperature/DHW OFF
Constant operation with standard room temperature, DHW in accordance with coding address “64” Central heating
OFF/DHW ON
Central heating
ON/DHW ON
Vitotronic 300, GW5B & MW1B Installation and Service
Making the LON Connection
Connection with Viessmann LON cable
The line may be up to ≤ 23 ft. (7 m) long
Legend
A
Control unit or Vitocom
B LON cable, 23 ft. (7 m) long
C Terminator
Installation, Vitotronic 300-K
The Viessmann LON system is designed for the
“Line” BUS topology with a terminator at both ends
(accessories). The transfer distances for LON are subject to the electrical properties of the respective cabling.
For this reason, only use the stated cable types.
Use only one type of cable within the LON.
Observe the cabling requirements for the operation of the LON interface FTT 10-A (see www.echelon.com).
All Viessmann equipment is connected via RJ45 plugs.
The Viessmann LON system always requires the cores
“1” and “2” and the screen. The cores are interchangeable. The installation is therefore safe from pole errors.
Connection with Viessmann LON cable and coupling
Connection with on-site cable and LON plug
Installation spacing 23 to 69 ft. (7 to 21 m)
Legend
A
Control unit or Vitocom
B
LON cable, 23 ft. (7 m) long
Max. 3 cables between 2 appliances
C Terminator
D LON coupling
Connection with LON cable, on-site cable and LON junction box
≤ 3000 ft.
The line may be up to ≤ 3000 ft. (900 m)
(with LON plug)
Legend
A
Control unit or Vitocom
B
On-site cable
C Terminator
D LON plug
E Up to 99 participants
≤ 3000 ft.
The line may be up to ≤ 3000 ft. (900 m) (with LON junction boxes)
Legend
A
Control unit or Vitocom
B
LON cable, 23 ft. (7 m) long
C Terminator
D LON junction boxes
E
On-site cable
F
Up to 99 participants
37
38
Power Supply
Power Supply
Vitotronic 300, GW5B & MW1B Installation and Service
Legend
L: Line
N: Neutral
G: Ground
A Power supply 120VAC, 1PH, 60Hz, provide disconnect means and overcurrent protection as per local codes
B Terminals N, G and 11 (in junction box)
C Junction box
1. Ensure that the main power supply to the control contains overcurrent protection with a minimum rating of 6A and 2-pole disconnect.
WARNING
The control must be grounded.
Ensure that “L”, “N” and “G” are not interchanged.
2. Connect power supply wire to the connection fÖ terminals 11, N and G on the DIN rail inside the box.
Vitotronic 300, GW5B & MW1B Installation and Service
Fitting the Control Unit Front
Opening and Closing the Control Units
Legend
A
Cable retaining tab
Opening the Control Unit
Note: Route the ribbon cable through retainer A.
39
40
Commissioning
Testing the High Limit Safety Cut-out
Vitotronic 300, GW5B & MW1B Installation and Service
The minimum circulation volume should be 10% of the circulation volume at rated load.
Reduce the heat consumption as far as possible.
1. Hold down the “TEST” key until the burner has shut down: Thermostat is bridged. The high limit safety cut-out must shut down the burner at the latest when the safety temperature has been reached.
2. Release the “TEST” key.
3. Wait until the boiler water temperature has dropped approx. 15 to 20 K below the selected safety temperature.
4. Reset the high limit safety cut-out by pressing reset button.
Operating instructions
Changing the Language on the Vitotronic 300-K
At the commissioning stage, the display is in German
(default setting).
Extended menu:
1.
2. “Einstellungen” (Settings)
3. “Sprache” (Language) Deutsch DE (German)
4. Set the required language with
Setting the Date and Time on the Vitotronic 300-K
During commissioning, or after prolonged time out of use, the time and date need to be reset.
Extended menu:
1.
2. “Settings”
3. “Time / Date”
4. Set current time and date.
Vitotronic 300, GW5B & MW1B Installation and Service
Matching the Coding Addresses to the System Version
Commissioning
Vitotronic 300, GW5B (set codes at every Vitotronic 300,
GW5B — boiler control)
Switching mode from standalone/weather compensated control to constant temperature control (see page 25).
Vitotronic 300, GW5B
Check all addresses in Code 1 and adjust if required.
Check the following coding addresses and adjust accordingly in Code 2:
“4C”
“4D”
“4E”
“98”
“9C”
Group
1 “General”
1 “General”
1 “General”
1 “General”
1 “General”
Function
Function plug sÖ
Function plug sL
Function plug gS
Viessmann system number
Monitoring LON participants
“39”
“3A”
“4C”
“4D”
“4E”
“55”
“7A”
“98”
“9C”
Group
“Cascade”
“Cascade”
“General”
“General”
“General”
“DHW”
“General”
“General”
“General”
Vitotronic 300-K
Check all addresses in Code 1 and adjust if required.
Check the following coding addresses and adjust accordingly in Code 2:
Function
Permanent lead boiler
Permanent last boiler
Function plug sÖ
Function plug sL
Function plug gS
DHW tank temperature control function
Central control
Viessmann system number
Monitoring LON participants
41
42
Commissioning
Vitotronic 300, GW5B & MW1B Installation and Service
Selecting the Boiler Sequence at the Vitotronic 300-K
Subject to the set codes in the “Cascade” group and internal control calculations, the control unit offers various boiler sequences.
Coding addresses that influence the boiler sequence:
“38” Changing the lead boiler and the boiler
“39” sequence
Permanent lead boiler
“3A” Permanent last boiler
“41” to “44” ECO thresholds
H
Via the ECO threshold, every boiler can be blocked or enabled subject to the outside temperature.
H
If the boiler is required to achieve the set supply temperature in the case of enabled boilers failing, the
ECO threshold is disabled.
H
At least the lead boiler remains active if all boilers in
a system are blocked by the ECO threshold.
1. Press .
3. Select the required boiler sequence and confirm with
OK.
Vitotronic 300, GW5B & MW1B Installation and Service
Connecting the Control Unit to the LON
Example of a multi boiler system
Commissioning
Legend
A Vitotronic 300 GW5B
B
Vitotronic 300 GW5B
C
Vitotronic 300-K
D
Vitotronic 200-K
E Vitocom
F LON system
G
Terminator
H
The LON communication module must be fitted into every Vitotronic 300, GW5B (see page 61).
Note: The communication module is integrated in the
Vitotronic 300-K.
H
Vitotronic 200-H:
The LON communication module (accessory) must be fitted.
Installation and service instructions,
Vitotronic 200-H
H
Within one LON, the same participant number must not be allocated twice.
H
Within one LON, the system number (coding address
“98” in the “General” group) must always be the same.
H
Only one Vitotronic may be programmed as fault manager.
H
The data transfer via the LON system can take several minutes.
43
44
Commissioning
Vitotronic 300, GW5B & MW1B Installation and Service
Connecting the Control Unit to the LON
(continued)
A
Multi boiler system.
Set code “01:2” in group 2 “Boiler”.
Boiler number 1.
Code “07:1” in group 2 “Boiler”.
With LON communication module
Code “76:1” in group 1 “General”; automatic recognition.
—
B
Multi boiler system.
Set code “01:2” in group 2 “Boiler”.
Boiler number 2.
Set code “07:2” in group 2 “Boiler”.
With LON communication module
Code “76:1” in group 1 “General”; automatic recognition.
—
Participant no. 1.
Code “77:1” in group
1 “General”.
Control unit is not fault manager.
Code “79:0” in group
1 “General”.
—
Participant no. 2.
Set code “77:2” in group 1 “General”.
Control unit is not fault manager.
Code “79:0” in group
1 “General”.
—
—
LON participant remote monitoring.
Code “9C:20” in group 1 “General”.
—
LON participant remote monitoring.
Code “9C:20” in group 1 “General”.
C
—
—
D
—
—
With LON communication module
Code “76:1” in the “General” group; automatic recognition.
Number of connected boilers.
Set codes
“35:1” to
“35:4” in the
“Cascade”group.
Participant no. 5.
Set code “77:5” in the “General” group.
Control unit is fault manager.
Set code “79:1” in the “General” group.
Control unit transmits the time.
Code “7B:1” in the
“General” group.
Control unit transmits outside temperature.
Set code
“97:2” in the
“General” group.
LON participant remote monitoring.
Code “9C:20” in the
“General” group.
With LON communication module
Code “76:1” in the “General” group; automatic recognition.
—
Participant no. 10.
Set code “77:10” in the “General” group.
Control unit is not fault manager.
Set code “79:0” in the “General” group.
The control unit receives the time.
Set code “81:3” in the “General” group.
Control unit receives the outside temperature.
Set code “97:1” in the “General” group.
LON participant remote monitoring.
Code “9C:20” in the
“General” group.
E
—
—
—
—
Participant no. 99.
Device is fault manager.
Device receives the time.
—
—
Vitotronic 300, GW5B & MW1B Installation and Service
Connecting the Control Unit to the LON
(continued)
Commissioning
Carrying out a LON participant check at the Vitotronic
300-K
Communication with the system devices connected to the fault manager is tested by means of a participant check.
Preconditions:
H
The control unit must be programmed as fault manager
(code “79:1”).
H
The LON participant no. must be programmed in all control units (coding address “77”).
The LON participant list in the fault manager must be
up to date.
Carrying out the participant check:
1. Press OK and simultaneously for approx. 4 sec.
4. Select participant (e.g. participant 10).
The participant check for the selected participant is initiated.
H
Successfully tested participants are designated with
“OK”.
H
Unsuccessfully tested participants are designated with “Not OK”.
Note: To carry out a new participant check, create a new participant list with “Delete list?” (participant list is updated).
Note: H Vitotronic 300, GW5B:
During the participant check, the display for the relevant participant flashes for approx. 1 min.
H
Vitotronic 200-H:
During the participant check, the display for the relevant participant shows the participant no. and “Wink” for approx. 1 min.
45
46
Commissioning
Vitotronic 300, GW5B & MW1B Installation and Service
Checking Actuators and Sensors at the Vitotronic 300 GW5B
Testing the relay
1. Press OK and simultaneously for approx. 4 sec.
2. “Actuator test”
Before an actuator is selected, all actuators are off.
The following actuators (relay outputs) can be switched subject to system equipment level:
Display
“All actuators”
“Burner modulation”
“Burner modulation”
Explanation
Off All actuators have been switched off.
Open Modulating burner.
Neutral Modulating burner.
“Burner modulation”
“Output 20”
“Output 52”
“Output 52”
“Output 52”
“Output 29”
“Compiled fault message”
“EA1 output 1”
“AM1 output 1”
“AM1 output 2”
Close Modulating burner.
On Output 20 active.
Open
Neutral
Close
On Output 29 active.
On
On Contact “P — S” on plug aBJ of extension EA1 closed.
On Output active.
On Output active.
Note: During burner operation, the pumps connected to the control unit are started.
Checking sensors
Service menu:
1. Press OK and simultaneously for approx. 4 sec.
2. “Diagnosis”
3. Select group (see page 50).
4. Scan actual temperature of the relevant sensor.
Vitotronic 300, GW5B & MW1B Installation and Service
Checking Actuators and Sensors at the Vitotronic 300-K
Commissioning
Carrying out a relay test
1. Press OK and simultaneously for approx. 4 sec.
The following relay outputs can be controlled subject to the system equipment level:
Display Explanation
“All actuators”
“Output 20”
“Output 52”
OFF
ON
Open —
All actuators have been switched off.
Output 20 enabled.
“Output 52”
“Output 52”
“DHW tank prim pump”
“DHW circ pump”
“Output 29”
“Central fault mess.”
“Htg circ pump HC2”
Neutral —
Closed —
ON
ON
ON
ON
ON
—
Output for circulation pump for DHW tank heating enabled.
Output for DHW recirculation pump enabled.
Output 29 enabled.
Output heating circuit pump enabled (heating circuit with mixing valve M2).
“Mixing valve HC2”
“Mixing valve HC2”
“Htg circ pump HC3”
“Mixing valve HC3”
“Mixing valve HC3”
“EA1 output 1”
Open
Closed
ON
Open
Closed
ON
Output “Mixing valve open” enabled (heating circuit with mixing valve M2).
Output “Mixing valve closed” enabled (heating circuit with mixing valve M2).
Output heating circuit pump enabled (heating circuit with mixing valve M3).
“Mixing valve open” enabled (heating circuit with mixing valve M3).
Output “Mixing valve open” enabled (heating circuit with mixing valve M3).
“AM1 output 1”
“AM1 output 2”
“Solar circuit pump”
ON
ON
ON
Contact “P — S” on plug aBJ for extension EA1 closed.
Output enabled.
Output enabled.
Output for solar circuit pump sF at solar control module, type SM1, enabled.
“Solar circ pmp min” ON
Output for solar circuit pump sF at solar control module, type SM1, switched to minimum speed.
“Solar circ pmp max” ON
Output for solar circuit pump sF at solar control module, type SM1, switched to maximum speed.
“SM1 output 22” ON
Output sS at solar control module, type SM1, enabled.
Checking sensors
1. Press OK and simultaneously for approx. 4 sec.
2. “Diagnosis”
3. Select group (see overview on page 51).
4. Scan actual temperature of the relevant sensor.
47
48
Commissioning
Adjusting Heating Curves
Vitotronic 300, GW5B & MW1B Installation and Service
The heating curves illustrate the relationship between the outside temperature and the boiler water or supply temperature.
To put it simply: The lower the outside temperature, the higher the boiler water or supply temperature.
The room temperature, again, depends on the boiler water or the supply temperature.
Settings in the factory set condition:
H
Slope = 1.4
H
Shift = 0
Boiler water or supply temperature
Room set-point temperature
Outdoor temperature
Example of outside temperature 7° F (−14° C)
Legend
A Underfloor heating system, slope 0.2 to 0.8
B Low temperature heating system, slope 0.8 to 1.6
C
Heating systems with a boiler water temperature in excess of 167° F (75° C), slope greater than 1.6
230 °F
(110 °C)
79 °F
(26 °C)
68 °F
(20 °C)
-4 °F
(-20 °C)
Legend
A Boiler water temperature or supply temperature
B
Outside temperature
C
Set room temperature
D Heating circuit pump OFF
E Heating circuit pump ON
Selecting the set room temperature
Individually adjustable for each heating circuit.
The heating curve is offset along the axis of the set room temperature. When the heating circuit pump logic function has been enabled, it modifies the starting and stopping characteristics of the heating circuit pump.
Standard set room temperature
Changing the standard room temperature from 68 to 79° F
(20 to 26° C)
Operating instructions
Vitotronic 300, GW5B & MW1B Installation and Service
Adjusting Heating Curves
(continued)
Commissioning
Reduced set room temperature
Changing the reduced room temperature from 37 to 57° F
(3 to 14° C)
Operating instructions
Legend
A
Boiler water temperature or supply temperature
B
Outside temperature
C Set room temperature
D Heating circuit pump OFF
E Heating circuit pump ON
Outside temperature
Legend
A Changing the slope
B Changing the shift (vertical parallel offset of the heating curve)
Changing the slope and shift
Individually adjustable for each heating circuit.
Extended menu:
1.
2. “Heating”
3. Select heating circuit.
5. “Slope” or “Shift”
6. Select heating curve according to the system requirements.
Example:
Heating curve setting with slope 1.5:
49
50
Service Scans, Vitotronic 300, GW5B
Calling up the Service Menu
Service menu overview
Service
Diagnosis
Actuator test
Coding level 1
Coding level 2
Fault history
Service functions
End service?
Vitotronic 300, GW5B & MW1B Installation and Service
Press OK and simultaneously for approx. 4 sec.
General
Brief scan
Reset data
Participant check
Service PIN
Service reset
“Coding level 2” is only displayed if this level has been enabled:
Press OK and simultaneously for approx. 4 sec.
Exiting the Service Menu
1. Select “End service?”.
2. Select “Yes”.
3. Confirm with OK.
Note: The system exits the service menu automatically after 30 min.
Vitotronic 300, GW5B & MW1B Installation and Service
Calling up the Service Menu
Service Scans, Vitotronic 300-K
Service menu overview
Press OK and simultaneously for approx. 4 sec.
Service
Diagnosis
Actuator test
Coding level 1
Coding level 2
Fault history
Service functions
Terminate service?
General
Heating circuit 1 HC1
Heating circuit 2 HC2
Heating circuit 3 HC3
DHW
Solar
Brief scan
Reset data
Participant check
Service PIN
Service reset
“Coding level 2” is only displayed if this level has been enabled:
Press OK and simultaneously for approx. 4 sec.
Scanning Operating Data
Operating data can be scanned in six areas (see
“Diagnosis” in the overview “Service menu”).
Operating data on heating circuits with mixing valves and solar can only be scanned if the components are installed in the system.
For further information on operating data, see chapter
“Brief scan”.
Note: “- — -” appears on the display if a sensor that has been scanned is faulty.
Calling up operating data
1. Press OK and simultaneously for approx. 4 sec.
2. “Diagnosis”
3. Select required group, e.g. “General”.
Resetting operating data
Saved operating data (e.g. hours run) can be reset to 0.
The value “Adjusted outside temp” is reset to the actual value.
1. Press OK and simultaneously for approx. 4 sec.
2. “Diagnosis”
4. Select required value or “All details”.
51
52
Service Scans, Vitotronic 300-K
Brief Scan
Vitotronic 300, GW5B & MW1B Installation and Service
In the brief scan, you can scan temperatures, software versions and connected components, for example.
1. Press OK and simultaneously for approx. 4 sec.
2. “Diagnosis”
4. Press OK. The display shows 9 lines with 6 fields each.
For an explanation of the relevant values in the individual lines, see the following table:
Line (brief scan) Field
1 2 3 4 5
1:
2:
3:
4:
5:
6:
7:
8:
System schemes 01 to 10
2
0
0
0
0
SNVT config.
0: Auto
1: Tool
0
0
0
0
0
Software version
Communic.
coproc.
0
0
6
Control unit software version
0 0
Programming unit software version
Appliance identification
ZE-ID
Number of KM BUS participants Software version
Solar control module
0
0
0
Subnet address/system number Node address
Software version
Neuron Chip
0 0
0
0
Software version, extension
AM1
0
0
0
Software version, extension
EA1
Number of LON participants
9:
10:
11:
0
0
System circuit HC1
0 0
0
0
Heating circuit HC2
0 0
0
Software version, extension for heating
0
0
Heating circuit HC3
0 0
0
Software version, extension for heating
0
0 circuits
2 and 3 with mixing valve circuits
2 and 3 with mixing valve
Note: The displays in fields 3 and 5 are the same.
Scanning and Resetting Service Display
No service interval can be set at the Vitotronic 300-K. In other words, no service display is shown.
Note: If a service display appears on the Vitotronic 300,
GW5B, the display will show “Participant fault” and the participant number.
Vitotronic 300, GW5B & MW1B Installation and Service
Fault Codes
Troubleshooting, Vitotronic 300, GW5B
Displayed fault code
0F
30
38
60
68
70
78
A0
A1
A2
A3
AA
AC
System characteristics Cause Measures
Control mode.
The burner is started and stopped via a temperature controller.
The burner is started and stopped via a temperature controller.
Boiler with maximum temperature, no output reduction, mixing valve return temperature control “Open”.
Boiler with maximum temperature, no output reduction, mixing valve return temperature control “Open”.
Shunt pump constantly “ON”.
Shunt pump constantly “ON”.
Boiler cools down.
Boiler cools down.
Boiler cools down.
Boiler cools down.
Control mode.
Control mode.
Service “0F” is only displayed in the fault history.
Short circuit, boiler water temperature sensor
Lead break, boiler water temperature sensor
Short circuit, temperature sensor aJA
Service the appliance.
Note: After the service, set code “24:0” in group 2
“Boiler”.
Check the boiler water temperature sensor
(see page 110).
Check the boiler water temperature sensor
(see page 110).
Check temperature sensor
(see page 110).
Lead break, temperature sensor aJA
Short circuit, temperature sensor aJB
Lead break, temperature sensor aJB
Fault, safety equipment at “X7” of plug-in adaptor
2 for external safety equipment
Fault, safety equipment at “X3” of plug-in adaptor
2 for external safety equipment
Fault, safety equipment at “X2” of plug-in adaptor
2 for external safety equipment
Fault, safety equipment at “X1” of plug-in adaptor
2 for external safety equipment
Therm-Control configuration fault:
Plug aJA not plugged in.
Check temperature sensor
(see page 110).
Without temperature sensor:
Set code “4A:0” in group 1
“General”.
Check temperature sensor
(see page 110).
Check temperature sensor
(see page 110).
Without temperature sensor:
Set code “4B:0” in group 1
“General”.
Check safety equipment, and reset if required.
Check safety equipment, and reset if required.
Check safety equipment, and reset if required.
Check safety equipment, and reset if required.
Insert plug aJA.
For Vitocrossal, code “0D:
0” in group 2 “Boiler” must be selected.
Insert plug aJA and check codes.
Return temperature control configuration error:
Code “0C:1” in group 2
“Boiler” has been set, but plug aJA is not plugged in and/or code “4E:0” in group 1 “General” is not set.
53
54
Troubleshooting, Vitotronic 300, GW5B
Fault Codes
(continued)
Vitotronic 300, GW5B & MW1B Installation and Service
B0
B1
B5
B6
Displayed fault code
AD
B7
B8
BF
C1
C8
C9
CA
CB
CE
CF
D1
D2
D4
System characteristics Cause Measures
Control mode.
Control mode.
Control mode.
Control mode.
Control mode.
Isolation valve configuration error:
Code “0C:2”, “0C:
3” or “0C:4” in group 2 “Boiler” is set and code “4E:1” in group 1
“General” is set.
Short circuit, flue gas temperature sensor
Communication fault, programming unit
Internal fault
Invalid hardware recognized
With isolation valve:
Set code “4E:0” in group 1
“General”.
Without isolation valve:
Set code “0C:1” in group 2 “Boiler”.
Check the flue gas temperature sensor (see page 110).
Check connections and replace the programming unit if required.
Check PCB and plug-in connections; replace PCB if required.
Check coding address
“92” in group 1 “General”;
“92:161” must be set.
Plug in boiler coding card or replace.
Boiler is regulated by the temperature controller.
Control mode.
Boiler coding card faulty
Lead break, flue gas temperature sensor
Check the flue gas temperature sensor (see page 110).
Without flue gas temperature sensor:
Set code “1F:0” in group 2 “Boiler”.
Replace LON communication module.
Control mode.
No communication via
LON.
Boiler cools down.
Incorrect LON communication module
Boiler cools down.
Boiler cools down.
Boiler cools down
Boiler cools down
Control mode.
Control mode.
No communication via
LON.
Boiler cools down
Control mode.
Boiler cools down
External safety equipment at plug abÖ
Fault, low water indicator at “X7” of plug-in adaptor 1 for external safety equipment
Fault, maximum pressure limiter at
“X3” of plug-in adaptor 1 for external safety equipment
Fault, minimum or maximum pressure limiter 2 at “X2” of plug-in adaptor 1 for external safety equipment
Additional high limit safety cut-out fault or temperature limiter at “X1” of plug-in adaptor 1 for external safety equipment
Communication fault, plug-in adaptor
1 for external safety equipment
Communication fault, LON communication module of control unit
Burner fault
Communication fault, plug-in adaptor
2 for external safety equipment
The high limit safety cut-out has responded or fuse F2 has blown
Check connection and external safety equipment.
Check the system water level; reset low water indicator.
Check system pressure; reset maximum pressure limiter.
Check system pressure, reset minimum or maximum pressure limiter 2.
Check system temperature; reset high limit safety cut-out.
Check plug-in adaptor.
Without plug-in adaptor:
Set code “30:0” in group 1 “General”.
Check LON communication module and replace if required.
Check the burner
Check plug-in adaptor.
Without plug-in adaptor:
Set code “31:0” in group 1 “General”.
Check the high limit safety cut-out or the burner, burner loop and fuse F2.
Vitotronic 300, GW5B & MW1B Installation and Service
Fault Display
Troubleshooting, Vitotronic 300-K
In the event of a fault, the red fault display flashes at the control unit. “Fault” is displayed and
The fault code is displayed with OK.
flashes.
Note: If a central fault message facility is connected, this is started.
For an explanation of the fault code, see chapter “Fault codes”.
For some faults, the type of fault is also displayed in plain text.
Acknowledging faults
Follow the instructions on the display.
Note: The fault message is transferred to the menu.
A fault message facility, if connected, will be switched off.
If an acknowledged fault is not remedied, the fault message will be re-displayed the following day and the fault message facility restarted.
Calling up acknowledged fault messages
Extended menu:
1.
2. “Fault”
Calling up fault codes from the fault memory (fault history)
The 10 most recent faults (including those remedied) are saved and can be called up.
Faults are sorted by date.
1. Press OK and simultaneously for approx. 4 sec.
3. “Display?”
55
56
Troubleshooting, Vitotronic 300-K
Fault Codes
Vitotronic 300, GW5B & MW1B Installation and Service
Displayed fault code
10
18
20
28
40
44
48
4C
50
51
58
59
System characteristics
Activates at 32 °F (0° C) outside temperature.
Activates at 32 °F (0° C) outside temperature.
Stand-alone control unit without supply temperature sensor (poss. supply temperature not high enough).
Stand-alone control unit without supply temperature sensor (poss. supply temperature not high enough).
Mixing valve is closed.
Mixing valve is closed.
Mixing valve is closed.
Mixing valve is closed.
DHW tank primary pump “ON”:
Set DHW temperature = set supply temperature
Priority control is cancelled.
or
With primary store system:
DHW tank heating is started and stopped by DHW tank temperature sensor 2.
With primary store system:
DHW tank heating is started and stopped by DHW tank temperature sensor 1.
DHW tank primary pump “ON”:
Set DHW temperature = set supply temperature
Priority control is cancelled.
or
With primary store system:
DHW tank heating is started and stopped by DHW tank temperature sensor 2.
With primary store system:
DHW tank heating is started and stopped by DHW tank temperature sensor 1.
Cause
Short circuit, outside temperature sensor
Lead break, outside temperature sensor
Short circuit, common supply temperature sensor
Lead break, common supply temperature sensor
Short circuit, supply temperature sensor, heating circuit with mixing valve M2 (heating circuit 2)
Short circuit, supply temperature sensor, heating circuit with mixing valve M3 (heating circuit 3)
Lead break, supply temperature sensor, heating circuit with mixing valve M2 (heating circuit 2)
Lead break, supply temperature sensor, heating circuit with mixing valve M3 (heating circuit 3)
Short circuit, DHW tank temperature sensor 1
Short circuit, DHW tank temperature sensor 2
Lead break, DHW tank temperature sensor 1
Lead break, DHW tank temperature sensor 2
Measures
Check outside temperature sensor (see page 110).
Check outside temperature sensor (see page 110).
Check supply temperature sensor
(see page 110).
Check supply temperature sensor
(see page 110).
Check supply temperature sensor
(see page 110).
Check supply temperature sensor
(see page 110).
Check supply temperature sensor
(see page 110).
Check supply temperature sensor
(see page 110).
Check the DHW tank temperature sensor
(see page 110).
Check the DHW tank temperature sensor
(see page 110).
Check the DHW tank temperature sensor (see page 110).
Check the DHW tank temperature sensor
(see page 110).
Vitotronic 300, GW5B & MW1B Installation and Service
Fault Codes
(continued)
Troubleshooting, Vitotronic 300-K
Displayed fault code
60
68
System characteristics
Boiler with maximum temperature, no output reduction, mixing valve return temperature control “Open”.
Boiler with maximum temperature, no output reduction, mixing valve return temperature control “Open”.
70
78
90
Shunt pump constantly “ON”.
With primary store system:
3-way mixing valve “Closed”; no DHW heating.
Shunt pump constantly “ON”.
With primary store system:
3-way mixing valve “Closed”; no DHW heating.
Control mode.
91
92
93
94
98
99
9A
Control mode.
No solar DHW heating.
Control mode
No solar DHW heating.
Control mode
Control mode
No solar DHW heating.
Cause Measures
Short circuit, temperature sensor aJ A
Check temperature sensor
(see page 110).
Lead break, temperature sensor aJ
A
Short circuit, temperature sensor aJ
B
Check temperature sensor
(see page 110).
Without temperature sensor:
Set code “4A:0” in the
“General” group.
Check temperature sensor
(see page 110).
Lead break, temperature sensor aJ B
Check temperature sensor
(see page 110).
Without temperature sensor:
Set code “4b:0” in the
“General” group.
Short circuit, temperature sensor
/ , connection to solar control module.
Short circuit, temperature sensor aÖ
, connection to solar control module.
Short circuit, collector temperature sensor, connection of temperature sensor & at solar control module or sensor at S1 of the Vitosolic.
Short circuit, temperature sensor, connection at S3 of the Vitosolic
Check temperature sensor /
(see separate installation and service instructions).
Check temperature sensor aÖ
(see separate installation and service instructions).
Check sensor at the solar control unit (see separate installation and service instructions).
Short circuit, DHW tank temperature sensor, connection of temperature sensor % at solar control module or sensor at S2 of the Vitosolic.
Lead break, temperature sensor
/ , connection to solar control module.
Lead break, temperature sensor aÖ , connection to solar control module.
Lead break, collector temperature sensor, connection of temperature sensor & at solar control module or sensor at S1 of the Vitosolic.
Check sensor at the solar control unit (see separate installation and service instructions).
Check sensor at the solar control unit (see separate installation and service instructions).
Check temperature sensor /
(see separate installation and service instructions).
Set coding address “20” in the
“Solar” group.
Check temperature sensor aÖ (see separate installation and service instructions).
Set coding address “20” in the
“Solar” group.
Check sensor at the solar control unit (see separate installation and service instructions).
57
58
Troubleshooting, Vitotronic 300-K
Fault Codes
(continued)
Vitotronic 300, GW5B & MW1B Installation and Service
Displayed fault code
9B
9C
9E
9F
AB
B1
B5
B6
BA
BC
BD
BE
BF
System characteristics Cause
Control mode.
Control mode.
Control mode.
Control mode, DHW tank may be cold.
Lead break, temperature sensor, connection at S3 of the Vitosolic
No solar DHW heating. Lead break, DHW tank temperature sensor, connection of temperature sensor % at solar control module or sensor at S2 of the Vitosolic.
No flow rate in solar circuit or flow rate too low, or temperature limiter has responded.
Solar control module or Vitosolic faulty.
Displayed if a fault occurs at these devices for which there is no fault code in the Vitotronic.
Primary store system configuration error:
Code “55:3” has been selected in the
“DHW” group, but plug aJB is not plugged in and/or codes “4C:1” and
“4E:2” in the “General” group have not been set.
Communication fault, programming unit
Internal fault
Invalid hardware recognized
Measures
Check sensor at the solar control unit
(see separate installation and service instructions).
Check sensor at the solar control unit
(see separate installation and service instructions).
Check solar circuit.
Acknowledge fault message (see separate installation and service instructions).
Check solar control unit (see separate installation and service instructions).
Insert plug aJB and check codes.
Control mode.
Control mode.
Constant mode.
Check connections and replace the programming unit if required.
Check PCB is plugged in correctly.
Check coding address
“92” in the “General” group; “92:187” must be set.
Mixing valve “Closed”. Communication fault, PCB, extension for heating circuits 2 and 3 with mixing valve
Control mode without remote control.
Control mode without remote control.
Control mode without remote control.
Control mode.
No communication via
LON.
Communication fault, remote control
Vitotrol system circuit A1 (heating circuit 1)
Communication fault, remote control
Vitotrol, heating circuit with mixing valve M2 (heating circuit 2)
Note: Code “8A:176” must be selected so that coding address “92” is displayed.
Check that the PCB and ribbon cable are plugged in, and replace PCB if required.
Check connections, lead (see separate installation and service instructions) and coding address “A0” in the “Heating circuit…” group.
Check connections, lead (see separate installation and service instructions) and coding address “A0” in the “Heating circuit…” group.
Communication fault, remote control
Vitotrol with mixing valve M3 (heating circuit 3)
Check connections, lead (see separate installation and service instructions) and coding address “A0” in the “Heating circuit…” group.
Incorrect LON communication module Replace LON communication module.
Vitotronic 300, GW5B & MW1B Installation and Service
Fault Codes
(continued)
Troubleshooting, Vitotronic 300-K
Displayed fault code
C2
CF
D3
D5
D6
D7
D8
DA
DB
DC
DD
DE
DF
System characteristics
Control mode.
Control mode.
No communication via LON.
Control mode.
Cause Measures
Lead break, KM
BUS to solar control module or
Vitosolic
Communication fault, LON communication module of control unit
Check KM BUS cable and appliance.
Without solar control unit:
Set code “54:0” in the “General” group.
Check LON communication module and replace if required.
Communication fault extension EA1 Check connections (see page 88).
Without extension EA1:
Set code “5B:0” in the “General” group.
Boiler does not log in at the cascade control unit
Check communication via participant check, leads/ cables to the Vitotronic 300, GW5B and codes.
Boiler ramps to the electronic maximum boiler water temperature limit.
Control mode.
Control mode.
Control mode.
Control mode without room influence.
Control mode without room influence.
Control mode without room influence.
Control mode without room influence.
Input DE1 at extension EA1 reports a fault
Input DE2 at extension
EA1 reports a fault
Input DE3 at extension EA1 reports a fault
Short circuit, room temperature sensor, system circuit A1
(heating circuit 1)
Short circuit, room temperature sensor, heating circuit with mixing valve M2 (heating circuit 2)
Short circuit, room temperature sensor, heating circuit with mixing valve M3 (heating circuit 3)
Lead break, room temperature sensor, system circuit A1
(heating circuit 1)
Remove fault at appliance concerned.
Remove fault at appliance concerned.
Remove fault at appliance concerned.
Check the room temperature sensor
(see page 110).
Check the room temperature sensor
(see page 110).
Check the room temperature sensor
(see page 110).
Control mode without room influence.
Control mode without room influence.
Lead break, room temperature sensor, heating circuit with mixing valve M2 (heating circuit 2)
Lead break, room temperature sensor, heating circuit with mixing valve M3 (heating circuit 3)
Check room temperature sensor (see page
110) and adjustment of the remote control
(see separate installation and service instructions).
Check room temperature sensor (see page
110) and adjustment of the remote control
(see separate installation and service instructions).
Check room temperature sensor (see page
110) and adjustment of the remote control
(see separate installation and service instructions).
59
60
Function Description
Vitotronic 300, GW5B & MW1B Installation and Service
Boiler Temperature Control of the Vitotronic 300 GW5B
Brief description
H
The boiler water temperature is regulated by starting and stopping the burner or through modulation.
H
The set boiler water temperature is specified by the
Vitotronic 300-K cascade control unit.
Functions
The boiler water temperature is captured by the following equipment:
Upper control range limits
H
High limit safety cut-out 210° F (99º C)
H
Temperature controller TR 203/212/230° F
(95/100/110º C)
H
Electronic maximum temperature limit:
– Setting range: 68 to 260° F (20 to 127º C)
– Changed via coding address “06” in the “Boiler”
group.
Lower control range limits
H
In standard mode and when frost protection is enabled, the boiler water temperature will be regulated subject
to the respective boiler.
Vitotronic 300, GW5B & MW1B Installation and Service
Function Description
Boiler Temperature Control of the Vitotronic 300, GW5B
(continued)
ON
OFF set low heat demand average heat demand high heat demand
Time
Switching hysteresis, burner
Permanent switching hysteresis
Code “04:0”
Heat demand-dependent switching hysteresis
The heat demand-dependent switching hysteresis takes the boiler load into account.
The switching hysteresis, i.e the burner runtime varies subject to actual heat demand.
ON
OFF set low heat demand average heat demand high heat demand
Time
ERB50 function
Code “04:1”
Subject to heat demand, values between 6 and 12 K result.
ON
OFF set low heat demand average heat demand high heat demand
Time
ERB80 function
Code “04:2”
Subject to heat demand, values between 6 and 20 K result.
Control sequence
Boiler goes cold
(set value −2 K)
The burner start signal is selected as the set boiler water temperature minus 2 K, and the burner starts its own monitoring program.
Note: The burner start may be delayed by a few minutes subject to the number of auxiliary circuits and the combustion type.
Boiler heats up
(Set value +2 K)
The burner shuts down.
Modulating burner:
The burner stop point is determined by the stop differential (coding address “13” in the “Boiler” group).
61
62
Function Description
Cascade Control of the Vitotronic 300-K
Vitotronic 300, GW5B & MW1B Installation and Service
Brief description
The supply temperature is regulated by starting or stopping the burners or by starting/stopping individual burner stages.
H
Stand-alone control
H
Sequential control
H
Subject to the system version, we differentiate between condensing strategy and two conventional strategies.
H
With supplytemperature sensor:
Set code “3B:1” or “3B:3” in the “Cascade” group.
The control deviation is calculated from the set supply temperature and the actual supply temperature to determine the start and shutdown criteria.
H
Without supply temperature sensor:
Set code “3B:0” or “3B:2” in the “Cascade” group.
To determine the start and stop criteria, the control deviation is calculated from the set boiler water temperature and the estimated average actual boiler water temperature of the currently active boilers.
Only boilers with open isolation valves are taken into consideration.
Set supply temperature
The set supply temperature is determined from the following parameters:
H
Set supply temperature of system circuit A1 (heating circuit 1) and heating circuits with mixing valve M2
(heating circuit 2) and M3 (heating circuit 3).
H
Set supply temperature of further consumers.
H
Set DHW temperature.
H
External demands.
Upper control range limits:
Maximum limit of the system supply temperature
(coding address “37” in the “Cascade” group).
Lower control range limits:
Minimum limit of the system supply temperature
(coding address “36” in the “Cascade” group).
Sequential control
H
With supply temperature sensor.
H
Set code “3B:4” in the “Cascade” group.
H
The control strategy is set automatically to conventional strategy 2, code “3C:2” (see page 64).
H
The cascade control unit regulates to the specified set supply temperature by stipulating the output for each individual boiler. The lead boiler can be operated in modulating mode. All other boilers are operated in two stages via a specified output (incl. modulating burners).
Cascading Layouts
Boilers connected in parallel
H
Without and with supply temperature sensor.
H
Set code “3B:0” or “3B:1” in the “Cascade” group.
H
The cascade control specifies the set boiler water temperature for all currently active boilers. Every boiler control unit regulates to the specified set value.
Control strategies
Condensing strategy
Benefit:
Optimum utilisation of the condensing effect and long burner runtimes.
Set code “3C:0” in the “Cascade” group.
It is the aim of the condensing strategy to operate as many boilers as possible at the lowest output level.
The following control strategies are available:
H
H
H
Condensing strategy
Conventional strategy 1 (see page 64)
Conventional strategy 2 (see page 64)
Boilers connected in series
H
Without and with supply temperature sensor.
H
Set code “3B:2” or “3B:3” in the “Cascade” group.
H
The control strategy is set automatically to conventional strategy 2, code “3C:2” (see page 64).
H
The cascade control specifies the set boiler water temperature for all currently active boilers. Every boiler control unit regulates to the specified set value.
If the lead boiler (condensing boiler) does not achieve the specified set value, it will only act to control the return temperature of the conventional boiler downstream. The conventional boiler is started late and is also shut down late.
H
Starting criterion:
Boilers are started via an output statement
(code “3D:1” in the “Cascade” group).
An additional boiler will start if the currently required output can also be achieved by the currently active boilers plus the next boiler in the boiler sequence (see page 63).
H
Shutdown criterion:
The boilers are shut down via a shutdown integral.
The shutdown criterion is met when the shutdown integral exceeds a limit set via coding address “46” in the “Cascade” group and the boiler started last will be shut down.
Vitotronic 300, GW5B & MW1B Installation and Service
Cascade Control of the Vitotronic 300-K
(continued)
Function Description
Conventional strategy 1
Benefit:
As few boilers as possible are active.
Set code “3C:1” in the “Cascade” group.
Conventional boilers are preferably operated at their upper output range, to reliably prevent formation of condensate due to low return temperatures. With this strategy, an additional boiler will only be started if the maximum output of all currently active burners is insufficient to achieve the set supply temperature. A boiler will be shut down when the remaining boilers can achieve the required output on their own.
H
Starting criterion:
The boilers are started via a starting integral. The next boiler in the boiler sequence will be started if the value set in coding address “45” in the “Cascade” group is exceeded (see page 93).
H
Shutdown criterion:
Boilers are shut down via an output statement (code
“3D:1” in the “Cascade” group). A boiler is shut down when the currently required output can be achieved without the boiler that was started last.
Condensing strategy (code “3C:0” in the “Cascade” group)
Example for the different control strategies
Two-boiler system with modulating burners:
H
Boiler 1: 100% rated output (base load set to 33%)
H
Boiler 2: 100% rated output (base load set to 33%)
Starting
Conventional strategy 2
Benefit:
Long burner runtimes.
Code “3C:2” in the “Cascade” group (factory set condition).
An additional boiler will only be started if the maximum output of all currently active burners is insufficient to achieve the set supply temperature.
A boiler will be shut down if the burners were returned to their minimum output because of a large negative control deviation and the output is still too high.
H
Starting criterion:
The boilers are started via a starting integral. The next boiler in the boiler sequence will be started if the value set in coding address “45” in the “Cascade” group is exceeded (see page 93).
H
Shutdown criterion:
The boilers are shut down via a shutdown integral.
The shutdown criterion is met when the shutdown integral exceeds a limit set via coding address “46” in the “Cascade” group and the boiler started last will be shut down.
Shutdown
t
63
64
Function Description
Vitotronic 300, GW5B & MW1B Installation and Service
Cascade Control of the Vitotronic 300-K
(continued)
Conventional strategy 1 (code “3C:1” in the “Cascade” group)
Starting
Conventional strategy 2 (code “3C:2” in the “Cascade” group)
Starting
Shutdown
Shutdown
Vitotronic 300, GW5B & MW1B Installation and Service
Heating Circuit Control Unit of the Vitotronic 300-K
Function Description
Brief description
H
The control unit has control circuits for one system circuit A1 (heating circuit 1) and two heating circuits with mixing valve M2 (heating circuit 2) and M3
(heating circuit 3).
H
The set supply temperature of every heating circuit is determined from the following parameters:
– Outside temperature
– Set room temperature
– Operating mode
– Heating curve slope and shift
H
The supply temperature of the system circuit corresponds to the common system supply temperature.
H
The supply temperature of the heating circuits with mixing valve is regulated by the gradual opening or closing of the mixing valves. The mixing valve motor control changes the actuating and pause times subject to the control differential (control deviation).
Functions
The system circuit is subject to the boiler water temperature and its control range limits.
The heating circuit pump is the only actuator.
The supply temperature of the heating circuits with mixing valve is recorded by the supply temperature sensor of the relevant heating circuit.
H
Upper control limit: Electronic maximum supply temperature limit Coding address “C6” in the “Heating circuit…” group.
H
Lower control range limit: Electronic minimum supply temperature limit Coding address “C5” in the “Heating circuit…” group.
Outside temperature
A heating curve must be set for matching the control unit to the building and the heating system.
The heating curve characteristics determine the set boiler water temperature subject to outside temperature. An average outside temperature is used for control purposes.
This comprises the actual and the adjusted outside temperature.
Room temperature
In conjunction with the remote control and room temperature hook-up (coding address “B0” in the
“Heating circuit…” group):
Compared with the outside temperature, the room temperature has a greater influence on the set boiler water temperature (changed via coding address “B2” in the “Heating circuit…” group).
In conjunction with heating circuits with mixing valve:
For control differentials (actual value deviation) above
2 K room temperature, the influence can be increased again (coding address “B6” in the “Heating circuit…” group):
H
Quick heat-up
The set room temperature must be raised by at least
2 K by the following measures:
– Enabling party mode
– Changing from central heating with reduced
temperature to central heating with standard
temperature
– Start optimization (coding address “B7” in the
“Heating circuit…” group)
Quick heat-up will stop when the set room temperature has been reached.
Time program
In accordance with the time program in the “Heating and DHW” heating program, the control unit regulates between “Central heating at standard room temperature” and “Central heating at reduced room temperature”.
Every operating mode has its own set level.
4 time phases per day can be selected.
H
Quick setback
The set room temperature must be reduced by at least
2 K by the following measures:
– Enabling economy mode
Changing from central heating with standard temperature to central heating with reduced temperature
–
“Heating circuit…” group)
Quick setback will stop when the set room temperature has been reached.
65
66
Function Description
Vitotronic 300, GW5B & MW1B Installation and Service
Heating Circuit Control Unit of the Vitotronic 300-K
(continued)
DHW temperature
Priority control
H
With priority control: (code “A2:2” in the “Heating circuit…” group):
The set supply temperature is set to 32° F (0° C)
during DHW tank heating. The mixing valve closes and
the heating circuit pump is switched off.
H
Without priority control: The heating circuit control unit continues to operate with the same set value.
System dynamics
You can influence the control characteristics of the mixing valves via coding address “C4” in the “Heating circuit…” group.
Central control
Central control for a heating circuit can be programmed via coding address “7A” in the “General” group.
The heating and holiday program then applies to all additional heating circuits of the system.
For these heating circuits, when the heating and holiday program is enabled, “Central control” is displayed. Any holiday programs that may have been set will be deleted.
Party and economy modes cannot be enabled on all control units.
Heating circuit pump logic (economy mode)
The heating circuit pump is switched off [set supply temperature set to 32° F (0° C)] if the outside temperature exceeds the value selected via coding address “A5” in the “Heating circuit…” group.
Extended economy mode
The heating circuit pump is switched off [set supply temperature set to 32° F (0° C)] if one of the following criteria is met:
H
The adjusted outside temperature exceeds the value selected via coding address “A6” in the “Heating circuit…” group.
H
The heating circuit pump can be switched off for a time calculated by the control unit when changing over from heating mode to reduced mode.
Requirement:
– There is no risk of frost.
– must be set to 0.
The idle period can be individually adjusted via coding
address “A9” in the “Heating circuit…” group.
Note: If, during the pump idle period, the system is switched over to heating mode or the set room temperature is increased, the heating circuit pump is switched on, even if the period has not yet expired.
H
The actual room temperature exceeds the value selected via coding address “B5” in the “Heating circuit…” group.
H
The mixing valve has been closed for 12 min. (mixing valve economy function, coding address “A7” in the
“Heating circuit…” group).
Frost protection
The supply temperature is maintained in accordance with the heating curve for the reduced set room temperature, but at min. 50° F (10° C).
A variable frost limit can be set in accordance with coding address “A3” in the “Heating circuit…” group.
Vitotronic 300, GW5B & MW1B Installation and Service
Heating Circuit Control Unit of the Vitotronic 300-K
(continued)
Function Description
Outside temperature
Legend
A
Maximum supply temperature limit (coding address
“37” in the “Cascade” group)
B Slope = 1.8 for system circuit
C Slope = 1.2 for heating circuit with mixing valve
D Common supply temperature (at a differential temperature = 8 K)
E
Lower common supply temperature
Supply temperature control
Differential temperature:
The differential temperature is adjustable via coding address “9F” in the “General” group, factory set condition
8 K.
The differential temperature is the value by which the common supply temperature should be higher than the highest currently required supply temperature of the heating circuit with mixing valve.
H
System with only one heating circuit with mixing valve:
The common set supply temperature is regulated automatically to 8 K above the set supply temperature of the heating circuit with mixing valve.
H
System with system circuit and heating circuits with mixing valve:
The common set supply temperature operates in accordance with its own heating curve. The differential temperature of 8 K towards the set supply temperature of the heating circuits with mixing valve is set at the factory.
Raising the reduced room temperature
During operation with reduced room temperature, the reduced set room temperature can be automatically raised subject to the outside temperature. The temperature is raised in accordance with the selected heating curve, but no higher than the set standard room temperature.
The outside temperature limits for the start and end of the temperature raising can be adjusted via coding addresses
“F8” and “F9” in the “Heating circuit…” group.
Example using the settings in the factory set condition
Reducing the heat-up time
During the transition from operation with reduced room temperature to operation with standard room temperature, the boiler water or supply temperature will be raised in accordance with the selected heating curve. The boiler water or supply temperature increase can be automatically raised.
The value and duration of the additional increase of the set boiler water or supply temperature can be adjusted in coding addresses “FA” and “FB” in the “Heating circuit…” group.
Boiler water or Supply temperature
Set room temperature
Outside temp.
Legend
A Heating curve for operation with standard room
temperature
B Heating curve for operation with reduced room
temperature
67
68
Function Description
Vitotronic 300, GW5B & MW1B Installation and Service
Heating Circuit Control Unit of the Vitotronic 300-K
(continued)
Example using the settings in the factory set condition
Time in h
Legend
A
Start of operation with standard room temperature
B Set boiler water or supply temperature in accordance with the selected heating curve
C Set boiler water or supply temperature in accordance with coding address “FA”:
122° F + 20% = 146° F
(50° C + 20% = 60° C)
D Duration of operation with raised set boiler water or supply temperature in accordance with coding address
“FB”: 60 min.
Control sequence
Mixing valve circuit
The mixing valve motor will not be controlled within the
“neutral zone” (±1 K).
Supply temperature drops
(Set value −1 K)
The mixing valve motor receives the signal “Mixing valve open”. The signal duration lengthens with an increasing control differential.
The duration of pauses reduces with an increasing control differential.
Supply temperature rises
(Set value +1 K)
The mixing valve motor receives the signal “Mixing valve closed”. The signal duration lengthens with an increasing control differential.
The duration of pauses reduces with an increasing control differential.
Vitotronic 300, GW5B & MW1B Installation and Service
DHW Tank Temperature Control of the Vitotronic 300-K
Function Description
Brief description
H
The DHW tank temperature control is a constant temperature control. This is the result of starting and stopping the circulation pump for DHW tank heating.
The switching differential is ±2.5 K.
H
When the DHW tank is heated, a set supply temperature is specified that is 20 K higher than the set
DHW temperature (adjustable via coding address “60” in the “DHW” group).
Frost protection
The DHW tank will be heated to 68° F (20° C) if the
DHW temperature sinks below 41° F (5° C).
Auxiliary function for DHW heating
This function is activated by providing a second set DHW temperature via coding address “58” in group “DHW” and activating the fourth DHW phase for DHW heating.
Functions
Time program
An automatic or an individual time program may be selected for DHW heating and the DHW recirculation pump.
Compared with the heating circuit heatup phase, DHW heating starts 30 min. earlier in automatic mode.
The individual time program enables up to 4 time phases per day to be set for DHW heating and the DHW recirculation pump for every day of the week.
All DHW tank heating sequences will be completed independently of the time program.
In conjunction with coding address “7F” in the “General” group
H
Detached house Code
“7F:1”:
– Automatic mode
The heating times for heating circuit 1 are applied to systems with two or three heating circuits.
– Individual time program
The time phases for DHW heating and the DHW recirculation pump have the same effect on all heating circuits.
H
Apartment building
Code “7F:0”:
– Automatic mode
For systems with two or three heating circuits, the heating times for the relevant heating circuit will be applied.
– Individual time program
The time phases for DHW heating and the DHW recirculation pump can be adjusted individually for each heating circuit.
Set DHW temperature
The set DHW temperature can be adjusted between 50 and 140° F (10 and 60° C).
The set value range can be extended to 203° F (95 ºC) via coding address “56” in the “DHW” group.
The set default value of the programming unit and/or the
Vitotrol 300A remote control units can be allocated via coding address “66” in the “DHW” group.
DHW recirculation pump
This delivers hot water to the draw-off points at adjustable times.
Four time phases can be selected at the control unit for every day.
Auxiliary circuits
DHW heating in conjunction with the heating circuits can be disabled or enabled by changing over the heating program (see coding address “D5” in the “Heating circuit
…” group).
System with primary store system
The above functions also apply in conjunction with primary store systems.
Set the following codes:
“55:3” in the “DHW” group; “4C:1”, “4E”:
2 in the “General” group.
System with solar control unit
A third set DHW temperature can be specified via coding address “67” in the “DHW” group.
The DHW tank is only reheated by the boiler if the temperature falls below this value.
Priority control
H
With priority control: (code “A2:2” in the “Heating circuit…” group):
The set supply temperature is set to 32° F (0° C)
during DHW tank heating. The mixing valve closes
and the heating circuit pump is switched off.
H
Without priority control:
The heating circuit control unit continues to operate with the same set value.
69
70
Function Description
Vitotronic 300, GW5B & MW1B Installation and Service
DHW Tank Temperature Control of the Vitotronic 300-K
(continued)
Control sequence
Code “55:0” in the “DHW” group, DHW tank heating
The DHW tank goes cold (set value −2.5 K, adjustable via coding address “59”):
H
The common set supply temperature is set 20 K higher than the set DHW temperature (adjustable via coding address “60”).
The DHW tank is hot (set value +2.5 K):
H
The common set supply temperature is returned to the set weather-compensated value.
H
Pump run-on:
The circulation pump runs on after DHW tank heating
until one of the following criteria is met:
– The set DHW temperature is exceeded by 5 K.
– The set max. run-on time is reached (coding address
“62”).
H
Without pump run-on (code “62:0”).
Code “55:2” in the “DHW” group, DHW tank temperature control with 2 DHW tank temperature sensors
DHW tank temperature sensor 1 enables the circulation pump for DHW tank heating and is evaluated for stop conditions during the pump run-on time.
DHW tank temperature sensor 2:
The DHW tank heating will be switched on early if a lot of hot water is drawn off. The DHW tank heating will be switched off early if no hot water is drawn off.
DHW tank goes cold:
H
Set value −2.5 K, adjustable via coding address “59”
or
H
Actual DHW temperature at sensor 2 < set DHW temperature x factor for start time (adjustment via coding address “69”)
The DHW tank is hot:
H
Set value +2.5 K and
H
Actual DHW temperature at sensor 2 > set DHW temperature x factor for stop time (adjustment via coding address “68”)
Code “55:1” in the “DHW” group, adaptive DHW tank heating
With adaptive DHW tank heating, the speed of the temperature rise during DHW heating is taken into account.
The DHW tank goes cold (set value −2.5 K, adjustable via coding address “59”):
H
The common set supply temperature is set 20 K higher than the set DHW temperature (adjustable via coding address “60”).
The DHW tank is hot:
H
The control unit checks whether the boiler will be required to supply heat after the DHW tank has been heated up or whether residual boiler heat should be transferred to the DHW tank.
Accordingly, the control unit determines the burner and circulation pump stop times to prevent the set DHW temperature being substantially exceeded after the
DHW tank has been heated up.
Code “55:3” in the “DHW” group, DHW tank temperature control, primary store system
The DHW tank goes cold (set value −2.5 K, adjustable via coding address “59”):
H
The common set supply temperature is set 20 K higher than the set DHW temperature (change via coding address “60”).
H
The primary pump in the primary store system starts.
H
The 3-way mixing valve opens and then regulates to the specified set value.
H
The circulation pump for DHW tank heating cycles
(briefly switches on and off) until the set supply temperature has been reached (set DHW temperature
+ 5 K). Then it runs constantly. If, during heating, the actual value falls below the required set temperature, the circulation pump for DHW tank heating will temporarily cycle again.
The DHW tank is hot:
H
DHW tank temperature sensor 1:
Actual value ≥ set value and
DHW tank temperature sensor 2:
Actual value > set value −1.5 K:
H
The common set supply temperature is returned to the set weather-compensated value.
H
The circulation pump for DHW tank heating stops immediately when the 3-way mixing valve is fully opened.
or
H
The circulation pump for DHW tank heating stops after expiry of the run-on time that is selected via code “62”.
Vitotronic 300, GW5B & MW1B Installation and Service
Calling up Coding Level 1
Coding 1, Vitotronic 300, GW5B
Prior to coding the Vitotronic 300 GW5B, ensure the boiler is in cascade mode. Refer to page 25.
For the Vitotronic 300 GW5B, see boiler
Service Instructions
1. Press and OK for approximately 4 seconds.
to scroll to service functionsand select
OK.
to scroll to multi-boiler systemand select
OK.
5. Allow control to restart.
6.
Upon restart, use to select ‘language’.
Note: Codes are displayed as plain text.
Codes that have no function due to the heating
system equipment level or the setting of other
codes are not displayed.
1. Press OK and for approximately 4 seconds.
2. “Coding level 1”
3. Select group of required coding address:
“General”
—
— “All codes std. device”
In this group, all coding addresses from coding level 1
4. Select coding address.
5. Select value according to the following tables and with
6. If you want to reset all codes to their factory setting:
Select “Standard setting” in “Coding level 1”.
Note: This also resets codes from coding level 2.
Group 1 “General”
Coding
Coding in the factory set condition
System design
00:0 Set automatically if code “01:2” is set.
Boiler control unit is linked into the cascade.
Servomotor runtime
40:…
Runtime, isolation valve servomotor at plug gSA1.
Factory set condition specified by boiler coding card.
Participant no.
77:1
8F:0
LON participant number. If this address does not appear, power down the control and install the LON card and restart.
Operation in the standard menu and extended menu enabled.
Note: The respective code is only activated when you exit the service menu(see page 37).
Possible change
00:1
40:5 to
40:199
77:1 to
77:99
8F:1
8F:2
No function.
Runtime adjustable from 5 to 199 sec.
LON participant number, adjustable from 1 to 99.
Operation in standard menu and extended menu blocked.
Operation enabled in the standard menu and blocked in the extended menu.
71
72
Coding 1, Vitotronic 300, GW5B
Group 2 “Boiler”
Vitotronic 300, GW5B & MW1B Installation and Service
Coding
Coding in the factory set condition
System design
01:2 Multi boiler system with cascade control via LON.
Possible change
01:1
01:3
Boiler
07:1 Consecutive boiler number in multi boiler system.
07:2 to
07:4
Flue gas monitor
1F:0 With flue gas temperature sensor:
Flue gas temperature is not monitored for service display.
1F: 34 (1) to
1F: 482° F
(250° C)
Burner service in 100 hour
21:0 No service interval (hours run) selected.
21:1 to
21:100
Single boiler system.
Do not adjust.
Consecutive boiler number in multi boiler system.
When the limit for the flue gas temperature is exceeded, is displayed.
The number of hours run before the burner should be serviced is adjustable from 100 to 10,000 h;
1 step 100 h
Service interval in months
23:0 No interval for service.
to
23:24
Interval adjustable from 1 to 24 months.
Service status
24:0
No display.
24:1
display (the address is automatically set and must be manually reset after a service has been carried out).
Vitotronic 300, GW5B & MW1B Installation and Service
Calling up Coding Level 2
Coding 2, Vitotronic 300, GW5B
Note: At coding level 2, all codes are accessible, including the codes at coding level 1.
Codes that have not been assigned due to the heating system equipment level or the setting of other codes are not displayed.
1. Press simultaneously for approximately
2. Press simultaneously for approximately
3. “Coding level 2”
4. Select group of required coding address:
“General”
5. Select coding address.
6. Select value according to the following tables and confirm with “OK”.
7. If you want to reset all codes to their factory setting:
Select “Standard setting” in “Coding level 2”.
Note: This also resets codes at coding level 1.
73
74
Coding 2, Vitotronic 300, GW5B
Group 1 “General”
(continued)
Vitotronic 300, GW5B & MW1B Installation and Service
Coding
Coding in the factory set condition
00:0 Set automatically if code “01:2” is set.
Boiler control unit is linked into the cascade.
30:0
31:0
Without plug-in adaptor 1, external safety equipment.
Without plug-in adaptor 2, external safety equipment.
32:0 Without extension AM1.
33:1
34:0
40:…
4A:0
Function output A1 at extension AM1:
Heating circuit pump.
Function output A2 at extension AM1:
DHW recirculation pump.
Runtime, isolation valve servomotor at plug gSA1.
Factory set condition specified by boiler coding card.
Sensor aJA not available.
Possible change
00:1 No function.
30:1
31:1
32:1
33:3
34:3
40:5 to
40:199
4A:1
With plug-in adaptor 1, external safety equipment; automatic recognition.
With plug-in adaptor 2, external safety equipment; automatic recognition.
With extension AM1; automatic recognition.
Circulation pump for neutralizing system or flue gas/ water heat exchanger.
Circulation pump for neutralizing system or flue gas/ water heat exchanger.
Runtime adjustable from 5 to 199 sec.
4B:0
4C:2
4D:1
4E:0
4F:5
Sensor aJB not available.
Connection at plug sÖ:
Switching contact,
Therm-Control.
Connection at plug sL:
Shunt pump.
Connection at plug gS:
Motor for isolation valve.
4B:1
4C:1
4C:3
4D:2
4D:3
4E:1
Run-on time, shunt or boiler circuit pump
5 min.
4E:2
4F:0
4F:1 to
4F:60
Sensor aJA available (e.g. Therm-
Control temperature sensor); automatic recognition.
Sensor aJB available (e.g. return temperature sensor T2); automatic recognition.
Do not adjust.
Circulation pump – flue gas/water heat exchanger.
Boiler circuit pump.
Boiler circuit pump with isolation valve function.
Motor for 3-way mixing valve for return temperature control.
Do not adjust.
No pump run-on.
Run-on time adjustable from 1 to 60 min.
Vitotronic 300, GW5B & MW1B Installation and Service
Group 1 “General”
(continued)
Coding 2, Vitotronic 300, GW5B
Coding
Coding in the factory set condition
52:0
54:0
Do Not Adjust
Do Not Adjust
5B:0
5C:0
Without extension EA1.
Function, output aBJ at extension EA1:
Central fault message.
5D:0
5E:0
Function input DE1 at extension EA1:
No function.
Function input DE2 at extension EA1:
No function.
5E:2
5E:3
5E:4
5E:5
5E:6
5C:5
5D:1
5D:2
5D:3
5D:4
5D:5
5D:6
5E:1
Possible change
—
—
5B:1
5C:1
—
—
With extension EA1; automatic recognition.
No function.
5C:2
5C:3
5C:4
No function.
No function.
No function.
No function.
No function.
No function.
External blocking.
External blocking with fault message.
Fault message input.
No function.
No function.
No function.
External blocking.
External blocking with fault message.
Fault message input.
No function.
75
76
Coding 2, Vitotronic 300, GW5B
Group 1 “General”
(continued)
Vitotronic 300, GW5B & MW1B Installation and Service
Coding in the factory set condition
5F:0 Function input DE3 at extension EA1:
No function.
6C:0
6D:0
76:0
77:1
78:1
79:0
No run-on time neutralizing system.
No run-on time neutralizing system.
Without LON communication module.
LON participant number.
LON communication enabled.
Control unit is not fault manager.
5F:5
5F:6
6C:1 to
6C:255
6D:1 to
6D:255
76:1
Possible change
5F:1
5F:2
5F:3
5F:4
77:1 to
77:99
78:0
79:1
No function.
No function.
External blocking.
External blocking with fault message.
Fault message input.
No function.
Run-on time neutralizing system at output A1 at extension AM1, adjustable from 1 to 255 sec.
Run-on time neutralizing system at output A2 at extension AM1, adjustable from 1 to 255 sec.
With LON communication module; automatic recognition.
LON participant number, adjustable from
1 to 99.
LON communication disabled.
Control unit is fault manager.
Vitotronic 300, GW5B & MW1B Installation and Service
Group 1 “General”
(continued)
Coding 2, Vitotronic 300, GW5B
Coding in the factory set condition
80:6
88:0
8A:175
8B:0
8F:0
93:0
95:0
98:1
9B:0
9C:20
9D:0
If a fault occurs for at least
30 sec., a fault message is displayed.
Temperature displayed in °C (Celsius).
Do Not Adjust.
Do Not Adjust.
Operation in the standard menu and extended menu enabled.
Note: The respective code is only activated when you exit the service menu (see page 50).
Fault messages during emissions test function/service display do not affect central fault messages.
Do Not Adjust.
Viessmann system number (in conjunction with monitoring several systems via Vitocom 300).
Do not adjust.
Monitoring LON participants:
If there is no response from a participant, values specified by the control unit are used after 20 min and a fault message is issued
Do not adjust.
95:1
98:1 to
98:5
9C:0
9C:5 to
9C:60
—
—
Possible change
88:0
80:2 to
80:199
88:1
8F:1
8F:2
—
—
Immediate fault message.
The minimum fault duration until a fault message is issued is adjustable from
10 to 995 sec;
1 step 5 sec.
Temperature displayed in °F
(Fahrenheit).
—
—
Operation in standard menu and extended menu blocked.
Operation enabled in the standard menu and blocked in the extended menu.
93:1 Fault messages during emissions test function/ service display affect central fault messages.
—
System number adjustable from 1 to 5.
No monitoring
—
Time adjustable from 5 to 60 min.
—
77
78
Coding 2, Vitotronic 300, GW5B
Group 2 “Boiler”
(continued)
Vitotronic 300, GW5B & MW1B Installation and Service
Coding in the factory set condition
01:2 Multi boiler system with cascade control via
LON.
07:1 Consecutive boiler number in multi boiler system.
0C:5
0D:2
1F:0
21:0
23:0
24:0
2B:5
2C:5
2D:0
Modulating isolation valve, independent of the set boiler water temperature.
With Therm-Control, affects the isolation valve (function disabled with code “0C:1”).
With flue gas temperature sensor:
Flue gas temperature is not monitored for service display.
No service interval (hours run) selected.
No interval for service.
No display.
Maximum preheating time of the isolation valve
5 min.
Maximum run-on time of the isolation valve
5 min.
Shunt pump control function only “ON” if the boiler is enabled.
2B:1 to
2B:60
2C:0
2C:1 to
2C:60
2D:1
Possible change
01:1
01:3
07:2 to
07:4
0C:0
0C:1
Single boiler system.
Do not adjust.
Consecutive boiler number in multi boiler system.
No function.
Constant return temperature control.
0C:2
0C:3
0C:4
0D:0
0D:1
Time-controlled isolation valve.
Isolation valve switching, subject to the set boiler water temperature.
Modulating isolation valve, subject to the set boiler water temperature.
Without Therm-Control.
With Therm-Control, affects the mixing valves of downstream heating circuits.
1F: 34 (1) to
1F: 482°F
(250°C)
When the flue gas temperature limit is exceeded, is displayed.
21:1 to
21:100
The number of hours run before the burner should be serviced is adjustable from 100 to
10,000 h.
1 step 100 h.
Interval adjustable from 1 to 24 months.
23:1 to
23:24
24:1
2B:0
display (the address is automatically set and must be manually reset after a service has been carried out).
No preheating time.
Preheating adjustable from 1 to 60 min.
No run-on time.
Run-on time adjustable from 1 to 60 min.
Shunt pump control function permanently
“ON”.
Vitotronic 300, GW5B & MW1B Installation and Service
Calling up Coding Level 1
Coding 1, Vitotronic 300-K
Note:
H
The codes are displayed as plain text.
H
Codes that have no function due to the heating system equipment level or the setting of other codes are not displayed.
H
Heating systems with one system circuit and one or two heating circuits with mixing valve: In the following, the system circuit is designated “Heating circuit 1” and the heating circuits with mixing valve as “Heating circuit 2” or “Heating circuit 3”.
If the heating circuits were given individual designations, the selected designation and “HC1”,
“HC2” or “HC3” appear instead.
1. Press OK and simultaneously for approx. 4 sec.
2. “Coding level 1”
3. Select group of required coding address:
H
“General”
H
“Cascade”
H
“DHW”
H
“Solar”
H
“Heating circuit 1/2/3”
H
“All codes std device”
In this group, all coding addresses from coding
level 1 (except the coding addresses from the
“Solar” group) are displayed in ascending order.
4. Select coding address.
5. Select value according to the following tables and confirm with OK.
6. If you want to reset all codes to their factory set condition:
Select “Standard setting” in “Coding level 1”.
Note: This also resets codes from coding level 2.
79
80
Coding 1, Vitotronic 300-K
“General” Group
Vitotronic 300, GW5B & MW1B Installation and Service
Coding
Coding in the factory set condition
System design
00:1 One system circuit A1 (heating circuit
1), without DHW heating
Possible change
00:2 to
00:10
For system schemes, see the following table.
4
5
2
3
Value address
00: …
6
7
8
9
10
Description
One system circuit A1 (heating circuit 1) with DHW heating (automatic recognition)
One heating circuit with mixing valve M2 (heating circuit 2) without DHW heating
One heating circuit with mixing valve M2 (heating circuit 2) with DHW heating
One system circuit A1 (heating circuit 1) One heating circuit with mixing valve M2 (heating circuit 2) without DHW heating (automatic recognition)
One system circuit A1 (heating circuit 1) One heating circuit with mixing valve M2 (heating circuit 2) with DHW heating (automatic recognition)
Two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3) without DHW heating
Two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3) with DHW heating
One system circuit A1 (heating circuit 1)
Two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3) without DHW heating (automatic recognition).
One system circuit A1 (heating circuit 1)
Two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3) with DHW heating (automatic recognition).
Coding in the factory set condition
Servomotor runtime
40:125 3-way mixing valve servomotor runtime in conjunction with permanent return temperature control at plug gSA1 125 s.
Participant no.
77:5 LON participant number.
Possible change
40:5 to
40:199
77:1 to
77:99
Runtime adjustable from 5 to 199 sec.
LON participant number, adjustable from
1 to 99:
1 — 4 = Boiler control unit
5 = Cascade control unit
10 — 98 = Vitotronic 200-H
99 = Vitocom
Detached house/apartment building
7F:1 Detached house.
7F:0 Apartment building.
Separate adjustment of holiday program and time program for DHW heating possible.
General
8F:0 Operation in the standard menu and extended menu enabled.
Note: The relevant code is only enabled when you exit the service level
(see page 51)
Set supply temperature for external demand
9B:70 Set supply temperature for external demand 158° F (70° C).
8F:1
8F:2
9B:0
9B:1 to
9B:127
Operation in the standard menu and extended menu blocked.
Operation enabled in the standard menu; blocked in the extended menu.
No default set value.
Set supply temperature adjustable from
34 to 260° F (1 to 127° C).
Vitotronic 300, GW5B & MW1B Installation and Service
“Cascade” Group
Coding 1, Vitotronic 300-K
Coding
Coding in the factory set condition
Number of boilers in cascade
35:4 4 boilers connected to the Vitotronic
300-K.
Possible change
35:1 to
35:4
Min. system supply temperature
36:0 Electronic minimum system supply temperature limit set to 32° F (0° C).
36:1 to
36:127
Max. system supply temperature
37:80 Electronic maximum system supply temperature limit set to 176° F (80° C).
37:20 to
37:127
1 to 4 boilers connected to the
Vitotronic 300-K.
Minimum limit adjustable from 32 to
260° F (0 to 127° C).
Maximum limit adjustable from 68 to
260° F (20 to 127° C).
Note: Value must not be higher than the lowest value of coding address
“06” in the “Boiler” group of every Vitotronic 300, GW5B.
Control type
3B:1 Stand-alone parallel boiler circuit with supply temperature sensor
(see page 62).
3B:0
3B:2
3B:3
3B:4
Stand-alone parallel boiler circuit without supply temperature sensor (see page 62).
Stand-alone serial boiler circuit without supply temperature sensor (see page 62).
Stand-alone serial boiler circuit with supply temperature sensor (see page 62).
Sequential control with supply temperature sensor (see page 62).
Control strategy
3C:2 Conventional strategy 2 (see page 64).
3C:0
3C:1
Condensing strategy (see page 63).
Conventional strategy 1 (see page 64).
“DHW” Group
Coding
Coding in the factory set condition
DHW
67:40 For solar DHW heating:
Set DHW temperature 104° F (40° C).
Reheating is suppressed above the selected set temperature (DHW heating by the boiler only if solar energy is not sufficient).
Possible change
67:0
67:10 to
67:95
No third set value.
Set DHW temperature adjustable from 50 to 203° F (10 to 95° C) (limited by boiler specific parameters).
Observe the setting of coding address “56”.
Enable DHW recirculation pump
73:0 DHW recirculation pump:
“ON” according to time program.
73:1 to
73:6
73:7
“ON” from once per hour for 5 min up to
6 times per hour for 5 min. during the time program.
Constantly “ON”.
81
82
Coding 1, Vitotronic 300-K
“Solar” Group
Vitotronic 300, GW5B & MW1B Installation and Service
Only in conjunction with solar control module, type SM1.
Coding
Coding in the factory set condition
Speed control solar circuit pump
02:0 Solar circuit pump (multi stage) without speed control by solar control module SM1.
Possible change
02:1
02:2
Solar circuit pump (multi stage) is speedcontrolled with wave pack control.
Solar circuit pump is speed-controlled with
PWM control.
DHW tank maximum temperature
08:60 The solar circuit pump stops when the actual DHW temperature reaches the maximum DHW tank temperature 140° F
(60° C).
Stagnation time reduction
0A:5 To protect system components and heat transfer medium: the speed of the solar circuit pump is reduced if the actual DHW temperature is 5 K below the maximum
DHW tank temperature.
Flow rate solar circuit
0F:70 The solar circuit flow rate at maximum pump speed is 7 l/min.
08:10 to
08:90
0A:0
0A:1 to
0A:40
0F:1 to
0F:255
The maximum DHW tank temperature is adjustable from 50 to 194° F (10 to 90° C).
Stagnation time reduction is disabled.
Value for stagnation time reduction is adjustable from 1 to 40 K.
Flow rate adjustable from 0.1 to 25.5 l/min;
1 step 0.1 l/min.
Extended solar control functions
20:0 No extended control functions enabled.
20:1
20:2
20:3
20:4
20:5
20:6
20:7
20:8
20:9
Additional function for DHW heating.
Differential temperature control 2.
Differential temperature control 2 and auxiliary function.
Differential temperature control 2 for central heating backup.
Thermostat function.
Thermostat function and auxiliary function.
Solar heating via external heat exchanger without additional temperature sensor.
Solar heating via external heat exchanger with additional temperature sensor.
Solar heating of two DHW tanks.
Vitotronic 300, GW5B & MW1B Installation and Service
Coding 1, Vitotronic 300-K
“Heating Circuit 1”, “Heating Circuit 2”, “Heating Circuit 3” Group
Coding
Coding in the factory set condition
Priority DHW heating
A2:2 DHW tank priority applicable to heating circuit pump and mixing valve.
Possible change
A2:0
A2:1
Without DHW tank priority applicable to heating circuit pump and mixing valve.
DHW tank priority applies only to the mixing valves.
Economy function outside temperature
A5:5 With heating circuit pump logic function
(economy circuit): Heating circuit pump “OFF” when the outside temperature (AT) is 1 K higher than the set room temperature (RT
AT > RT set
+ 1 K set
)
A5:0
A5:1 to
A5:15
Without heating circuit pump logic function.
With heating circuit pump logic function:
Heating circuit pump “OFF”; see the following table.
Pump idle time, transition reduced mode. Operation
A9:7 With pump idle time (heating circuit pump
“OFF”).
(See function description on page 51).
Possible change
A7:1 With mixing valve economy function (extended heating circuit pump logic):
Heating circuit pump also “OFF”:
— If the mixing valve has been closed for longer than 20 min.
Heating circuit pump “ON”:
— If the mixing valve changes to control function.
— If there is a risk of frost.
A9:0
A9:1 to
A9:15
Without pump idle time.
With pump idle time; adjustable from 1 to 15.
1: short idle period
15: long idle period
83
Coding 1, Vitotronic 300-K
Vitotronic 300, GW5B & MW1B Installation and Service
“Heating Circuit 1”, “Heating Circuit 2”, “Heating Circuit 3” Group
(continued)
Coding in the factory set condition
Extended economy function mixing valve
Weather-compensated/room temperature hook-up
B0:0 With remote control:
*2
Heating mode/reduced mode: weathercompensated.
Possible change
B0:1
B0:2
B0:3
Economy function room temperature
B5:0 With remote control:
No room temperature dependent heating circuit pump logic function.
*2
B5:1 to
B5:8
Heating mode: weather-compensated
Reduced mode: with room temperature hook-up
Heating mode: with room temperature hook-up
Reduced mode: weather-compensated
Heating mode/reduced mode: with room temperature hook-up
Heating circuit pump logic function, see the following table.
84
Coding in the factory set condition
Min. supply temperature heating circuit
C5:20 Electronic minimum supply temperature limit
68° F (20° C) (only in operation at standard room temperature).
Max. supply temperature heating circuit
C6:75 Electronic maximum supply temperature limit set to 167° F (75° C).
Possible change
C5:1 to
C5:127
C6:10 to
C6:127
Heating program — changeover
D5:0 With external heating program changeover
(observe setting for coding addresses “5D”,
“5E” and “5F” in the “General” group).
Heating program switches to “Constant central heating with reduced room temperature” or
“Standby mode” (subject to the settings of the set reduced room temperature).
External heating program changeover to heating circuit
D8:0 No heating program changeover via extension
EA1.
D5:1
D8:1
D8:2
D8:3
Minimum limit adjustable from 32 to 260° F
(1 to 127° C) (limited by boiler-specific parameters).
Maximum limit adjustable from 50 to 260° F
(10 to 127° C) (limited by boiler-specific parameters).
The heating program changes to “Constant operation with standard room temperature”.
Heating program changeover via input DE1 at extension EA1.
Heating program changeover via input DE2 at extension EA1.
Heating program changeover via input DE3 at extension EA1.
Vitotronic 300, GW5B & MW1B Installation and Service
Coding 1, Vitotronic 300-K
“Heating Circuit 1”, “Heating Circuit 2”, “Heating Circuit 3” Group
(continued)
Coding in the factory set condition
Slab curing function (Not used)
F1:0 Slab curing function disabled. (Not used)
Possible change
F1:1 to
F1:6
F1:15
Party mode time limit
F2:8 Time limit for party mode or external heating program changeover via pushbutton: 8 h
*1
.
Note: Observe settings of coding addresses
“5D”, “5E”, “5F” in the “General” group, as well as “D5” and “D8” in the
“Heating circuit…” group.
Start temperature raising
F8:-5 Temperature limit for raising reduced mode
23° F (-5º C); see example on page 67.
Observe the setting of coding address “A3”.
F2:0
F2:1 to
F2:12
F8:+10 to
F8:-60
F8:-61
End temperature raising
F9:-14 Temperature limit for raising the reduced set room temperature 7° F (-14º C); see example on page 67.
Set supply temperature increase
FA:20 Raising the set boiler water or supply temperature by 20% when changing from operation with reduced room temperature to operation with standard room temperature.
See example on page 67.
Duration set supply temperature increase
FB:30 Duration for raising the set boiler water or supply temperature (see coding address “FA”)
60 min.
See example on page 67.
F9:+10 to
F9:-60
FA:0 to
FA:50
FB:0 to
FB:150
Only for heating circuits with mixing valve:
Slab curing function adjustable in accordance with 6 optional temperature/time profiles.
(Not used)
Constant supply temperature 68° F (20° C).
No time limit
*1
.
Time limit adjustable from 1 to 12 h
Temperature limit adjustable from
+50 to -76° F (+10 to -60° C).
Function disabled.
*1
.
Limit for raising the set room temperature to the value selected for standard mode adjustable from +50 to -76° F (+10 to -60° C).
Temperature rise adjustable from 0 to 50%.
Duration adjustable from 0 to 300 min;
1 step 2 min.
*1
Party mode ends automatically in the “Heating and DHW” heating program when the system changes over to operation with standard room temperature.
85
86
Coding 2, Vitotronic 300-K
Calling up Coding Level 2
Vitotronic 300, GW5B & MW1B Installation and Service
Note:
H
In coding level 2, all codes are accessible, including the codes from coding level 1.
H
Codes that have no function due to the heating system equipment level or the setting of other codes are not displayed.
H
Heating systems with one system circuit and one or two heating circuits with mixing valve:
In the following, the system circuit is designated
“Heating circuit 1” and the heating circuits with mixing valve as “Heating circuit 2” or “Heating circuit 3”.
If the heating circuits were given individual designations, the selected designation and “HC1”,
“HC2” or “HC3” appear instead.
1. Press OK and simultaneously for approx. 4 sec.
2. Press OK and simultaneously for approx. 4 sec.
3. “Coding level 2”
4. Select group of required coding address:
H
“General”
H
“Boiler”
H
“DHW”
H
“Solar”
H
“Heating circuit 1/2/3”
H
“All codes std device” In this group, all coding addresses (except the coding addresses from the
“Solar” group) are displayed in ascending order.
5. Select coding address.
6. Select value according to the following tables and confirm with “OK”.
7. If you want to reset all codes to their factory set condition:
Select “Standard setting” in “Coding level 2”.
Note: This also resets codes from coding level 1.
Vitotronic 300, GW5B & MW1B Installation and Service
“General” Group
Coding 2, Vitotronic 300-K
Coding
Coding in the factory set condition
00:1 One system circuit A1 (heating circuit 1), without DHW heating.
Possible change
00:2 to
00:10
For system schemes, see the following table.
3
4
5
Coding
Value address
00: …
2
6
7
8
9
10
Description
One system circuit A1 (heating circuit 1) with DHW heating (automatic recognition)
One heating circuit with mixing valve M2 (heating circuit 2) without DHW heating
One heating circuit with mixing valve M2 (heating circuit 2) with DHW heating
One system circuit A1 (heating circuit 1)
One heating circuit with mixing valve M2 (heating circuit 2) without DHW heating (automatic recognition)
One system circuit A1 (heating circuit 1)
One heating circuit with mixing valve M2 (heating circuit 2) with DHW heating (automatic recognition).
Two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3) without DHW heating
Two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3) with DHW heating
One system circuit A1 (heating circuit 1)
Two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3) without DHW heating (automatic recognition).
One system circuit A1 (heating circuit 1)
Two heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3) with DHW heating (automatic recognition).
Coding in the factory set condition
12:5
1E:0
With extension EA1:
DHW recirculation pump runtime for brief operation:
5 min.
With extension EA1 (analogue input 0-10 V):
Temperature demand from 32 to 212° F
(0 to 100° C):
1 V 50° F (10° C)
10 V 212° F (100° C)
2E:0
2F:0
Do not adjust.
Do not adjust.
40:125 3-way mixing valve servomotor runtime in conjunction with permanent return temperature control at plug gSA1 125 sec.
4A:0
Sensor aJA not available.
Possible change
12:1 to
12:60
Runtime adjustable from 1 to 60 min.
1E:1
—
—
40:5 to
40:199
4A:1
—
—
Temperature demand from 86 to 248° F
(30 to 120° C):
1 V 86° F (30° C)
10 V 248° F (120° C)
Runtime adjustable from 5 to 199 sec.
4B:0
4C:0
Sensor aJB not available.
Connection at plug sÖA1:
Heating circuit pump.
4B:1
4C:1
Sensor aJA available (e.g. return temperature sensor T1); automatic recognition.
Sensor aJB available (e.g. return temperature sensor T2); automatic recognition.
Primary pump, primary store system.
87
88
Coding 2, Vitotronic 300-K
“General” Group
(continued)
Vitotronic 300, GW5B & MW1B Installation and Service
Coding in the factory set condition
4D:1
4E:1
4F:5
54:0
Connection at plug sL:
Shunt pump.
Possible change
4D:0
Connection at plug gSA1:
3-way mixing valve for return temperature control.
Without solar thermal system.
4E:2
Run-on time, shunt or distribution pump 5 min.
4F:0
4F:1 to
4F:60
54:1
54:2
54:3
Distribution pump.
Motor for 3-way mixing valve, primary store system.
No pump run-on.
Run-on time adjustable from 1 to 60 min.
5B:0
5C:0
5D:0
5E:0
Without extension EA1.
Function output aBJ at extension EA1:
Central fault message.
Function input DE1 at extension EA1:
No function.
Function input DE2 at extension EA1:
No function.
54:4
5B:1
5C:1
5C:2
5C:3
5C:4
5C:5
5D:1
5D:2
5D:3
5D:4
5D:5
5D:6
5E:1
5E:2
5E:3
5E:4
5E:5
5E:6
With Vitosolic 100; automatic recognition.
With Vitosolic 200; automatic recognition.
With solar control module, type SM1, without auxiliary function; automatic recognition.
With solar control module, type SM1, with auxiliary function, e.g. central heating backup; automatic recognition.
With extension EA1; automatic recognition.
Accessories pump.
No function.
Heating circuit pump A1 is switched to low speed (reduced mode).
Heating circuit pump M2 is switched to low speed (reduced mode).
Heating circuit pump M3 is switched to low speed (reduced mode).
Heating program changeover.
External demand with minimum set supply temperature.
Selection of set value in coding address “9B” in the “General” group.
External blocking.
External blocking with fault message.
Fault message input.
Brief operation, DHW recirculation pump
(pushbutton function).
Setting of runtime for DHW recirculation pump in coding address “12” in the “General” group.
Heating program changeover.
External demand with minimum set supply temperature.
Selection of set value in coding address “9B” in the “General” group.
External blocking.
External blocking with fault message.
Fault message input.
Brief operation, DHW recirculation pump
(pushbutton function).
Setting of runtime for DHW recirculation pump in coding address “12” in the “General” group.
Vitotronic 300, GW5B & MW1B Installation and Service
“General” Group
(continued)
Coding in the factory set condition
5F:0 Function input DE3 at extension EA1:
No function.
6E:50
76:0
77:5
78:1
79:1
7A:0
7B:1
7F:1
80:6
81:1
82:3
83:5
No display correction of the outside temperature.
Without LON communication module.
LON participant number.
LON communication enabled.
With LON communication module:
Control unit is fault manager.
Without central control of heating circuits.
With LON communication module:
Control unit transmits the time.
Detached house.
If a fault occurs for at least
30 s, a fault message is displayed.
Automatic summer/wintertime changeover.
Summer time starts:
March
Summer time starts:
Week 5 of the selected month.
Coding 2, Vitotronic 300-K
7A:1
7A:2
7A:3
7B:0
7F:0
80:0
80:2 to
80:199
81:0
81:2
81:3
82:1 to
82:12
83:1 to
83:5
Possible change
5F:1 Heating program changeover.
5F:2 External demand with minimum set supply temperature.
Selection of set value in coding address “9B” in the “General” group.
5F:3
5F:4
5F:5
5F:6
6E:0 to
6E:49
6E:51 to
6E:99
76:1
External blocking.
External blocking with fault message.
Fault message input.
Brief operation, DHW recirculation pump
(pushbutton function).
Setting of runtime for DHW recirculation pump in coding address “12” in the “General” group.
Display correction –5 K to
Display correction –0.1 K
Display correction +0.1 K to
Display correction +4.9 K
With LON communication module (automatic recognition).
77:1 to
77:99
78:0
79:0
LON participant number, adjustable from 1 to
99:
1 – 4 = Boiler control unit
5 = Cascade control unit
10 – 97 = Vitotronic 200-H
98 = Vitogate
99 = Vitocom
LON communication disabled.
Control unit is not fault manager.
With central control (see page 66):
System circuit A1 (heating circuit 1).
Heating circuit with mixing valve M2
(heating circuit 2).
Heating circuit with mixing valve M3
(heating circuit 3).
Time not transmitted.
Apartment building.
Separate adjustment of holiday program and time program for DHW heating possible.
Immediate fault message.
The minimum fault duration until a fault message is issued is adjustable from 10 to
995 sec; 1 step 5 sec.
Manual summer/wintertime changeover.
Use of the radio clock receiver (automatic recognition).
With LON communication module:
The control unit receives the time.
January to December
Week 1 to week 5 of the selected month
89
90
Coding 2, Vitotronic 300-K
“General” Group
(continued)
Vitotronic 300, GW5B & MW1B Installation and Service
Coding in the factory set condition
84:7
85:10
86:5
87:7
88:0
8A:175
8F:0
91:0
96:1
97:2
98:1
Summer time starts:
Last Sunday of the selected month.
Wintertime starts:
October.
Wintertime starts:
Week 5 of the selected month.
Summer time starts:
Last Sunday of the selected month.
Temperature displayed in °C (Celsius).
Do not adjust.
Operation in the standard menu and extended menu enabled.
Note: The relevant code is only enabled when you exit the service level (see page 51).
90:128 Time constant for calculating adjusted outside temperature 21.3 h.
Connection at terminals 1 and 2 in plug aVD disabled (external heating program changeover)
(see page 36).
With extension for heating circuits 2 and 3 with mixing valve.
With LON communication module:
The control unit sends the outside temperature to the Vitotronic 200-H.
With LON communication module:
Viessmann system number (in conjunction with monitoring several systems via Vitocom LAN1).
86:1 to
86:5
87:1 to
87:7
88:1
Possible change
84:1 Monday to Sunday to
84:7
85:1 to
85:12
January to December
Week 1 to week 5 of the selected month
Monday to Sunday
Temperature displayed in °F (Fahrenheit).
—
8F:1
8F:2
Operation in the standard menu and extended menu blocked.
Operation enabled in the standard menu; blocked in the extended menu.
90:1 to
90:199
91:1
91:2
91:3
91:4
91:5
91:6
91:7
96:0
97:0
97:1
98:1 to
98:5
Fast (low values) or slow (high values) matching of the supply temperature, subject to the set value when the outside temperature changes. 1 step 10 min.
Contact affects the following heating circuits:
System circuit A1 (heating circuit 1).
Heating circuit with mixing valve M2 (heating circuit 2).
Heating circuits without mixing valve A1
(heating circuit 1) and heating circuit with mixing valve M2 (heating circuit 2).
Heating circuit with mixing valve M3 (heating circuit 3).
Heating circuits without mixing valve A1
(heating circuit 1) and heating circuit with mixing valve M3 (heating circuit 3).
Heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3).
System circuit A1 (heating circuit 1) and heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3).
Without extension for heating circuits 2 and 3 with mixing valve.
The outside temperature of the sensor connected to the control unit is only utilized internally.
The control unit receives the outside temperature from the Vitotronic 200-H.
System number adjustable from 1 to 5.
Vitotronic 300, GW5B & MW1B Installation and Service
“General” Group
(continued)
Coding 2, Vitotronic 300-K
Coding in the factory set condition
99:0
9A:0
9B:70
9C:20
9F:8
Connection at terminals 2 and 3 in plug aVD disabled (external blocking/ external “Mixing valve closed”) (see page 36).
Connection at terminals 1 and 2 in plug aVD disabled (external “Mixing valve open”)
(see page 36).
Set supply temperature for external demand
158° F (70° C).
With LON communication module:
Monitoring LON participants.
If there is no response from a participant after
20 min., the values specified inside the control unit are used. Only then will a fault message be issued.
Differential temperature 8 K; only in conjunction with heating circuits with mixing valve M2 and M3.
9F:0 to
9F:40
Possible change
99:1 No function.
99:2 External “Mixing valve closed”
Heating circuit with mixing valve
M2 (heating circuit 2).
99:3
99:4
99:5
99:6
No function.
External “Mixing valve closed”
Heating circuit with mixing valve
M3 (heating circuit 3).
No function.
99:7
99:8
99:9
99:10
External “Mixing valve closed”
Heating circuits with mixing valve M2
(heating circuit 2) and M3 (heating circuit 3).
No function.
External blocking.
No function.
External blocking/external
“Mixing valve closed”
Heating circuits with mixing valve M2
(heating circuit 2).
99:11
99:12
99:13
99:14
99:15
9A:1
9A:2
No function.
External blocking/external
“Mixing valve closed”
Heating circuit with mixing valve
M3 (heating circuit 3).
No function.
External blocking/external
“Mixing valve closed”
Heating circuits with mixing valve M2
(heating circuit 2) and M3 (heating circuit 3).
No function.
No function.
9A:3
9A:4
9A:5
9A:6
9A:7
9B:0 to
9B:127
9C:0
9C:5 to
9C:60
External “Mixing valve open”
Heating circuit with mixing valve M2
(heating circuit 2).
No function.
External “Mixing valve open”
Heating circuit with mixing valve M3
(heating circuit 3).
No function.
External “Mixing valve open”
Heating circuits with mixing valve M2 (heating circuit 2) and M3 (heating circuit 3).
No function.
Set value adjustable from 32 to 260° F
(0 to 127° C).
No monitoring.
Time adjustable from 5 to 60 min.
Differential temperature adjustable from 0 to
40 K.
91
92
Coding 2, Vitotronic 300-K
“Cascade” Group
Vitotronic 300, GW5B & MW1B Installation and Service
Coding
Coding in the factory set condition
35:4
36:0
37:80
38:0
39:0
3A:0
3B:1
3C:2
3D:1
3E:0
3F:0
41:31
42:31
4 boilers connected to the Vitotronic 300-K.
Electronic minimum system supply temperature limit set to 32° F (0° C).
Electronic maximum system supply temperature limit set to 176° F (80° C).
No lead boiler or boiler sequence changeover; see function description in chapter “Cascade control”.
No permanent lead boiler.
No permanent last boiler.
Stand-alone parallel boiler circuit:
With supply temperature sensor (see page 62).
3C:2 Conventional strategy 2 (see page 64).
Output statement for condensing strategy and conventional strategy 1.
Distribution pump only runs when there is a heat demand.
Without DHW tank priority control for distribution pump.
No ECO threshold boiler 1.
No ECO threshold boiler 2.
38:2 to
38:200
39:1 to
39:4
3A:1 to
3A:4
3B:0
Possible change
35:1 to
35:4
1 to 4 boilers connected to the Vitotronic 300-K.
36:1 to
36:127
37:20 to
37:127
Minimum limit adjustable from 32 to 260° F
(0 to 127° C).
Maximum limit adjustable from 68 to 260° F
(20 to 127° C).
38:1
Note: Value must not be higher than the lowest value of coding address “06” in the
“Boiler” group of every Vitotronic 300,
GW5B.
Lead boiler changeover:
Every first day of the month, the boiler with the shortest number of hours run by its burner becomes the lead boiler.
Lead boiler changeover after 200 to 20,000 hours run.
1 step 100 hours run
Boiler 1, 2, 3 or 4 is the permanent lead boiler.
Boiler 1, 2, 3 or 4 is permanently the last boiler.
3B:2
3B:3
3B:4
3C:0
3C:1
3D:0
Stand-alone parallel boiler circuit:
Without supply temperature sensor
(see page 62).
Stand-alone serial boiler circuit:
Without supply temperature sensor
(see page 62).
Stand-alone serial boiler circuit:
With supply temperature sensor
(see page 62).
Sequential control with supply temperature sensor (see page 62).
Condensing strategy (see page 63).
Conventional strategy 1 (see page 64).
No output statement.
3E:1
3F:1
41:−30 to
41:+30
42:−30 to
42:+30
Note: Vitotronic 300-K regulates only according to conventional strategy 2.
Distribution pump always runs; shutdown through “External blocking” signal.
With DHW tank priority control for distribution pump.
ECO threshold boiler 1 adjustable from
-22 to +86° F (−30 to +30° C).
ECO threshold boiler 2 adjustable from
-22 to +86° F (−30 to +30° C).
Vitotronic 300, GW5B & MW1B Installation and Service
“Cascade” Group
(continued)
Coding in the factory set condition
43:31 No ECO threshold boiler 3.
44:31
45:60
46:40
47:15
48:35
49:40
No ECO threshold boiler 4.
Start integral threshold set to 60 K x min.
Stop integral threshold set to 40 K x min.
Stop differential set to 15 K.
Do not adjust.
Do not adjust.
Coding 2, Vitotronic 300-K
Possible change
43:−30 to
43:+30
ECO threshold boiler 3 adjustable from
-22 to +86° F (−30 to +30° C).
44:−30 to
44:+30
45:1 to
45:255
ECO threshold boiler 4 adjustable from
-22 to +86° F (−30 to +30° C).
Start integral threshold adjustable from 1 to
255 K x min.
46:1 to
46:255
Note: If the threshold is exceeded, one boiler or one burner stage is switched on.
Stop integral threshold adjustable from 1 to
255 K x min.
47:2 to
47:30
Note: If the threshold is exceeded, one boiler or one burner stage is switched off.
Stop differential adjustable from 2 to 30 K.
—
Note: One boiler or one burner stage will be switched off if the actual supply temperature exceeds the set supply temperature by this value.
—
—
“DHW” Group
Coding in the factory set condition
55:0 DHW tank heating, hysteresis ± 2.5 K.
56:0
58:0
59:0
5A:0
Set DHW temperature adjustable from 50 to
140° F (10 to 60° C).
Without auxiliary function for DHW heating.
DHW tank heating:
Set start point –2.5 K
Set stop point +2.5 K
For DHW heating:
The set supply temperature is determined by the highest system supply temperature demand.
Possible change
55:1 Adaptive DHW tank heating enabled.
55:2
55:3
DHW tank temperature control with 2 DHW tank temperature sensors.
DHW tank temperature control, primary store system.
56:1 Set DHW temperature adjustable from 50 to 194° F
(10 to 95° C).
58:10 to
58:60
59:1 to
59:10
Note: Observe the max. permissible DHW temperature.
Adjust the temperature controller “R”.
Input of a second set DHW temperature, adjustable from 50 to 194° F (10 to 95° C).
(observe coding addresses “56” and “63”).
Start point adjustable from 1 to 10 K below set value.
5A:1 For DHW heating:
The set supply temperature is determined by the
DHW tank supply temperature demand.
60:20 During DHW heating, the common supply temperature is max. 20 K higher than the set
DHW temperature.
61:1 The circulation pump for DHW tank heating is started immediately.
60:10 to
60:50
61:0
The differential between the common supply temperature and the set DHW temperature is adjustable from 10 to 50 K.
The circulation pump for DHW tank heating is started depending on the boiler water temperature.
93
94
Coding 2, Vitotronic 300-K
“DHW” Group
(continued)
Vitotronic 300, GW5B & MW1B Installation and Service
Coding in the factory set condition
62:10 Circulation pump with a run-on time after DHW
73:0
75:0 tank heating of max. 10 min.
64:2 During party mode and after external changeover to constant operation with the standard room temperature:
Constant DHW heating enabled and DHW recirculation pump “ON”.
66:4 Input of the set DHW temperature:
At the control unit programming unit and all installed Vitotrol 300A remote controls.
66:0
66:1
67:40 For solar DHW heating:
Set DHW temperature 104° F (40° C).
Reheating is suppressed above the selected set temperature (DHW heating by the boiler only if solar energy is not sufficient).
68:8 With 2 DHW tank temperature sensors
(code “55:2”):
DHW tank heating stop point at set value x 0.8.
69:7 With 2 DHW tank temperature sensors
(code “55:2”):
DHW tank heating start point at set value x 0.7.
6A:75 Runtime, servomotor, mixing valve, heat exchanger set, Vitotrans 222, (80 and 120 kW):
75 sec.
70:0 DHW recirculation pump “ON” according to time program when DHW heating is enabled.
71:0 DHW recirculation pump:
“ON” according to time program.
72:0 DHW recirculation pump:
“ON” according to time program.
DHW recirculation pump:
“ON” according to time program.
DHW recirculation pump “ON” during economy mode according to time program.
Possible change
62:0
62:1 to
62:15
64:0
Circulation pump without run-on.
Run-on time adjustable from 1 to 15 min.
64:1
No DHW heating, DHW recirculation pump
“OFF”.
DHW heating and DHW recirculation pump according to time program.
66:2
66:3
66:5
66:6
66:7
67:0
67:10 to
67:95
68:2 to
68:10
69:1 to
69:9
6A:10 to
6A:255
70:1
71:1
71:2
72:1
72:2
73:1 to
73:6
73:7
75:1
At the control unit programming unit.
At the control unit programming unit and remote control system circuit A1 (heating circuit ).
At the control unit programming unit and remote control heating circuit with mixing valve
M2 (heating circuit 2).
At the control unit programming unit and remote control heating circuit with mixing valve
M3 (heating circuit 3).
At the remote control system circuit A1
(heating circuit 1).
At the remote control heating circuit with mixing valve M2 (heating circuit 2).
At the remote control heating circuit with mixing valve M3 (heating circuit 3).
No third set value.
Set DHW temperature adjustable from 50 to
194° F (10 to 95° C). (limited by boiler specific parameters).
Observe the setting of coding address “56”.
Factor adjustable from 0.2 to 1;
1 step 0.1
Factor adjustable from 0.1 to 0.9;
1 step 0.1
For heat exchanger set Vitotrans 222 (240 kW): set 113 sec.
Runtime adjustable from 10 to 255 sec.
DHW recirculation pump “ON” according to time program.
“OFF” during DHW heating to the first set value.
“ON” during DHW heating to the first set value.
“OFF” during DHW heating to the second set value.
“ON” during DHW heating to the second set value.
“ON” from once per hour for 5 min. up to
6 times per hour for 5 min. during the time program.
Constantly “ON”.
DHW recirculation pump “OFF” during economy mode.
Vitotronic 300, GW5B & MW1B Installation and Service
“Solar” Group
Coding 2, Vitotronic 300-K
Only in conjunction with solar control module, type SM1.
Coding
Coding in the factory set condition
00:8
01:4
02:0
The solar circuit pump starts when the collector temperature exceeds the actual DHW temperature by 8 K.
The solar circuit pump stops when the differential between the collector temperature and the actual DHW temperature is less than
4 K.
Solar circuit pump (multi stage) without speed control by solar control module SM1.
02:1
Possible change
00:2 to
00:30
01:1 to
01:29
The differential between the actual DHW temperature and the start point for the solar circuit pump is adjustable from 2 to 30 K.
The differential between the actual DHW temperature and the stop point for the solar circuit pump is adjustable from 1 to 29 K.
03:10
04:4
05:10
06:75
07:0
The temperature differential between the collector temperature and actual DHW temperature is regulated to 10 K.
Controller amplification of the speed control
4%/K.
Minimum speed of the solar circuit pump
10% of the maximum speed.
Maximum speed of the solar circuit pump
75% of the maximum possible speed.
Interval function of the solar circuit pump switched off.
02:2
03:5 to
03:20
04:1 to
04:10
05:2 to
05:100
06:1 to
06:100
07:1
Solar circuit pump (multi stage) is speedcontrolled with wave pack control.
Solar circuit pump is speed-controlled with
PWM control.
The differential temperature control between the collector temperature and actual DHW temperature is adjustable from 5 to 20 K.
Controller amplification adjustable from 1 to
10%/K.
Minimum speed of the solar circuit pump is adjustable from 2 to 100%.
Maximum speed of the solar circuit pump is adjustable from 1 to 100%.
08:60
09:130
0A:5
0B:0
0C:1
The solar circuit pump stops when the actual
DHW temperature reaches the maximum DHW tank temperature 140° F (60° C).
The solar circuit pump stops if the collector temperature reaches 266° F (130° C)
(maximum collector temperature to protect the system components).
To protect system components and heat transfer medium:
The speed of the solar circuit pump is reduced if the actual DHW tank temperature is 5 K below the maximum DHW tank temperature.
Frost protection function for solar circuit switched off.
Delta T monitoring switched on.
No flow rate captured in the solar circuit, or flow rate too low.
08:10 to
08:90
09:20 to
09:200
0A:0
0A:1 to
0A:40
0B:1
0C:0
Interval function of the solar circuit pump switched on.
To capture the collector temperature more accurately, the solar circuit pump starts for short cycles.
The maximum DHW tank temperature is adjustable from 50 to 194° F (10 to 90° C).
The temperature is adjustable from 68 to
392° F (20 to 200° C).
Stagnation time reduction is disabled.
Value for stagnation time reduction is adjustable from 1 to 40 K.
Frost protection function for solar circuit switched on (not required with Viessmann heat transfer medium).
Delta T monitoring switched off.
95
96
Coding 2, Vitotronic 300-K
“Solar” Group
(continued)
Vitotronic 300, GW5B & MW1B Installation and Service
Coding in the factory set condition
0D:1
0E:1
Night circulation monitoring switched on.
Unintentional flow rate is captured in the solar circuit (e.g. at night).
Calculation of solar yield with Viessmann heat transfer medium.
0F:70
10:0
The solar circuit flow rate at maximum pump speed is 7 L/min.
Possible change
0D:0
0E:2
0E:0
0F:1 to
0F:255
10:1
Night circulation monitoring switched off.
Calculation of solar yield with water as heat transfer medium (never adjust, as operation is only possible with Viessmann heat transfer medium).
Calculation of solar yield switched off.
Flow rate adjustable from 0.1 to 25.5 l/min.
1 step 0.1 l/min
Target temperature control switched on.
11:50
12:10
20:0
Target temperature control switched off (see coding address “11”).
Set solar DHW temperature 122° F (50° C).
— Target temperature control switched on
(code “10:1”): Temperature at which the solar heated water in the DHW tank is to be stratified.
— Extended control functions set to heat two
DHW tanks (code “20:8”): The second
DHW tank is heated when one DHW tank reaches its set DHW temperature.
Minimum collector temperature 50° F (10° C).
The solar circuit pump will only start when the set minimum collector temperature is exceeded.
No extended control functions enabled.
11:10 to
11:90
12:0
12:1 to
12:90
20:1
20:2
20:3
The set solar DHW temperature is adjustable from 50 to 194° F (10 to 90° C).
Minimum collector temperature function disabled.
The minimum collector temperature is adjustable from 1
22:8 Start temperature differential for central heating backup: 8 K.
Switching output sS is switched on when the temperature at sensor / exceeds the temperature at sensor aÖ by the selected value.
20:4
20:5
20:6
20:7
20:8
20:9
22:2 to
22:30
Additional function for DHW heating.
Differential temperature control 2.
Differential temperature control 2 and auxiliary function.
Differential temperature control 2 for central heating backup.
Thermostat function.
Thermostat function and auxiliary function.
Solar heating via external heat exchanger without additional temperature sensor.
Solar heating via external heat exchanger with additional temperature sensor
Solar heating of two DHW tanks.
Start temperature differential for central heating backup is adjustable from 2 to 30 K.
Vitotronic 300, GW5B & MW1B Installation and Service
“Solar” Group
(continued)
Coding 2, Vitotronic 300-K
Coding in the factory set condition
23:4
24:40
25:50
26:1
Stop temperature differential for central heating backup: 4 K.
Switching output sS is switched off when the temperature at sensor / falls below the stop point. The stop point is the sum of the temperature at sensor aÖ and the value selected for the stop temperature differential.
Start temperature for thermostat function 104° F
(40° C).
Start temperature for thermostat function ≤ stop temperature for thermostat function:
Thermostat function, e.g. for reheating.
Switching output sS is switched on when the temperature at sensor / falls below the start temperature for the thermostat function.
Start temperature for thermostat function > stop temperature for thermostat function:
Thermostat function, e.g. for utilizing excess heat.
Switching output sS is switched on when the temperature at sensor / exceeds the start temperature for the thermostat function.
Stop temperature for thermostat function 122° F
(50° C).
Start temperature for thermostat function ≤ stop temperature for thermostat function:
Thermostat function e.g. for reheating. Switching output sS is switched off when the temperature at sensor / exceeds the start temperature for the thermostat function.
Start temperature for thermostat function > stop temperature for thermostat function:
Thermostat function e.g. for utilizing excess heat.
Switching output sS is switched off when the temperature at sensor / falls below the start temperature for the thermostat function.
Priority for DHW tank 1 – with alternate heating.
Only when setting code “20:8”
Possible change
23:2 to
23:30
24:0 to
24:100
25:0 to
25:100
26:0
Stop temperature differential for central heating backup is adjustable from 1 to 29 K.
Start temperature for thermostat function is adjustable from 0 to 100 K.
Start temperature for thermostat function is adjustable from 0 to 100 K.
27:15
28:3
Alternate heating time 15 min.
The DHW tank without priority is heated at most for the duration of the set alternate heating time if the DHW tank with priority is heated up.
Alternate pause time 3 min.
After the selected alternate heating time for the
DHW tank without priority has expired, the rise in collector temperature is captured during the alternate pause time.
26:2
26:3
26:4
27:5 to
27:60
28:1 to
28:60
Priority for DHW tank 1
– without alternate heating
Priority for DHW tank 2
– without alternate heating.
Priority for DHW tank 2
– with alternate heating.
Alternate heating without priority for one of the DHW tanks.
The alternate heating time is adjustable from 5 to 60 min.
The alternate pause time is adjustable from 1 to 60 min.
97
Coding 2, Vitotronic 300-K
Vitotronic 300, GW5B & MW1B Installation and Service
“Heating Circuit 1”, “Heating Circuit 2”, “Heating Circuit 3” Group
98
Parameter Address A3:…
-6
-5
-4
-3
-9
-8
-7
0
1
-2
-1
2 to
15
Coding
Coding in the factory set condition
A0:0
A1:0
A2:2
A3:2
Without remote control.
Only with Vitotrol 200A: All possible settings at the remote control can be accessed.
DHW tank priority applicable to heating circuit pump and mixing valve.
Outside temperature below 34° F (1° C):
Heating circuit pump “ON”.
Outside temperature above 37° F (3° C):
Heating circuit pump “OFF”.
Possible change
A0:1 With Vitotrol 200A; automatic recognition.
A0:2 A0:2 With Vitotrol 300A or Vitohome 300; automatic recognition.
A1:1
A2:0
A2:1
A3:-9 to
A3:15
Only party mode can be set at the remote control.
Without DHW tank priority applicable to heating circuit pump and mixing valve.
DHW tank priority applies only to the mixing valves.
Heating circuit pump “ON/ OFF” (see the following table).
Note: If a value below 34° F (1° C) is selected, there is a risk that pipes outside the thermal envelope of the building could freeze up. The standby mode in particular should be taken into consideration, e.g. during holidays.
Heating circuit pump
“ON”
14° F (-10° C)
16° F (-9° C)
18° F (-8° C)
19° F (-7° C)
21° F (-6° C)
23° F (-5° C)
25° F (-4° C)
27° F (-3° C)
28° F (-2° C)
30° F (-1° C)
32° F (0° C)
34° F (1° C) to
57° F (14° C)
“OFF”
18° F (-8° C)
19° F (-7° C)
21° F (-6° C)
23° F (-5° C)
25° F (-4° C)
27° F (-3° C)
28° F (-2° C)
30° F (-1° C)
32° F (0° C)
34° F (1° C)
36° F (2° C)
37° F (3° C) to
61° F (16° C)
Coding in the factory set condition
A4:0
A5:5
With frost protection.
With heating circuit pump logic function
(economy circuit): Heating circuit pump
“OFF” when the outside temperature (AT) is 1 K higher than the set room temperature
(RT set
) AT > RT set
+ 1 K.
Possible change
A4:1 No frost protection; this setting is only possible if code “A3:-9” has been selected.
Note: Observe information regarding coding address “A3”.
A5:0
A5:1 to
A5:15
Without heating circuit pump logic function.
With heating circuit pump logic function:
Heating circuit pump “OFF”; see the following table.
4
5
6
7 to
15
2
3
Parameter address A5:…
1
With heating circuit pump logic function: Heating circuit pump “OFF”
AT > RT set
AT > RT set
AT > RT set
AT > RT set
+ 5 K
+ 4 K
+ 3 K
+ 2 K
+ 1 K AT > RT set
AT > RT set
AT > RT set
— 1 K
AT > RT set
— 9 K
Vitotronic 300, GW5B & MW1B Installation and Service
Coding 2, Vitotronic 300-K
“Heating Circuit 1”, “Heating Circuit 2”, “Heating Circuit 3” Group
(continued)
4
5
6
7
8
1
2
3
Coding in the factory set condition
A6:36
A7:0
A9:7
AA:2
B0:0
B2:8
B5:0
Extended economy control disabled.
Only for heating circuits with mixing valve:
Without mixing valve economy function.
With pump idle time
(heating circuit pump “OFF”)
(See function description on page 51).
With output reduction by temperature sensor aJ A.
With remote control:
*2
Heating mode/reduced mode: weathercompensated.
With remote control and for the heating circuit, operation with room temperature hookup must be programmed:
*2
Room influence factor 8.
With remote control:
*2
No room temperature dependent heating circuit pump logic function.
Possible change
A6:5 to
A6:35
A7:1
Extended economy control enabled, i.e. the burner and heating circuit pump will be stopped and the mixing valve closed at a variable value, adjustable between 41 to 95° F
(5 and 35° C) plus 34° F (1° C).
The base value is the adjusted outside temperature.
This value is based on the actual outside temperature and a time constant, which takes the cooling down of an average building into consideration.
With mixing valve economy function
(extended heating circuit pump logic):
Heating circuit pump also “OFF”:
— If the mixing valve has been closed for longer than 12 min.
Heating circuit pump “ON”:
A9:0
A9:1 to
A9:15
AA:0
AA:1
B0:1
B0:2
B0:3
B2:0
B2:1 to
B2:64
B5:1 to
B5:8
— If the mixing valve changes to control function.
— If there is a risk of frost.
Without pump idle time.
With pump idle time; adjustable from 1 to 15.
1: short idle period
15: long idle period
Without output reduction.
No function.
Heating mode: weather-compensated
Reduced mode: with room temperature hook-up
Heating mode: with room temperature hook-up
Reduced mode: weather-compensated
Heating mode/reduced mode: with room temperature hook-up
Without room influence.
Room influence factor adjustable from 1 to
64.
Heating circuit pump logic function, see the following table.
*2
Only change the code for the system circuit A1 for boilers without lower temperature limit or for the heating circuits with mixing valve if a remote control is connected to them.
Parameter address B5:…
With heating circuit pump logic function:
Heating circuit pump “OFF”
1 RT actual
> RT set
+ 5 K
2 RT actual
> RT set
+ 4 K
3 RT actual
> RT set
+ 3 K
4 RT actual
> RT set
+ 2 K
5 RT actual
> RT set
+ 1 K
6 RT actual
> RT set
7 RT actual
> RT set
8 RT actual
> RT set
Heating circuit pump “ON”
RT actual
< RT set
+ 4 K
RT actual
< RT set
+ 3 K
RT actual
< RT set
+ 2 K
RT actual
< RT set
+ 1 K
RT actual
< RT set
RT actual
< RT set
— 1 K
— 1 K RT actual
< RT set
— 2 K
— 2 K RT actual
< RT set
— 3 K
99
100
Coding 2, Vitotronic 300-K
Vitotronic 300, GW5B & MW1B Installation and Service
“Heating Circuit 1”, “Heating Circuit 2”, “Heating Circuit 3” Group
(continued)
Coding in the factory set condition
B6:0 With remote control:
*2
Without quick heat-up/ quick setback.
B7:0 With remote control and for the heating circuit, operation with room temperature hook-up must be programmed:
*2
Without start optimization.
B8:10
B9:0
C0:0
With remote control and for the heating circuit, operation with room temperature hook-up must be programmed:
*2
Heat-up gradient start optimization 10 min/K.
With remote control and for the heating circuit, operation with room temperature hook-up must be programmed:
*2
Without learning start optimization.
With remote control:
*2
Without stop optimization.
Possible change
B6:1 With quick heat-up/quick setback (see function description on page 65).
B7:1
B7:2
With start optimization, max. heat-up time delay 2 h 30 min.
With start optimization, max. heat-up time delay 15 h 50 min.
B8:11 to
B8:255
Heat-up gradient adjustable from 11 to 255 min/K.
B9:1
C0:1
With learning start optimization.
C1:0
C2:0
With remote control:
*2
Without stop optimization.
C0:2
C1:1 to
C1:12
C2:1
With stop optimization, max. setback time delay 1 h.
With stop optimization, max. setback time delay 2 h.
With stop optimization of setback time delay, adjustable from 10 to 120 min;
1 step 10 min
With learning stop optimization.
C3:125
C4:1
C5:20
With remote control:
*2
Without learning stop optimization.
Only for heating circuits with mixing valve:
Mixing valve runtime 125 sec.
System dynamics:
Mixing valve control characteristics
C3:10 to
C3:255
C4:0 to
C4:3
Runtime adjustable from 10 to 255 sec.
Controller responds too quickly (cycles between “Open” and “Closed”): select a lower value.
Controller responds too slowly (temperature is not held sufficiently): select a higher value.
Minimum limit adjustable from 34 to 260° F
(1 to 127° C).
C6:75
C8:31
D5:0
Electronic minimum supply temperature limit
68° F (20° C) (only in operation at standard room temperature).
Electronic maximum supply temperature limit set to 167° F (75° C).
With remote control and for the heating circuit, operation with room temperature hook-up must be programmed:
No room influence limit.
*2
With external heating program changeover
(observe setting of coding address “5D”,
“5E” and “5F” and “91” in the “General” group):
Heating program switches to “Constant central heating with reduced room temperature” or “Standby mode” (subject to the settings of the set reduced room temperature).
C5:1 to
C5:127
C6:10 to
C6:127
C8:1 to
C8:30
D5:1
Maximum limit adjustable from 50 to 260° F
(10 to 127° C).
Room influence limit adjustable from 1 to 30 K.
The heating program changes to “Constant operation with standard room temperature”.
*2
Only change the code for the system circuit A1 for boilers without lower temperature limit or for the heating circuits with mixing valve if a remote control is connected to them.
Vitotronic 300, GW5B & MW1B Installation and Service
Coding 2, Vitotronic 300-K
“Heating Circuit 1”, “Heating Circuit 2”, “Heating Circuit 3” Group
(continued)
Coding in the factory set condition
D8:0 No heating program changeover via extension
EA1
E1:1
E2:50
F1:0
F2:8
F8:-5
With remote control:
Set day temperature adjustable at the remote control unit from 50 to 86° F (10 to 30º C).
50 With remote control:
No display correction of the actual room temperature.
Slab curing function disabled. (Not used)
Time limit for party mode or external heating program changeover via pushbutton: 8 h
*1
.
Note: Observe settings of coding addresses
“5D”, “5E”, “5F” in the “General” group, as well as “D5” and “D8” in the
“Heating circuit…” group.
Temperature limit for raising reduced mode
23° F (-5º C); see example on page 67.
Observe the setting of coding address “A3”.
Possible change
D8:1 Heating program changeover via input DE1 at extension
EA1.
D8:2
D8:3
E1:0
Heating program changeover via input DE2 at extension
Heating program changeover via input DE3 at extension
Set day temperature adjustable from 37 to 73° F
(3 to 23º C).
E1:2
E2:0 to
E2:49
Set day temperature adjustable from 63 to 99° F
(17 to 37º C).
Display correction –5 K to
Display correction –0.1 K
E2:51 to
E2:99
F1:1 to
F1:6
F1:15
F2:0
F2:1 to
F2:12
Display correction +0.1 K to
Display correction +4.9 K
Only for heating circuits with mixing valve:
Slab curing function adjustable in accordance with 6 optional temperature/time profiles.
(Not used)
Constant supply temperature 68° F (20° C).
No time limit
*1
.
Time limit adjustable from 1 to 12 h
*1
.
F9:-14
FA:20
FB:30
Temperature limit for raising the reduced set room temperature 7° F (-14º C); see example on page 67.
Raising the set boiler water or supply temperature by 20% when changing from operation with reduced room temperature to operation with standard room temperature.
See example on page 68.
Duration for raising the set boiler water or supply temperature (see coding address
“FA”) 60 min.
See example on page 68
F8:+10 to
F8:-60
Temperature limit adjustable from
+50 to -76° F (+10 to -60° C).
F8:-61 Function disabled.
F9:+10 to
F9:-60
Limit for raising the set room temperature to the value selected for standard mode adjustable from +50 to -76° F (+10 to -60° C).
FA:0 to
FA:50
Temperature rise adjustable from 0 to 50 %.
FB:0 to
FB:150
Duration adjustable from 0 to 300 min;
1 step 2 min.
*1
Party mode ends automatically in the “Heating and DHW” heating program when the system changes over to operation with standard room temperature.
101
102
Coding 2, Vitotronic 300-K
Vitotronic 300, GW5B & MW1B Installation and Service
“Heating Circuit 1”, “Heating Circuit 2”, “Heating Circuit 3” Group
(continued)
Coding in the factory set condition
F2:8 Time limit for party mode or external heating program changeover via pushbutton: 8 h
*1
.
Note: Observe settings of coding addresses
“5D”, “5E”, “5F” in the “General” group, as well as “D5” and “D8” in the
“Heating circuit…” group.
Possible change
F2:0
F2:1 to
F2:12
No time limit
*1
.
Time limit adjustable from 1 to 12 h
*1
.
F8:-5 Temperature limit for raising reduced mode
23° F (-5º C); see example on page 67.
Observe the setting of coding address “A3”.
F8:+10 to
F8:-60
Temperature limit adjustable from
+50 to -76° F (+10 to -60° C).
F8:-61 Function disabled.
F9:-14 Temperature limit for raising the reduced set room temperature 7° F (-14 ºC); see example on page 67.
F9:+10 to
F9:-60
Limit for raising the set room temperature to the value selected for standard mode adjustable from +50 to -76° F (+10 to -60° C).
FA:20
FB:30
Raising the set boiler water or supply temperature by 20% when changing from operation with reduced room temperature to operation with standard room temperature.
See example on page 68.
FA:0 to
FA:50
Duration for raising the set boiler water or supply temperature (see coding address “FA”)
60 min.
See example on page 68
FB:0 to
FB:150
Temperature rise adjustable from 0 to 50 %.
Duration adjustable from 0 to 300 min;
1 step 2 min.
*1
Party mode ends automatically in the “Heating and DHW” heating program when the system changes over to operation with standard room temperature.
Vitotronic 300, GW5B & MW1B Installation and Service
Connection and Wiring Diagram
Wiring, Vitotronic 300, GW5B
A1 PCB, extension for heating circuit 2 and 3 with
mixing valve (optional accessory)
A2 PCB, low voltage
A3 PCB 120V~
A6 Programming unit
A7 Optolink PCB/emissions test switch
A8 PCB
A9 Boiler coding card
A10 LON communication module (accessories)
A11 Power supply unit PCB
A12 Programming unit ON/OFF switch
X Electrical interfaces
103
Wiring, Vitotronic 300, GW5B
Connection and Wiring Diagram
(continued)
Vitotronic 300, GW5B & MW1B Installation and Service
Main PCB low voltage
104
Legend
!
Outdoor air temperature sensor (No function)
§
Boiler water temperature sensor
%
A No function
% B No function
) No function aG
Flue gas temperature sensor aJ
A Therm-Control temperature sensor
or
Return temperature sensor T1 aJ B Return temperature sensor T2 aVD External hook-up aVG KM BUS participant aVH
External hook-up
LON Connecting cable for data exchange (accessory)
S3 Emissions test switch “
V1 Fault indicator (red)
V2 ON indicator (green)
X Electrical interfaces
S ”
Vitotronic 300, GW5B & MW1B Installation and Service
Connection and Wiring Diagram
(continued)
PCB 120V~
Wiring, Vitotronic 300, GW5B sÖ A1 High temperature circuit pump sA DHW circulation pump sK
DHW recirculation pump sL
Accessories pump fÖ
Power supply, 120V/60 Hz fA
Burner (call for heat) gÖ
Central fault message gS A1 Isolation valve
or
3-way mixing valve, primary store system (optional
accessory) aBÖ
External connections, e.g. supplementary safety equipment aBA
Safety chain, potential free aBH
Power supply for accessories
F1, F2 Fuse/MCB
K1-K10 Relay
S1 ON/OFF switch
X Electrical interfaces
105
Wiring, Vitotronic 300-K
Connection and Wiring Diagram
Overview
Vitotronic 300, GW5B & MW1B Installation and Service
106
Legend
A1 PCB, extension for heating circuits 2 and 3 with
mixing
A2 PCB low voltage
A3 PCB 120V~
A6 Programming unit
A7 Optolink PCB/emissions test switch
A8 PCB
A10 LON communication module (accessory)
A11 Power supply unit PCB
A12 ON/OFF switch
X Electrical interfaces
Vitotronic 300, GW5B & MW1B Installation and Service
Connection and Wiring Diagram
(continued)
PCB 120V~
Wiring, Vitotronic 300-K
Legend
sÖ
Heating circuit pump sA Circulation pump for DHW tank heating
(accessory) sK sL
DHW recirculation pump (on site)
Shunt pump or distribution pump (on site) fÖ gÖ
Power supply, 120V/60 Hz
Central fault message gS
Motor for 3-way mixing valve, primary store
system abH Power supply connection for accessories
F Fuse
K1-K10 Relay
S1
X
ON/OFF switch
Electrical interfaces
107
Wiring, Vitotronic 300-K
Connection and Wiring Diagram
(continued)
Vitotronic 300, GW5B & MW1B Installation and Service
PCB low voltage
108
Legend
!
Outside temperature sensor
?
Supply temperature sensor
% A DHW tank temperature sensor
% B DHW tank temperature sensor 2 for primary store
system)
)
No aG No function aJ A No function aJ B Return temperature sensor T2
or
Temperature sensor primary store system aVD External hook-up aVG KM BUS participant aVH
External hook-up
LON Connecting cable for data exchange (accessory)
S3 Emissions test switch “
V1 Fault indicator (red)
V2 ON indicator (green)
X Electrical interfaces
S ”
Vitotronic 300, GW5B & MW1B Installation and Service
Connection and Wiring Diagram
(continued)
PCB, extension for heating circuits 2 and 3 with mixing valve
Wiring, Vitotronic 300-K
Legend
?
Supply temperature sensors sÖ Heating circuit pumps fÖ Power supply gS
Mixing valve motors
K1-K6 Relay
X Electrical interfaces
109
110
Components
Sensors
Temperature
Vitotronic 300, GW5B & MW1B Installation and Service
Boiler water, DHW tank, supply, return and room temperature sensors
Note:
H
The supply temperature sensor can be used as a contact or immersion temperature sensor.
Note: The supply temperature sensor in the mixing valve extension kit is a contact temperature sensor.
H
The room temperature sensor is connected at terminals
3 and 4 in the Vitotrol 300A.
Installation and service instructions,
Vitotronic 200-H
Viessmann NTC 10 kΩ (blue identification)
1. Pull corresponding plug.
2. Check the sensor resistance and compare it with the curve.
3. In the case of severe deviation, check the installation and replace the sensor if required.
Outside temperature sensor
Viessmann NTC 10 kΩ (blue identification)
plug .
2. Check the sensor resistance across plug terminals
“1” and “2” and compare with the curve.
3. If the results are very different from the curve, disconnect the wires from the sensor and repeat the test on the sensor.
4. Depending on the result, replace the lead or the outside temperature sensor.
Temperature
Vitotronic 300, GW5B & MW1B Installation and Service
Boiler Coding Card
Boiler
Vitocrossal 200, type CM2
Boiler coding card
Display in brief scan
1042
Mixing Valve Motor Kit
Mixing valve “Open”
Mixing valve “Closed”
Legend
A Mixing valve plug
B Field wiring
C Connection to mixing valve adaptor
Part no.
7841113
Components
Components:
H
Mixing valve motor (not for flanged mixing valve)
H
Connecting plug for the heating circuit pump
H
Supply temperature sensor as contact temperature sensor for measuring the supply temperature, with connecting cable 19 ft. (5.8 m) long.
Changing the rotational direction (if required)
1. Insert 3-pin plug A in the mixing valve motor rotated through 180°.
2. Check the rotational direction.
Manual mixing valve adjustment
Lift the motor lever, unhook the mixing valve handle and pull plug A.
Specification mixing valve motor
Rated voltage
Rated frequency 60
Power consumption
120V~
Hz
4 W
Permissible ambient temperature
H during operation 32 to 104° F (0 to +40° C)
H during storage and transport -4 to +149° F (–20 to +65° C)
111
112
Components
Extension EA1 Accessory (optional)
Vitotronic 300, GW5B & MW1B Installation and Service
Digital data inputs DE1 to DE3
Functions:
External heating program changeover, separate for heating circuits 1 to 3
External blocking
External blocking with fault message input
External demand with minimum boiler water
temperature
Fault message input
Brief operation of the DHW recirculation pump
When connecting external contacts, observe the requirements of safety category II, i.e. 8.0 mm air-gap and creep path or maintain a 2.0 mm insulation thickness against ‘live’ parts.
Input function assignment
Select the input functions by means of the following codes in the “General” group at the boiler control unit:
DE1: Coding address “5D”
DE2: Coding address “5E”
DE3: Coding address “5F”
Assigning the heating program changeover function to the heating circuits
The allocation of the heating program changeover to the relevant heating circuit is selected via coding address
“D8” in the “Heating circuit…” group:
Code “D8:1”: Changeover via input DE1
Code “D8:2”: Changeover via input DE2
Code “D8:3”: Changeover via input DE3
The effect of the heating program changeover is selected via coding address “D5” in the “Heating circuit…” group.
Duration of the heating program changeover
Contact constantly closed:
The changeover is active as long as the contact closed.
Contact only closed briefly via pushbutton:
The changeover is enabled for the time selected in coding address “F2” in the “Heating circuit…” group.
DHW recirculation pump runtime for brief operation
The DHW recirculation pump can be started outside the times when it is enabled according to the time program.
The DHW recirculation pump is started by closing the contact at DE1, DE2 or DE3 by means of a pushbutton.
The runtime is adjusted via coding address “3D” in the
“General” group.
Analogue input 0–10V
The 0–10V hook-up provides an additional set boiler water temperature:
0–1V Is taken as “no default for set boiler water
temperature”.
Note: Ensure DC separation between the LV output and the earth conductor of the onsite voltage
source.
Coding address “1E” in the “General” group:
“1E:0” ≙ temperature demand adjustable in the range from 32 to 212° F (0 to 100° C) 1V ≙ 50° F
(10° C) set value change 10V ≙ 212° F (100° C) set value change
“1E:1” ≙ temperature demand adjustable in the range from 86 to 248° F (30 to 120° C) 1V ≙ 86° F
(30° C) set value change 10V ≙ 248° F (120° C) set value change
Output aBJ
Connection of a central fault messaging facility or signalling reduced mode (reduction of the heating circuit pump speed).
Select the function of output aBJ via coding address
“5C” in the “General” group.
Refer to the EA1 module Installation Instructions
Vitotronic 300, GW5B & MW1B Installation and Service
Parts List Vitotronic 300, GW5B
Ordering Replacement Parts:
Please provide model no. from rating plate and serial no. when ordering replacement parts. Order replacement components from your Viessmann distributor.
Parts
0001 Hinge
0008 Supporting stay
0011 Safety valve with wiring
0013 Casing front with frame
0014 PCB cover
0015 Front flap
0016 Casing, rear section
0018 Programming unit
0019 Fascia, left
0020 Fascia, right
0021 Ribbon cable, 14-pole
0022 Connecting cable for extension for heating circuit 2 and 3 with mixing valve
0023 Connecting cable, emissions test switch
0024 Fuse holder cap for control fuse
0025 Fuse holder for control fuse
0037 Emissions test switch, single-pole
0038 ON/OFF switch, 2-pole
0040 Outside temperature sensor !
0042 Temperature sensor with plug
0045 Contact temperature sensor with plug
(supply temperature sensor)
0048 PCB, extension heating circuits 2 and 3 cover
0049 PCB, low voltage
0050 PCB
0051 PCBs, Optolink and emissions test switch
0052 PCB 120V~
0054 Power supply unit PCB
0056 LON communication module
0057 LON cable
0058 Terminator (2 pieces)
0074 Connecting cable
0080 Installation and service instructions
0081 Operating instructions
0092 Fuse 6.3 A/250V~, slow
0100 Plug for LV (7 pieces)
0101 Plug for pumps (3 pieces)
0102 Plug gS (3 pieces)
0103 Plug aBH (3 pieces)
0104 Power plug fÖ (3 pieces)
0105 Plug aBÖ
0106 Plug gÖ (3 pieces)
0108 Plug aVD, aVG, aVH (3-pole)
0109 Burner plug (3-pole)
Parts Lists
113
114
Parts Lists
Parts List Vitotronic 300-K
Ordering parts
The following information is required:
H
Serial no. (see type plate A)
H
Position number of the part (from this parts list)
Obtain standard parts from your local supplier.
Parts
0001 Hinge
0008 Supporting stay
0011 Safety valve with wiring
0012 circuits 2 and 3 with mixing valve
0013 Casing front with frame
0014 PCB cover flap
0016 Rear section of enclosure
0018 Programming unit
0019 Fascia left
0020 Fascia right
0021 Ribbon cable, 10-pole
0022 circuits 2 and 3 with mixing valve
0023 Connecting cable, emissions test switch
0024 Fuse holder cap for control fuse
0025 Fuse holder for control fuse
0037 Emissions test switch, single-pole
0038 ON/OFF switch, 2-pole
0040 Outside temperature sensor !
0042 Temperature sensor with plug
0045
(supply temperature sensor)
0049 PCB low voltage
0048 Extension for heating circuits 2 and 3 with mixing valve
0050 PCB
0051 PCBs, Optolink and emissions test switch
0052 PCB 120V~
0054 Power supply unit PCB
0056 LON communication module
0057 LON connecting cable
0058 Terminator (2 pce)
0074 Connecting cable, 16-pole
0080 Installation and service instructions
0081 Operating instructions
0092 Fuse 6.3 A (slow)/250V~
0100 Plug for LV (7 pce)
0101 Plug for pumps (3 pce)
0102 Plug gS (3 pce)
0103 Plug aBH (3 pce)
0104 Power supply plug fÖ (3 pce)
0106 Plug gÖ (3 pce)
0108 Plug aVD, aVG, aVH (3-pole)
Vitotronic 300, GW5B & MW1B Installation and Service
Vitotronic 300, GW5B & MW1B Installation and Service
Specification Vitotronic 300, GW5B
Rated voltage 120V~
Rated frequency 60
Rated current
Power consumption
Permissible ambient temperature:
2 x 6A~
10 W
During operation 32 to 104° F (0 to +40° C)
Installation in living spaces or boiler rooms (standard conditions)
During storage and transport -4 to 149° F (−20 to +65° C)
Specification
Rated relay output breaking capacity at 120V~ sÖ Primary pump, primary store system
or
Circulation pump – flue gas/water heat exchanger 2A~
*1
sA sL
Circulation pump for DHW tank heating
Shunt pump or boiler circuit pump
2A~
2A~
*1
*1
gÖ
Central fault message 2A~
*1
gS
Isolation
Mixing valve motor, return temperature raising facility
or
Motor, 3-way mixing valve, primary store system 0.1A~
*1
fA
*1
Total max. 6A~ (shared between all 120V outputs)
Specification Vitotronic 300-K
Rated voltage 120V~
Hz
Rated current
Power consumption
6A
10 W
Permiss. ambient temperature
H
During operation 32 to 104° F (0 to +40° C)
Installation in living spaces or boiler rooms (standard ambient conditions)
H
During storage and transport -4 to 149° F (−20 to +65° C)
Rated relay output breaking capacity at 120V~ sÖ
Heating circuit pump or
Primary pump, primary store system sA sK sL gÖ
Circulation pump for DHW tank heating
DHW recirculation pump
Shunt pump/distribution pump
Central fault message
Motor, 3-way mixing valve,
primary store system gS Mixing valve motor, extension kit, mixing valve or
Motor, 3-way mixing valve,
return temperature control or
*2
Total max. 6A~ (shared between all 120V outputs)
2A~
*2
2A~
*2
2A~
*2
2A~
*2
2A~
*2
0.1A~
*2
115
Vitotronic 300, GW5B and MW1B Installation and Service
Printed on environmentally friendly (recycled and recyclable) paper.