This document covers the installation of cMT2078X Series HMI, for the detailed specifications and

operation, please refer to Datasheet, Brochure and EasyBuilder Pro User Manual. Please read all

warnings, precautions, and instructions on the device carefully before use.

Install Environment:

NEMA Rating

The HMI product is UL Type 4X (NEMA 4) rated, indoor use only.

The

HMI product has been tested to conform to European CE requirements. This

Electrical

means that the circuitry is designed to resist the effects of electrical noise. This

Environment

does not guarantee noise immunity in severe cases. Proper wire routing and

grounding will insure proper operation.

(1) Make sure that the displays are installed correctly and that the operating

limits are followed. Avoid installing units in environments where severe

mechanical vibration or shocks are present.

(2) Do not operate the unit in areas subject to explosion hazards due to

flammable gases, vapors or dusts.

Environmental

(3) Do not install the unit where acid gas, such as SO2 exists.

Considerations

(4) This device should be mounted in the vertical position and for use on the flat

surface enclosure.

(5) Conform to UL 61010-1 3rd ed. and UL 61010-2-201 2nd ed. safety

requirement for use in Pollution Degree 2 Environment and dry location.

(6) Relative Humidity: 10% ~ 90% (non-condensing)

Cleaning

Clean the device using dry cloths. Do not use liquid or spray detergents for

Considerations

cleaning.

IP Rating

IP 66

Protection impairment if used in a manner not specified by the manufacturer.

Warning

Déficit de protection si utilisé d’une manière non spécifiée par le fabricant.

2

Unpacking the Unit

Unpack and check the delivery. If damage is found, please contact the supplier.

NOTE:

Place the operator panel on a stable surface during installation. Dropping it or letting it

fall may cause damage.

The package includes:

(1) Installation Instruction, 2-sided A4 *1 (2) Human Machine Interface *1 (3) Power Connector *1

(4) Brackets & Screws *1 pack (5) USB Stick Clamp & Tying Strap *1

USB Stick Clamp Usage

Combining the USB Stick with the clamp and the tying strap can prevent USB stick from disconnecting

with HMI when strong vibration is present.

1. Insert the USB connector to the clamp and tie them together with the tying strap.

2. Press the spring and insert the USB stick into HMI.

Installation Instruction

3

Installation Instructions

Use a control box that provides enough stiffness.

Cutout Dimension: 192 mm x 138 mm. Secure the

operator panel in position, using all the fastening holes

and the provided brackets and screws. Screw Torque:

2.6 ~ 3.9 lbf.in. (For reaching waterproof effect and

preventing the panel from being deformed.)

Plan for adequate space around the unit and inside the

enclosure, for ventilation and cables. Consider the

heat from other devices inside the enclosure. The

ambient temperature around the unit must be 0 ~ 55°C

Minimum required clearances (along the overlay): Top

/ Bottom / Sides 15 mm

Maximum panel thickness: 4.5 mm

Power Connections

4

Power Connector Specifications:

Wire AWG: 24~12

Wiring Conductor Minimum Temperature: 75°C

Screw Torque: 4.5 lbf-in (max.)

Copper conduct only.

NOTE:

1. Connect positive DC line to the ‘+’ terminal and the DC ground to the

‘-‘ terminal.

2. When downloading project using a USB cable, do not connect HMI

with PLC and PC simultaneously, for electric potential difference may

result in damage to HMI or PC.

5

System Settings

When HMI is powered up and displays image, press the

round Start Button in the upper-left corner of the screen to

open the Setting dialog box. Tap the lock icon

in. (Default System Password: 111111)

Go to the Network tab, and setup your network.

In Setting dialog box you can see device information,

configure general settings, set HMI Time/Date/Name, and

more.

EasyBuilder Pro Software Settings

6

Launch EasyBuilder Pro software, select your project file,

press F7 shortcut key to open the download dialog box: Select Ethernet > IP tab > Enter your HMI IP >

Click Download to download this project file to HMI.

Using screensaver and backlight saver is recommended in order to avoid image persistence caused

by displaying the same image on HMI for a long time.

(Please refer to EasyBuilder Pro User Manual for software operation details.)

Spécifications du connecteur d’alimentation:

AWG de fil: 24 ~ 12

Température minimale du conducteur de câblage: 75°C

Couple de vis: 4.5 lbf-in (max.)

Conducteur en cuivre seulement

and log

Официальный дистрибьютор Weintek в России

Панель оператора 7 » (CODESYS / MQTT / OPC UA) — Weintek cMT2078X

  • 3xCOM / 2-порта Ethernet / USB host
  • Удаленный доступ по VNC / FTP / EasyAccess
  • Лицензия EasyAccess 2.0 покупается отдельно
  • Лицензия CODESYS – покупается отдельно
  • Управление через веб-браузер / без специального ПО WebView).
  • Рамка для панели
  • Воспроизведение звука с помощью модуля аудио-оповещения DAO1EM

Подробнее

Цены указаны с НДС

Уточните сроки

Нашли дешевле?

Оплата

Оплата

По счету, банковской картой, наличными и QR. Подробнее

Жмите запросить цену

Оборудование со склада и под заказ

Конcультируйтесь +7 (343) 381-75-75, отправляйте спецификации ipcsales@aveon.ru

АВЕОН – дистрибьютор АСУ и IT | Собственное производство защищенных ПК
Техподдержка | Гарантия | Сервис | Доставка по России от 1 дня!
Самовывоз: Екатеринбург, Челябинск, Пермь, Тюмень, Ханты-Мансийск, Сургут

  • Описание
  • Характеристики
  • Документация
  • Зарегистрировать проект
  • Оплата и доставка

Описание

COM-порты панели cMT2078X

Название разъема:

Con.B: COM1 /COM3 [RS232] 9 Pin, Male, D-sub

Тип:

DB-9 M ( Папа )

Pin # COM1 (RS232) COM3 (RS232)
1
2 RxD
3 TxD
4
5 GND GND
6
7 RTS TxD
8 CTS RxD
9 GND GND

Название разъема:

Con.A: COM2 /COM3 [RS485] 9 Pin, Female, D-sub

Тип:

DB-9 F ( Мама )

Pin # COM2[RS485]2W COM2[RS485]4W COM3[RS485]2W
1 Data- Rx-
2 Data+ Rx+
3 Tx-
4 Tx+
5 GND GND GND
6 Data-
7
8
9 Data+

Характеристики

Дисплей

  • Диагональ экрана (в дюймах)7
  • Макс. разрешение дисплея800×480
  • Количество цветов дисплея16.7 млн

Процессор

  • Тип предустановленного процессораCortex-A17 Quad-core 64-bit RISC 1.5GHz

Оперативная память

  • Предустановленный объем оперативной памяти1 Гб

Встроенная память

  • Объем встроенной Flash-памяти4 Гб

Интерфейсы ввода-вывода

  • Портов RS-232/422/4853xCOM, 2xEthernet, USB host

Программное обеспечение

  • Совместимое программное обеспечениеEasyBuilderPro, EasyLauncher, cMT Viewer

Производство

  • ПроизводительWeintek

Основные показатели датчика

  • Материалы корпуса в контакте с изм. средойПластик

Зарегистрировать проект

Зарегистрируйте проект, чтобы купить по специальной цене.

АВЕОН напрямую сотрудничает с производителями, поэтому вы можете зафиксировать проект за вашей организацией или за конечным заказчиком, получить скидку, запросить увеличение гарантийного срока.


Напоминаем, что все цены, опубликованные на данном сайте, приведены как справочная информация, не являются публичной офертой, определяемой положениями статьи 437 Гражданского кодекса Российской Федерации, и могут быть изменены в любое время без предупреждения.

Сертифицированные специалисты БЕСПЛАТНО помогут подобрать оборудование под ваш проект, составить спецификацию промышленного компьютера, порекомендуют актуальные замены для снятых с производства компонентов. Позвоните +7 (343) 381-75-75, напишите на ipcsales@aveon.ru или постучитесь в ЧАТ.

Вы можете заказать оборудование для тестирования на вашем предприятии, чтобы оценить характеристики и совместимость с уже установленными устройствами.


Самые ходовые компоненты АСУ ТП всегда на складе в Екатеринбурге и в Москве. Под заказ – 2 недели со склада в Тайване (при наличии у производителя). Самовывоз в Екатеринбурге, Челябинске, Тюмени и Перми. Доставка по России.

Условия оплаты

  • Оплата заказов с сайта по безналичному расчету осуществляется по счету-оферте, который действителен в день его создания. В случае оплаты в последующие дни, стоимость заказа может быть пересчитана на дату оплаты по текущему курсу USD как ЦБ+2% по решению поставщика. При оплате по безналичному расчету с физических лиц может сниматься комиссия банка от 1%.

  • Можно оплатить заказ наличными в офисе АВЕОН или при доставке курьером до двери.

  • После оплаты выдается кассовый чек.


Условия доставки

  • Доставка во все регионы России транспортными компаниями до терминала ТК в городе доставки, либо до двери заказчика.

  • Срок доставки и стоимость определяются тарифами компаний-грузоперевозчиков.

  • Также вы можете самостоятельно забрать товары из пунктов самовывоза в вашем городе.

Более подробная информация
здесь.

  • Промышленные компьютеры и периферия

    • ПК в стойку 19″

    • ПК настенно-настольного исполнения

    • Серверы

    • Панельные ПК и рабочие станции

    • Мобильные решения

    • Мониторы и LCD-панели

    • Клавиатуры

  • Встраиваемые решения

    • Встраиваемые компьютеры

    • Встраиваемые процессорные платы

    • Оборудование Compact PCI

    • Оборудование PXI/PXIe

    • AdvancedTCA

    • Процессорные модули и базовые платы

  • Коммуникационное оборудование

    • Промышленные коммутаторы

    • Серверы последовательных интерфейсов

    • Конвертеры и повторители

    • Медиаконвертеры Ethernet Fiber

    • Шлюзы протоколов

    • Мультипортовые платы

    • Беспроводное оборудование

    • KVM-решения

    • Системы видеонаблюдения

  • Системы сбора данных и управления

    • Датчики, измерители

    • Контроллеры

    • Модули удаленного ввода-вывода

    • Платы ввода-вывода

    • Панели оператора

    • Платы и модули АЦП/ЦАП, крейты L-Card

    • Нормализаторы сигналов

    • Корзины расширения

    • Выносные и платы клеммников

  • Комплектующие для промПК, сетей и АСУ

    • Корпусы

    • Объединительные платы

    • Материнские платы

    • Источники и адаптеры питания

    • Накопители

    • Оперативная память

    • Платы клеммников

    • Разъемы и переходники

    • Кабели

    • Элементы крепежа

    • Аксессуары к нормализаторам

    • Прочие аксессуары

    • Шкафы, компоненты СКС

  • Программное обеспечение

    • AdAstra TRACE MODE 6

    • ПО Advantech

    • ПО ICP DAS Indusoft, ISaGRAF

    • Kaspersky

    • Microsoft

    • ПО MOXA MXview, SoftCmS, SoftNVR

  • Скидки! Распродажа!

  • Отраслевые решения

    • Реклама

    • ВПК

    • Машинное зрение и IoT

    • Медицина

    • Морское применение

    • Нефтяная и газовая отрасли

    • Транспорт

    • Энергетика

    • Ритейл

Российские промышленные компьютеры iROBO

Будьте в курсе!

Узнавайте о мероприятиях и акциях первым

Specifications:

2200/2200564-cmt2078x_series.pdf file (08 Oct 2022)

Accompanying Data:

weintek cMT2078X Series Recording Equipment PDF Installation Instruction (Updated: Saturday 8th of October 2022 08:13:30 PM)

Rating: 4.4 (rated by 24 users)

Compatible devices: mTV series, cMT-3103, cMT2158X Series, cMT-iPC15, cMT3072X Series, cMT-SVR-200 series, cMT-SVR, cMT-iPC10 series.

Recommended Documentation:

weintek cMT2078X Series: Text of Manual, Installation Instruction

(Ocr-Read Version Summary of Contents, UPD: 08 October 2022)

Installation and Startup Guide
This document covers the installation of cMT2078X Series HMI, for the detailed specifications and
operation, please refer to Datasheet, Brochure and EasyBuilder Pro User Manual. Please read all
warnings, precautions, and instructions on the device carefully before use.
Install Environment:

NEMA Rating

The HMI product is UL Type 4X (NEMA 4) rated, indoor use only.

Electrical
Environment

The HMI product has been tested to conform to European CE requirements. This
means that the circuitry is designed to resist the effects of electrical noise. This
does not guarantee noise immunity in severe cases. Proper wire routing and
grounding will insure proper operation.

Environmental
Considerations

(1) Make sure that the displays are installed correctly and that the operating
limits are followed. Avoid installing units in environments where severe
mechanical vibration or shocks are present.
(2) Do not operate the unit in areas subject to explosion hazards due to
flammable gases, vapors or dusts.
(3) Do not install the unit where acid gas, such as SO2 exists.
(4) This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5) Conform to UL 61010-1 3rd ed. and UL 61010-2-201 2nd ed. safety
requirement for use in Pollution Degree 2 Environment and dry location.
(6) Relative Humidity: 10% ~ 90% (non-condensing)

Cleaning
Considerations

Clean the device using dry cloths. Do not use liquid or spray detergents for
cleaning.

IP Rating

IP 66

Warning

Protection impairment if used in a manner not specified by the manufacturer.
Déficit de protection si utilisé d’une manière non spécifiée par le fabricant.

Unpacking the Unit
Unpack and check the delivery. If damage is found, please contact the supplier.
NOTE: Place the operator panel on a stable surface during installation. Dropping it or letting it
fall may cause damage.
The package includes:
(1) Installation Instruction, 2-sided A4 *1 (2) Human Machine Interface *1 (3) Power Connector *1
(4) Brackets & Screws *1 pack (5) USB Stick Clamp & Tying Strap *1
USB Stick Clamp Usage
Combining the USB Stick with the clamp and the tying strap can prevent USB stick from disconnecting
with HMI when strong vibration is present.
1. Insert the USB connector to the clamp and tie them together with the tying strap.
2. Press the spring and insert the USB stick into HMI.

Installation Instructions
Use a control box that provides enough stiffness.
Cutout Dimension: 192 mm x 138 mm. Secure the
operator panel in position, using all the fastening holes
and the provided brackets and screws. Screw Torque:
2.6 ~ 3.9 lbf.in. (For reaching waterproof effect and
preventing the panel from being deformed.)
Plan for adequate space around the unit and inside the
enclosure, for ventilation and cables. Consider the
heat from other devices inside the enclosure. The
ambient temperature around the unit must be 0 ~ 55°C
Minimum required clearances (along the overlay): Top
/ Bottom / Sides 15 mm
Maximum panel thickness: 4.5 mm
Power Connections

Power Connector Specifications:
Wire AWG: 24~12
Wiring Conductor Minimum Temperature: 75°C
Screw Torque: 4.5 lbf-in (max.)
Copper conduct only.

Spécifications du connecteur d’alimentation:
AWG de fil: 24 ~ 12
Température minimale du conducteur de câblage: 75°C
Couple de vis: 4.5 lbf-in (max.)
Conducteur en cuivre seulement

NOTE:
1. Connect positive DC line to the ‘+’ terminal and the DC ground to the
‘-’ terminal.
2. When downloading project using a USB cable, do not connect HMI
with PLC and PC simultaneously, for electric potential difference may
result in damage to HMI or PC.
System Settings
When HMI is powered up and displays image, press the
round Start Button in the upper-left corner of the screen to
open the Setting dialog box. Tap the lock icon and log
in. (Default System Password: 111111)
Go to the Network tab, and setup your network.
In Setting dialog box you can see device information,
configure general settings, set HMI Time/Date/Name, and
more.

EasyBuilder Pro Software Settings

Launch EasyBuilder Pro software, select your project file,
press F7 shortcut key to open the download dialog box: Select Ethernet > IP tab > Enter your HMI IP >
Click Download to download this project file to HMI.
Using screensaver and backlight saver is recommended in order to avoid image persistence caused
by displaying the same image on HMI for a long time.
(Please refer to EasyBuilder Pro User Manual for software operation details.)

cMT2078X series

Installation Instruction

1

2

3

4

5

6

Communication Connections
NOTE:
1. Only Tx & Rx (no RTS/CTS) may be used for COM1 RS232 when COM3 RS-232 is also used.
Con.B Con.A
COM1/COM3 [RS232], 9 Pin, Male, D-sub COM2/COM3 [RS485], 9 Pin, Female, D-sub

Touchscreen Calibration & Restore Factory Default

Restore Factory Default:
Follow Step 5 to open the Setting dialog box. After login, press the button of “Reset HMI to default”.
Another way to restore factory default is entering “default111111” when logging in. An Attention window
shows, enter “yes’.
Please note that the projects and data stored in the unit are all cleared after restoring factory default.
Another way to enter touch screen calibration mode: Press and hold anywhere on the screen until HMI
starts.

Battery Replacement
Battery Specification: UL Certification Battery, Type CR2032, Rated 3V, Max. Abnormal Charging
Current 10mA, Working Temperature: max. 80°C
Battery replacement shall be performed by qualified personnel (engineer) only and care must be taken
when handling lithium batteries. For more information on battery replacement and disposal
considerations, please refer to the following link:
http://www.weintek.com/download/MT8000/eng/FAQ/FAQ_103_Replace_Battery_en.pdf

NOTE: Make sure that all local and national electrical standards are met when
installing the unit. Contact your local authorities to determine which codes apply.

Power

Use power output that meets SELV (Safety Extra-Low Voltage) requirements. The unit can be
powered by DC power only, voltage range: 24±20%, compatible with most controller DC
systems. The power conditioning circuitry inside the unit is accomplished by a switching power
supply. The peak starting current can be as high as 2A.

Fusing Require-
ments

If the display does not come on within 5 seconds of power up, remove power. A resettable fuse
will protect against overcurrent faults in DC circuit and the resetting will take place after a period
of time. Check wiring for proper connections and try to power up again.

High Voltage

A resettable fuse will prevent damage for overcurrent condition however it isn’t guaranteed.
DC voltage sources should provide proper isolation from main AC power and similar hazards.

Emergency Stop

A Hard-wired EMERGENCY STOP should be fitted in any system using an HMI to comply with
ICS Safety Recommendations.

Supply Voltage
Condition

Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same
power supply. Note: The 24 VDC output from some controllers may not have enough current to
power the unit.

Wire Routing

a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).
b. Please use twisted pair cables for power wire and signal wire and conform to the
impedance matching.
c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression
devices.
d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.
e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power
supply and the frame ground. This provides a path for static and high frequency
dissipation. Typical values to use are 1M Ohm and 4700pF.

Hardware
Considerations

The system designer should be aware that devices in Controller systems could fail and
thereby create an unsafe condition. Furthermore, electrical interference in an operator
interface can lead to equipment start-up, which could result in property damage and/or
physical injury to the operator.
If you use any programmable control systems that require an operator, be aware that this
potential safety hazard exists and take appropriate precautions. Although the specific design
steps depend on your particular application, the following precautions generally apply to
installation of solid-state programmable control devices, and conform to the guidelines for
installation of Controllers recommended in NEMA ICS 3-304 Control Standards.

Programming
Considerations

To conform to ICS Safety Recommendations, checks should be placed in the controller to
ensure that all writable registers that control critical parts of plant or machinery have limit
checks built into the program, with an out-of-limit safe shut down procedure to ensure safety of
personnel.
GMEC278XU_cMT2078X_UL_Installation_210809

CAUTION

DANGER

PIN#

COM1
[RS232]

COM3
[RS232]

1

2

RxD

3

TxD

4

5

GND

6

7

RTS

TxD

8

CTS

RxD

9

GND

PIN#

COM2
[RS485]2W

COM2
[RS485]4W

COM3
[RS485]2W

1

Data-

Rx-

2

Data+

Rx+

3

Tx-

4

Tx+

5

GND

6

Data-

7

8

9

Data+

CAUTION

NOTE:
Make sure that all local and national electrical standards are met when installing
the unit. Contact your local authorities to determine which codes apply.

CAUTION

NOTE:
Make sure that all local and national electrical standards are met when installing
the unit. Contact your local authorities to determine which codes apply.

SW1

SW2

SW3

SW4

Mode

ON

OFF

OFF

OFF

Touch Screen Calibration Mode
& Reset HMI to Default

OFF

ON

OFF

OFF

Hide Start Button

OFF

OFF

ON

OFF

Update OS

OFF

OFF

OFF

ON

Reserved

OFF

OFF

OFF

OFF

Normal

Limited Warranty

This product is limited warranted against defects in design and manufacture.
The proven defective product will either be repaired or replaced, at Weintek’s discretion.
This warranty shall not cover any product which is
(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products.
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.

7

8

9

weintek cMT2078X Series: Recommended Instructions

47110A, DAC15009EE, 1000HA — Eee PC — Atom 1.6 GHz, GA-6VXC7-4X-P, 2115WC, G0447

  • VORT PROMETEO PLUSHR 400Libretto istruzioniInstruction bookletNotice d’emploi et d’entretienBetriebsanleitungInstructieboekjeBrugervejledningVORTICE LIMITEDBeeches House — Eastern AvenueBurton on TrentDE13 0BBTel. (+44) 1283-492949Fax (+44) 1283-544121UNITED KINGDOMVORTICE FRANCE72 Rue Baratte-Cholet94106 Saint Maur CedexTel. (+33) 1-55.12.50.00Fax (+33) 1-55.12.50.01FRANCEVORTICE ELETTROSOCI …

    HR 400 40

  • QuietTime® GT-2 mini User Guide Version 1.0 A product of 4111-A North Freeway Boulevard Sacramento, CA 95834, USA © 2013 Burgett Inc. You are not allowed to completely or partially copy this user guide without obtaining explicit, written authorization from PianoDisc, a member of the Burgett Inc. Group of companies. QuietTime, PianoDisc …

    QuietTime GT-2 mini 32

  • KEYSTONE OM11 — EPI2 DEVICENET INTERFACEInstallatIon and maIntenance InstructIonsTABLE OF CONTENTS1. Introduction …………………………………………… 12. Operation and storage ……………………………. 13. Distinguish OLD/NEW models ………………… 14. Installation …………………………………………….. 3 4.1 Assembling proc …

    Keystone OM11 15

  • [1] MAN #650588D BIM-01-2-HLLY Bus Interface Module for Holley EFI This Bus Interface Module is designed to read engine information from specific Holley EFI kits. The Holley Terminator, HP, Sniper, Dominator and Terminator X and X Max. The module is connected to the Holley EFI through the CAN-bus plug on the EFI harness. Depending on your EFI module you ma …

    BIM-01-2-HLLY 12

  • No.EX※※-OMX1011 PRODUCT NAME Fieldbus system EtherNet/IPTM compatible SI Unit IO-Link Master Unit MODEL / Series / Product Number EX600-SEN3-X80 EX600-ED# EX600-LAB1 EX600-LBB1 …

    EX600 Series 137

  • Installation Manual 24V Thermostat Interface Model name: TCB-IFTH1GUL English • Read this manual before using the TCB- IFTH1GUL 24V Thermostat Interface. • Refer to installation manuals supplied with Indoor Unit, Remote Controller, and Thermostat for any installation instructions. FOR INSTALLER …

    TCB-IFTH1GUL 16

  • Pub. 42004-401D GAI-TRONICS 3030 KUTZTOWN RD. READING, PA 19605 USA 610-777-1374  800-492-1212  Fax: 610-796-5954 VISIT WWW.GAI-TRONICS.COM FOR PRODUCT LITERATURE AND MANUALS GAI-TRONICS® A HUBBELL COMPANY Model 10961-101 AMI Centra-Page Interface Confidentiality Notice This manual is provided solely as an operational, installation, and maintenance guide and contains sensit …

    10961-101 23

  • STOPPAUS EPLAY24378561910+10REC_DUBBING_NORMAL HIGHRELAYMODECD CD-RENTERMENU893267PROG/DIRECTCALLRANDOMDISPLAY SEL.FADER INPUT FINALIZE1 / ALL A — BCHARACTERTIMETITLEBREMOTE CONTROL UNIT RC-278M +CLEARCLEARA ! «J ( )D # % G & ‘P , −Y < >V : ;S . /[ = ] { ? }*OPEN / CLOSETIMETIMECLEAR INPUTMENU5O …

    CDR-W1500 98

  • Copyright © 2013 Electronic Theatre Controls, Inc.All Rights reserved.Product information and specifications subject to change.Part Number: 7184M1210 Rev AReleased: October 2013Handheld Touchscreen and Wireless AccessoriesConfiguration and User ManualRevision A …

    PARADIGM 44

  • Version 26.11.2019 V5-NBT-PNP v.LOGiC Intelligent Solution Interface V5-NBT-PNP Compatible for the F-series BMW with navigation system or radio and 6.5”, 7”, 8.8” or 10.25” monitor with 4+2pin HSD2 LVDS connector …

    V5-NBT-PNP 26

  • KFC 500Pilot’s GuideBendix/King®Flight Control SystemHoneywell International Inc.One Technology Center23500 W. 105thStreetOlathe, Kansas 66061FAX 913-791-1302Telephone: (913) 712-0400Copyright ©1993 Honeywell International Inc.All rights reserved.006-08750-0000Rev. 0 Sept/93 N006-08750-0000September 1993 …

    Skymap IIIC 67

Additional Information:

Popular Right Now:
Operating Impressions, Questions and Answers:

Communication Connections

7

NOTE:

1.

Only Tx & Rx (no RTS/CTS) may be used for COM1 RS232 when COM3 RS-232 is also used.

Con.B

COM1/COM3 [RS232], 9 Pin, Male, D-sub

COM2/COM3 [RS485], 9 Pin, Female, D-sub

COM1

COM3

PIN#

[RS232]

[RS232]

1

2

RxD

3

TxD

4

5

GND

6

7

RTS

TxD

8

CTS

RxD

9

GND

8

Touchscreen Calibration & Restore Factory Default

SW1

SW2

ON

OFF

OFF

ON

OFF

OFF

OFF

OFF

OFF

OFF

Restore Factory Default:

Follow Step 5 to open the Setting dialog box. After login, press the button of «Reset HMI to default».

Another way to restore factory default is entering «default111111» when logging in. An Attention window

shows, enter «yes’.

Please note that the projects and data stored in the unit are all cleared after restoring factory default.

Another way to enter touch screen calibration mode: Press and hold anywhere on the screen until HMI

starts.

Battery Replacement

9

Battery Specification: UL Certification Battery, Type CR2032, Rated 3V, Max. Abnormal Charging

Current 10mA, Working Temperature: max. 80°C

Battery replacement shall be performed by qualified personnel (engineer) only and care must be taken

when handling lithium batteries. For more information on battery replacement and disposal

considerations, please refer to the following

link:

http://www.weintek.com/download/MT8000/eng/FAQ/FAQ_103_Replace_Battery_en.pdf

Con.A

COM2

COM2

COM3

PIN#

[RS485]2W

[RS485]4W

[RS485]2W

1

Data-

Rx-

2

Data+

Rx+

3

Tx-

4

Tx+

5

GND

6

Data-

7

8

9

Data+

SW3

SW4

Mode

Touch Screen Calibration Mode

OFF

OFF

& Reset HMI to Default

Hide Start Button

OFF

OFF

ON

OFF

Update OS

Reserved

OFF

ON

OFF

OFF

Normal

NOTE: Make sure that all local and national electrical standards are met when

CAUTION

installing the unit. Contact your local authorities to determine which codes apply.

Use power output that meets SELV (Safety Extra-Low Voltage) requirements. The unit can be

powered by DC power only, voltage range: 24±20%, compatible with most controller DC

Power

systems. The power conditioning circuitry inside the unit is accomplished by a switching power

supply. The peak starting current can be as high as 2A.

If the display does not come on within 5 seconds of power up, remove power. A resettable fuse

Fusing Require-

will protect against overcurrent faults in DC circuit and the resetting will take place after a period

ments

of time. Check wiring for proper connections and try to power up again.

A resettable fuse will prevent damage for overcurrent condition however it isn’t guaranteed.

High Voltage

DC voltage sources should provide proper isolation from main AC power and similar hazards.

A Hard-wired EMERGENCY STOP should be fitted in any system using an HMI to comply with

Emergency Stop

ICS Safety Recommendations.

Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same

Supply Voltage

power supply. Note: The 24 VDC output from some controllers may not have enough current to

Condition

power the unit.

a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).

b. Please use twisted pair cables for power wire and signal wire and conform to the

impedance matching.

c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression

Wire Routing

devices.

d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.

e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power

supply and the frame ground. This provides a path for static and high frequency

dissipation. Typical values to use are 1M Ohm and 4700pF.

DANGER

The system designer should be aware that devices in Controller systems could fail and

thereby create an unsafe condition. Furthermore, electrical interference in an operator

interface can lead to equipment start-up, which could result in property damage and/or

physical injury to the operator.

Hardware

If you use any programmable control systems that require an operator, be aware that this

Considerations

potential safety hazard exists and take appropriate precautions. Although the specific design

steps depend on your particular application, the following precautions generally apply to

installation of solid-state programmable control devices, and conform to the guidelines for

installation of Controllers recommended in NEMA ICS 3-304 Control Standards.

To conform to ICS Safety Recommendations, checks should be placed in the controller to

ensure that all writable registers that control critical parts of plant or machinery have limit

Programming

checks built into the program, with an out-of-limit safe shut down procedure to ensure safety of

Considerations

personnel.

Limited Warranty

This product is limited warranted against defects in design and manufacture.

The proven defective product will either be repaired or replaced, at Weintek’s discretion.

This warranty shall not cover any product which is

(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products.

(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.

(c) Product has been repaired or taken apart by unauthorized technicians.

(d) Products whose identification markings have been removed or damaged.

GMEC278XU_cMT2078X_UL_Installation_210809

Дисплей
  • Диагональ экрана7» 
  • Тип матрицыTFT 
  • Контрастность800:1 
  • Яркость экрана400 кд/кв.м 
  • Разрешение экрана800 x 480 
  • Продолжительность работы лампы подсветки, час> 30 000 
  • Цветность16.7 M 
  • Тип подсветкиLED 
Интерфейсы
  • USB1 x USB 2.0 
  • ВидеовходОтсутствует 
  • АудиовыходОтсутствует 
  • Последовательные портыCom1: RS-232 
    Com2: RS-485 
    Com3: RS-232/RS-485 
  • Ethernet2 x 10/100 BaseTx 
  • Слот для SD-картыОтсутствует 
Основные характеристики контроллеров
  • Flash-память4 Гб 
  • RAM1 Гб 
Требования к электропитанию
  • Рабочее напряжение24 ± 20% В пост. 
  • Потребление тока850 мА
  • Разъем электропитанияКлемма 
  • Развязка цепи питанияЕсть 
Условия эксплуатации
  • Рабочая температура, °C0 ~ +50 
  • Температура хранения, °C-20 ~ +60 
  • Рабочая влажность, %10 ~ 90, без образования конденсата 
Защита
  • Защита лицевой панелиNEMA4 / IP65 
Системные характеристики
  • Операционная системаПроприетарная Linux-based OS 
  • Процессор4-ядерный 64-битный 1.5 ГГц 
  • Среда разработки проектовEasyBuilder Pro 
  • Удаленный доступEasyAccess 2.0 (опционально) 
    VNC Client 
    VNC Server 
    cMT Server 
  • Часы реального времениЕсть 
Конструктивные свойства
  • Материал корпусаПластик 
  • Размер монтажного отверстия, мм192 x 138
Размеры и вес
  • Габаритные размеры, мм200.3 x 146.3 x 35.0
  • Вес нетто, кг0.6
Монтаж
  • МонтажПанельный 
Наличие международных сертификатов
  • СертификатыCE, UL, RoHS 
Гарантийный срок
  • Гарантийный срок18 месяцев 
Комплект поставки
  • Комплект поставкиКрепежные элементы, предохранитель, разъем питания, инструкция 
    Устройство 
Файлы
  • Документация

    Datasheet: скачать

    Инструкция по установке: скачать

    Мануал по CODESYS: скачать

  • Программное обеспечение

    EasyBuilder Pro: скачать

    EasyAccess 2.0: скачать

Понравилась статья? Поделить с друзьями:
  • Монэкс спрей назальный инструкция по применению
  • Руководство по fluidsim
  • Как сделать фургон из лего инструкция
  • Амоксиклав инструкция по применению для детей суспензия 125 как принимать
  • Фст 03м руководство пользователя